heatit Z-TRM6 DC Z Wave Electronic Thermostat
HEATIT Z-TRM6 DC Installers manual
INTRODUCTION
- Heatit Z-TRM6 DC is an electronic thermostat with a potential free relay, designed for boiler control or actuators. The thermostat can be controlled through your Z-Wave™ network or via the buttons on the front. The thermostat has a user-friendly interface.
- Heatit Z-TRM6 DC has 3 modes; Heat – Cool and Eco.
- The thermostat fits in standard European junction boxes and may be used with most System 55 frames. It has a sturdy metal frame for secure fastening on the junction box. The thermostat has one built-in room temperature sensor. Two additional external temperature sensors may also be connected.
- Heatit Z-TRM6 DC allows you to set the power metering value manually.
- The thermostat can be set up with multiple associations and can be used as a master thermostat. It can control up to 10 thermostats and 10 external relays E.g wall plugs.
- The device has a built-in potential free relay of max 3A that is designed for the usage of up to 3x 24VDC actuators.
STATEMENT REGARDING PRODUCTS FROM MULTIPLE MANUFACTURERS
Please read this before installation
This device may be used with all devices certified with the Z-Wave Plus™
certificate and should be compatible with such devices produced by any
manufacturer. Every primary controller is different depending on the
manufacturer, their target audience and intended use/application. Please
review the functionalities implemented by the primary controller you intend to
use with our Z-Wave Plus certified device to ensure that it provides the
necessary controls to take full advantage of our product’s capabilities.
BEHAVIOR WITHIN THE Z-WAVE NETWORK
This device may be operated within any Z-Wave™ network with Z-Wave-certified
devices from other manufacturers. All non-battery-operated nodes within the
network will act as repeaters regardless of manufacturer to increase the
reliability of the network. On delivery, the device does not belong to any
Z-Wave network. The device needs to be added to an existing network to
communicate with the other devices within it. Devices may also be removed from
a network. The add/remove processes are initiated by the primary controller of
the Z-Wave network.
QUICK START
- Switch off the mains voltage (disable the fuse).
- Open the junction box.
- Connect the wires according to the description in Chapter 6; ”Connections”. Optional: Connect external wired sensors.
- After verifying the connections, switch on the mains voltage.
- Set the primary controller in add mode (security/non-security).
- Hold the Center button until “OFF” is shown in the display (approx. 5 seconds).
- Press the ”+” button once to reach “CON”, and hold the center button until the display shows a rotating light pattern.
- The thermostat will display “INCL” when the thermostat is successfully added. NB! If adding/removing fails, Err (error) will appear.
INSTALLATION DISCLAIMER
Installation must be done by a qualified electrician in accordance with national building codes. Before installation, disconnect the power to the device from the mains. During installation of the device, power to the device must be disconnected AT ALL TIMES!
CONNECTIONS
Max tightening torque for terminal screws: 2Nm.
If the cable used has multiple strands, using an end sleeve is advised.
The product allows for wiring of cables with a cross-section of up to
1×2.5mm2.
The screw terminals are located at the back of the device, and are accessable
at all times.
INSTALLATION
To install the thermostat in the junction box, hold the sides of the display and gently pull outwards to detach the front piece. Connect all wires according to the correct diagram. Align the thermostat with the junction box mounting screws, and mount it into the junction box using 2 screws. Position the thermostat front over the part mounted in the junction box, then carefully press the front until it clicks into place.
ADD/REMOVE
Please read this before installation
The primary controller/gateway has a mode for adding or removing devices.
Please refer to your primary controller manual on how to set the primary
controller in add/remove mode. The device may only be added or removed from
the network if the primary controller is in add/remove mode. When the device
is removed from the network, it will NOT revert to factory settings.
An always listening node must be powered continuously and reside in a fixed
position in the installation to secure the routing table. Adding the device
within a 2 meter range from the gateway can minimize faults during the
Interview process.
There are two ways to add the device to a Z-Wave network.
Method 1: Standard (Manual)
Add/remove mode is indicated on the device by rotating LED segments on the
display. It indicates this for 90 seconds until a timeout occurs, or until the
device has been added to/removed from the network. Configuration mode can also
be cancelled by performing the same procedure used for starting Configuration
mode.
