Sonel CMP-200F Clamp Meters Handheld Devices User Manual

June 16, 2024
Sonel

Sonel CMP-200F Clamp Meters Handheld Devices

Product Information

Specifications

  • Product: CMP-200F
  • Version: 1.04
  • Date: 19.12.2023

Description

The True RMS CMP-200F Multimeter is designed for measuring DC and AC voltage, AC, resistance, and electrical capacitance, as well as testing diodes and continuity.

Features

  • Large 4-digit display (reading up to 6000)
  • HOLD function to freeze the reading on the meter screen
  • Built-in flashlight for illuminating the measurement area
  • Audible continuity circuit indication
  • Auto power off when not in use

Usage Instructions

Preparing the Meter for Use

Ensure the meter is used by qualified individuals with appropriate electrical installation credentials.

Safety Precautions

  • Familiarize yourself with the user manual.
  • The meter should only be operated by properly qualified and trained personnel in terms of occupational health and safety.
  • Exercise caution when measuring voltages exceeding the following limits (according to standard PN-EN 61010-1:2010/AMD1:2016):
    • Normal conditions: 60 V DC, 30 V AC RMS, 42.4 V AC peak value
    • Humid conditions: 35 V DC, 16 V AC RMS, 22.6 V AC peakvalue
  • Hold the measurement probes by their designated insulated areasto avoid accidental contact with exposed metal parts.
  • If the “OL” symbol appears on the screen during measurement, it indicates that the measured value exceeds the measurementrange.

Functional Description

  • Measurement Sockets and Functions
    • The meter is equipped with various measurement sockets and functions for different types of measurements.
  • Display
    • The large 4-digit display shows the measurement readings.
  • Test Leads
    • The meter comes with test leads for connecting to the measurement sockets.

Special Functions

  • HOLD Button
    • The HOLD function freezes the measurement reading on the screen.
  • Flashlight
    • The built-in flashlight allows for illuminating the measurement area.
  • MODE Button
    • The MODE button is used to change the measurement mode and activate backlighting.
  • MAX/MIN Button
    • The MAX/MIN button is used to display the maximum and minimum values of a measurement.
  • Auto Power Off
    • The meter will automatically power off when not in use.

Battery Replacement

Instructions for replacing the battery can be found in the user manual.

Maintenance and Care

Instructions for maintenance and care can be found in the user manual.

Storage

Instructions for proper storage can be found in the user manual.

Technical Specifications

Basic Data
Measurement range: Up to 6000

Operating Data
Measurement functions: DC voltage, AC voltage, AC current, resistance, electrical capacitance, diode testing, continuity testing

Service
For servicing the CMP-200F meter, refer to the user manual.

Frequently Asked Questions (FAQ)

  • Q: Who can use the CMP-200F meter?
    A: The CMP-200F meter can only be used by qualified individuals with appropriate electrical installation credentials.

  • Q: What should I do if the measured value exceeds the measurement range?
    A: If the “OL” symbol appears on the screen during measurement, it means that the measured value exceeds the measurement range.

CMP-200F True RMS multimeter is intended for measuring direct and alternating voltage, alternating current, resistance, and capacitance, and for testing diodes and circuit continuity.

The most important features of CMP-200F include:

  • non-contact current measurement
  • non-contact voltage detector,
  • automatic detection of AC and DC voltage
  • automatic range setting,
  • low-impedance voltage measurement LowZ,
  • MAX/MIN function for displaying maximum, minimum and average values,
  • The HOLD function is used to maintain the read-pot on the meter screen,
  • built-in flashlight for lighting the measurement location,
  • sound signal for circuit continuity,
  • AUTO-OFF function,
  • 4-digit display (read-out 6000).

Introduction

Thank you for purchasing the Sonel multimeter. CMP-200F meter is a modern, easy, and safe measuring device. Please acquaint yourself with this manual to avoid measuring errors and prevent possible problems in the operation of the meter. This manual contains three types of warnings. They are presented as framed text describing the possible risks for the user and the device. Text WARNING describes situations, that may endanger a user’s life or health when instructions are not followed. Texts CAUTION! begin a description of a situation, which may result in device damage, when instructions are not followed. The indication of possible problems is preceded by a symbol.

