PHOENIX GP10PL 10 HP Rotary Phase Converter Installation Guide
- June 17, 2024
- Phoenix
Table of Contents
PHOENIX GP10PL 10 HP Rotary Phase Converter
Product Information
Specifications
- Model: GP10PL
- Power Requirements: Single Phase
- Idler Motor: 10 HP
Product Usage Instructions
1. Power Requirements
Before installation, it is important to verify the KVA size of the transformer with your electric company. The KVA number should be larger than the HP of the idler motor. Failure to ensure this can result in damage to the idler motor, which will not be covered under warranty.
2. Checking Connections
Before using the converter, check that all connections, including factory connections to the power block, are secure. It is recommended to recheck connections after a few weeks of using the converter to ensure they remain secure.
3. Power Requirements and Breaker Sizes
For motors, it is recommended to use a breaker that is double the amps size of the machine. For example, if the equipment pulls 20 amps, use a 40 amp breaker. When multiple machines will be running at the same time, calculate the total amps by adding the amps of the largest machine and the other machines that will run simultaneously. For example, if you have a 20 AMP lathe, a 9 amp saw, and a 6 amp milling machine, the total amps would be 20 X 2 = 40 + 9 + 6 = 45 amps. In this case, use the next standard size breaker, which would be a 50 Amps two-pole breaker. It is important to follow local and state laws regarding wire and breaker sizes. In rural areas, it is recommended to increase the minimum size breaker by 20%.
4. Wire and Breaker Sizes
For single-phase connections, use 6 AWG copper wire if the distance is under 50 feet. For the idler motor, use 8 AWG copper wire. The recommended breaker/fuse size is 20 amps minimum and 40 amps maximum.
5. Connecting the Idler Motor Wires
Refer to the provided illustrations for connecting the idler motor wires. Avoid using wire nuts and use bolt-down lugs instead. Choose the appropriate illustration based on the number of leads at the motor.
6. Installation by a Licensed Electrician
The product must be installed by an industrial licensed electrician. This ensures proper installation and compliance with safety regulations.
7. Wiring Diagram
The wiring diagram is located on the connection cover. Depending on the voltage, refer to the appropriate diagram for either 230V or 460V connections.
FAQ
- Q: What is the model of the product?
- A: The model of the product is GP10PL.
- Q: What are the power requirements?
- A: The product is designed for single-phase power.
- Q: What is the horsepower of the idler motor?
- A: The idler motor has a horsepower of 10 HP.
SPECIFICATIONS
ELECTRICAL SPECIFICATIONS SHEET
Optional Feature
- 208, 460 Volt Output (includes transformer)
- AutoStart and AutoOff with load detection
- PL Model (includes Start and Stop with Built-in Mag Starter)
- GPX Model (includes WFI Cloud Controls, Timers, Energy Monitor)
- Wireless Remote ON/OFF
INSTALLATION
READ FIRST – BEFORE INSTALLATION
- Most important step to know.
- NEVER Start the phase converter with a load, this includes transformers.
- Make sure you have the incoming service to start the phase converter, call your electric company verify the KVA size of the transformer, that KVA number should be larger then the HP of the idler motor.
- DO NOT use WIRE NUTS for any connection, use the bolt down lugs. Check all make sure all connections even factory connections to the power block are secure, also recheck connections after a few week of using the converter.
- When powering up the unit, if the idler does NOT come up to FULL SPEED, then shut the phase converter down right away. If you don’t understand then call us or a qualified electrician. if you do not turn the unit off you have a chance to damage the idler motor that will not be covered under warranty.
- Must be installed by a license industrial electrician, our guidelines are not to supersede local and state laws.
Power requirements
- You will need to use a motor load type breaker. NOT a quick blow or trip breaker.
- Sizing a breaker for a single machine with an inductive load (motors) double the amps size of the machine. Example if the equipment pulls 20 amps use a 40 amp breaker.
- Sizing the equipment for multiple machine double the amp of the largest machine and add the the other machine that will run at the same time. Example; 20 AMP Lathe. 9 amp saw, 6 amp milling machine. 20 X 2 = 40 +9 + 6 = 45 amps, use the next standard size breaker which would be 50 Amps two pole breaker.
- Use the chart to make sure you don’t go over or under the Minimum and maximum size allowed. For rural areas increase the minimum size breaker by 20% Click on the next picture to see this chart.
WIRE AND BREAKER SIZES
SINGLE PHASE
| 6 AWG Copper under 50 feet
IDLER MOTOR
|
8 AWG COPPER
BREAKER/FUSE
|
20 MIN / 40 MAX
Mounting the Phase Converter Panel
Mount the enclosure first, to a non-vibrating surface, there are two options provided for mounting, next install the back plate with the four nuts provided. Mounting the phase converter panel near the breaker panel is recommended the larger wire is you single phase line, that is best to keep as short as possible. Every 50 feet you will need to inerease the size of the sinale nhase wire
CONNECTING THE IDLER MOTOR WIRES
THIS IS JUST AN ILLUSTRATION OF WHAT WIRES GET CONNECTED TOGETHER, DO NOT USE WIRE NUTS, USE BOLT DOWN LUGS
- IF YOU HAVE 9 LEADS AT THE MOTOR CLICK HERE
- IF YOU HAVE 12 LEADS AT THE MOTOR CLICK HERE
PL AND PH MODELS
MUST BE INSTALLED BY A INDUSTRIAL LICENSED ELECTRICIAN
10 HP Rotary Phase Converter Components
Item Number
| Description (click on the description to visit the link to the item)|
Quantity in Model
|
PRICE
| SKU#
Click SKU for 3d Viewing
1
|
Two Pole Contactor – 230 Volts 30-40 Amps
|
1
|
28.00
|
GP2P30A
2
|
Relay 90-66
|
1
|
47.00
|
GP90-66
3
|
100 MFD 370V Run
Capacitor (SILVER CAP)
|
2
|
26.00
|
4
|
630 MFD 220V Start
Capacitor (BLACK LARGER CAP)
|
1
|
24.14
|
5
| 270-324 MFD 220V
Start Capacitor (BLACK SMAL CAP)
|
1
|
18.00
|
6
|
Capacitor Holder and Lid
|
1
|
115.00
|
7
|
3 Pole Contactor 50-60 AMP 230 Volts
|
1
|
52.84
|
C375C
8
|
5 HP 3 Pole Power Block
|
1
|
45.00
|
References
- Autodesk A360
- Autodesk A360
- 100 MFD Round Motor Run Capacitor (370V) – Phoenix Phase Converters
- 630-750 MFD - 250V Start Capacitor – Phoenix Phase Converters
- CONTACTOR 3 POLE 60 AMPS 208/240 COIL VOLTAGE – Phoenix Phase Converters
- Potential Relay 90-66 | Phoenix Phase Converters
- Power Block fit 25 HP to 40 HP Rotary Phase Converters – Phoenix Phase Converters
- Start Capacitor – Phoenix Phase Converters
- Two Pole Contactor 230 Volts - 30 Amps | Phoenix Phase Converters
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>