-
Hold the Center button for 5 seconds.
The display will show “OFF”. -
Press the ”+” button once to see “CON” in the display.
-
Start the add/remove device process in your primary controller.
-
Start the configuration mode on the thermostat by holding the Center button for approximately 2 seconds.
The device is now ready for use with default settings.
NB! When the device is removed from the gateway, the parameters are not reset.
To reset the parameters, see Chapter ”Factory reset”.
If inclusion fails, please perform a ”remove device” process and try again. If
inclusion fails again, please see “Factory reset”.
Method 2: SmartStart (Automatic)
SmartStart enabled products may be added to a Z-Wave network by scanning the
Z-Wave QR-Code on the product
if your primary controller supports SmartStart inclusion. No further action is
required and the SmartStart product will be added automatically after being
powered on within range of the primary controller.
FACTORY RESET
Enter the menu by holding the Center button for about 5 seconds, navigate in
the menu with the ”+” button til you see FACT. Press the Center button until
you see “– –” blinking in the display, then hold for about 5 seconds to
perform a reset. You may also initiate a reset by holding the Right and Center
buttons for 60 seconds.
When either of these procedures has been performed, the thermostat will
perform a complete factory reset. The device will display “RES” for 5 seconds
while performing a factory reset. When “RES” is no longer displayed, the
thermostat has been reset.
Please use this procedure only when the primary controller is missing or
otherwise inoperable.
STARTUP
After powering up the device for the first time, all parameters will have
default settings and the thermostat will start by asking which sensor mode
should be used.
PRINCIPLES OF REGULATION
The thermostat uses temperature readings retrieved from the internal sensor
and/or from external wired sensors to regulate the temperature. The thermostat
will regulate the temperature using hysteresis or PWM, based on the setpoint
temperature. To select either “HYST” or “PWM” you can find the “REG” menu
option or use Parameter 13 “REG”.
Hysteresis
Hysteresis will turn on and off the load based on the hysteresis value in
comparison to the setpoint. You can make changes to the thermostat hysteresis.
You may choose hysteresis values between 0.3°C and 3.0°C using Parameter 14
“HYST”. The default setting is 0.5°C. When using waterbased heating we
recommend a hysteresis of 1.0°C.
You may also change the hysteresis by entering the local settings menu and
holding the Center button for 2 seconds when “REG” is displayed. Here you can
choose values between 0.3 and 3.0.
Pulse-width modulation PWM
With pulse-width modulation (PWM) regulation enabled, the thermostat will
regulate based on duty cycles. The thermostat is turned on and off in
percentage intervals of the cycle. The amount of time the relay will be on is
based on how far the measured temperature is from the setpoint.
LOCAL SETTINGS MENU
To enter the settings menu, hold the Center button for 5 seconds. The display
will display “OFF”. You are now in the settings menu. While in the settings
menu, “SET” will be displayed in the bottom right of the display. You can now
scroll up and down using the Left and Right buttons. Some options have
submenus. To navigate the submenus, press the Center button once to enter or
exit the submenu. Press the Left and Right buttons to find your desired value
and hold the Center button for 2 seconds to confirm your selection. “STOR”
will appear to indicate settings are stored.
DISPLAY MENU STRUCTURE
See flowchart at the end of this manual.
TEMPERATURE SHOWN IN DISPLAY
By default, the temperature shown on the display while
in standby state is the setpoint. This may be altered with Parameter 15
”Temperature display”. It may also be changed by entering the local settings
menu and holding the Center button for 2 seconds when “MODE” is displayed. You
can choose between “SETT” and “RELT”. “SETT” is the Setpoint temperature and
“RELT” is the real-time temperature.
STANDBY AND MAIN SCREEN
When the thermostat remains untouched for a while, it will automatically go to
the standby screen. The standby will by default show the setpoint temperature.
By pressing any button once, you will see the measured temperature. By
pressing the Left or Right button multiple times, you will change the
setpoint.
KWH VALUE IN MENU
The device supports setting power metering values to give insight into the
power consumption of the heating. The total consumption of the device can be
seen in the system from the “kWh” menu option. The total consumption data can
be reset by holding the Center button while in the kWh menu.
SIZE OF LOAD
In the “load” menu or from Parameter 27 “Size of load”, the load value can be
set manually. The size of load can be adjusted in 100W increments up to 9900W.
CHOICE OF SENSOR
The thermostat has multiple sensors and sensor modes. This lets you configure
the thermostat to work correctly in most installations. The sensors and modes
may be selected from either the local settings menu or via Parameter 2 “OPER”.
Available sensor modes:
- F Floor sensor
- A Internal room sensor
- AF Internal room sensor + Floor sensor
- A2 External room sensor
- A2F External room sensor + Floor sensor
NOTE: Some types of floor require that a floor sensor is connected in order to limit the floor temperature to a maximum of 27°C (check the manual from the floor
manufacturer). When the thermostat is used in (AF or A2F) the floor limiter FHI is automatically set to 27°C. When using any other sensor type (A, F or A2) the minimum and maximum limits are 5°C and 40°C respectively.
SELECTING SENSOR VALUE
The thermostat allows the selection of multiple different resistance values of
an NTC sensor and can be selected using either the local settings menu or via
Parameter 3 “SEN”. The supported sensor values are as follows:
6.8, 10, 12, 15, 22, 33, 47 or 100KΩ.
The factory default value is 10kΩ. When connecting both the floor sensor and
the external sensor, make sure to use sensors with the same Ohm value.
CALIBRATION
If the temperature sensor readout is not correct, you can make minor changes
to the temperature readout. The temperature readings can be calibrated by ±6°C
using Parameter 10 “CAR”, 11 “CAF” and 12 “CAE”. The calibration can also be
performed from the menu using CAR, CAF and CAE. The adjusted value will be
displayed in the controller/gateway indicating what the thermostat uses for
regulation.
SENSOR TYPE | IN MENU STRUCTURE | PARAMETER |
---|---|---|
Internal sensor | CAR | 10 |
External sensor | CAE | 11 |
Floor sensor | CAF | 12 |
BRIGHTNESS
Using the menu choices “BR1” and “BR2”, the brightness
of the display in Active and Standby state can be changed respectively. “BR1”
and “BR2” are also included in the device as Parameter 16 “BR1” and Parameter
17 “BR2”.
DISPLAY ON/OFF (DON/DOFF)
The thermostat has a display ON/OFF function which decides whether the display
should turn completely off when in Standby. To enable/disable this function,
hold the Left and Center buttons for 10 seconds. The display will show “DOFF”
when the function is activated and “DON” when the function is disabled. When
operating any button, the display will light up.
DISPLAY ICONS
CHILD LOCK
Child lock is a function for disabling the buttons from the display locally.
It will show “LOCK” when attempting to operate it while the function is
enabled. To enable or disable the function, hold the Left and Right buttons
for 10 seconds. Enabling the function will show “LOCK” in the display,
disabling the function will show “OPEN”.
OPEN WINDOW DETECTION OWD
Open Window Detection (OWD) is a function which will reduce the thermostat
setpoint on detection of an open window. This happens when the temperature
sensor registers a rapid temperature drop.
When OWD is active, the setpoint is reduced to 5°C in order not to waste
energy. OWD will automatically be cancelled if OWD has been active for more
than 1 hour, or if the temperature increases by 3°C. OWD can also be cancelled
manually by increasing/decreasing the setpoint with the Left and Right
buttons.
By default, OWD is not enabled. The feature may be enabled by selecting “OWD”
from the menu. Choose between options “OFF” and “ON”. It can also be enabled
by setting Parameter 26 “Open window detection” to 1.
ERROR CODES
- Err Adding fail. See Chapter 7 “Add/remove”.
- Err1 Internal error. Most probably a faulty unit. Replace unit.
- Err2 Z-Wave error. Most probably a faulty unit. Replace unit.
- Err3 Internal error. Most probably a faulty unit. Replace unit.
- Err4 Floor sensor error. You have chosen F, AF or A2F sensor mode without having a floor sensor connected, or the sensor may be damaged.