WARNING

  • CMP-200F meter is designed to measure the current and AC/DC voltage, frequency, resistance, and capacitance, as well as to test the circuit continuity and diodes. Any application that differs from those specified in the present manual may result in damage to the device and constitute a source of danger for the user.
  • CMP-200F meter must be operated only by appropriately qualified personnel with relevant certificates authorizing the personnel to perform works on electronic systems. Unauthorized use of the meter may result in its damage and may be a source of serious hazard to the user.
  • Before operating the device, read thoroughly this manual and observe the safety regulations and guidelines provided by the producer. Failure to follow the instructions specified in this manual may result in damage to the device and be a source of serious hazard to the user.

Safety

General rules

To provide conditions for correct operation and the correctness of the obtained results, the following recommendations must be observed:

  • before using the meter read carefully this manual,
  • the meter should be operated only by qualified persons who have passed health and safety training,
  • be very careful when measuring voltages exceeding (as per IEC 61010-1:2010/AMD1:2016):
    Normal locations| Wet locations
    ---|---
    60 V DC| 35 V DC
    30 V AC RMS| 16 V RMS
    42.4 V AC of peak value| 22.6 V AC of peak value

as they generate a potential risk of electric shock,

  • do not exceed the maximum limits of the input signal,
  • during the voltage measurements do not switch the device in the current or resistance measuring mode and vice versa,
  • when changing ranges, always disconnect the test leads from the tested circuit,
  • hold the measuring probes by the spot provided, restricted by a special barrier to avoid accidental contact with exposed metal parts,
  • If during the measurement symbol OL appears on the screen, it indicates that the measured value exceeds the measurement range,
  • It is unacceptable to operate:
    • a damaged meter which is completely or partially out of order,
    • a device with damaged insulation of test leads,
    • a meter stored for an excessive period in disadvantageous conditions (e.g. excessive humidity).
  • repairs may be carried out only by an authorized service point.

WARNING

  • Never start the measurements if you have wet hands.
  • Do not perform measurements in explosive atmospheres (e.g. in the presence of flammable gases, vapors, dusts, etc.). Using the meter in such conditions may result in sparking and cause an explosion.
    The limit values of the input signal

    Function| The maximum

input value

200 A AC| 200 A AC
V DC, V AC| 1000 V DC/AC RMS
V DC, V AC (Low Z)| 600 V DC/AC RMS
Resistance, continuity, diode

test, capacitance

| 300 V DC/AC RMS

The limit values of the input signal

Safety symbols

  • This symbol located near another symbol or terminal, indicates that the user should read the further information contained in the manual.
  • This symbol located near the terminal, indicates that in normal use there is a possibility of dangerous voltages.
  • Protection class II – double insulation
  • Terminals with this marking cannot be connected to a circuit where the voltage to ground exceeds the maximum safe voltage of the device.

Preparing the meter for operation

After purchasing the meter, check whether the content of the package is complete.
Before performing the measurement:

  • make sure that the battery level is sufficient for measurements,
  • check whether the meter casing and insulation of the test leads are not damaged,
  • to ensure consistent measurement results it is recommended to connect black lead to COM terminal and red lead to the second terminal,
  • when the meter is not in use, set the function switch in OFF position.

The device has the AUTO-OFF function triggered after approx. 15 minutes of user inactivity. To turn the meter on again, set the function switch to OFF position and then set it at the desired function.

WARNING

  • Connecting wrong or damaged leads may cause electric shock.
  • The meter must not be connected to the voltage source when it is set to current or resistance measurement or to diode test. Failure to observe this precaution may damage the meter!

When using the meter, be sure to:

  • discharge capacitors in the tested power sources,
  • disconnect the power supply when measuring the resistance and diode tests,
  • turn off the meter and disconnect test leads before removing the back cover to replace the battery.

WARNING

  • Do not use the meter if the cover of battery compartment is removed.
  • It is possible that in certain low ranges of AC or DC volt-age, when the meter is not connected to the leads, the screen will show random and variable readings. This is a normal phenomenon, which results from the input sensitivi-ty with high input resistance. When connected to a circuit, the read-out will stabilize and the meter will provide the cor-rect value.

