FRIEDRICH RHPBZR Series Packaged Heat Pump
Product Information
Specifications
- Series: RHPBZR
- SEER Rating: 13.4
- Nominal Sizes: 2-5 Tons [7-17.6 kW]
- Base Rails: Sturdy 18-gauge G-90 sheet metal for separation between unit base and ground level, protecting from ground moisture and providing air circulation
- Duct Collar: Two round 14 duct collars are included for easy attachment of ducts
- Easy Access to Internal Components: Outdoor-section top cover is easily removed for access to the scroll compressor, outdoor fan motor, and refrigerant tubing; the Indoor-section top cover easily opens to access blower housing, motor, and indoor coil
- Indoor Motor and Blower System: Achieves a nominal 400 CFM per ton up to a minimum of .8 inches of static pressure
- Optional Electric Heat: Easily installed in the field with dual- or single-point power
- Gauge Ports: Two gauge ports inside the control box for easy and accurate measurement of high and low-pressure
- Foil-Faced Insulation: Securely glued and captured to the cabinet for better indoor air quality; Closed-cell insulation used on the base to prevent moisture absorption
- Drain Pan: Removable, sloped drain pan accessible through a small side panel for maintaining indoor air quality
- Low-Pressure Control: Standard on all models; High-pressure control standard on the -060 model
Product Usage Instructions
Installation
- Ensure proper sizing of the equipment by consulting with a contractor or visit www.energystar.gov for details.
- Place the unit on a flat surface, ensuring separation from the ground using the base rails.
- Attach the ducts to the provided duct collars, crimping them around the leading edge for secure installation.
- For easy maintenance and service, remove the outdoor section top cover to access the scroll compressor, outdoor fan motor, and refrigerant tubing.
- To access the blower housing, motor, and indoor coil, open the indoor-section top cover.
- If desired, optional electric heat can be installed in the field with dual- or single-point power.
- Measure high and low pressure accurately using the gauge ports located inside the control box.
- Maintain indoor air quality by regularly checking and cleaning the removable, sloped drain pan.
Operation
- Power on the unit using the designated power source.
- Set the desired temperature using the controls provided.
- Monitor the unit for any abnormal sounds or behavior.
- If any issues arise, consult the troubleshooting section of the user manual or contact customer support.
FAQ
Q: Can I install electric heat in this unit?
- A: Yes, optional electric heat can be easily installed in the field with either dual- or single-point power. It can also be specified as factory-installed.
Q: What is the SEER rating of this series?
- A: The SEER rating of the RHPBZR series is 13.4.
Q: How can I access the internal components for maintenance?
- A: The outdoor-section top cover can be easily removed to access the scroll compressor, outdoor fan motor, and refrigerant tubing.
- The indoor-section top cover also opens to access the blower housing, motor, and indoor coil.
Unit Features & Benefits
- The RHPBZR series of Packaged Heat Pumps are designed to be the quickest to install, easiest to service, and most reliable units in the industry – while still maintaining an affordable price.
- This platform provides you with a full line of nominal capacities from 2 through 5 tons. AHRI-certified at 13.4 SEER2.
- As with all units offered by Friedrich®, we started our design process with input from the customer.
- From the fan grille to the base rails, Friedrich has combined 30 years’ worth of package unit design experience with input from Dealers to meet the latest application requirements.
- Starting at the bottom, the base rails ( 1 ) allow for separation between the unit base and the ground level, protecting the base from ground moisture and providing air circulation around the unit.
- Constructed from sturdy 18-gauge G-90 sheet metal, the base rails also allow for easier maneuverability during installation.
- To provide flexibility in space-limited installations, the unit can be installed flush to the structure without blocking airflow over the outdoor coil or making any screws inaccessible for maintenance.
- Furthermore, the cabinet is a slim 33″ wide. Full-louver coil protection ( 2 ) makes Friedrich® unique in the industry and also totally protects the outdoor coil from vandalism and weather extremes.
- Two round 14″ duct collars ( 3) are included with the unit, which makes attaching the duct a snap. The collar is crimped around the leading edge, making it easier to install ducts onto the collar.
- A metal bead around the circumference prevents the attached ducting from sliding off after installation.
- Keeping service technicians in mind, Friedrich takes pride in providing easy access to internal components.
- The outdoor-section top cover ( 4 ) is easily removed to allow access to the scroll compressor ( 5 ), outdoor fan motor ( 6 ), and refrigerant tubing ( 7 ).
- The indoor-section top cover also easily opens to access the removable blower housing and motor ( 8). This also gains total access to the indoor coil for cleaning and service (9 ).
- The indoor motor and blower system will achieve a nominal 400 CFM per ton up to a minimum of .8 inches of static pressure, which helps to eliminate customer dissatisfaction over poor airflow brought about by high-static duct designs.
- Optional electric heat ( 10 ) can be easily installed in the field, with either dual- or single-point power, and is designed to be easily installed into the unit. Electric heat can also be specified as factory-installed.
- The controls are located in a large, easy-to-access control box ( 11), which provides plenty of space in which to troubleshoot. A demand defrost control ( 12) is used to manage the defrost cycle.
- The transformer ( 13) is protected by an in-line fuse, which protects the transformer during a low-voltage electrical short. The low-voltage ( 14 15) wiring connections are easily accessed and have ample room around which to maneuver.
- Troubleshooting is further aided with number- and color-coded wiring, which corresponds with the large, easy-to-read wiring diagram located on the inside of the control box access panel.
- High and low pressure can easily and accurately be measured using the two gauge ports ( 16 ) located inside the control box.
- A small side panel grants access to a removable, sloped drain pan ( 17 ), which helps to ensure indoor air quality (IAQ) throughout the life of the unit.
- “Patent 7,430,877”
- Foil-faced insulation is securely glued and captured to the cabinet. On the base of the unit, closed-cell insulation is used to prevent moisture from being absorbed and help reduce mold content to provide better indoor air quality.
- Friedrich® uses 100% scroll compressor technology (19) on packaged platforms.
- (Note: The RHPBZR uses a two-stage scroll compressor).
- Low-pressure control standard on all models (20).
- High-pressure control standard on -060 model.
Heat Pumps
Designates Metric Conversions
Available Models
RHPBZR024AJT000NA
RHPBZR024AJT101NA
RHPBZR030AJT000NA
RHPBZR030AJT101NA
RHPBZR036AJT000NA
RHPBZR036AJT101NA
RHPBZR042AJT000NA
RHPBZR042AJT151NA
RHPBZR048AJT000NA
RHPBZR048AJT151NA
RHPBZR060AJT000NA
RHPBZR060AJT201NA
- Note: Bold represents 2-stage compressor models.
- Further heater kits are available to purchase for field installation. Tinned evaporator coil options (AUA) are also available.
General Data
NOMINAL SIZES 2-5 TONS [7-17.6 kW]
Model RHPBZR- Series| 024AJT| 030AJT| 036AJT|
042AJT
---|---|---|---|---
Cooling Performance 1| | | | CONTINUED
Gross Cooling Capacity Btu [kW]| 24,000 [7.03]| 29,000 [8.5]| 36,200 [10.61]|
41,000 [12.01]
EER2/SEER2 2| 10.6/13.4| 10.6/13.4| 10.6/13.4| 10.6/13.4
Nominal CFM/AHRI Rated CFM [L/s]| 800/800 [378/378]| 1000/1000 [472/472]|
1200/1200 [566/566]| 1400/1400 [661/661]
AHRI Net Cooling Capacity Btu [kW]| 23,600 [6.91]| 28,200 [8.26]| 35,400
[10.37]| 40,000 [11.72]
Net Sensible Capacity Btu [kW]| 19,080 [5.59]| 23,450 [6.87]| 27,870 [8.17]|
30,770 [9.02]
Net Latent Capacity Btu [kW]| 4,520 [1.32]| 4,750 [1.39]| 7,530 [2.21]| 9,230
[2.7]
Net System Power [kW]| 2.03| 2.35| 3.15| 3.54
Heating Performance (Heat Pumps)| | | |
High Temp. Btuh [kW] Rating| 22,400 [6.56]| 27,000 [7.91]| 36,000 [10.55]|
37,400 [10.96]
System Power KW / COP| 1.94/3.42| 2.24/3.58| 3.16/3.44| 3.66/3.32
Low Temp. Btuh [kW] Rating| 12,600 [3.69]| 15,200 [4.45]| 20,800 [6.09]|
21,800 [6.39]
System Power KW / COP| 1.79/2.08| 2.01/2.3| 2.72/2.24| 2.98/2.2
HSPF2 3 ** (Btu/Watts-hr)| 6.7| 6.7| 6.7| 6.7
Compressor| | | |
No./Type| 1/Scroll| 1/Scroll| 1/Scroll| 1/Scroll
Outdoor Sound Rating (dB) 4| 78| 77| 80| 80
Outdoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm] OD| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 12.65 [1.18]| 20.57 [1.91]| 16.54 [1.54]| 26.9
[2.5]
Rows / FPI [FPcm]| 1 / 20 [8]| 2 / 16 [6]| 1 / 22 [9]| 2 / 18 [7]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Indoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm] OD| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 4.33 [0.4]| 4.33 [0.4]| 5.78 [0.54]| 5.78 [0.54]
Rows / FPI [FPcm]| 2 / 15 [6]| 3 / 13 [5]| 2 / 15 [6]| 3 / 13 [5]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Drain Connection No./Size in. [mm]| 1/0.75 [19.05]| 1/0.75 [19.05]| 1/1
[25.4]| 1/0.75 [19.05]
Outdoor Fan—Type| Propeller| Propeller| Propeller| Propeller
No. Used/Diameter in. [mm]| 1/24 [609.6]| 1/24 [609.6]| 1/24 [609.6]| 1/24
[609.6]
Drive Type/No. Speeds| Direct/1| Direct/1| Direct/1| Direct/1
CFM [L/s]| 3200 [1510]| 3200 [1510]| 3300 [1557]| 4000 [1888]
No. Motors/HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP
Motor RPM| 825| 825| 825| 1075
Indoor Fan—Type| FC Centrifugal| FC Centrifugal| FC Centrifugal| FC
Centrifugal
No. Used/Diameter in. [mm]| 1/10×9 [254×229]| 1/10×9 [254×229]| 1/12×9
[305×229]| 1/12×9 [305×229]
Drive Type| Direct| Direct| Direct| Direct
No. Speeds| Multiple| Multiple| Multiple| Multiple
No. Motors| 1| 1| 1| 1
Motor HP| 1/2| 1/2| 3/4| 3/4
Motor RPM| 1050| 1050| 1050| 1050
Motor Frame Size| 48| 48| 48| 48
Filter— Type| Field Supplied| Field Supplied| Field Supplied| Field
Supplied
Furnished| No| No| No| No
(NO.) Size Recommended in. [mm x mm x mm]| (1)1x20x20 [25x508x508]| (1)1x20x20
[25x508x508]| (1)1x24x24 [25x610x610]| (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]| 103.2 [2926]| 155 [4394]| 113 [3204]| 202.4
[5738]
Weights**| | | |
Net Weight lbs. [kg]| 302 [137]| 329 [149]| 350 [159]| 400 [181]
Ship Weight lbs. [kg]| 327 [148]| 354 [161]| 375 [170]| 425 [193]
NOMINAL SIZES 2-5 TONS [7-17.6 kW]
Model RHPBZR- Series | 048AJT | 060AJT |
---|---|---|
Cooling Performance 1 | ||
Gross Cooling Capacity Btu [kW] | 48,000 [14.06] | 58,500 [17.14] |
EER2/SEER2 2 | 10.6/13.4 | 10.6/13.4 |
Nominal CFM/AHRI Rated CFM [L/s] | 1600/1600 [755/755] | 2000/1900 [944/897] |
AHRI Net Cooling Capacity Btu [kW] | 46,500 [13.62] | 56,500 [16.55] |
Net Sensible Capacity Btu [kW] | 36,250 [10.62] | 45,090 [13.21] |
Net Latent Capacity Btu [kW] | 10,250 [3] | 11,410 [3.34] |
Net System Power [kW] | 4 | 5.09 |
Heating Performance (Heat Pumps) | ||
High Temp. Btuh [kW] Rating | 46,500 [13.62] | 57,500 [16.85] |
System Power KW / COP | 4.14/3.3 | 4.95/3 |
Low Temp. Btuh [kW] Rating | 26,800 [7.85] | 31,400 [9.2] |
System Power KW / COP | 3.62/2.1 | 4.26/2.16 |
HSPF2 3 **** (Btu/Watts-hr) | 6.7 | 6.7 |
Compressor | ||
No./Type | 1/Scroll | 1/Scroll |
Outdoor Sound Rating (dB) 4 | 77 | 80 |
Outdoor Coil—Fin Type | Louvered | Louvered |
Tube Type | Rifled | Rifled |
Tube Size in. [mm] OD | 0.375 [9.5] | 0.375 [9.5] |
Face Area sq. ft. [sq. m] | 2690 [249.91] | 32.39 [3.01] |
Rows / FPI [FPcm] | 2 / 18 [7] | 2 / 18 [7] |
Refrigerant Control | TX Valves | TX Valves |
Indoor Coil—Fin Type | Louvered | Louvered |
Tube Type | Rifled | Rifled |
Tube Size in. [mm] OD | 0.375 [9.5] | 0.375 [9.5] |
Face Area sq. ft. [sq. m] | 5.78 [0.54] | 5.78 [0.54] |
Rows / FPI [FPcm] | 3 / 13 [5] | 4 / 13 [5] |
Refrigerant Control | TX Valves | TX Valves |
Drain Connection No./Size in. [mm] | 1/1 [25.4] | 1/1 [25.4] |
Outdoor Fan—Type | Propeller | Propeller |
No. Used/Diameter in. [mm] | 1/24 [609.6] | 1/24 [609.6] |
Drive Type/No. Speeds | Direct/1 | Direct/1 |
CFM [L/s] | 4000 [1888] | 4000 [1888] |
No. Motors/HP | 1 at 1/3 HP | 1 at 1/2 HP |
Motor RPM | 1075 | 1075 |
Indoor Fan—Type | FC Centrifugal | FC Centrifugal |
No. Used/Diameter in. [mm] | 1/12×9 [305×229] | 1/12×9 [305×229] |
Drive Type | Direct | Direct |
No. Speeds | Multiple | Multiple |
No. Motors | 1 | 1 |
Motor HP | 3/4 | 1 |
Motor RPM | 1050 | 1050 |
Motor Frame Size | 48 | 48 |
Filter— Type | Field Supplied | Field Supplied |
Furnished | No | No |
(NO.) Size Recommended in. [mm x mm x mm] | (1)1x24x24 [25x610x610] | (1)1x24x24 |
[25x610x610]
Refrigerant Charge Oz. [g]| 175 [4961]| 212 [6010]
Weights| |
Net Weight lbs. [kg]| 397 [180]| 429 [195]
Ship Weight lbs. [kg]| 422 [191]| 454 [206]
See Page 10 for Notes.| | [ ] Designates Metric Conversions
NOTES:
- Cooling Performance is rated at 95°F ambient, 80°F entering the dry bulb, and 67°F entering the wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified under the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
- EER2 and/or SEER2 are rated at ARI conditions and under DOE test procedures for 1-phase models. EER and/or SEER are rated at ARI conditions and under DOE test procedures for 3-phase models.
- HSPF2 is rated at ARI conditions and under DOE test procedures for 1-phase models. HSPF is rated at ARI conditions and under DOE test procedures for 3-phase models.
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR024AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 900 [425]| 800 [378]| 650
[307]| 900 [425]| 800 [378]| 650 [307]|
900 [425]| 800 [378]| 650 [307]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 30.0 [8.8]
17.5 [5.1]
1.7
| 29.4 [8.6]
16.5 [4.8]
1.7
| 28.4 [8.3]
15.1 [4.4]
1.6
| 28.1 [8.2]
21.0 [6.2]
1.7
| 27.5 [8.1]
19.9 [5.8]
1.7
| 26.6 [7.8]
18.1 [5.3]
1.6
| 26.8 [7.9]
24.4 [7.2]
1.7
| 26.2 [7.7]
23.1 [6.8]
1.7
| 25.3 [7.4]
21.1 [6.2]
1.6
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 29.2 [8.6]
17.2 [5.0]
1.8
| 28.5 [8.4]
16.2 [4.7]
1.7
| 27.6 [8.1]
14.8 [4.3]
1.7
| 27.3 [8.0]
20.7 [6.1]
1.8
| 26.7 [7.8]
19.6 [5.7]
1.7
| 25.8 [7.6]
17.9 [5.2]
1.7
| 25.9 [7.6]
24.1 [7.1]
1.8
| 25.4 [7.4]
22.8 [6.7]
1.7
| 24.5 [7.2]
20.8 [6.1]
1.7
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 28.3 [8.3]
16.8 [4.9]
1.9
| 27.6 [8.1]
15.9 [4.7]
1.8
| 26.7 [7.8]
14.5 [4.2]
1.8
| 26.3 [7.7]
20.4 [6.0]
1.9
| 25.8 [7.6]
19.2 [5.6]
1.8
| 24.9 [7.3]
17.6 [5.2]
1.8
| 25.0 [7.3]
23.8 [7.0]
1.9
| 24.5 [7.2]
22.5 [6.6]
1.8
| 23.6 [6.9]
20.5 [6.0]
1.8
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 27.3 [8.0]
16.4 [4.8]
2.0
| 26.7 [7.8]
15.5 [4.5]
1.9
| 25.8 [7.6]
14.2 [4.2]
1.9
| 25.4 [7.4]
20.0 [5.9]
2.0
| 24.8 [7.3]
18.9 [5.5]
1.9
| 24.0 [7.0]
17.2 [5.0]
1.9
| 24.0 [7.0]
23.4 [6.9]
2.0
| 23.5 [6.9]
22.1 [6.5]
1.9
| 22.7 [6.7]
20.2 [5.9]
1.9
95
[35]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 26.2 [7.7]
16.0 [4.7]
2.1
| 25.7 [7.5]
15.1 [4.4]
2.0
| 24.8 [7.3]
13.8 [4.0]
2.0
| 24.3 [7.1]
19.6 [5.7]
2.1
| 23.8 [7.0]
18.5 [5.4]
2.0
| 23.0 [6.7]
16.9 [5.0]
2.0
| 23.0 [6.7]
23.0 [6.7]
2.1
| 22.5 [6.6]
21.7 [6.4]
2.0
| 21.7 [6.4]
19.8 [5.8]
2.0
100
[37.8]
| Total BTUH [kW]
Sens BTUH [kW] Power
| 25.1 [7.4]
15.6 [4.6]
2.2
| 24.6 [7.2]
14.7 [4.3]
2.2
| 23.7 [6.9]
13.4 [3.9]
2.1
| 23.2 [6.8]
19.1 [5.6]
2.2
| 22.7 [6.7]
18.0 [5.3]
2.2
| 21.9 [6.4]
16.5 [4.8]
2.1
| 21.9 [6.4]
21.9 [6.4]
2.2
| 21.4 [6.3]
21.3 [6.2]
2.2
| 20.7 [6.1]
19.4 [5.7]
2.1
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 24.0 [7.0]
15.1 [4.4]
2.3
| 23.5 [6.9]
14.2 [4.2]
2.3
| 22.7 [6.7]
13.0 [3.8]
2.2
| 22.1 [6.5]
18.6 [5.5]
2.3
| 21.6 [6.3]
17.6 [5.2]
2.3
| 20.8 [6.1]
16.0 [4.7]
2.2
| 20.7 [6.1]
20.7 [6.1]
2.3
| 20.3 [5.9]
20.3 [5.9]
2.3
| 19.6 [5.7]
19.0 [5.6]
2.2
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 22.8 [6.7]
14.5 [4.2]
2.4
| 22.3 [6.5]
13.7 [4.0]
2.4
| 21.5 [6.3]
12.5 [3.7]
2.4
| 20.9 [6.1]
18.1 [5.3]
2.4
| 20.4 [6.0]
17.1 [5.0]
2.4
| 19.7 [5.8]
15.6 [4.6]
2.4
| 19.5 [5.7]
19.5 [5.7]
2.4
| 19.1 [5.6]
19.1 [5.6]
2.4
| 18.4 [5.4]
18.4 [5.4]
2.4
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 21.5 [6.3]
14.0 [4.1]
2.6
| 21.0 [6.2]
13.2 [3.9]
2.5
| 20.3 [5.9]
12.1 [3.5]
2.5
| 19.6 [5.7]
17.5 [5.1]
2.6
| 19.1 [5.6]
16.6 [4.9]
2.5
| 18.5 [5.4]
15.1 [4.4]
2.5
| 18.2 [5.3]
18.2 [5.3]
2.6
| 17.8 [5.2]
17.8 [5.2]
2.5
| 17.2 [5.0]
17.2 [5.0]
2.5
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 20.2 [5.9]
13.4 [3.9]
2.7
| 19.7 [5.8]
12.7 [3.7]
2.7
| 19.0 [5.6]
11.6 [3.4]
2.6
| 18.2 [5.3]
1.07 [5.0]
2.7
| 17.8 [5.2]
16.0 [4.7]
2.7
| 17.2 [5.0]
14.6 [4.3]
2.6
| 16.9 [5.0]
16.9 [5.0]
2.7
| 16.5 [4.8]
16.5 [4.8]
2.7
| 16.0 [4.7]
16.0 [4.7]
2.6
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 18.8 [5.5]
12.8 [3.8]
2.9
| 18.4 [5.4]
12.1 [3.5]
2.8
| 17.7 [5.2]
11.0 [3.2]
2.8
| 16.9 [5.0]
16.3 [4.8]
2.9
| 16.5 [4.8]
15.4 [4.5]
2.8
| 15.9 [4.7]
14.1 [4.1]
2.8
| 15.5 [4.5]
15.5 [4.5]
2.9
| 15.2 [4.5]
15.2 [4.5]
2.8
| 14.7 [4.3]
14.7 [4.3]
2.8
- DR —Depression ratio dbE —Entering air dry bulb wbE —Entering air wet bulb
- Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power —KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR030AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 1075 [507]| 1000 [472]| 775
[366]| 1075 [507]| 1000 [472]| 775 [366]|
1075 [507]| 1000 [472]| 775 [366]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 32.5 [9.5]
19.7 [5.8]
1.9
| 32.1 [9.4]
19.0 [5.6]
1.9
| 30.8 [9.0]
17.0 [5.0]
1.9
| 31.1 [9.1]
24.4 [7.2]
1.9
| 30.7 [9.0]
23.5 [6.9]
1.9
| 29.4 [8.6]
21.1 [6.2]
1.9
| 30.2 [8.9]
28.3 [8.3]
1.9
| 29.8 [8.7]
27.3 [8.0]
1.9
| 28.5 [8.4]
24.5 [7.2]
1.9
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 32.2 [9.4]
19.9 [5.8]
2.0
| 31.7 [9.3]
19.2 [5.6]
2.0
| 30.4 [8.9]
17.2 [5.0]
2.0
| 30.8 [9.0]
24.6 [7.2]
2.0
| 30.3 [8.9]
23.7 [6.9]
2.0
| 29.1 [8.5]
21.2 [6.2]
2.0
| 29.8 [8.7]
28.5 [8.4]
2.0
| 29.4 [8.6]
27.5 [8.1]
2.0
| 28.2 [8.3]
24.6 [7.2]
2.0
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 31.7 [9.3]
20.0 [5.9]
2.2
| 31.2 [9.1]
19.3 [5.7]
2.1
| 30.0 [8.8]
17.3 [5.1]
2.1
| 30.3 [8.9]
24.6 [7.2]
2.1
| 29.9 [8.8]
23.8 [7.0]
2.1
| 28.6 [8.4]
21.3 [6.2]
2.1
| 29.3 [8.6]
28.6 [8.4]
2.1
| 28.9 [8.5]
27.6 [8.1]
2.1
| 27.7 [8.1]
24.7 [7.2]
2.1
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 31.0 [9.1]
19.9 [5.8]
2.3
| 30.6 [9.0]
19.2 [5.6]
2.3
| 29.4 [8.6]
17.2 [5.0]
2.2
| 29.6 [8.7]
24.6 [7.2]
2.3
| 29.2 [8.6]
23.8 [7.0]
2.2
| 28.0 [8.2]
21.3 [6.2]
2.2
| 28.7 [8.4]
28.5 [8.4]
2.2
| 28.3 [8.3]
27.6 [8.1]
2.2
| 27.1 [7.9]
24.7 [7.2]
2.2
95
[35]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 30.2 [8.9]
19.7 [5.8]
2.4
| 29.8 [8.7]
19.1 [5.6]
2.4
| 28.6 [8.4]
17.1 [5.0]
2.3
| 28.8 [8.4]
24.4 [7.2]
2.4
| 28.5 [8.4]
23.6 [6.9]
2.4
| 27.3 [8.0]
21.1 [6.2]
2.3
| 27.9 [8.2]
27.9 [8.2]
2.4
| 27.5 [8.1]
27.4 [8.0]
2.3
| 26.4 [7.7]
24.5 [7.2]
2.3
100
[37.8]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 29.3 [8.6]
19.4 [5.7]
2.5
| 28.9 [8.5]
18.8 [5.5]
2.5
| 27.8 [8.1]
16.8 [4.9]
2.5
| 27.9 [8.2]
24.1 [7.1]
2.5
| 27.6 [8.1]
23.3 [6.8]
2.5
| 26.4 [7.7]
20.9 [6.1]
2.4
| 27.0 [7.9]
27.0 [7.9]
2.5
| 26.6 [7.8]
26.6 [7.8]
2.5
| 25.5 [7.5]
24.3 [7.1]
2.4
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 28.3 [8.3]
19.0 [5.6]
2.7
| 27.9 [8.2]
18.4 [5.4]
2.6
| 26.7 [7.8]
16.5 [4.8]
2.6
| 26.9 [7.9]
23.7 [6.9]
2.6
| 26.5 [7.8]
22.9 [6.7]
2.6
| 25.4 [7.4]
20.5 [6.0]
2.6
| 25.9 [7.6]
25.9 [7.6]
2.6
| 25.6 [7.5]
25.6 [7.5]
2.6
| 24.5 [7.2]
23.9 [7.0]
2.6
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 27.1 [7.9]
18.5 [5.4]
2.8
| 26.7 [7.8]
17.9 [5.2]
2.8
| 25.6 [7.5]
16.0 [4.7]
2.7
| 25.7 [7.5]
23.2 [6.8]
2.8
| 25.3 [7.4]
22.4 [6.6]
2.8
| 24.3 [7.1]
20.0 [5.9]
2.7
| 24.7 [7.2]
24.7 [7.2]
2.8
| 24.4 [7.2]
24.4 [7.2]
2.7
| 23.4 [6.9]
23.4 [6.9]
2.7
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 25.7 [7.5]
17.8 [5.2]
2.9
| 25.4 [7.4]
17.2 [5.0]
2.9
| 24.3 [7.1]
15.4 [4.5]
2.9
| 24.3 [7.1]
22.5 [6.6]
2.9
| 24.0 [7.0]
21.7 [6.4]
2.9
| 23.0 [6.7]
19.4 [5.7]
2.8
| 23.4 [6.9]
23.4 [6.9]
2.9
| 23.1 [6.8]
23.1 [6.8]
2.9
