systemair KT 50-25-6 Centrifugal Rectangular Duct Fan Instructions

June 4, 2024
systemair

systemair KT 50-25-6 Centrifugal Rectangular Duct Fan

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
PRODUCT

Description

  • Swing-out
  • Speed-controllable
  • Integral thermal contacts
  • Can be installed in any position
  • Maintenance-free and reliable

The KT models have impellers with forward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. The casing is manufactured from galvanised sheet steel. To protect the motor from overheating the fans have integral thermal contacts with external leads for connection to a motor protection device. The fans can be installed in any position and are easy to connect using the DS flexible connections. The KT fans have a prewired, integral terminal box.

Technical parameters

Nominal data|
---|---
Voltage| 400| V
Frequency| 50| Hz
Phase| 3| ~
Input power (P1)| 220| W
Current| 0,44| A
Max. airflow| 0,381| m³/s
R.p.m.| 826| r.p.m.
Weight| 16,5| kg
| |
Temperature data| |
Max. temperature of transported air| 70| °C
Max. temperature of transported air when speed-controlled| 70| °C
| |
Sound data| |
Sound pressure level at 3 m| 43,7| dB(A)
| |
Protection / Classification| |
Insulation class| F|
Enclosure class, motor| IP54|

Energy class label

Energy class, basic unit

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
FIG-1

Energy class, unit with local demand control

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
FIG-2

Diagrams

Diagrams

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
FIG-3

Max efficiency

Hydraulic data|
---|---
Working air flow| | | | | | | | 0,19| m³/s|
Working static pressure| | | | | | | | 132| Pa|
Power| | | | | | | | 107| W|
Speed| | | | | | | | 940| r.p.m.|
Current| | | | | | | | 0,31| A|
SFP| | | | | | | | 0,564| W/(l/s)|
Voltage| | | | | | | | 400| V|
Sound power level| | 63| 125| 250| 500| 1k| 2k| 4k| 8k| Tot
Inlet| dB(A)| 52| 59| 55| 52| 54| 53| 50| 44| 63
Outlet| dB(A)| 50| 55| 56| 61| 59| 58| 55| 48| 66
Surrounding| dB(A)| 33| 41| 46| 45| 44| 37| 33| 30| 51
****| | | | | | | | | |

Dimensions

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
FIG-4

**A B C D E F G H I***

  • KT 40-20 398 198 220 420 440 240 502 32 530
  • KT 50-25 498 248 270 520 540 290 532 68 610
  • KT 50-30 498 298 320 520 540 340 562 68 695
  • KT 60-30 598 298 320 620 640 340 642 89 715
  • KT 60-35 598 348 370 620 640 390 717 92 805
  • KT 70-40-4 698 398 420 720 740 440 787 92 900
  • KT 70-40-6/8 698 398 420 720 740 440 787 92 900
  • KT 80-50 798 497 520 820 840 540 880 113 1090
  • KT 100-50 998 497 520 1020 1040 540 980 113 1140

I* = Dimension with fully open hatch

Wiring

systemair-KT-50-25-6-Centrifugal-Rectangular-Duct-Fan-
FIG-5

Accessories

Electric accessories

  • RTRD 2 Speed Cont. Systemair (5941)
  • RTRDU 2 Speed contr. Systemair (5945)
  • RT 0-30 Room Thermostat (5151)
  • STDT 16 Motor Protection (5152)
  • STDT 16E Motor Protection (5153)
  • CO2RT-R-D Transmitter (6993)
  • Presence detector/IR24-P (6995)
  • DTV200 (6261)
  • REV-5POL/07 ON/OFF (33980)
  • DTV500A (96807)
  • RBM 50-25/15 400V/3 Duct heate (5451)
  • PGK 50-25-3-2,0 Duct cooler (6606)
  • VBR 50-25-2 Water heating batt (5464)
  • VBR 50-25-4 Water heating batt (5472)
  • LDR 50-25 Silencer (5070)
  • FFK 50-25 Filter cassette rect (1752)
  • DS 50-25 Flexible connection (1542)
  • GFL 50-25 Counter flange (2706)
  • VK-50-25 Louvre shutter (5647)
  • WSG 50-25 weather prot. guard (30590)
  • SRK 50-25 Class 3 Damper (7021)
  • DXRE 50-25-3-2,5 Duct cooler (7952)
  • RB 50-25/15-1 400V/3 Duct heat (9629)
  • RB 50-25/22-2 400V/3 Duct heat (9633)
  • RKT-SYS-500×250-S (43630)
  • RK-SYS-500×250-R (43644)
  • RK-SYS-500×250-S (43653)

Documentation
202341_Fans_Instructions_CE_A010.pdf (1,83MB)

Specification text

Circular duct fan for easy and direct installation in ducts. Galvanized steel sheet housing. Service cover. The fan unit is mounted on the service cover for easy cleaning and maintenance. Free-running, forward curved circular impeller made of galvanized steel sheet. Impeller acc. to VDI 2060, balancing quality G 6.3, dynamically balanced in two planes. Voltage controllable external rotor motor (IP44), maintenance-free, the motor is placed inside the air flow for cooling. Integral thermal contacts acc. to EN 60335-2-80 with leads to a motor protection device. Speed-controlled by voltage reduction via transformer. Controllable via frequency inverter and all-pole sinusoidal filter. Terminal box on the casing. For extract and supply air. Installation in any mounting position. For indoor installation

Get In Touch

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals