Altronix AL125220 Series Access Control Power Supply/Charger Installation Guide
- June 16, 2024
- Altronix
Table of Contents
Altronix AL125220 Series Access Control Power Supply/Charger Installation
Guide
Overview:
Altronix AL125220 and AL125X220 Power Supply/Chargers convert 220VAC (working
range 198VAC – 256VAC),
50/60Hz input into two individually PTC protected auto-resettable 12VDC or
24VDC outputs (see specifications).
They are intended for use in Access Control applications and applications
requiring an interface with Fire Alarm
Control Panels.
Specifications
Input:
- 220VAC (working range 198VAC – 256VAC), 50/60 Hz, 0.3A.
Output:
- Two (2) 12VDC or 24VDC outputs.
- 1A total supply current @ 12VDC or 24VDC.
- Filtered and electronically regulated output.*
Battery Backup:
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current: 400mA.
- Automatic switch over to stand-by battery when AC fails.
Special Features:
- AC power and unit status indicator on the front panel.
- Normally Open [NO] trigger input.
- Supervised Fire Alarm Disconnect (Latching w/reset or Non-Latching).
Enclosure Dimensions (H x W x D):
- AL125220:
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).
Accommodates one (1) 12VDC/4AH battery.
• AL125X220:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
Accommodates up to two (2) 12VDC/7AH batteries.
Note: When unit is powered by battery back up (AC Fail condition), the voltage range is 9.3V-13.2V and 19.55V-26.4V for 12 and 24 volt operation respectively.
Power Supply Output Specifications:
Output VDC| Switch Position| Max. Stand-by Load DC| Max. Alarm Load DC|
Battery (optional)
---|---|---|---|---
12VDC| SW2 OFF| 1A| 1A| 12VDC
24VDC| SW2 ON| 1A| 1A| 24VDC
Stand-by Specifications:
Output| 4hr. of Stand-by & 5 min. of Alarm| | Output| 4hr. of Stand-by & 5
min. of Alarm
---|---|---|---|---
12VDC / 4AH Battery| 0.5A / 1A| | 12VDC / 7AH Battery| 1A / 1A
24VDC / 4AH Battery| 0.5A / 1A| | 24VDC / 7AH Battery| 1A / 1A
Installation Instructions:
The units should be installed in accordance with article 760 of The National
Electrical Code and NFPA 72 as
well as all applicable Local Codes.
See Terminal Identification Chart on page 4 for a description of each
terminal function.
-
Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 7-8). -
Power connections: Connect secondary (blue and yellow leads) from the transformer to the Power Supply
Board terminals marked [XFMR] ( Fig. 1 – Application Diagram, pg. 5). Connect unstitched AC
circuit (220VAC, 50/60Hz) as follows: Green branch wire (ground) connects to the terminal marked ,
Line connects to the terminal marked [L], and Neutral connects to the terminal marked [N] of the Inlet Appliance Connector. Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs). Use 22 AWG to 18 AWG for power-limited circuits (Trigger inputs, Dry outputs, DC outputs). -
Measure output voltage before connecting devices. This helps avoiding potential damage.
-
Set the desired DC output voltage by setting switch SW2 to the appropriate position (Power Supply Output Specifications Table, pg. 2, Fig. 1a, pg. 5).
-
Connect Fail-Safe locking devices to the terminals marked [COM –] and [LOCK+]. Connect Fail-Secure locking devices to the terminals marked [COM –] and [STRIKE +] (Fig. 1, pg. 5).
-
Connect normally open access control device (i.e. card reader, request to exit device, access control system) to the terminals marked TRG INPUT [NO, GND] (Fig. 1 – Application Diagram, pg. 5).
-
Connect FACP interface to the terminals marked [FACP1] and [FACP2]. Wire the 2.2K resistor (supplied) in series for a normally closed input or in parallel for a normally open input (Fig. 1, pg. 5). If required, set the latching FACP interface mode by turning SW1 ON ( Fig. 1, pg. 5 ), and connect a normally open reset device to the terminals marked RESET [NO, GND].
-
Connect battery to the terminals marked [+ BAT –] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. -
Please ensure that the cover is secured with the provided cam lock.
Maintenance:
Unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test: Under normal load conditions, the DC output voltage
should be checked for proper voltage level (Power Supply Output Specifications
Table, pg. 2).
Battery Test: Under normal load conditions check that the battery is
fully charged, check specified voltage both at battery terminal and at the
board terminals marked [+ BAT –] to ensure that there is no break in the
battery connection wires.
Note: Maximum charging current under discharge is 400mA.
Note : Expected battery life is 5 years; however, it is recommended
changing batteries in 4 years or less if needed
Terminal Identification:
Terminal Legend | Function/Description |
---|---|
XFMR | Low voltage transformer connections. |
+ AUX – | Aux. power output terminals. These terminals supply 12VDC or 24VDC |
not affected by trig- ger, reset or fire alarm interface.
LOCK + STRIKE + COM –| Switched power output. Fail-Safe [LOCK +] supplies
positive power when unit is not trig- gered and FACP interface is inactive.
Fail-Secure [STRIKE +] supplies positive power when unit is triggered and/or
fire alarm interface is activated.[COM –] supplies negative power.
FACP1 FACP2| Supervised by 2.2K end of line resistor FACP interface. Short or
open will cause power to be dropped to terminal marked [LOCK +] and supply
power to terminal marked [STRIKE +]. Condition can be maintained even after
restoration of the circuit (latching mode).
TRG INPUT NO, GND| Short between these two terminals will cause power to be
dropped to the terminal marked [LOCK+] and supplied to the terminal marked
[STRIKE +].
RESET NO, GND| Momentary short between these terminals would end latching FACP
interface condition. Feature active only if latching FACP is selected (SW1
ON).
+ BAT –| Stand-by battery connections.
LED Diagnostics:
Red | Power Supply Status |
---|---|
ON | Normal function. |
OFF | No DC output. |
Slow Blink | Loss of AC. |
Rapid Blink | Unit is triggered, awaiting reset. Fire alarm interface |
activated.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside. Refer servicing to qualified
service personnel.
Application Diagram:
Enclosure Dimensions (H x W x D):
AL125220 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).
AL125X220 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
Altronix is not responsible for any typographical errors 140 58th Street,
Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com | e-mail:
info@altronix.com | Lifetime Warranty IIAL125220 Series.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>