| 22.1 [6.5]
22.1 [6.5]
2.8
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 24.2 [7.1]
17.0 [5.0]
3.1
| 23.9 [7.0]
16.4 [4.8]
3.1
| 22.9 [6.7]
14.7 [4.3]
3.0
| 22.8 [6.7]
21.7 [6.4]
3.1
| 22.5 [6.6]
21.0 [6.2]
3.0
| 21.6 [6.3]
18.8 [5.5]
3.0
| 21.9 [6.4]
21.9 [6.4]
3.1
| 21.6 [6.3]
21.6 [6.3]
3.0
| 20.7 [6.1]
20.7 [6.1]
3.0
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 22.6 [6.6]
16.1 [4.7]
3.2
| 22.3 [6.5]
15.5 [4.5]
3.2
| 21.4 [6.3]
13.9 [4.1]
3.2
| 21.2 [6.2]
20.8 [6.1]
3.2
| 20.9 [6.1]
20.1 [5.9]
3.2
| 20.1 [5.9]
18.0 [5.3]
3.1
| 20.3 [5.9]
20.3 [5.9]
3.2
| 20.0 [5.9]
20.0 [5.9]
3.2
| 19.2 [5.6]
19.2 [5.6]
3.1
- DR —Depression ratio dbE —Entering air dry bulb wbE —Entering air wet bulb
- Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power —KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR036AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 1325 [625]| 1200 [566]| 975
[460]| 1325 [625]| 1200 [566]| 975 [460]|
1325 [625]| 1200 [566]| 975 [460]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 43.4 [12.7]
26.4 [7.7]
2.6
| 42.6 [12.5]
25.2 [7.4]
2.6
| 41.1 [12.0]
23.0 [6.7]
2.5
| 41.2 [12.1]
31.6 [9.3]
2.6
| 40.4 [11.8]
30.2 [8.9]
2.5
| 39.1 [11.5]
27.5 [8.1]
2.5
| 39.0 [11.4]
36.2 [10.6]
2.5
| 38.3 [11.2]
34.5 [10.1]
2.5
| 37.0 [10.8]
31.5 [9.2]
2.5
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 42.1 [12.3]
25.6 [7.5]
2.7
| 41.3 [12.1]
24.4 [7.2]
2.7
| 39.9 [11.7]
22.2 [6.5]
2.7
| 40v [11.7]
30.8 [9.0]
2.7
| 39.2 [11.5]
29.4 [8.6]
2.7
| 37.9 [11.1]
26.8 [7.9]
2.6
| 37.8 [11.1]
35.3 [10.3]
2.7
| 37.1 [10.9]
33.7 [9.9]
2.7
| 35.8 [10.5]
30.7 [9.0]
2.6
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 40.9 [12.0]
24.8 [7.3]
2.9
| 40.1 [11.8]
23.7 [6.9]
2.9
| 38.8 [11.4]
21.6 [6.3]
2.8
| 38.7 [11.3]
30.0 [8.8]
2.9
| 38.0 [11.1]
28.6 [8.4]
2.8
| 36.7 [10.8]
26.1 [7.6]
2.8
| 36.6 [10.7]
34.6 [10.1]
2.9
| 35.9 [10.5]
33.0 [9.7]
2.8
| 34.7 [10.2]
30.1 [8.8]
2.8
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 39.6 [11.6]
24.1 [7.1]
3.1
| 38.9 [11.4]
23.0 [6.7]
3.0
| 37.6 [11.0]
21.0 [6.2]
3.0
| 37.5 [11.0]
29.3 [8.6]
3.0
| 36.8 [10.8]
28.0 [8.2]
3.0
| 35.5 [10.4]
25.5 [7.5]
3.0
| 35.3 [10.3]
33.9 [9.9]
3.0
| 34.7 [10.2]
32.3 [9.5]
3.0
| 33.5 [9.8]
29.5 [8.6]
2.9
95
[35]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 38.4 [11.3]
23.5 [6.9]
3.2
| 37.7 [11.0]
22.4 [6.6]
3.2
| 36.4 [10.7]
20.5 [6.0]
3.1
| 36.2 [10.6]
28.7 [8.4]
3.2
| 35.6 [10.4]
27.4 [8.0]
3.2
| 34.4 [10.1]
25.0 [7.3]
3.1
| 34.1 [10.0]
33.3 [9.8]
3.2
| 33.4 [9.8]
31.7 [9.3]
3.2
| 32.3 [9.5]
29.0 [8.5]
3.1
100
[37.8]
| Total BTUH [kW]
Sens BTUH [kW] Power
| 37.2 [10.9]
23.0 [6.7]
3.4
| 36.5 [10.7]
21.9 [6.4]
3.4
| 35.2 [10.3]
20.0 [5.9]
3.3
| 35.0 [10.3]
28.2 [8.3]
3.4
| 34.3 [10.1]
26.9 [7.9]
3.4
| 33.2 [9.7]
24.6 [7.2]
3.3
| 32.8 [9.6]
32.8 [9.6]
3.4
| 32.2 [9.4]
31.2 [9.1]
3.4
| 31.1 [9.1]
28.5 [8.4]
3.3
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 35.9 [10.5]
22.6 [6.6]
3.6
| 35.3 [10.3]
21.5 [6.3]
3.6
| 34.1 [10.0]
19.6 [5.7]
3.5
| 33.8 [9.9]
27.8 [8.1]
3.6
| 33.1 [9.7]
26.5 [7.8]
3.6
| 32.0 [9.4]
24.2 [7.1]
3.5
| 31.6 [9.3]
31.6 [9.3]
3.6
| 31.0 [9.1]
30.8 [9.0]
3.5
| 29.9 [8.8]
28.1 [8.2]
3.5
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 34.7 [10.2]
22.2 [6.5]
3.8
| 34.0 [10.0]
21.2 [6.2]
3.8
| 32.9 [9.6]
19.3 [5.7]
3.7
| 32.5 [9.5]
27.4 [8.0]
3.8
| 31.9 [9.3]
26.2 [7.7]
3.8
| 30.8 [9.0]
23.9 [7.0]
3.7
| 30.3 [8.9]
30.3 [8.9]
3.8
| 29.8 [8.7]
29.8 [8.7]
3.7
| 28.8 [8.4]
27.8 [8.1]
3.7
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 33.4 [9.8]
21.9 [6.4]
4.0
| 32.8 [9.6]
20.9 [6.1]
4.0
| 31.7 [9.3]
19.1 [5.6]
3.9
| 31.3 [9.2]
27.2 [8.0]
4.0
| 30.7 [9.0]
25.9 [7.6]
4.0
| 29.6 [8.7]
23.6 [6.9]
3.9
| 29.1 [8.5]
29.1 [8.5]
4.0
| 28.6 [8.4]
28.6 [8.4]
4.0
| 27.6 [8.1]
27.6 [8.1]
3.9
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 32.2 [9.4]
21.8 [6.4]
4.2
| 31.6 [9.3]
20.7 [6.1]
4.2
| 30.5 [8.9]
18.9 [5.5]
4.1
| 30.0 [8.8]
27.0 [7.9]
4.2
| 29.5 [8.6]
25.7 [7.5]
4.2
| 28.5 [8.4]
23.5 [6.9]
4.1
| 27.9 [8.2]
27.9 [8.2]
4.2
| 27.3 [8.0]
27.3 [8.0]
4.2
| 26.4 [7.7]
26.4 [7.7]
4.1
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 31.0 [9.1]
21.7 [6.4]
4.5
| 30.4 [8.9]
20.6 [6.0]
4.4
| 29.4 [8.6]
18.8 [5.5]
4.3
| 28.8 [8.4]
26.9 [7.9]
4.4
| 28.3 [8.3]
25.6 [7.5]
4.4
| 27.3 [8.0]
23.4 [6.9]
4.3
| 26.6 [7.8]
26.6 [7.8]
4.4
| 26.1 [7.6]
26.1 [7.6]
4.4
| 25.2 [7.4]
25.2 [7.4]
4.3
- DR —Depression ratio
- dbE —Entering air dry bulb
- wbE —Entering air wet bulb
- Total —Total capacity x 1000 BTUH
- Sens —Sensible capacity x 1000 BTUH
- Power —KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR042AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 1575 [743]| 1400 [661]| 1125
[531]| 1575 [743]| 1400 [661]| 1125 [531]|
1575 [743]| 1400 [661]| 1125 [531]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 52.8 [15.5]
32.6 [9.6]
3.0
| 51.6 [15.1]
30.8 [9.0]
2.9
| 49.8 [14.6]
28.0 [8.2]
2.9
| 49.8 [14.6]
38.3 [11.2]
2.9
| 48.7 [14.3]
36.2 [10.6]
2.9
| 47.0 [13.8]
32.9 [9.6]
2.8
| 46.8 [13.7]
41.0 [12.0]
2.9
| 45.8 [13.4]
38.8 [11.4]
2.9
| 44.1 [12.9]
35.2 [10.3]
2.8
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 51.0 [14.9]
31.4 [9.2]
3.1
| 49.9 [14.6]
29.6 [8.7]
3.1
| 48.1 [14.1]
26.9 [7.9]
3.0
| 48 .0[14.1]
37.1 [10.9]
3.1
| 46.9 [13.7]
35.0 [10.3]
3.0
| 45.3 [13.3]
31.8 [9.3]
3.0
| 45.0 [13.2]
39.8 [11.7]
3.0
| 44.0 [12.9]
37.6 [11.0]
3.0
| 42.4 [12.4]
34.1 [10.0]
3.0
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW] Power| 49.2 [14.4]
30.3 [8.9]
3.3
| 48.1 [14.1]
28.6 [8.4]
3.2
| 46.4 [13.6]
26.0 [7.6]
3.2
| 46.2 [13.5]
35.9 [10.5]
3.2
| 45.2 [13.2]
34.0 [10.0]
3.2
| 43.6 [12.8]
30.9 [9.1]
3.1
| 43.2 [12.7]
38.7 [11.3]
3.2
| 42.3 [12.4]
36.5 [10.7]
3.2
| 40.7 [11.9]
33.2 [9.7]
3.1
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW] Power| 47.4 [13.9]
29.3 [8.6]
3.4
| 46.4 [13.6]
27.6 [8.1]
3.4
| 44.7 [13.1]
25.1 [7.4]
3.3
| 44.4 [13.0]
35.0 [10.3]
3.4
| 43.4 [12.7]
33.0 [9.7]
3.4
| 41.9 [12.3]
30.0 [8.8]
3.3
| 41.4 [12.1]
37.7 [11.0]
3.4
| 40.5 [11.9]
35.6 [10.4]
3.3
| 39.1 [11.5]
32.3 [9.5]
3.3
95
[35]
| Total BTUH [kW] Sens BTUH [kW] Power| 45.7 [13.4]
28.4 [8.3]
3.6
| 44.6 [13.1]
26.8 [7.9]
3.5
| 43.0 [12.6]
24.4 [7.2]
3.5
| 42.6 [12.5]
34.1 [10.0]
3.6
| 41.7 [12.2]
32.2 [9.4]
3.5
| 40.2 [11.8]
29.3 [8.6]
3.5
| 39.6 [11.6]
36.8 [10.8]
3.5
| 38.8 [11.4]
34.8 [10.2]
3.5
| 37.4 [11.0]
31.6 [9.3]
3.4
100
[37.8]
| Total BTUH [kW] Sens BTUH [kW] Power| 43.9 [12.9]
27.6 [8.1]
3.8
| 42.9 [12.6]
26.1 [7.6]
3.7
| 41.4 [12.1]
23.7 [6.9]
3.7
| 40.9 [12.0]
33.3 [9.8]
3.7
| 39.9 [11.7]
31.5 [9.2]
3.7
| 38.5 [11.3]
28.6 [8.4]
3.6
| 37.8 [11.1]
36.0 [10.6]
3.7
| 37.0 [10.8]
34.1 [10.0]
3.7
| 35.7 [10.5]
30.9 [9.1]
3.6
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW] Power| 42.1 [12.3]
27.0 [7.9]
3.9
| 41.1 [12.0]
25.5 [7.5]
3.9
| 39.7 [11.6]
23.2 [6.8]
3.8
| 39.1 [11.5]
32.7 [9.6]
3.9
| 38.2 [11.2]
30.9 [9.1]
3.9
| 36.8 [10.8]
28.1 [8.2]
3.8
| 36.1 [10.6]
35.4 [10.4]
3.9
| 35.3 [10.3]
33.5 [9.8]
3.8
| 34.0 [10.0]
30.4 [8.9]
3.8
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW] Power| 40.3 [11.8]
26.5 [7.8]
4.1
| 39.4 [11.5]
25.0 [7.3]
4.1
| 38.0 [11.1]
22.7 [6.7]
4.0
| 37.3 [10.9]
32.2 [9.4]
4.1
| 36.4 [10.7]
30.4 [8.9]
4.0
| 35.1 [10.3]
27.6 [8.1]
4.0
| 34.3 [10.1]
34.3 [10.1]
4.1
| 33.5 [9.8]
33.0 [9.7]
4.0
| 32.3 [9.5]
30.0 [8.8]
3.9
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 38.5 [11.3]
26.1 [7.6]
4.3
| 37.6 [11.0]
24.7 [7.2]
4.3
| 36.3 [10.6]
22.4 [6.6]
4.2
| 35.5 [10.4]
31.8 [9.3]
4.3
| 34.7 [10.2]
30.1 [8.8]
4.2
| 33.5 [9.8]
27.3 [8.0]
4.2
| 32.5 [9.5]
32.5 [9.5]
4.2
| 31.8 [9.3]
31.8 [9.3]
4.2
| 30.6 [9.0]
29.6 [8.7]
4.1
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 36.7 [10.8]
25.8 [7.6]
4.5
| 35.9 [10.5]
24.4 [7.2]
4.5
| 34.6 [10.1]
22.2 [6.5]
4.4
| 33.7 [9.9]
31.5 [9.2]
4.5
| 33.0 [9.7]
29.8 [8.7]
4.4
| 31.8 [9.3]
27.1 [7.9]
4.3
| 30.7 [9.0]
30.7 [9.0]
4.4
| 30.0 [8.8]
30.0 [8.8]
4.4
| 28.9 [8.5]
28.9 [8.5]
4.3
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 34.9 [10.2]
25.7 [7.5]
4.7
| 34.1 [10.0]
24.3 [7.1]
4.7
| 32.9 [9.6]
22.1 [6.5]
4.6
| 31.9 [9.3]
31.4 [9.2]
4.7
| 31.2 [9.1]
29.7 [8.7]
4.6
| 30.1 [8.8]
26.9 [7.9]
4.5
| 28.9 [8.5]
28.9 [8.5]
4.6
| 28.3 [8.3]
28.3 [8.3]
4.6
| 27.2 [8.0]
27.2 [8.0]
4.5
- DR —Depression ratio
- dbE —Entering air dry bulb
- wbE—Entering air wet bulb
- Total —Total capacity x 1000 BTUH
- Sens —Sensible capacity x 1000 BTUH
- Power—KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR048AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 1775 [838]| 1600 [755]| 1275
[602]| 1775 [838]| 1600 [755]| 1275 [602]|
1775 [838]| 1600 [755]| 1275 [602]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 58.7 [17.2]
34.9 [10.2]
3.4
| 57.6 [16.9]
33.2 [9.7]
3.3
| 55.5 [16.3]
30.1 [8.8]
3.3
| 55.5 [16.3]
41.7 [12.2]
3.3
| 54.4 [15.9]
39.7 [11.6]
3.3
| 52.4 [15.4]
36.0 [10.6]
3.3
| 52.3 [15.3]
47.2 [13.8]
3.3
| 51.3 [15.0]
44.9 [13.2]
3.3
| 49.4 [14.5]
40.7 [11.9]
3.2
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 56.9 [16.7]
34.1 [10.0]
3.5
| 55.8 [16.4]
32.5 [9.5]
3.5
| 53.7 [15.7]
29.4 [8.6]
3.4
| 53.7 [15.7]
41.0 [12.0]
3.5
| 52.6 [15.4]
39.0 [11.4]
3.5
| 50.7 [14.9]
35.3 [10.3]
3.4
| 50.4 [14.8]
46.4 [13.6]
3.5
| 49.5 [14.5]
44.2 [13.0]
3.5
| 47.6 [14.0]
40.0 [11.7]
3.4
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 55.1 [16.1]
33.3 [9.8]
3.7
| 54.0 [15.8]
31.7 [9.3]
3.7
| 52.0 [15.2]
28.7 [8.4]
3.6
| 51.8 [15.2]
40.2 [11.8]
3.7
| 50.8 [14.9]
38.2 [11.2]
3.6
| 49.0 [14.4]
34.6 [10.1]
3.6
| 48.6 [14.2]
45.6 [13.4]
3.7
| 47.7 [14.0]
43.4 [12.7]
3.6
| 45.9 [13.5]
39.3 [11.5]
3.6
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 53.2 [15.6]
32.5 [9.5]
3.9
| 52.2 [15.3]
30.9 [9.1]
3.8
| 50.3 [14.7]
28.0 [8.2]
3.8
| 50.0 [14.7]
39.4 [11.5]
3.9
| 49.0 [14.4]
37.5 [11.0]
3.8
| 47.2 [13.8]
33.9 [9.9]
3.8
| 46.8 [13.7]
44.8 [13.1]
3.8
| 45.9 [13.5]
42.7 [12.5]
3.8
| 44.2 [13.0]
38.6 [11.3]
3.7
95
[35]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 51.4 [15.1]
31.7 [9.3]
4.1
| 50.4 [14.8]
30.2 [8.9]
4.0
| 48.5 [14.2]
27.3 [8.0]
4.0
| 48.2 [14.1]
38.6 [11.3]
4.1
| 47.2 [13.8]
36.7 [10.8]
4.0
| 45.5 [13.3]
33.2 [9.7]
3.9
| 44.9 [13.2]
44.0 [12.9]
4.0
| 44.1 [12.9]
41.9 [12.3]
4.0
| 42.4 [12.4]
37.9 [11.1]
3.9
100
[37.8]
| Total BTUH [kW]
Sens BTUH [kW] Power
| 49.6 [14.5]
30.9 [9.1]
4.3
| 48.6 [14.2]
29.4 [8.6]
4.2
| 46.8 [13.7]
26.6 [7.8]
4.2
| 46.3 [13.6]
37.7 [11.0]
4.3
| 45.4 [13.3]
35.9 [10.5]
4.2
| 43.7 [12.8]
32.5 [9.5]
4.1
| 43.1 [12.6]
43.1 [12.6]
4.2
| 42.3 [12.4]
41.1 [12.0]
4.2
| 40.7 [11.9]
37.2 [10.9]
4.1
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 47.7 [14.0]
30.0 [8.8]
4.5
| 46.8 [13.7]
28.6 [8.4]
4.4
| 45.1 [13.2]
25.9 [7.6]
4.4
| 44.5 [13.0]
36.9 [10.8]
4.5
| 43.6 [12.8]
35.1 [10.3]
4.4
| 42.0 [12.3]
31.8 [9.3]
4.3
| 41.3 [12.1]
41.3 [12.1]
4.4
| 40.5 [11.9]
40.3 [11.8]
4.4
| 39.0 [11.4]
36.5 [10.7]
4.3
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW]
Power
| 45.9 [13.5]
29.2 [8.6]
4.7
| 45.0 [13.2]
27.8 [8.1]
4.7
| 43.3 [12.7]
25.2 [7.4]
4.6
| 42.7 [12.5]
36.1 [10.6]
4.7
| 41.8 [12.3]
34.3 [10.1]
4.6
| 40.3 [11.8]
31.1 [9.1]
4.6
| 39.4 [11.5]
39.4 [11.5]
4.7
| 38.7 [11.3]
38.7 [11.3]
4.6
| 37.2 [10.9]
35.8 [10.5]
4.5
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 44.1 [12.9]
28.4 [8.3]
4.9
| 43.2 [12.7]
27.0 [7.9]
4.9
| 41.6 [12.2]
24.4 [7.2]
4.8
| 40.8 [12.0]
35.2 [10.3]
4.9
| 40.0 [11.7]
33.5 [9.8]
4.9
| 38.5 [11.3]
30.3 [8.9]
4.8
| 37.6 [11.0]
37.6 [11.0]
4.9
| 36.9 [10.8]
36.9 [10.8]
4.8
| 35.5 [10.4]
35.0 [10.3]
4.8
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 42.2 [12.4]
27.5 [8.1]
5.2
| 41.4 [12.1]
26.2 [7.7]
5.1
| 39.9 [11.7]
23.7 [6.9]
5.0
| 39.0 [11.4]
34.3 [10.1]
5.1
| 38.2 [11.2]
32.7 [9.6]
5.1
| 36.8 [10.8]
29.6 [8.7]
5.0
| 35.8 [10.5]
35.8 [10.5]
5.1
| 35.1 [10.3]
35.1 [10.3]
5.1
| 33.8 [9.9]
33.8 [9.9]
5.0
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 40.4 [11.8]
26.6 [7.8]
5.4
| 39.6 [11.6]
25.3 [7.4]
5.4
| 38.1 [11.2]
22.9 [6.7]
5.3
| 37.2 [10.9]
33.5 [9.8]
5.4
| 36.4 [10.7]
31.8 [9.3]
5.3
| 35.1 [10.3]
28.8 [8.4]
5.2
| 33.9 [9.9]
33.9 [9.9]
5.4
| 33.3 [9.8]
33.3 [9.8]
5.3
| 32.0 [9.4]
32.0 [9.4]
5.2
- DR —Depression ratio
- dbE —Entering air dry bulb
- wbE—Entering air wet bulb
- Total —Total capacity x 1000 BTUH
- Sens —Sensible capacity x 1000 BTUH
- Power—KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
GROSS SYSTEMS COOLING PERFORMANCE DATA—RHPBZR060AJT000NA
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE C
wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F
[17.2°C]
CFM [L/s]| 2175 [1026]| 2000 [944]| 1575
[743]| 2175 [1026]| 2000 [944]| 1575 [743]|
2175 [1026]| 2000 [944]| 1575 [743]
DR C| .05| .09| .12| .05| .09| .12|
.05| .09| .12
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 75
[23.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 72.1 [21.1]
43.2 [12.7]
4.5
| 71.0 [20.8]
41.5 [12.2]
4.4
| 68.3 [20.0]
37.4 [11.0]
4.3
| 67.2 [19.7]
51.7 [15.2]
4.4
| 66.1 [19.4]
49.7 [14.6]
4.4
| 63.6 [18.6]
44.7 [13.1]
4.3
| 63.6 [18.6]
59.6 [17.5]
4.3
| 62.6 [18.3]
57.2 [16.8]
4.3
| 60.2 [17.6]
51.5 [15.1]
4.2
80
[26.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 70.2 [20.6]
42.1 [12.3]
4.6
| 69.1 [20.3]
40.4 [11.8]
4.6
| 66.4 [19.5]
36.4 [10.7]
4.5
| 65.2 [19.1]
50.6 [14.8]
4.6
| 64.2 [18.8]
48.6 [14.2]
4.5
| 61.7 [18.1]
43.8 [12.8]
4.4
| 61.7 [18.1]
58.5 [17.1]
4.5
| 60.7 [17.8]
56.2 [16.5]
4.5
| 58.4 [17.1]
50.6 [14.8]
4.4
85
[29.4]
| Total BTUH [kW] Sens BTUH [kW] Power| 68.1 [20.0]
40.9 [12.0]
4.8
| 67.0 [19.6]
39.3 [11.5]
4.8
| 64.4 [18.9]
35.4 [10.4]
4.7
| 63.2 [18.5]
49.5 [14.5]
4.7
| 62.2 [18.2]
47.5 [13.9]
4.7
| 59.8 [17.5]
42.8 [12.5]
4.6
| 59.6 [17.5]
57.3 [16.8]
4.7
| 58.7 [17.2]
55.1 [16.1]
4.7
| 56.4 [16.5]
49.6 [14.5]
4.6
90
[32.2]
| Total BTUH [kW] Sens BTUH [kW] Power| 65.9 [19.3]
39.8 [11.7]
5.0
| 64.9 [19.0]
38.3 [11.2]
5.0
| 62.4 [18.3]
34.5 [10.1]
4.9
| 61.0 [17.9]
48.4 [14.2]
4.9
| 60.0 [17.6]
46.5 [13.6]
4.9
| 57.7 [16.9]
41.8 [12.3]
4.8
| 57.4 [16.8]
56.2 [16.5]
4.9
| 56.5 [16.6]
54.0 [15.8]
4.8
| 54.3 [15.9]
48.7 [14.3]
4.8
95
[35]
| Total BTUH [kW] Sens BTUH [kW] Power| 63.6 [18.6]
38.7 [11.3]
5.2
| 62.6 [18.3]
37.2 [10.9]
5.2
| 60.2 [17.6]
33.5 [9.8]
5.1
| 58.7 [17.2]
47.2 [13.8]
5.2
| 57.8 [16.9]
45.4 [13.3]
5.1
| 55.5 [16.3]
40.9 [12.0]
5.0
| 55.2 [16.2]
55.1 [16.1]
5.1
| 54.3 [15.9]
52.9 [15.5]
5.1
| 52.2 [15.3]
47.7 [14.0]
5.0
100
[37.8]
| Total BTUH [kW] Sens BTUH [kW] Power| 61.2 [17.9]
37.5 [11.0]
5.4
| 60.3 [17.7]
36.0 [10.6]
5.4
| 58.0 [17.0]
32.5 [9.5]
5.3
| 56.3 [16.5]
46.0 [13.5]
5.4
| 55.4 [16.2]
44.2 [13.0]
5.3
| 53.3 [15.6]
39.8 [11.7]
5.2
| 52.8 [15.5]
52.8 [15.5]
5.3
| 51.9 [15.2]
51.8 [15.2]
5.3
| 49.9 [14.6]
46.7 [13.7]
5.2
105
[40.6]
| Total BTUH [kW] Sens BTUH [kW] Power| 58.8 [17.2]
36.3 [10.6]
5.7
| 57.8 [16.9]
34.9 [10.2]
5.6
| 55.6 [16.3]
31.4 [9.2]
5.5
| 53.8 [15.8]
44.9 [13.2]
5.6
| 53.0 [15.5]
43.1 [12.6]
5.6
| 50.9 [14.9]
38.8 [11.4]
5.5
| 50.3 [14.7]
50.3 [14.7]
5.6
| 49.5 [14.5]
49.5 [14.5]
5.5
| 47.6 [14.0]
45.6 [13.4]
5.4
110
[43.3]
| Total BTUH [kW] Sens BTUH [kW] Power| 56.2 [16.5]
35.1 [10.3]
5.9
| 55.3 [16.2]
33.7 [9.9]
5.9
| 53.2 [15.6]
30.4 [8.9]
5.8
| 51.2 [15.0]
43.7 [12.8]
5.9
| 50.4 [14.8]
41.9 [12.3]
5.8
| 48.5 [14.2]
37.8 [11.1]
5.7
| 47.7 [14.0]
47.7 [14.0]
5.8
| 46.9 [13.7]
46.9 [13.7]
5.8
| 45.1 [13.2]
44.6 [13.1]
5.7
115
[46.1]
| Total BTUH [kW] Sens BTUH [kW] Power| 53.5 [15.7]
33.9 [9.9]
6.2
| 52.6 [15.4]
32.6 [9.6]
6.2
| 50.6 [14.8]
29.3 [8.6]
6.0
| 48.5 [14.2]
42.4 [12.4]
6.2
| 47.8 [14.0]
40.8 [12.0]
6.1
| 45.9 [13.5]
36.7 [10.8]
6.0
| 45.0 [13.2]
45.0 [13.2]
6.1
| 44.3 [13.0]
44.3 [13.0]
6.0
| 42.6 [12.5]
42.6 [12.5]
5.9
120
[48.9]
| Total BTUH [kW] Sens BTUH [kW] Power| 50.7 [14.9]
32.7 [9.6]
6.5
| 49.9 [14.6]
31.4 [9.2]
6.4
| 47.9 [14.0]
28.3 [8.3]
6.3
| 45.7 [13.4]
41.2 [12.1]
6.4
| 45.0 [13.2]
39.6 [11.6]
6.4
| 43.3 [12.7]
35.7 [10.5]
6.3
| 42.2 [12.4]
42.2 [12.4]
6.4
| 41.5 [12.2]
41.5 [12.2]
6.3
| 39.9 [11.7]
39.9 [11.7]
6.2
125
[51.7]
| Total BTUH [kW] Sens BTUH [kW] Power| 47.8 [14.0]
31.4 [9.2]
6.8
| 47.0 [13.8]
30.2 [8.9]
6.8
| 45.2 [13.2]
27.2 [8.0]
6.6
| 42.8 [12.5]
40.0 [11.7]
6.7
| 42.2 [12.4]
38.4 [11.3]
6.7
| 40.5 [11.9]
34.6 [10.1]
6.6
| 39.3 [11.5]
39.3 [11.5]
6.7
| 38.7 [11.3]
38.7 [11.3]
6.6
| 37.2 [10.9]
37.2 [10.9]
6.5
- DR —Depression ratio
- dbE —Entering air dry bulb
- wbE—Entering air wet bulb
- Total —Total capacity x 1000 BTUH
- Sens —Sensible capacity x 1000 BTUH
- Power—KW input
- NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
- Designates Metric Conversions
HEATING PERFORMANCE DATA—RHPBZR024AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 850 [401]| 800 [378]| 600
[283]| 850 [401]| 800 [378]| 600 [283]|
850 [401]| 800 [378]| 640 [302]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 7.7 [2.3]
1.6
| 7.6 [2.2]
1.6
| 7.5 [2.2]
1.7
| 6.8 [2.0]
1.8
| 6.8 [2.0]
1.8
| 6.7 [2.0]
1.9
| 5.9 [1.7]
2.0
| 5.9 [1.7]
2.0
| 5.8 [1.7]
2.0
5
[- 15]
| Total BTUH [kW] Power| 9.4 [2.8]
1.6
| 9.3 [2.7]
1.6
| 9.2 [2.7]
1.7
| 8.5 [2.5]
1.8
| 8.5 [2.5]
1.8
| 8.3 [2.4]
1.9
| 7.6 [2.2]
1.9
| 7.6 [2.2]
2.0
| 7.5 [2.2]
2.0
10
[- 12.2]
| Total BTUH [kW] Power| 11.1 [3.3]
1.6
| 11.0 [3.2]
1.6
| 10.8 [3.2]
1.7
| 10.2 [3.0]
1.8
| 10.1 [3.0]
1.8
| 10.0 [2.9]
1.8
| 9.3 [2.7]
1.9
| 9.3 [2.7]
2.0
| 9.1 [2.7]
2.0
15
[- 9.4]
| Total BTUH [kW] Power| 12.7 [3.7]
1.6
| 12.7 [3.7]
1.6
| 12.5 [3.7]
1.7
| 11.9 [3.5]
1.8
| 11.8 [3.5]
1.8
| 11.6 [3.4]
1.9
| 11.0 [3.2]
1.9
| 11.0 [3.2]
2.0
| 10.8 [3.2]
2.0
20
[- 6.7]
| Total BTUH [kW] Power| 14.4 [4.2]
1.6
| 14.4 [4.2]
1.6
| 14.1 [4.1]
1.7
| 13.6 [4.0]
1.8
| 13.5 [4.0]
1.8
| 13.3 [3.9]
1.9
| 12.7 [3.7]
2.0
| 12.6 [3.7]
2.0
| 12.4 [3.6]
2.0
25
[- 3.9]
| Total BTUH [kW] Power| 16.1 [4.7]
1.6
| 16.0 [4.7]
1.7
| 15.8 [4.6]
1.7
| 15.3 [4.5]
1.8
| 15.2 [4.5]
1.8
| 14.9 [4.4]
1.9
| 14.4 [4.2]
2.0
| 14.3 [4.2]
2.0
| 14.1 [4.1]
2.0
30
[- 1.1]
| Total BTUH [kW] Power| 17.8 [5.2]
1.7
| 17.7 [5.2]
1.7
| 17.4 [5.1]
1.7
| 16.9 [5.0]
1.8
| 16.9 [5.0]
1.8
| 16.6 [4.9]
1.9
| 16.1 [4.7]
2.0
| 16.0 [4.7]
2.0
| 15.7 [4.6]
2.1
35
[1.7]
| Total BTUH [kW] Power| 19.5 [5.7]
1.7
| 19.4 [5.7]
1.7
| 19.1 [5.6]
1.8
| 18.6 [5.5]
1.9
| 18.5 [5.4]
1.9
| 18.2 [5.3]
1.9
| 17.8 [5.2]
2.0
| 17.7 [5.2]
2.0
| 17.4 [5.1]
2.1
40
[4.4]
| Total BTUH [kW] Power| 21.2 [6.2]
1.7
| 21.1 [6.2]
1.7
| 20.7 [6.1]
1.8
| 20.3 [5.9]
1.9
| 20.2 [5.9]
1.9
| 19.9 [5.8]
2.0
| 19.4 [5.7]
2.0
| 19.4 [5.7]
2.1
| 19.0 [5.6]
2.1
45
[7.2]
| Total BTUH [kW] Power| 22.9 [6.7]
1.8
| 22.8 [6.7]
1.8
| 22.4 [6.6]
1.8
| 22.0 [6.4]
1.9
| 21.9 [6.4]
1.9
| 21.5 [6.3]
2.0
| 21.1 [6.2]
2.1
| 21.0 [6.2]
2.1
| 20.7 [6.1]
2.2
50
[10]
| Total BTUH [kW] Power| 24.6 [7.2]
1.8
| 24.5 [7.2]
1.8
| 24.0 [7.0]
1.9
| 23.7 [6.9]
2.0
| 23.6 [6.9]
2.0
| 23.2 [6.8]
2.0
| 22.8 [6.7]
2.1
| 22.7 [6.7]
2.1
| 22.3 [6.5]
2.2
- IDB —Indoor air dry bulb
HEATING PERFORMANCE DATA—RHPBZR030AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 1025 [484]| 1000 [472]| 750
[354]| 1025 [484]| 1000 [472]| 750 [354]|
1025 [484]| 1000 [472]| 750 [354]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 9.1 [2.7]
1.8
| 9.1 [2.7]
1.8
| 8.9 [2.6]
1.9
| 8.5 [2.5]
2.0
| 8.5 [2.5]
2.0
| 8.3 [2.4]
2.1
| 7.9 [2.3]
2.2
| 7.9 [2.3]
2.2
| 7.8 [2.3]
2.3
5
[- 15]
| Total BTUH [kW] Power| 11.1 [3.3]
1.8
| 11.1 [3.3]
1.8
| 10.9 [3.2]
1.9
| 10.5 [3.1]
2.0
| 10.5 [3.1]
2.0
| 10.3 [3.0]
2.1
| 9.9 [2.9]
2.2
| 9.9 [2.9]
2.2
| 9.7 [2.8]
2.3
10
[- 12.2]
| Total BTUH [kW] Power| 13.1 [3.8]
1.8
| 13.1 [3.8]
1.8
| 12.8 [3.8]
1.9
| 12.5 [3.7]
2.0
| 12.5 [3.7]
2.0
| 12.3 [3.6]
2.1
| 11.9 [3.5]
2.2
| 11.9 [3.5]
2.2
| 11.7 [3.4]
2.3
15
[- 9.4]
| Total BTUH [kW] Power| 15.1 [4.4]
1.8
| 15.0 [4.4]
1.8
| 14.8 [4.3]
1.9
| 14.5 [4.2]
2.0
| 14.5 [4.2]
2.0
| 14.2 [4.2]
2.1
| 13.9 [4.1]
2.2
| 13.9 [4.1]
2.2
| 13.6 [4.0]
2.3
20
[- 6.7]
| Total BTUH [kW] Power| 17.1 [5.0]
1.8
| 17.0 [5.0]
1.8
| 16.7 [4.9]
1.9
| 16.5 [4.8]
2.0
| 16.5 [4.8]
2.0
| 16.2 [4.7]
2.1
| 15.9 [4.7]
2.2
| 15.9 [4.7]
2.2
| 15.6 [4.6]
2.3
25
[- 3.9]
| Total BTUH [kW] Power| 19.1 [5.6]
1.9
| 19.0 [5.6]
1.9
| 18.7 [5.5]
1.9
| 18.5 [5.4]
2.1
| 18.5 [5.4]
2.1
| 18.1 [5.3]
2.1
| 17.9 [5.2]
2.3
| 17.9 [5.2]
2.3
| 17.6 [5.2]
2.3
30
[- 1.1]
| Total BTUH [kW] Power| 21.1 [6.2]
1.9
| 21.0 [6.2]
1.9
| 20.7 [6.1]
2.0
| 20.5 [6.0]
2.1
| 20.5 [6.0]
2.1
| 20.1 [5.9]
2.2
| 19.9 [5.8]
2.3
| 19.9 [5.8]
2.3
| 19.5 [5.7]
2.4
35
[1.7]
| Total BTUH [kW] Power| 23.1 [6.8]
1.9
| 23.0 [6.7]
1.9
| 22.6 [6.6]
2.0
| 22.5 [6.6]
2.1
| 22.5 [6.6]
2.1
| 22.1 [6.5]
2.2
| 21.9 [6.4]
2.3
| 21.9 [6.4]
2.3
| 21.5 [6.3]
2.4
40
[4.4]
| Total BTUH [kW] Power| 25.1 [7.4]
2.0
| 25.0 [7.3]
2.0
| 24.6 [7.2]
2.0
| 24.5 [7.2]
2.2
| 24.5 [7.2]
2.2
| 24.0 [7.0]
2.2
| 23.9 [7.0]
2.4
| 23.9 [7.0]
2.4
| 23.5 [6.9]
2.4
45
[7.2]
| Total BTUH [kW] Power| 27.1 [7.9]
2.0
| 27.0 [7.9]
2.0
| 26.6 [7.8]
2.1
| 26.5 [7.8]
2.2
| 26.5 [7.8]
2.2
| 26.0 [7.6]
2.3
| 25.9 [7.6]
2.4
| 25.9 [7.6]
2.4
| 25.4 [7.4]
2.5
50
[10]
| Total BTUH [kW] Power| 29.1 [8.5]
2.1
| 29.0 [8.5]
2.1
| 28.5 [8.4]
2.2
| 28.5 [8.4]
2.3
| 28.5 [8.4]
2.3
| 28.0 [8.2]
2.4
| 27.9 [8.2]
2.5
| 27.9 [8.2]
2.5
| 27.4 [8.0]
2.6
IDB —Indoor air dry bulb
Designates Metric Conversions
HEATING PERFORMANCE DATA—RHPBZR036AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 1400 [661]| 1200 [566]| 1000
[472]| 1400 [661]| 1200 [566]| 1000 [472]|
1400 [661]| 1200 [566]| 1000 [472]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 12.7 [3.7]
2.1
| 12.5 [3.7]
2.2
| 12.4 [3.6]
2.2
| 11.8 [3.5]
2.4
| 11.7 [3.4]
2.5
| 11.5 [3.4]
2.6
| 10.9 [3.2]
2.8
| 10.8 [3.2]
2.8
| 10.7 [3.1]
2.9
5
[- 15]
| Total BTUH [kW] Power| 15.4 [4.5]
2.2
| 15.2 [4.5]
2.3
| 15.1 [4.4]
2.3
| 14.5 [4.2]
2.5
| 14.4 [4.2]
2.6
| 14.2 [4.2]
2.6
| 13.7 [4.0]
2.8
| 13.5 [4.0]
2.9
| 13.3 [3.9]
3.0
10
[- 12.2]
| Total BTUH [kW] Power| 18.2 [5.3]
2.3
| 18 [5.3]
2.3
| 17.7 [5.2]
2.4
| 17.3 [5.1]
2.6
| 17.1 [5.0]
2.7
| 16.9 [5.0]
2.7
| 16.4 [4.8]
2.9
| 16.2 [4.7]
3.0
| 16 [4.7]
3.0
15
[- 9.4]
| Total BTUH [kW] Power| 20.9 [6.1]
2.4
| 20.7 [6.1]
2.4
| 20.4 [6.0]
2.5
| 20.0 [5.9]
2.7
| 19.8 [5.8]
2.7
| 19.6 [5.7]
2.8
| 19.2 [5.6]
3.0
| 18.9 [5.5]
3.1
| 18.7 [5.5]
3.1
20
[- 6.7]
| Total BTUH [kW] Power| 23.7 [6.9]
2.4
| 23.4 [6.9]
2.5
| 23.1 [6.8]
2.5
| 22.8 [6.7]
2.8
| 22.5 [6.6]
2.8
| 22.2 [6.5]
2.9
| 21.9 [6.4]
3.1
| 21.6 [6.3]
3.1
| 21.4 [6.3]
3.2
25
[- 3.9]
| Total BTUH [kW] Power| 26.4 [7.7]
2.5
| 26.1 [7.6]
2.6
| 25.8 [7.6]
2.6
| 25.5 [7.5]
2.8
| 25.2 [7.4]
2.9
| 24.9 [7.3]
3.0
| 24.6 [7.2]
3.1
| 24.3 [7.1]
3.2
| 24.1 [7.1]
3.3
30
[- 1.1]
| Total BTUH [kW] Power| 29.1 [8.5]
2.6
| 28.8 [8.4]
2.7
| 28.5 [8.4]
2.7
| 28.3 [8.3]
2.9
| 27.9 [8.2]
3.0
| 27.6 [8.1]
3.0
| 27.4 [8.0]
3.2
| 27.1 [7.9]
3.3
| 26.7 [7.8]
3.4
35
[1.7]
| Total BTUH [kW] Power| 31.9 [9.3]
2.7
| 31.5 [9.2]
2.7
| 31.1 [9.1]
2.8
| 31.0 [9.1]
3.0
| 30.6 [9]
3.1
| 30.3 [8.9]
3.1
| 30.1 [8.8]
3.3
| 29.8 [8.7]
3.4
| 29.4 [8.6]
3.5
40
[4.4]
| Total BTUH [kW] Power| 34.6 [10.1]
2.8
| 34.2 [10.0]
2.8
| 33.8 [9.9]
2.9
| 33.7 [9.9]
3.1
| 33.4 [9.8]
3.1
| 33.0 [9.7]
3.2
| 32.9 [9.6]
3.4
| 32.5 [9.5]
3.5
| 32.1 [9.4]
3.5
45
[7.2]
| Total BTUH [kW] Power| 37.4 [11]
2.9
| 36.9 [10.8]
2.9
| 36.5 [10.7]
3.0
| 36.5 [10.7]
3.2
| 36.1 [10.6]
3.2
| 35.6 [10.4]
3.3
| 35.6 [10.4]
3.5
| 35.2 [10.3]
3.6
| 34.8 [10.2]
3.6
50
[10]
| Total BTUH [kW] Power| 40.1 [11.8]
2.9
| 39.6 [11.6]
3.0
| 39.2 [11.5]
3.1
| 39.2 [11.5]
3.3
| 38.8 [11.4]
3.3
| 38.3 [11.2]
3.4
| 38.4 [11.3]
3.6
| 37.9 [11.1]
3.7
| 37.5 [11.0]
3.7
IDB —Indoor air dry bulb
HEATING PERFORMANCE DATA—RHPBZR042AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 1550 [732]| 1400 [661]| 1125
[531]| 1550 [732]| 1400 [661]| 1125 [531]|
1550 [732]| 1400 [661]| 1125 [531]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 13.5 [4.0]
2.2
| 13.4 [3.9]
2.2
| 13.2 [3.9]
2.2
| 11.9 [3.5]
2.4
| 11.8 [3.5]
2.4
| 11.6 [3.4]
2.5
| 10.2 [3.0]
2.7
| 10.1 [3.0]
2.7
| 10.0 [2.9]
2.8
5
[- 15]
| Total BTUH [kW] Power| 16.7 [4.9]
2.3
| 16.6 [4.9]
2.4
| 16.4 [4.8]
2.4
| 15.0 [4.4]
2.6
| 14.9 [4.4]
2.6
| 14.7 [4.3]
2.7
| 13.4 [3.9]
2.9
| 13.3 [3.9]
2.9
| 13.1 [3.8]
3.0
10
[- 12.2]
| Total BTUH [kW] Power| 19.9 [5.8]
2.5
| 19.8 [5.8]
2.5
| 19.5 [5.7]
2.6
| 18.2 [5.3]
2.8
| 18.1 [5.3]
2.8
| 17.8 [5.2]
2.9
| 16.6 [4.9]
3.0
| 16.4 [4.8]
3.1
| 16.2 [4.7]
3.1
15
[- 9.4]
| Total BTUH [kW] Power| 23.1 [6.8]
2.7
| 22.9 [6.7]
2.7
| 22.6 [6.6]
2.8
| 21.4 [6.3]
2.9
| 21.3 [6.2]
3.0
| 21.0 [6.2]
3.0
| 19.7 [5.8]
3.2
| 19.6 [5.7]
3.2
| 19.3 [5.7]
3.3
20
[- 6.7]
| Total BTUH [kW] Power| 26.3 [7.7]
2.8
| 26.1 [7.6]
2.9
| 25.7 [7.5]
2.9
| 24.6 [7.2]
3.1
| 24.4 [7.2]
3.1
| 24.1 [7.1]
3.2
| 22.9 [6.7]
3.3
| 22.8 [6.7]
3.4
| 22.4 [6.6]
3.5
25
[- 3.9]
| Total BTUH [kW] Power| 29.5 [8.6]
2.9
| 29.3 [8.6]
3.0
| 28.9 [8.5]
3.1
| 27.8 [8.1]
3.2
| 27.6 [8.1]
3.2
| 27.2 [8.0]
3.3
| 26.1 [7.6]
3.5
| 25.9 [7.6]
3.5
| 25.6 [7.5]
3.6
30
[- 1.1]
| Total BTUH [kW] Power| 32.7 [9.6]
3.1
| 32.4 [9.5]
3.1
| 32.0 [9.4]
3.2
| 31.0 [9.1]
3.3
| 30.8 [9.0]
3.4
| 30.3 [8.9]
3.4
| 29.3 [8.6]
3.6
| 29.1 [8.5]
3.6
| 28.7 [8.4]
3.7
35
[1.7]
| Total BTUH [kW] Power| 35.9 [10.5]
3.2
| 35.6 [10.4]
3.2
| 35.1 [10.3]
3.3
| 34.2 [10.0]
3.4
| 33.9 [9.9]
3.5
| 33.4 [9.8]
3.5
| 32.5 [9.5]
3.7
| 32.3 [9.5]
3.7
| 31.8 [9.3]
3.8
40
[4.4]
| Total BTUH [kW] Power| 39.1 [11.5]
3.2
| 38.8 [11.4]
3.3
| 38.2 [11.2]
3.4
| 37.4 [11.0]
3.5
| 37.1 [10.9]
3.6
| 36.6 [10.7]
3.6
| 35.7 [10.5]
3.8
| 35.4 [10.4]
3.8
| 34.9 [10.2]
3.9
45
[7.2]
| Total BTUH [kW] Power| 42.2 [12.4]
3.3
| 41.9 [12.3]
3.4
| 41.3 [12.1]
3.4
| 40.6 [11.9]
3.6
| 40.3 [11.8]
3.6
| 39.7 [11.6]
3.7
| 38.9 [11.4]
3.8
| 38.6 [11.3]
3.9
| 38 [11.1]
4.0
50
[10]
| Total BTUH [kW] Power| 45.4 [13.3]
3.4
| 45.1 [13.2]
3.4
| 44.5 [13.0]
3.5
| 43.8 [12.8]
3.6
| 43.4 [12.7]
3.7
| 42.8 [12.5]
3.8
| 42.1 [12.3]
3.9
| 41.8 [12.3]
3.9
| 41.2 [12.1]
4.0
- IDB —Indoor air dry bulb
- Designates Metric Conversions
HEATING PERFORMANCE DATA—RHPBZR048AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 1750 [826]| 1600 [755]| 1275
[602]| 1750 [826]| 1600 [755]| 1275 [602]|
1750 [826]| 1600 [755]| 1275 [602]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 13.0 [3.8]
3.2
| 12.9 [3.8]
3.3
| 12.7 [3.7]
3.4
| 11.5 [3.4]
3.6
| 11.5 [3.4]
3.6
| 11.3 [3.3]
3.7
| 10.1 [3.0]
4.0
| 10.0 [2.9]
4.0
| 9.9 [2.9]
4.1
5
[- 15]
| Total BTUH [kW] Power| 16.8 [4.9]
3.2
| 16.7 [4.9]
3.2
| 16.4 [4.8]
3.3
| 15.3 [4.5]
3.6
| 15.2 [4.5]
3.6
| 15.0 [4.4]
3.7
| 13.8 [4.0]
3.9
| 13.7 [4.0]
4.0
| 13.5 [4.0]
4.1
10
[- 12.2]
| Total BTUH [kW] Power| 20.5 [6.0]
3.2
| 20.4 [6.0]
3.2
| 20.1 [5.9]
3.3
| 19.1 [5.6]
3.5
| 18.9 [5.5]
3.6
| 18.7 [5.5]
3.7
| 17.6 [5.2]
3.9
| 17.5 [5.1]
3.9
| 17.2 [5.0]
4.0
15
[- 9.4]
| Total BTUH [kW] Power| 24.3 [7.1]
3.2
| 24.1 [7.1]
3.2
| 23.8 [7.0]
3.3
| 22.8 [6.7]
3.5
| 22.7 [6.7]
3.6
| 22.4 [6.6]
3.7
| 21.4 [6.3]
3.9
| 21.2 [6.2]
3.9
| 20.9 [6.1]
4.0
20
[- 6.7]
| Total BTUH [kW] Power| 28.1 [8.2]
3.2
| 27.9 [8.2]
3.3
| 27.5 [8.1]
3.3
| 26.6 [7.8]
3.6
| 26.4 [7.7]
3.6
| 26.0 [7.6]
3.7
| 25.1 [7.4]
3.9
| 25.0 [7.3]
4.0
| 24.6 [7.2]
4.1
25
[- 3.9]
| Total BTUH [kW] Power| 31.8 [9.3]
3.3
| 31.6 [9.3]
3.3
| 31.2 [9.1]
3.4
| 30.4 [8.9]
3.6
| 30.2 [8.9]
3.7
| 29.7 [8.7]
3.8
| 28.9 [8.5]
4.0
| 28.7 [8.4]
4.0
| 28.3 [8.3]
4.1
30
[- 1.1]
| Total BTUH [kW] Power| 35.6 [10.4]
3.3
| 35.4 [10.4]
3.4
| 34.9 [10.2]
3.5
| 34.1 [10.0]
3.7
| 33.9 [9.9]
3.7
| 33.4 [9.8]
3.8
| 32.7 [9.6]
4.1
| 32.4 [9.5]
4.1
| 32.0 [9.4]
4.2
35
[1.7]
| Total BTUH [kW] Power| 39.4 [11.5]
3.4
| 39.1 [11.5]
3.5
| 38.5 [11.3]
3.6
| 37.9 [11.1]
3.8
| 37.6 [11.0]
3.8
| 37.1 [10.9]
3.9
| 36.4 [10.7]
4.2
| 36.2 [10.6]
4.2
| 35.7 [10.5]
4.3
40
[4.4]
| Total BTUH [kW] Power| 43.1 [12.6]
3.6
| 42.8 [12.5]
3.6
| 42.2 [12.4]
3.7
| 41.7 [12.2]
3.9
| 41.4 [12.1]
4.0
| 40.8 [12.0]
4.1
| 40.2 [11.8]
4.3
| 39.9 [11.7]
4.3
| 39.3 [11.5]
4.4
45
[7.2]
| Total BTUH [kW] Power| 46.9 [13.7]
3.7
| 46.6 [13.7]
3.8
| 45.9 [13.5]
3.9
| 45.4 [13.3]
4.1
| 45.1 [13.2]
4.1
| 44.5 [13.0]
4.2
| 44 [12.9]
4.4
| 43.7 [12.8]
4.5
| 43 [12.6]
4.6
50
[10]
| Total BTUH [kW] Power| 50.7 [14.9]
3.9
| 50.3 [14.7]
3.9
| 49.6 [14.5]
4.0
| 49.2 [14.4]
4.3
| 48.9 [14.3]
4.3
| 48.2 [14.1]
4.4
| 47.7 [14.0]
4.6
| 47.4 [13.9]
4.7
| 46.7 [13.7]
4.8
IDB —Indoor air dry bulb
HEATING PERFORMANCE DATA—RHPBZR060AJT000NA
IDB| 60°F [15.5°C]| 70°F [21.1°C]| 80°F
[26.7°C]
---|---|---|---
CFM [L/s]| 2175 [1026]| 2000 [944]| 1575
[743]| 2175 [1026]| 2000 [944]| 1575 [743]|
2175 [1026]| 2000 [944]| 1575 [743]
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
| 0
[- 17.8]
| Total BTUH [kW] Power| 17.2 [5.0]
3.6
| 17.1 [5.0]
3.7
| 16.8 [4.9]
3.8
| 15.1 [4.4]
4.0
| 15.0 [4.4]
4.1
| 14.8 [4.3]
4.2
| 13.1 [3.8]
4.4
| 13.0 [3.8]
4.5
| 12.8 [3.8]
4.6
5
[- 15]
| Total BTUH [kW] Power| 21.8 [6.4]
3.7
| 21.6 [6.3]
3.7
| 21.3 [6.2]
3.8
| 19.7 [5.8]
4.1
| 19.6 [5.7]
4.1
| 19.3 [5.7]
4.2
| 17.7 [5.2]
4.4
| 17.6 [5.2]
4.5
| 17.3 [5.1]
4.6
10
[- 12.2]
| Total BTUH [kW] Power| 26.3 [7.7]
3.7
| 26.2 [7.7]
3.8
| 25.8 [7.6]
3.9
| 24.3 [7.1]
4.1
| 24.1 [7.1]
4.2
| 23.8 [7.0]
4.3
| 22.2 [6.5]
4.5
| 22.1 [6.5]
4.5
| 21.8 [6.4]
4.7
15
[- 9.4]
| Total BTUH [kW] Power| 30.9 [9.1]
3.8
| 30.7 [9.0]
3.8
| 30.3 [8.9]
3.9
| 28.9 [8.5]
4.2
| 28.7 [8.4]
4.2
| 28.3 [8.3]
4.3
| 26.8 [7.9]
4.6
| 26.7 [7.8]
4.6
| 26.3 [7.7]
4.7
20
[- 6.7]
| Total BTUH [kW] Power| 35.5 [10.4]
3.9
| 35.3 [10.3]
3.9
| 34.7 [10.2]
4.0
| 33.4 [9.8]
4.2
| 33.2 [9.7]
4.3
| 32.7 [9.6]
4.4
| 31.4 [9.2]
4.6
| 31.2 [9.1]
4.7
| 30.7 [9.0]
4.8
25
[- 3.9]
| Total BTUH [kW] Power| 40.1 [11.8]
4.0
| 39.8 [11.7]
4.0
| 39.2 [11.5]
4.1
| 38 [11.1]
4.3
| 37.8 [11.1]
4.4
| 37.2 [10.9]
4.5
| 36.0 [10.6]
4.7
| 35.8 [10.5]
4.8
| 35.2 [10.3]
4.9
30
[- 1.1]
| Total BTUH [kW] Power| 44.7 [13.1]
4.1
| 44.4 [13]
4.1
| 43.7 [12.8]
4.2
| 42.6 [12.5]
4.4
| 42.3 [12.4]
4.5
| 41.7 [12.2]
4.6
| 40.6 [11.9]
4.8
| 40.3 [11.8]
4.9
| 39.7 [11.6]
5.0
35
[1.7]
| Total BTUH [kW] Power| 49.2 [14.4]
4.2
| 48.9 [14.3]
4.2
| 48.2 [14.1]
4.3
| 47.2 [13.8]
4.6
| 46.9 [13.7]
4.6
| 46.2 [13.5]
4.7
| 45.1 [13.2]
4.9
| 44.9 [13.2]
5.0
| 44.2 [13.0]
5.1
40
[4.4]
| Total BTUH [kW] Power| 53.8 [15.8]
4.3
| 53.5 [15.7]
4.4
| 52.7 [15.4]
4.5
| 51.8 [15.2]
4.7
| 51.4 [15.1]
4.7
| 50.7 [14.9]
4.9
| 49.7 [14.6]
5.1
| 49.4 [14.5]
5.1
| 48.7 [14.3]
5.3
45
[7.2]
| Total BTUH [kW] Power| 58.4 [17.1]
4.5
| 58 [17.0]
4.5
| 57.2 [16.8]
4.6
| 56.3 [16.5]
4.8
| 56.0 [16.4]
4.9
| 55.2 [16.2]
5.0
| 54.3 [15.9]
5.2
| 54.0 [15.8]
5.3
| 53.2 [15.6]
5.4
50
[10]
| Total BTUH [kW] Power| 63 [18.5]
4.6
| 62.6 [18.3]
4.7
| 61.6 [18.1]
4.8
| 60.9 [17.8]
5.0
| 60.6 [17.8]
5.1
| 59.6 [17.5]
5.2
| 58.9 [17.3]
5.4
| 58.5 [17.1]
5.4
| 57.6 [16.9]
5.6
IDB —Indoor air dry bulb
Designates Metric Conversions
INDOOR AIRFLOW PERFORMANCE—RHPBZR – 208/230V
Nominal Cooling Capacity Tons [kW]| Motor Speed from Factory| Manufacturer Recommended Cooling Airflow (Min/Max)| Blower Size, Motor HP
[W] &
# of Speeds
| ****
Motor Speed
| | External Static Pressure – Inches W.C. [kPa] (Side Discharge-Dry
Coil)
---|---|---|---|---|---|---
Cool| Heat| 0.1 [.02]| 0.2 [.05]| 0.3 [.07]| 0.4
[.10]| 0.5 [.12]| 0.6 [.15]| 0.7 [.17]| 0.8 [.20]|
0.9 [.22]| 1.0 [.25]
2.0
[7.03]| ****
Tap 2
| ****
Tap 2
| ****
700 CFM /
900 CFM
| ****
10×9 Blower 1/2 hp [372]
2 Speed (Constant Torque)
| ****
Low-Speed Tap 1
| CFM| 882| 818| 759| 650| 577| 512| 433| 368| 304| 241
RPM| 457| 533| 600| 693| 750| 818| 876| 931| 972| 1015
Watts| 63| 71| 78| 89| 94| 102| 109| 115| 120| 124
High Speed Tap 2
| CFM| 1217| 1165| 1113| 1067| 1021| 920| 859| 830| 780| 728
RPM| 538| 597| 657| 715| 772| 864| 909| 946| 996| 1040
Watts| 122| 132| 143| 154| 165| 181| 189| 196| 205| 213
2.5
[8.79}| ****
Tap 2
| ****
Tap 2
| ****
1000 CFM /
1400 CFM
| ****
10×9 Blower 1/2 hp [372]
2 Speed (Constant Torque)
| ****
Low-Speed Tap 1
| CFM| 1143| 1088| 1043| 989| 878| 836| 798| 750| 706| 656
RPM| 519| 591| 657| 721| 818| 857| 898| 952| 998| 1049
Watts| 107| 119| 129| 140| 156| 162| 169| 178| 186| 194
High Speed Tap 2
| CFM| 1354| 1309| 1265| 1224| 1182| 1122| 1028| 989| 957| 922
RPM| 577| 635| 689| 749| 806| 871| 954| 990| 1026| 1062
Watts| 160| 173| 186| 199| 211| 226| 244| 252| 260| 269
3.0
[10.55]| ****
Tap 2
| ****
Tap 2
| ****
1000 CFM /
1400 CFM
| ****
12×9 Blower 3/4 hp [559]
2 Speed (Constant Torque)
| ****
Low-Speed Tap 1
| CFM| 1287| 1212| 1136| 1080| 1011| 945| 882| 787| 726| 669
RPM| 451| 504| 572| 623| 681| 733| 775| 838| 877| 941
Watts| 121| 135| 151| 162| 174| 185| 193| 209| 219| 233
High Speed Tap 2
| CFM| 595| 1522| 1454| 1387| 1337| 1286| 1233| 1186| 1139| 1103
RPM| 524| 564| 612| 673| 715| 763| 808| 852| 889| 914
Watts| 206| 219| 235| 254| 268| 283| 298| 313| 324| 334
3.5
[12.31]| ****
Tap 2
| ****
Tap 2
| ****
1200 CFM /
1600 CFM
| ****
12×9 Blower 3/4 hp [559]
2 Speed (Constant Torque)
| ****
Low-Speed Tap 1
| CFM| 1858| 1704| 1655| 1603| 1543| 1495| 1446| 1362| 1328| 1304
RPM| 584| 593| 633| 675| 718| 764| 805| 876| 905| 926
Watts| 301| 269| 284| 299| 315| 332| 346| 372| 384| 391
High Speed Tap 2
| CFM| 1592| 1526| 1479| 1426| 1361| 1307| 1250| 1202| 1147| 1101
RPM| 514| 561| 598| 640| 693| 744| 798| 835| 873| 911
Watts| 197| 212| 223| 236| 253| 269| 286| 297| 309| 321
4.0
[14.07]| ****
Tap 2
| ****
Tap 2
| ****
1350 CFM /
1850 CFM
| ****
12×9 Blower 3/4 hp [559]
2 Speed (Constant Torque)
| ****
Low-Speed Tap 1
| CFM| 1871| 1818| 1766| 1720| 1673| 1614| 1573| 1535| 1498| 1456
RPM| 591| 613| 657| 702| 742| 787| 826| 859| 896| 934
Watts| 309| 313| 330| 348| 365| 383| 400| 413| 429| 445
**** High Speed Tap 2| CFM| 1871| 1818| 1766| 1720| 1673| 1614| 1573| 1535|
1498| 1456
RPM| 591| 613| 657| 702| 742| 787| 826| 859| 896| 934
Watts| 309| 313| 330| 348| 365| 383| 400| 413| 429| 445
5.0
[17.59]| ****
Tap 2
| ****
Tap 2
| ****
1600 CFM /
2100 CFM
| ****
12×9 Blower 1 hp [746]
2 Speed (Constant Torque)
| 1st Stage Low Speed (Tap 1)| CFM| 1704| 1574| 1467| 1422| 1371| 1326| 1265|
1225| 1181| 1136
RPM| 586| 589| 617| 659| 710| 758| 809| 847| 883| 923
Watts| 255| 224| 221| 232| 247| 260| 276| 288| 300| 311
2nd Stage Low Speed (Tap 2)| CFM| 2189| 2170| 2144| 2114| 2083| 2048| 2014|
1978| 1947| 1908
RPM| 722| 740| 757| 779| 809| 844| 874| 906| 941| 977
Watts| 522| 532| 540| 553| 569| 589| 608| 626| 647| 663