Functional description

Measuring terminals and functionsSonel-CMP-200F-Clamp-Meters-Handheld-
Devices-fig- \(1\)

  1. Non-contact voltage detector

  2. Fork clamp

  3. Indicator light of the non-contact voltage detector

  4. LCD display

  5. HOLD button

  6. Freezing the measurement results on the display (press shortly)

  7. Flashlight mode (press and hold)

  8. Function buttons

  9. MODE button

  10. Changing the measurement mode in functions: resistance / diode test / continuity / capacitance / LowZ AC / LowZ DC (press shortly)

  11. Backlight (press and hold)

  12. MAX/MIN button – displaying the highest / lowest value from those currently recorded

  13. To enable the function – press shortly

  14. Selection of maximum or minimum value – press shortly

  15. To disable the function – press and hold for approx. 1 sec

  16. COM measuring terminal

  17. Measuring input, common for all measuring functions excluding current.

  18. Measurement terminal

  19. Measuring input for measurements other than current measurement

  20. Rotary switch
    Function selection:

  21. – resistance measurement, diode test, continuity, capacitance measurement

  22. – measurement of alternating current, up to 200 A

  23. – measurement of direct and alternating voltage

  24. OFF – the meter is switched off

  25. – low-impedance voltage measurement

  26. Flashlight

Display

Sonel-CMP-200F-Clamp-Meters-Handheld-Devices-fig-
\(9\)

Leads
The manufacturer guarantees the correctness of read-outs only when original test leads are used.

WARNING
Connecting wrong leads may cause electric shock or measurement errors.

  • The probes are equipped with additional removable tip guards.
  • The probes must be stored in a designated area.

Measurements

The content of this chapter should be thoroughly read and un-derstood since it describes methods of measurements and basic principles of interpreting measurement results.

Current measurement
WARNING:
Disconnect the test leads before measuring current us-ing fork clamp.

To perform the current measurement:

  • set the rotary switch at 200A,
  • set the measuring fork clamp so that there is a single cable within it – at the height of the arrows,
  • read the measurement result on the display.

Sonel-CMP-200F-Clamp-Meters-Handheld-Devices-fig-
\(10\)

Non-contact voltage detector WARNING

  • The detector is designed to detect the presence of a voltage, not for determining its absence.
  • Electric shock hazard. Before using the tester, check if its operational by testing it on a known AC voltage (i.e. next applicable socket with live voltages).

To activate the detector:

  • set the rotary switch at any position,
  • touch the tip of the detector to the tested object. If the AC voltage is present, the indicator light will glow red.
  • The wires in the extension cords are often twisted. For best results, move the tip of the detector along the wire to locate the live line.
  • The indicator has a high sensitivity. It can be randomly actuated by static electricity or other energy sources. This is normal.
  • The type and thickness of the insulation, distance from the power source, shielded cables and other factors may affect the operation of the tester. If you are unsure about the test result, check the presence of voltage in a differ-ent way.

AC/DC voltage measurement

  • Electric shock hazard. The ends of measuring probes, due to their length, may not reach the live parts inside some network connections of low-voltage electrical equipment, because the contacts are arranged inside the sockets. In such a case, the read-out will be 0 V with the simultaneous presence of voltage in the socket.
  • Before acknowledging the absence of voltage in the socket make sure that the ends of the of the probe touch the metal contacts inside the socket.

CAUTION!
Do not measure the voltage when an electric motor located within the circuit is being switched on or off. Resulting voltage spikes may damage the meter

To perform AC or DC voltage measurement:

  • set the rotary switch at ,
  • connect black test lead to COM terminal, and red test lead to terminal,
  • contact the tips of test probes to the points of measurement,
  • read the measurement result on the display.

Resistance measurement
Do not perform measurements on the circuit under the voltage. Before the measurement disconnect the power and discharge capacitors

To perform measurement of resistance:

  • set the rotary switch at ,
  • connect black test lead to COM terminal, and red test lead to terminal,
  • contact the tips of test probes to the points of measurement; the best solution is to disconnect one side of the tested element, to prevent the remaining part of the circuit interfere with the read-out of the resistance value,
  • read the measurement result on the display

Circuit continuity test
Do not perform measurements on the circuit under the voltage. Before the measurement disconnect the power and discharge capacitors.

