CombiSteel SF-103ST Digital Temperature Controller User Guide

June 17, 2024
CombiSteel

CombiSteel-logo

CombiSteel SF-103ST Digital Temperature Controller

Specifications

  • Power supply : 220V ~240VAC 50/60Hz
  • Temperature sensor : NTC (B=3380, 10k=25)
  • Range of temperature displayed : 45 – 99 (45 – 210) Accuracy: ±1 (±2)
  • Range of set temperature : E1~E2 Factory default: 00 (32)
  • Dimension : 77 (Length) x 35 (Width) x 32 (Depth) mm
  • Mounting hole dimension : 71 (Length) x 29 (Width) mm
  • Relay box dimension : 106 (Length) x 96 (Width) x 46 (Depth) mm
  • Temperature of the operating environment : 10 – 60 (14 – 140)
  • Relative Humidity : 20% – 90% (Non-condensing)
  • Relay contact capacity
    • Compressor : N.O. 30A/250VAC (Can connect 1HP compressor, if more it needs to connect an AC contactor)
    • Evap. fan : N.O. 10A/250VAC
    • Light : N.O. 10A/250VAC

Product Usage Instructions

Front Panel Operation

  1. 1. Set temperature (compressor stop temperature) adjustment
    • Parameter: PA
    • Function: Password
    • Set range: 00 – 50 – 99 (Factory default: 82)

Energy Saving Control
The controller features energy-saving control options. Follow these steps to optimize energy usage:

  1. 1.  **t0 Energy saving switch:** Adjust to turn energy-saving mode on or off.
  2. t1 Energy saving temp. Hysteresis: Set the temperature difference for energy-saving mode activation.

Frequently Asked Questions (FAQ)

  • Q: How do I set the temperature display range?
    A: Use the Set temperature adjustment feature on the front panel to set the desired range within the specified limits.

  • Q: Can I use this controller for a compressor greater than 1HP?
    A: For compressors larger than 1HP, you will need to connect an AC contactor as specified in the relay contact capacity section.

Model: SF-103ST Digital Temperature Controller

Features of Function

  • Mini-sized and integrated intelligent control and applicable to the compressor of one HP.(Include 1HP).
  • Temperature Display/ Temperature Control/ Energy saving control/Manual, automatic defrost/Evap. Fan control/ Light Control /Time to end defrost/ Value Storing/ Self Testing

Specifications

  1. Power supply :220V ~240VAC 50/60Hz
  2. Temperature sensor : NTC (B=3380,10k=25 ) ,
  3. Range of temperature displayed : 45 99 ( 45 210 ) Accuracy: 1 (2) Factory default : 00 (32 )
  4. Range of set temperature : E1~E2
  5. Dimension :77(Length) 35(Width) 32(Depth)mm Mounting hole dimension: 71(Length) 29(Width)mm Relay box dimension :106(Length) 96(Width) 46(Depth)mm
  6. Temperature of the operating environment : 10 60 (14 140 ) Relative Humidity:20%~90%(Non-condensing)
  7. Relay contact capacity
    • Compressor : N. O. 30A/250VAC (Can connect 1HP compressor, if more it needs to connect an AC contactor)
    • Evap. fan : N. O. 10A/250VAC
    • Light : N. O. 10A/250VAC

font Panel Operation

  1. Set temperature (compressor stop temperature) adjustment

    • Press button, the set temperature is displayed.
    • Press button to modify and store the displayed value. Press and display the cold-room temperature.
    • If no more button is pressed within 6 seconds, the cold-room temperature will be displayed. (Set temperature adjustment range: E1 E2)
  2.   Manual start/stop defrost : Press button and hold for 6 seconds to defrost or stop defrost.

  3. Clock adjustment: Press and for once to enter clock adjustment state, t + hour flash display, press to adjust the hour, press again for once, t + minutes flash display, press and It will exit, if no more button is pressed within 6 seconds.

  4. Refrigeration LED : during the delay start, LED flashes. During refrigeration, the LED is on; during temperature constant state, the LED turns off.

  5. Defrost LED : during defrosting, the LED is on; during dripping time the LED flashes.

  6. Evap. Fan LED : during fan operation, the LED is on. When the fan stops operation, the LED is off.

  7. Light control : press for once can turn on or turn off the light, when power on, it can still memorize.

  8. Parameters setup
    Press button for 6 seconds to enter parameter setting(PA will display and flash);and then press button, E1, E2 CPA, E1 will display sequentially, press button to display and revise the values; if no more button is pressed within 6 seconds, it will exit and store new values. Note: only when it enters inner parameter manual (PA is displayed) and enter correct password, the parameter values can be adjusted. If the entered password is wrong, then all the parameters just can be checked and can not be changed, the set temperature adjustment is still valid. If the user forget the password, then it need to resume factory defaults.

  9. Factory default resumption : press and button simultaneously for 6 seconds, “888 ” will be displayed. At that moment all the parameters and set temperature will resume to factory default, after 6 seconds it will return to normal operation.

  10. Only after enter correct password when it enters inner parameter “CPA “press button can display and change  password, and then press button to confirm and store new password. ( When “CPA ” value is set to “00 ” that means cancel password).

Function details

  1. Temperature control(When power on, press for once to cancel the delay and enter automatic control mode.)
    • After turning on for delay time(E40), the compressor starts operating when cold room temperature (set temp.+ Hysteresis E3 ), and will be off when cold room temperature set temp.
    • To protect the compressor, it can not re-start unless the time when the compressor stops every time is longer than the delay time (Parameter E41).

Parameter| Function| Set range| Default| Parameter| Function| Set range| Default|
---|---|---|---|---|---|---|---|---
PA| Password| 00  50  99| 82| t0| Energy saving switch| 00=off 01=on| 01|
t1| Energy saving temp. Hysteresis| 00 15

00 27

| 07

04

|
E1| Lower set point limit| 45     set temp.

49

| 02

35.6

|
t2| Energy saving power on time: hr| 00  23hr| 05hr|
E2| Higher set point limit| Set temp.  45

113

| 10

50

|
t3| Energy saving power on time: min| 00  59min| 00min|
t4| Energy saving stop time: hr| 00  23hr| 11hr|
E3| Temp. Hysteresis| 01  10

02  18

| 03

09

|
t5| Energy saving stop time: min| 00  59min| 00min|
E40| When power on, Comp. start delay time (Effective for the first time after power on)| 00  10min| 02min| t6| Light on time: hr| 00  23hr| 00hr|
t7| Light on time: min| 00  59min| 00min|
E41| Reach the temperature, comp. Stop,the comp. Must delay start time| 00 10min| 05min|
t8| Light off time: hr| 00  23hr| 00hr|
E5| Offset on room temp.| 05 05

09 09

| -1

00

| t9| Light off time: min| 00  59min| 00min|
LS| Set temp. Adjustment mode| 00=set temp. adjustable 01=set temp. Non- adjustable, can be checked only| 00|
E7| Cold-room sensor failure Compressor stop time| 01  180min| 15min|
E8| Cold-room sensor failure compressor operation time| 01  180min| 45min| H1| High temperature alar m for cold-room sensor| 45        H2/113       H2| 45

113

|
F1| Max. Defrost duration| 01 60min| 10min| H2| Low temperature alarm for cold-room sensor| H1        45

H1        49

| 40

40

|
F2| Defrost interval time| 00 24hr| 04hr|
H5| Power on alarm delay| 00  180min| 60min|
F4| Display during defrost| 00=Normal display 01 = Last value before
defrost  02=Defrost code dEF| 01|
H6| Continue alarm delay| 00  180min| 00min|
F5| Power on fan start mode|

  • 00=Parallel with comp.(stop when defrost) 01=Continuous running( stop when defrost)
  • 02=Parallel with comp.(start when defrost) 03= Continuous running (start when defrost)
  • 04=when comp. Stops, on for3 minutes and off for 1 minute (start when defrost)
  • 05= when comp. Stops, on for 2 minutes and off for 2 minutes (start when defrost)

|

03

|
A1| Room temperature display mode| 00=Normal display 01 = locked low temperature display| 00|
CF| Temperature unit| =Celsius