- Err5 External sensor error. You have chosen A2 or A2F sensor mode without having an external sensor connected, or the sensor may be damaged.
- Err6 Overheating. Contact your electrician.
SAFETY FEATURES
The device has safety features to ensure safe operation and warn the user of
any faults/unexpected behavior. The device has an Overheat function. If the
thermostat registers an Overheat incident, the thermostat will switch off and
an error will appear in the display.
Overheating
The device features internal temperature sensors that detect overheating. It
warns the user and turns off the relay to prevent any damage.
When overheating is detected, the device will:
- Turn off the relay.
- Display Err6 in the display.
- Send a notification to the gateway.
Sensor failure
The device has the ability to detect when there is no sensor connected or the
sensor is broken or otherwise defective, causing an open circuit.
When the device detects the sensor error, the device will:
- Turn off the relay.
- Display an error in the display, changes based on which sensor is not connected/faulty.
To clear the “Sensor not connected” error the device has to be disconnected from the mains, and the wiring and sensor(s) need to be checked. When the fault is resolved the mains can be reconnected and the device will function normally again.
QR-CODE PLACEMENT (DSK)
The QR-Code is needed when including a device using S2 security or SmartStart.
The DSK can be found in the QR-Code and is located;
- On the product.
- In the Quick Guide.
- On the packaging box/gift box.
SECURITY
S2 security enhances Z-Wave Plus with an additional layer of AES 128-bit
encryption of the wireless Z-Wave communication to prevent hacking and man-in-
middle attacks on the home network.
This device supports S2 and has a Z-Wave DSK QR-Code label that may be used
when the device is added to the Z-Wave home network. The primary controller
will ask for a 5-digit code. They are the first underlined 5 digits located on
the QR code sticker. The primary controller will then ask you to confirm the
rest of the code that is contained in the QR-Code.
NODE INFORMATION FRAME
The node information frame is the ”business card” of a Z-Wave device. It
contains information about the device type and
its technical features. The add and remove procedure of
the device is confirmed by sending out a node information frame. Besides this,
it may be necessary for certain network operations to send out a node
information frame.
ASSOCIATIONS Z-
Wave devices interact with other Z-Wave devices. The relationship between one
device controlling another device is called an association. In order to
control a subordinate device, the controlling device needs to maintain a list
of devices that will receive controlling commands. These lists are called
”Association Groups”. They are always related to the specific event triggered
(e.g., sensor reports). In case the event is triggered, all devices stored in
the respective association group will receive a joint wireless command.
Setting and Removing Associations
Associations may be assigned and removed via Z-Wave commands. Please refer to
your primary controller/Z-Wave gateway for more information.
Multi Channel support
Heatit Z-TRM6 DC has support for the Multi Channel Command Class. This allows
the thermostat to be perceived as multiple devices by the primary controller,
which enables the reporting of multiple temperature sensors and the ability to
distinguish between the reports coming from the device.
No Multi Channel support
If the primary controller or the Z-Wave devices to be associated with Heatit
Z-TRM6 DC do not support the
Multi Channel Association Command Class (Multi Channel encapsulation), only
the association groups in the root device are accessible. This device contains
3 association groups in addition to the Lifeline Group.
ASSOCIATION GROUPS
Without Multi Channel support:
MULTI LEVEL SWITCH DEVICE | DESCRIPTION |
---|---|
Group 1 | Lifeline. |
Lifeline Group to be used by primary controller, sends:
- Thermostat Mode Report
- Thermostat Setpoint Report
- Thermostat Operating State Report
- Protection Report
- Notification Report
- Meter Report
- Sensor Multilevel Report
- Device Reset Locally Notification
- Indicator Report
- Configuration Report
- Max nodes in group: 1
Group 2| Binary Switch Set.
Send Binary Switch set commands based on the internal relay state, sends:
- Binary Switch Set
Max nodes in group: 10
|
MULTI LEVEL SWITCH DEVICE| DESCRIPTION
---|---
Group 3| Thermostat Setpoint set.
Sends Thermostat Setpoint set commands based on own setpoint to allow for use as master thermostat, sends:
- Thermostat Setpoint Set
- Max nodes in group: 10
Group 4| Thermostat Mode set.
Sends Thermostat Mode set commands based on own mode to allow for use as master thermostat, sends:
- Thermostat Mode Set
- Max nodes in group: 10
With Multi Channel support:
1: THERMOSTAT DEVICE | THE MAIN THERMOSTAT DEVICE |
---|---|
Group 1 | Lifeline. |
Lifeline Group to be used by primary controller, sends:
- Thermostat Mode Report
- Thermostat Setpoint Report
- Thermostat Operating State Report
- Protection Report
- Notification Report
- Meter Report
- Sensor Multilevel Report
- Device Reset Locally Notification
- Indicator Report
- Configuration Report
- Max nodes in group: 1
Group 2| Binary Switch Set
Send Binary Switch set commands based on the internal relay state, sends:
- Binary Switch Set
Max. nodes in group: 10
Group 3| Thermostat Setpoint Set
Sends Thermostat Setpoint set commands based on own setpoint to allow for use as master thermostat, sends:
- Thermostat Setpoint Set
Max. nodes in group: 10
Group 4| Thermostat Mode Set.
Sends Thermostat Mode set commands based on own mode to allow for use as master thermostat, sends:
- Thermostat Mode Set
Max. nodes in group: 10
2: MULTILEVEL SENSOR DEVICE| INTERNAL SENSOR
Group 1| Lifeline.
Lifeline Group for internal sensor, sends:
- Sensor Multilevel Report
Max. nodes in group: 0
3: MULTILEVEL SENSOR DEVICE| EXTERNAL SENSOR
Group 1| Lifeline.
Lifeline Group for external sensor, sends:
- Sensor Multilevel Report
Max. nodes in group: 0
4: MULTILEVEL SENSOR DEVICE| FLOOR SENSOR
Group 1| Lifeline.
Lifeline Group for floor sensor, sends:
- Sensor Multilevel Report
Max. nodes in group: 0
CONFIGURATION PARAMETERS
Z-Wave products are supposed to work out of the box after inclusion. Some
device configuration may, however, alter the functionality to better serve user
needs or unlock further enhanced features. All the parameters below do not
feature altering capabilities, advanced or read only flags.
PARA NO#| PARA SIZE (BYTE)| NAME| SHORT
DESCRIPTION / COMMENT| MIN| MAX| DEFAULT|
DESCRIPTION OF VALUE
---|---|---|---|---|---|---|---
1| 1| Disable buttons| Disable buttons, must be en- abled through the
parameter, or turned back on locally by holding the center and right button
for 30 seconds until the display shows “UNLK”.|
0
| | 0| Enabled, buttons on the front of the device work. (Default)
| | Disabled, buttons on the front of the device are disabled.
2| 1| Sensor mode (OPER)| Choose which sensor mode the device should operate
with.| 0| 1| F, Floor sensor
1| A, Internal sensor (Default)
2| AF, Internal sensor with floor sensor limitations
3| A2, External sensor
4| A2F, External sensor with floor sensor limitations
PARA NO#| PARA SIZE (BYTE)| NAME| SHORT
DESCRIPTION / COMMENT| MIN| MAX| DEFAULT|
DESCRIPTION OF VALUE
---|---|---|---|---|---|---|---
3
|
1
|
Sensor value (SEN)
|
Select the resistance value of the connected NTC.
| 0|
0
| 10KΩ (Default)
1| 12KΩ
2| 15KΩ
3| 22KΩ
4| 33KΩ
5| 47KΩ
6| 6.8KΩ
7| 100KΩ
4| 2| Internal sensor min temp limit| Decides the lowest tempera- ture allowed
by the thermostat when using sensor mode A.| 50| 400| 50| 5°C to 40°C
(Default is 5°C)
5| 2| Floor sensor min temp limit| Devices the lowest tempera- ture allowed by the thermostat when using sensor mode
AF, F, A2F.
| 50| 400| 50| 5°C to 40°C
(Default is 5°C)
6| 2| External sensor min temp limit| Decides the lowest tempera- ture allowed by the thermostat when using sensor mode
A2, A2F.
| 50| 400| 50| 5°C to 40°C
(Default is 5°C)
7| 2| Internal sensor max temp limit| Decide the highest tempera- ture allowed by the thermostat when using sensor mode A.| 50| 400| 400| 5°C to 40°C
(Default is 40°C)
8| 2| Floor sensor max temp limit| Decide the highest tempera- ture allowed by the thermostat when using sensor mode
AF, F, A2F.
| 50| 400| 400| 5°C to 40°C
(Default is 40°C)
9| 2| External sensor max temp limit| Decide the highest tempera- ture allowed by the thermostat when using sensor mode A2.| 50| 400| 400| 5°C to 40°C
(Default is 40°C)
10| 1| Internal sensor calibration (CAR)| Manually calibrate sensor A ±6°C.| -60| 60| 0| -6.0°C to 6.0°C
Calibrates the sensor by
±6°C. (Default is 0°C)
NB! To set a negative value, use 256 and subtract the desired value.
11| 1| Floor sensor calibration (CAF)| Manually calibrate sensor F ±6°C.| -60| 60| 0| -6.0°C to 6.0°C
Calibrates the sensor by
±6°C. (Default is 0°C)
NB! To set a negative value, use 256 and subtract the desired value.
12| 1| External sensor calibration (CAE)| Manually calibrate sensor A2 ±6°C.| -60| 60| 0| -6.0°C to 6.0°C.
Calibrates the sensor by
±6°C. (Default is 0°C)
NB! To set a negative value, use 256 and subtract the desired value.
13| 1| Regulation mode (REG)| Choose between regulation modes PWM and
Hysteresis.| 0| | 0| Hysteresis (Default)
| 1| PWM regulation
14| 1| Tempera- ture control hysteresis (HYST)| Choose the hysteresis used
when regulation mode is set to HYST.| 3| 30| 10| 0.3°C to 3.0°C.
Default is 10 (1.0°C)
15| 1| Tempera- ture display| Select what is shown on the display during
Standby state.| 0| | 0| Display setpoint tempera- ture. (Default)
| 1| Display measured temperature.
16| 1| Active display brightness (BR1)| Configure the brightness of the
display during active state.| 1| 10| 10| 10 to 100%
(Default 100%)
17| 1| Standby display brightness (BR2)| Configure the brightness of the display during standby state.| 1| 10| 5| 10 to 100%
(Default 50%)
18| 2| Tempera- ture report interval| Set the time interval between consecutive temperature reports.| 30| 65535| 840| 30 to 65535 seconds.
840s (14 min 5 sek) (Default)
19| 1| Tempera- ture report hysteresis| Set the change in temperature required to send a temperature report based on change.| 1| 100| 10| 0.1°C to 10°C
10 (1°C) (Default)
20| 2| Action after error| Decide how the device should react when the overheating features has turned OFF relay.|
0
|
0
| 0, device will turn off and show an error in the display. (Default)
10
|
65535
| 10 to 65535 seconds, de- vice will attempt to turn on again after an error
based on the delay specified. Will display error if off.
21| 2| Heating setpoint| Set setpoint for Heating mode.| 50| 400| 210| 5°C to
40°C.
21°C (Default)
22| 2| Cooling setpoint| Set setpoint for Cooling mode.| 50| 400| 180| 5°C to 40°C.
18°C (Default)
23| 2| ECO
setpoint
| Set setpoint for ECO mode.| 50| 400| 180| 5°C to 40°C.
18°C (Default)
24
|
2
| Thermostat state update interval| Set the time interval of how often the device updates Thermostat Setpoint set, Ther- mostat Mode set and Binary set to associated devices.|
0
| 43200| Sends only when changed.
30
|
65535
| 30 to 65535 seconds. 43200 seconds + when changed. (Default)
PARA NO#| PARA SIZE (BYTE)| NAME| SHORT
DESCRIPTION / COMMENT
| MIN| MAX| DEFAULT| DESCRIPTION OF VALUE
---|---|---|---|---|---|---|---
25| 1| Operating Mode (MODE)| Set the thermostat mode.| 0| 1| OFF
Thermostat will not operate
1| Heating mode (Default)
2| Cooling mode
3| ECO mode
26
|
1
| Open window detection|
Choose to enable or disable the Open windows detection.
| 0|
0
| Open window detection disabled. (Default)
1| Open windows detection enabled.