To perform the continuity test:

  • set the rotary switch at ,
  • connect black test lead to COM terminal, and red test lead to terminal,
  • press MODE button to display on the screen,
  • contact the tips of test probes to the points of measurement,
  • read the measurement result on the display; the beep will be activated when resistance values are below approx. 50 Ω.

Diode test
Do not perform measurements on the circuit under the voltage. Before the measurement disconnect the power and discharge capacitors. Do not test the diode under voltage.

To perform the diode test:

  • set the rotary switch at ,
  • connect black test lead to COM terminal, and red test lead to terminal,
  • press MODE button to display on the screen,
  • contact the tips of test probes to the diode. The red test probe should contact the anode and the black should contact cathode,
  • read the test result on the display – the forward voltage is displayed.
    • For a typical silicon rectifier diode, it is approx. 0.7 V, and for a germanium diode it is approx. 0.3 V
    • For LEDs with a low power, typical voltage value is in the range of 1.2…5.0 V depending on the colour.
    • If the diode is polarized in the reverse direction, or there is a break in the circuit, the display will show OL.
    • When the diode is shorted, the meter will show a value near 0 V,
  • after completing the measurements, remove test leads from the terminals of the meter

Capacitance measurement
Risk of electric shock. Disconnect the power supply from the tested capacitor and discharge all capacitors before any starting capacity measurements.

To perform the measurement:

  • set the rotary switch at Ω CAP,
  • connect black test lead to COM terminal, and red test lead to VΩ CAP terminal,
  • press MODE button to display F on the screen,
  • contact the probe tips to the tested capacitor,
  • read the measurement result on the display

Low Z measurement (elimination of interference and induced voltages)

Measurement function in ‘Low Z’ mode eliminates the influence of interference voltages or induced voltages, making the measurement more accurate and reliable. These voltages may occur due tocapacitive coupling between the live conductors and the unused conductors located in the vicinity.

To perform the measurement:

  • set the rotary switch at V Low Z,
  • press MODE button to display the following symbol:
    • , if an alternating voltage is to be measured,
    • , if a constant voltage is to be measured,
  • connect black test lead to COM terminal, and red test lead to ,
  • contact probe blades to measurement points (for DC circuits: connect red probe to the positive pole),
  • read the measurement result on the display

Special features

Button HOLD

  • HOLD function
  • This function is used to ‘freeze’ the measurement result on the display. To do this, shortly press HOLD button. When the func-tion is enabled, the display shows symbol HOLD.
  • To return to the normal operation mode of the device, press HOLD button again.

Flashlight
Press and hold HOLD button for 1 second to turn on/off the flashlight mode.

Button MODE

  • Changing the measurement mode
    Press shortly MODE button to switch between the available measurement modes.

  • Backlight
    Pressing and holding MODE button for 1 second will turn on/off the backlight of the rotary switch and functions.

Button MAX/MIN

  • To enable the mode, press MAX/MIN.
  • Press the MAX/MIN button to switch between the extreme values of the ongoing measurement.
    • Symbol MAX symbol – the meter displays the highest value out of existing measurement readings.
    • MIN symbol – the meter displays the lowest value out of existing measurement readings.
  • To disable the function, press and hold the MAX/MIN button for approximately. 1 second or turn the rotary switch.
    • If the reading is outside the measurement range, the symbol OL is displayed.
    • The button is not active for voltage and capacitance measurement, as well as continuity and diode tests.

Auto-Off
The meter automatically shuts off after 15 minutes of user inactivity. The symbol in the upper left corner of the display indicates the activated function.

The auto-off function may be temporarily disabled. For this purpose:

  • set the rotary switch at the OFF position,
  • Press and hold the MODE button,
  • set the rotary switch at the desired measuring function,
  • wait until the meter reaches measurement readiness,
  • release MODE button. When the automatic shutdown is deactivated, the display does not show an icon

Each pass of the rotary switch through the “OFF” position with the non-pressed MODE button, will activate again the Auto-Off function.