=Fahrenheit

| |
CPA| Change menu
password| 00-99 (if it is set to 00, that means cancel password)| 82|
F8| After defrost fan start time| 00  20min| 00min|

  1. Temperature display

    • When A1=01, the temperature will display in low speed: in the speed of every 30 seconds 1 degree to reach the actual temperature, and do not affect the compressor work normally. When power on, and the actual temperature reach the set temperature for once, only if the cold room temperature is within the range of
      (set temperature+E3+2 /4 ), will display the set temperature, otherwise the temperature will display in low speed.
  2.  Defrosting by turning off compressor

    • After worked for a defrost interval F2 will enter defrost state automatically. The defrost LED is on, the compressor stops.
    • When reached defrost duration F1, will exit defrost and enter automatic refrigeration state.
    • When the defrost interval is set to “00” , the function of automatic defrost will be cancelled.
  3. Display during defrost

    • When setting parameter F4=0, it will display cold room temperature normally.

    • When setting the parameter F4=1,the room temp. is locked during defrost, and the last value before
      defrost is displayed. When defrost ends, normal display will be resumed after 20 minutes delay of room temp. Display (or cold room temperature< set temperature + hysteresis E3). The defrost LED flashes during the locked delay.

    • When setting parameter F4=2, it will display “dEF “. When defrost ends, normal display will be resumed after 20 minutes delay of room temp. Display (or cold room temperature set temperature + hysteresis E3). The defrost LED flashes during the locked delay.

  4. Fan control:

    • During refrigeration, the fan start mode is determined by parameter F5 outside the bracket. During defrosting, the fan start mode is determined by parameter F5 inside the bracket. After defrosting, the fan start pass F8 time. Energy saving mode temperature control Note: When the energy-saving start-up time is the same as the shutdown time, it will not enter the energy-saving mode)
      When the system work to energy saving start time, the operation temperature will set to (original set temperature + t1) values automatically, flash display tE. When operate to energy saving end time, the operation temperature will adjust to the original set temperature automatically, and display normally. When the energy saving mode t0=1, the energy saving mode start, when t0=0, the energy saving mode stop.
  5.  Energy saving mode light control (Note: When the lighting time is the same as the lighting time in energy-saving mode, the lighting is always on, and it can also be turned on or off manually)

    • When system work to light on time, the light is on automatically. When work to light off  time, the light is off automatically. During energy saving mode can press upward button to control the light switch, when work to the next light on or off time, the light is on or off automatically.
  6.  High/low temperature overrun alarm
    After power on delay time exceeds parameter H5, when cold-room temperature is higher than the value of parameter H1, after alarm delay time (parameter H6),the cold-room temperature and Hi will display and flash, it will exit defrost and start the compressor. When cold-room temperature is lower than the value of parameter H2, after alarm delay time (parameter H6),the cold-room temperature and Lo will display and flash, the compressor control output will be disconnected .At the same time the buzzer will sound, the sound can be stopped by pressing random button.

  7.  Abnormal work mode:

Failure code Description Operation Mode
1H Cold-room sensor is short-circuited or exceeds
high temperature limit (  99  /210     ) Compressor works according
1L
Cold-room sensor is open-circuited or exceeds to E8, E7mode
low temperature limit (         45     /  49     )

Circuit Diagram

CombiSteel-SF-103ST-Digital-Temperature-Controller-image
\(6\)

Notes for Installation

  1. The sensor cable leads must be kept separately from main voltage wires in order to avoid high frequency noise induced. Separate the 12V low-voltage lines from the high-voltage lines of the controller.
  2. When install the sensor, it shall be placed with the head upward and the wire downward.
  3. In case of long-distance probe installation from the controller, the probe cable may be prolonged up to 100 m max. without any re-calibration
  4. The temperature controller can not be installed in the area with water drops.
  5. The temperature controller can not be installed in the corrosive and strong electromagnetic pulse interference places.