27
|
2
| Size of load| Allows the user to decide the power consumption of the connected load in 100W increments.| 0| | Uses power metering values. (Default)
1
|
99
| 1-99 = 100-9900 Watt
Allows the user to set the size of the load, used when connected to a contactor.
28| 1| Inverted output| Decides if the device output should be inverted.| 0|
0| Inverted output
1
29
|
1
|
Valve inactivity exercise
|
Relay will turn on to open valves for the selected amount of time after 30 days of inactivity.
| 0|
0
| Valves do not open periodically. (Default).
1 to 30 minutes, amount of time relays should be turned on for after 30 days
of relay inactivity.
1
|
30
COMMAND CLASSES
Additional information regarding Command Classes and their functionality:
Basic Command Class
A Basic command to the device will change the thermostat mode. Uses the
following values:
- 0x00 = OFF (0x00)
- 0xFF = HEAT (0x01)
- If the thermostat is in ECO or COOL mode, 0x00 will still change the mode to OFF. ECO or COOL cannot be enabled with a Basic Set command.
Meter Command Class
The device supports Meter Command Class Get, and the thermostat will only
respond on supported electric meter scales: kWh (accumulated) and Watt
(instant).
The device will report when asked:
- Rate type : Import (0x01)
- Meter type : Electric meter (0x01)
TYPE| SCALE| VALUE| SIZE| PRECISION| REPORT
HYSTERESIS
---|---|---|---|---|---
Electric| kWh| 0x01| 4| 1| 3600s and on state change, not configurable
Electric| W| 0x01| 4| 1| 3600s, state change and on change in LOAD parameter,
not configurable
Protection Command Class
- Protection Command Class allows you to disable local control of the thermostat, this is separately from the Child Lock function.
- To enable the Protection Command Class, either set Parameter 1 “Disable buttons” to value 1, enabling Local Protection State 0x02, or send a Protection Set with Local Protection State 0x01 or 0x02.
- During Protection State 0x01, the device is protected by a button sequence and allows for no local operation until it is unlocked. To unlock the thermostat while in Protection state 0x01, first press twice on the Left button, then press twice on the Right button and then finally twice on the Center button. This will unlock the thermostat until it goes back to standby, requiring you to unlock it again.
- Protection State to 0x02 means that no operation is possible and the thermostat can only be unlocked by setting Parameter 1 “Disable buttons” to 0, or by holding the Center and Right buttons for 30 seconds.
Thermostat Setpoint Command Class
Thermostat Setpoint is implemented with 3 setpoints, Heating, Cooling and ECO.
Supported setpoints are from 5°C – 40°C with 0.5°C increments.
Thermostat Mode Command Class
It is possible to change the operating mode of the thermostat by sending a
Thermostat Mode set command. The accessible operating modes are:
- 0x00: OFF (Thermostat regulation and display are deactivated).
- 0x01: Heating Mode (Thermostat regulation is active).
- 0x02: Cooling Mode (Thermostat regulation is inverted).
- 0x0B: ECO Mode (Thermostat regulation is active with a separate setpoint from Heating Mode).
Thermostat Operating State Command Class
The thermostat reports the operating state of the interal relay using this
Command Class.
- 0x00 = Idle
- 0x01 = Heating (used for Heating and ECO mode)
- 0x02 = Cooling
Indicator Command Class
The device supports the Indicator Command Class. The indicator Command Class
will flash the display.
Notification Command Class
The product features security features that announce any action using the
Notification Command Class.
The following commands are implemented:
NAME| VALUE| EVEN/ STAT| STATE VARIABLE|
STATE VARIABLE AFTER| NOTIFICATION NAME| VALUE
---|---|---|---|---|---|---
Heat alarm| 0x04| State| Heat sensor status| Idle| Overheating detected| 0x02
Binary Switch Command Class
Binary Switch commands are used to control external relays associated with
group 2.
Uses the following values:
- 0x00 = OFF
- 0xFF = ON
This Command Class is based on the operating state of the thermostat (relay on or off).
SUPPORTED COMMAND CLASSES
The following table lists all Command Classes supported by the Z-Wave device. The device supports S0, S2 Authenticated security and S2 Unauthenticated security.
ASSOCIATION| VERSION| INSECURE ON SECURE INCLUSION|
SECURE ON SECURE INCLUSION
---|---|---|---
Association| v2| | Yes
Association Group Information| v3| | Yes
Device Reset Locally Notification| v1| | Yes
Firmware Update MD| v5| | Yes
Indicator| v3| | Yes
Manufacturer Specific| v2| | Yes
Multi channel Association| v3| | Yes
Multi channel| v4| | Yes
Power level| v1| | Yes
Security| v1| Yes|
Security v2| v1| Yes|
Supervision| v1| Yes|
Transport Service| v2| Yes|
Version| v3| | Yes
Z-Wave Plus Information| v2| Yes|
Configuration| v4| | Yes
Basic| v2| | Yes
Notification| v11| | Yes
Meter| v5| | Yes
Sensor Multilevel| v11| | Yes
Protection| v1| | Yes
Thermostat Mode| v3| | Yes
Thermostat Operating State| v1| | Yes
Thermostat Setpoint| v3| | Yes
CONTROLLED COMMAND CLASSES
ASSOCIATION| VERSION| INSECURE ON SECURE INCLUSION|
SECURE ON SECURE INCLUSION
---|---|---|---
Binary Switch| 2| | Yes
THERMOSTAT DIMENSIONS
THERMOSTAT CONTROLS
CHART – DISPLAY MENU STRUCTURE
Hold the middle button for 5 seconds to enter menu.
Error messages in display
General display messages
PRODUCT INFO Heatit Z-TRM6 DC 3A
FEATURES
- Z-Wave thermostat
- Internal room sensor
- External room sensor (wired)
- Floor sensor
- Temperature limiter
- Boiler control
- Control of actuators
- 3 modes; Heat, Cool, Eco
- Hysteresis/PWM
- Temperature calibration
- Open window detection
- Relay status icon
- Supports encryption mode: S0, S2 Authenticated Class, S2 Unauthenticated Class
- Adjustable display brightness
- Single pole switch
- Lock mode/child lock
- Temperature read out in gateway
- Weekly schedule in gateway
- Manual power metering
- SmartStart
- Firmware update (OTA)
The product must be used with a security-enabled Z-Wave controller in order to fully utilize security/encryption.
TECHNICAL DATA
- Protocol Z-Wave, 868.4MHz
- Chip Z-Wave 800 chip
- Rated voltage 230VAC 50Hz
- Max load 3A 24VDC
- Max actuators 3x24VDC actuators
- Power consumption <2W
- Ambient temperature 5°C to 40°C
- Temperature range 5°C to 40°C
- Storage temperature -30°C to 70°C
- Hysteresis 0.3°C to 3.0°C (default 0.5°C)
- Humidity 10% to 85% RH
- Compatible with NTCsensor
- with values 6.8, 10, 12, 15, 22, 33, 47 or
- 100kΩ @ 25°C
- Range RF Min. 40 meter
- Screw terminals Max. 2.5mm2 2Nm
- IP Code IP21
- Size (LxWxH) 84 x 84 x 45mm
- Approvals Z-Wave Plus v2, CE, Nemko
MAINTENANCE
The device is maintenance-free. Indoor use only.
DISPOSAL GUIDELINES
- Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities. Contact your local government for information regarding the collection systems available. If electrical appliances are disposed of in landfills or dumps, hazardous substances can leak into the groundwater and get into the food chain, damaging health and well-being.
- We have designed this product in accordance with our strict quality requirements (ISO 9001) and environmental requirements (ISO 14001). All electrical installations must be carried out by an authorized electrical installer. The product must be installed in accordance with our installers manual and national building codes. Any wrongful installation, misuse or damage to the product is not covered under warranty.
- Heatit Controls AB can not be held liable for any type of errors or omittances in our product information. Product specifications may change without further notice.
Heatit Controls AB · Läkarvägen 4, 454 31 BRASTAD, SWEDEN Phone: +47 61 18 77 77 · post@heatit.com · heatit.com