Replacing the battery

WARNING

  • To avoid electric shock, do not use the meter if the battery compartment cover is not in place or is not properly fastened.
  • The meter is powered by 2 AA 1.5 V batteries. It is recom-mended to use alkaline batteries.

To replace the battery:

  • set the rotational function selector at OFF,
  • remove test leads from the terminals of the meter.
  • unscrew 1 screw fixing the compartment cover,
  • remove the cover,
  • remove the batteries and insert new ones, observing the polarity,
  • put on the cover and tighten the fixing screw.
  1. While performing the measurements with the battery symbol displayed, the user must be aware of additional measurement uncertainties or unstable operation of the device.
  2. If the meter does not work properly, check the batteries to ensure that they are in proper condition and properly installed in the device.

Maintenance and care

The digital multimeter has been designed for many years of reliable use, provided that the following recommendations are ob-served for its maintenance and care:

  1. THE METER MUST BE DRY. Wipe the dampened meter.
  2. THE METER MUST BE USED AND STORED IN NORMAL TEMPERATURES. Extreme temperatures may shorten the life of electronic components and distort or melt plastic parts.
  3. THE METER MUST BE HANDLED CAREFULLY AND GENTLY. Dropping the meter may damage its electronic elements or the housing.
  4. THE METER MUST BE KEPT CLEAN. From time to time wipe the housing with a damp cloth. DO NOT use chemicals, solvents or detergents.
  5. USE ONLY NEW BATTERIES OF THE RECOMMENDED SIZE AND TYPE. Remove the old or discharged batteries from the meter to avoid leakage and damage.
  6. IF THE METER IS TO BE STORED FOR LONGER THAN 60 DAYS, remove the batteries and keep them separately.

The electronic system of the meter does not require maintenance.

Storage

During the storage of the device, the following recommenda-tions must be observed:

  • disconnect the test leads from the meter,
  • make sure that the meter and accessories are dry,
  • when the device is to be stored for longer time, remove the bat-tery.

Dismantling and disposal

  • Worn-out electric and electronic equipment should be gathered selectively, i.e. it must not be placed with waste of another kind.
  • Worn-out electronic equipment should be sent to a collection point in accordance with the law of waste electrical and electronic equipment.
  • Before the equipment is sent to a collection point, do not dis-mantle any elements.
  • Observe local regulations concerning disposal of packages, waste batteries and accumulators.

Technical data

Basic data

“m.v.” means a standard measured value.

True RMS measurement for AC current

Range Resolution Accuracy
200.0 A 0.1 A ± (3% m.v. + 5 digits)
  • All AC current ranges are specified from 5% to 100% of range
  • Frequency range: 50 Hz…60 Hz

True RMS voltage measurement

Range Resolution Accuracy
6.000 V 0.001 V ± (1.2% m.v. + 5 digits)
60.00 V 0.01 V ± (1.2% m.v. + 2 digits)
600.0 V 0.1 V
1000 V 1 V ± (1.5% m.v. + 2 digits)
  • All AC voltage ranges are specified from 5% to 100% of range
  • Input impedance: 10 MΩ
  • Frequency range: 50 Hz…1000 Hz (sine wave), 50/60 Hz (all waves)
  • Overload protection: 1000 V DC/AC RMS

DC voltage measurement

Range Resolution Accuracy
6.000 V 0.001 V ± (0.9% m.v. + 5 digits)
60.00 V 0.01 V ± (1.0% m.v. + 2 digits)
600.0 V 0.1 V
1000 V 1 V ± (1.2% m.v. + 2 digits)
  • Input impedance: 10 MΩ
  • Overload protection: 1000 V DC/AC RMS

Low Z measurement

Range Resolution Accuracy
6.000 V 0.001 V ****

± (3.0% m.v. + 40 digits)

60.00 V| 0.01 V
600.0 V| 0.1 V

  • All AC voltage ranges are specified from 5% to 100% of range
  • Input impedance: 3 kΩ
  • Frequency range: 50 Hz…1000 Hz (sine wave), 50/60 Hz (all waves)
  • Overload protection: 600 V DC/AC RMS

Resistance measurement

Range Resolution Accuracy
600.0 Ω 0.1 Ω ± (1.0% m.v. + 4 digits)
6.000 kΩ 0.001 kΩ ****