Notes: (1) For Constant Torque Motors: Use motor taps 3-5 to achieve rated airflow at AHRI minimum external static pressure.
DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s]| 800 [378]| 1000 [472]| 1200 [566]| 1400 [661]| 1600
[755]| 1800 [849]| 2000 [944]
Pressure Drop—Includes W.C. [kPa]| .02 [.005]| .05 [.012]|
.07 [.017]| .1 [.025]| .12 [.030]| .15 [.037]| .17 [.042]
Designates Metric Conversions
Electrical Data
ELECTRICAL DATA – RHPBZR SERIES
| | 024AJT| 030AJT| 036AJT| 042AJT| 048AJT|
060AJT
Unit Information| Unit Operating Voltage Range| 187-253| 187-253|
187-253| 187-253| 187-253| 187-253
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1
Hz| 60| 60| 60| 60| 60| 60
Minimum Circuit Ampacity| 20| 21| 27| 28| 31| 40
Minimum Overcurrent Protection Device Size| 25| 30| 40| 40| 45| 60
Maximum Overcurrent Protection Device Size| 25| 30| 40| 40| 45| 60
Compressor Motor| No.| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1
RPM| 0| 0| 0| 0| 0| 0
HP, Compressor 1| 0| 0| 0| 0| 0| 0
Amps (RLA), Comp. 1| 10.8| 11.7| 15.4| 15.9| 18.3| 23.5
Amps (LRA), Comp. 1| 55| 71.3| 92.1| 112.3| 108| 118
HP, Compressor 2| | | | | |
Amps (RLA), Comp. 2| | | | | |
Amps (LRA), Comp. 2| | | | | |
Condenser Motor| No.| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1
HP| 1/3| 1/3| 1/3| 1/3| 1/3| 1/2
Amps (FLA, each)| 1.5| 1.5| 1.5| 1.8| 1.8| 2.3
Amps (LRA, each)| | | | | |
Evaporator Fan| No.| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1
HP| 1/2| 1/2| 3/4| 3/4| 3/4| 1
Amps (FLA, each)| 4.1| 4.1| 6| 6| 6| 7.6
Amps (LRA, each)| | | | | |
Electric Heater Kits
208/240 VOLT, SINGLE PHASE, 60 Hz, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply for Both Unit and Heater Kit| Separate Power Supply for Both Unit and Heater Kit
Model Number
| Heater Kit| Heat Pump| Heater Kit| Heat
Pump
RXQJ-
Heater Kit Nominal kW
| No. of Sequence Steps| Rated Heater kW @ 208/240 V|
Heater KBTU/Hr @ 208/240 V| Heater Amp. @ 208/240 V|
Unit Min. Ckt. Ampacity @ 208/240 V| Over Current
Protective Device Size| Min. Ckt. Ampacity 208/240V|
Max. Fuse Size 208/240V| Min. Circuit Ampacity
208/240V| Over Current Protective Device Size
Min./Max. @ 208 V| Min./Max. @ 240 V| Min./Max. @ 208
V| Min./Max. @ 240 V
RHPBZR024AJT
| No Heat| —| —| —| —| 20/20| 25/25| 25/25| —| —| 20/20| 25/25| 25/25
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 41/45| 45/45| 50/50| 22/25| 25/25|
20/20| 25/25| 25/25
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 52/57| 60/60| 60/60| 33/38| 35/40|
20/20| 25/25| 25/25
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 63/70| 70/70| 80/80| 44/50| 45/50|
20/20| 25/25| 25/25
RHPBZR030AJT
| No Heat| —| —| —| —| 21/21| 30/30| 30/30| —| —| 21/21| 30/30| 30/30
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 42/46| 45/45| 50/50| 22/25| 25/25|
21/21| 30/30| 30/30
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 53/58| 60/60| 60/60| 33/38| 35/40|
21/21| 30/30| 30/30
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 64/71| 70/70| 80/80| 44/50| 45/50|
21/21| 30/30| 30/30
C15J| 1| 10.8/14.4| 36.85/49.13| 52.0/60.0| 86/96| 90/90| 100/100| 65/75|
70/80| 21/21| 30/30| 30/30
RHPBZR036AJT
| No Heat| —| —| —| —| 27/27| 40/40| 40/40| —| —| 27/27| 40/40| 40/40
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 49/52| 60/60| 60/60| 22/25| 25/25|
27/27| 40/40| 40/40
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 60/65| 70/70| 70/70| 33/38| 35/40|
27/27| 40/40| 40/40
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 71/77| 80/80| 80/80| 44/50| 45/50|
27/27| 40/40| 40/40
C15J| 1| 10.8/14.4| 36.85/49.13| 52.0/60.0| 92/102| 100/100| 110/110| 65/75|
70/80| 27/27| 40/40| 40/40
RHPBZR042AJT
| No Heat| —| —| —| —| 28/28| 40/40| 40/40| —| —| 28/28| 40/40| 40/40
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 50/53| 60/60| 60/60| 22/25| 25/25|
28/28| 40/40| 40/40
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 61/66| 70/70| 70/70| 33/38| 35/40|
28/28| 40/40| 40/40
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 72/78| 80/80| 80/80| 44/50| 45/50|
28/28| 40/40| 40/40
C15J| 1| 10.8/14.4| 36.85/49.13| 52.0/60.0| 93/103| 100/100| 110/110| 65/75|
70/80| 28/28| 40/40| 40/40
RHPBZR048AJT
| No Heat| —| —| —| —| 31/31| 45/45| 45/45| —| —| 31/31| 45/45| 45/45
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 53/56| 60/60| 60/60| 22/25| 25/25|
31/31| 45/45| 45/45
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 64/69| 70/70| 80/80| 33/38| 35/40|
31/31| 45/45| 45/45
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 75/81| 80/80| 90/90| 44/50| 45/50|
31/31| 45/45| 45/45
C15J| 1| 10.8/14.4| 36.85/49.13| 52.0/60.0| 96/106| 100/100| 110/110| 65/75|
70/80| 31/31| 45/45| 45/45
C20J| 1| 14.4/19.2| 49.13/65.51| 69.3/80.0| 118/131| 125/125| 150/150| 87/100|
90/100| 31/31| 45/45| 45/45
RHPBZR060AJT
| No Heat| —| —| —| —| 40/40| 60/60| 60/60| —| —| 40/40| 60/60| 60/60
C05J| 1| 3.6/4.8| 12.28/16.38| 17.3/20.0| 61/65| 70/80| 70/80| 22/25| 25/25|
40/40| 60/60| 60/60
C07J| 1| 5.4/7.2| 18.43/24.57| 26.0/30.0| 72/77| 80/80| 80/90| 33/38| 35/40|
40/40| 60/60| 60/60
C10J| 1| 7.2/9.6| 24.57/32.76| 34.7/40.0| 83/90| 90/90| 100/100| 44/50| 45/50|
40/40| 60/60| 60/60
C15J| 1| 10.8/14.4| 36.85/49.13| 52.0/60.0| 105/115| 110/110| 125/125| 65/75|
70/80| 40/40| 60/60| 60/60
C20J| 1| 14.4/19.2| 49.13/65.51| 69.3/80.0| 126/140| 150/150| 150/150| 87/100|
90/100| 40/40| 60/60| 60/60
FRONT VIEW
DIMENSIONS
Model | Height “A” |
---|---|
024, 030 | 29 1/8″ |
036, 042, 048, 060 | 37 1/8″ |
REARVIEW
ELECTRICAL CONNECTIONS
BOTTOM VIEW
Designates Metric Conversions
Typical Installations
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
GENERAL TERMS OF LIMITED WARRANTY
- Friedrich® will furnish a replacement for any part of this product that fails in normal use and service within the applicable periods stated, per the terms of the limited warranty.
- For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
- Conditional Parts (Registration Required) 1 Phase, Residential Applications………………Ten (10) Years
- Compressor 1 Phase, Residential Applications………………Ten (10) Years
- 1 & 3 Phase, Commercial Applications………..Five (5) Years Parts
- 1 & 3 Phase, Commercial Applications………….One (1) Year
- Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
- © 2023 Rheem Manufacturing Company. Friedrich trademarks are owned by Friedrich Air Conditioning LLC.
- Rheem and other trademarks are owned by Rheem Manufacturing Company.
- In keeping with its policy of continuous progress and product improvement, Friedrich reserves the right to make changes without notice.
- 5600 Old Greenwood Road
- Fort Smith, Arkansas 72908 www.friedrich.com
- 125 Edgeware Road, Unit 1
- Brampton, Ontario • L6Y 0P5
- Proper sizing and installation of equipment are critical to achieve optimal
- performance. Ask your Contractor for details or visit www.energystar.gov.”
References