± (1.5% m.v. + 4 digits)

60.00 kΩ| 0.01 kΩ
600.0 kΩ| 0.1 kΩ
6.000 MΩ| 0.001 MΩ| ± (2.5% m.v. + 4 digits)
60.00 MΩ| 0.01 MΩ| ± (3.5% m.v. + 4 digits)

Overload protection: 300 V DC/AC RMS

Capacitance measurement

Range Resolution Accuracy
60.00 nF 0.01 nF ****

± (3.0% m.v. + 5 digits)

600.0 nF| 0.1 nF
6.000 µF| 0.001 µF
60.00 µF| 0.01 µF
600.0 µF| 0.1 µF| ± (3.5% m.v. + 10 digits)
4000 µF| 1 µF| ± (5.0% m.v. + 10 digits)

  • Accuracy unspecified for capacitance of <6 nF
  • All capacitance ranges are specified from 10% to 100% of range
  • Overload protection: 300 V DC/AC RMS

Operating data

  • measurement category according to IEC 61010-1 …………………. CAT IV 600 V (III 1000 V)
  • type of insulation ………………………………………………………………………………. double, Class II
  • housing type …………………………………………………………………………………. double-composite
  • degree of housing protection acc. to EN 60529 ……………………………………………………. IP40
  • pollution degree …………………………………………………………………………………………………….. 2
  • opening of measurement clamp ……………………………………………………………… 16 mm (0.6”)
  • power supply of the meter ……………………………………………………… 2x LR6 AA 1.5 V battery
  • diode test ………………………………………………………………………….. I = 0.15 mA, U0 < 3 V DC
  • continuity test …………………………………………………………………. acoustic signal for R < 50 Ω…………………………………………………………………………………….. measuring current <0.35 mA
  • indication for range exceeding …………………………………………………………………..OL symbol
  • low battery indication ……………………………………………………………………………. symbol
  • measurement rate ………………………………………………………….3 measurements per second
  • crest factor ………………………………………………………………………………………………………… < 3
  • range of the non-contact voltage detector ………………………. 200…1000 V AC (50…60 Hz)
  • input impedance ……………………………………………………………….. approx. 10 MΩ (V AC/DC)
  • input impedance for Low Z ……………………………………………………………………. approx. 3 kΩ
  • AC read-out …………………………………………………………………….True RMS (A AC and V AC)
  • AC bandwidth
    • sine waves ………………………………………………………………………………………… 50…1000 Hz
    • all waves……………………………………………………………………………………………….. 50 / 60 Hz
  • display …………………………………………………………………………………………………… 4 digit LCD ………………………………………………………………………….. 6000 counts with function indicators
  • dimensions ……………………………………………………………………………………. 230 x 44 x 66 mm
  • meter weight …………………………………………………………………………………………………… 270 g
  • meter weight (without batteries) ………………………………………………………………………… 223 g
  • operating temperature ………………………………………………………………………………. +5..+40C
  • operating humidity ………………………. < 80% up to 31ºC decreasing linearly to 50% at 40ºC
  • storage temperature ………………………………………………………………………………… -20..+60C
  • storage humidity …………………………………………………………………………………………….. < 80%
  • drop test ……………………………………………………………………………………………………………. 2 m
  • maximum operating altitude …………………………………………………………………………… 2000 m
  • Auto-Off function ……………………………………………………………………………….. approx. 15 min
  • compliance with the requirements of the following standards ……………………….EN 61010-1 ……………………………………………………………… EN 61010-2-32, EN 61010-2-033, EN 61326
  • quality standard ………………………………………………………………………………………… ISO 9001

Service

The provider of guarantee and post-guarantee services is:
SONEL S.A. Wokulskiego 11 58-100 Świdnica Poland
tel. +48 74 884 10 53 (Customer Service)
e-mail : customerservice@sonel.com
web page : www.sonel.com

CAUTION!
Service repairs must be performed only by the manufacturer.

SONEL S.A. Wokulskiego 11 58-100 Swidnica Poland

Customer Service
tel. +48 74 884 10 53
e-mail (GLOBAL):
customerservice@sonel.com
e-mail (PL):
bok@sonel.pl
www.sonel.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals