Honeywell RMA805 Enraf FlexLine Remote Indicator Installation Guide
- June 16, 2024
- Honeywell
Table of Contents
- Documentation
- Installation and Startup
- Display Installation Precautions
- Mounting Remote Indicator
- Mounting Dimensions
- Wiring the RMA805 Enraf FlexLine Remote Indicator
- Explosion-Proof Conduit Seal
- Jumper Settings
- Configuration Guide
- Appendix A. PRODUCT CERTIFICATIONS
- EU DECLARATION OF CONFORMITY
- A2 Marking ATEX Directive
- Control Drawing
- RMA 800 Series Remote Meter
- RMA801, Analog/DE Communications
- NON-HAZARDOUS LOCATION
- HAZARDOUS (CLASSIFIED) LOCATION
- INSTALLATIONS
- Sales and Service
- WARRANTY/REMEDY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell RMA805 Enraf FlexLine Remote Indicator Installation Guide
Documentation
To access complete documentation, including language variants, scan the QR code below using your smart phone/device or QR code scanner.
Go to the APP store for your free Smartphone QR scanner
Or you can follow the URL to access the online Tank Storage Documentation.
The Documentation page will contain direct links to open the product documentation.
URL
QR Code
https://www.hwll.co/TankStorageDocs
Installation and Startup
Installation Site Evaluation
Evaluate the site selected for the RMA805 Engraft Flexile Remote Indicator
installation with respect to the process system design specifications and
Honeywell’s published performance characteristics for your particular model.
Some parameters that you may want to include in your site evaluation are:
- Environmental Conditions:
- Ambient Temperature
- Relative Humidity
- Potential Noise Sources:
- Radio Frequency Interference (RFI)
- Electromagnetic Interference (EMI)
- Vibration Sources
- Motorized System Devices (e.g., pumps)
Display Installation Precautions
Temperature extremes can affect display quality. The display can go blank if
the
temperature is below -20°C or above +70°C; however, this is only a temporary
condition.
The display will again be readable when temperatures return to within operable
limits.
Mounting Remote Indicator
Summary
Remote Indicator models can be attached to a two-inch (50 millimeter) vertical
or horizontal pipe using Honeywell’s optional pipe mounting bracket.
Honeywell’s optional wall mounting bracket is also shown below.
Figure 1 shows typical bracket-mounted installations.
HORIZONTAL PIPE MOUNTING
WALL MOUNTING
**VERTICAL PIPE MOUNTING
**
Mounting Dimensions
Refer to Honeywell drawing number 50094836 for detailed electronic housing dimensions. Refer to Honeywell drawing numbers 50095917 for detailed pipe mounting dimensions and 50095918 for detailed wall mounting dimensions. Abbreviated overall dimensions are also shown on the Specification Sheets for the Remote Indicator models. This section assumes that the mounting dimensions have already been taken into account and the mounting area can accommodate the Remote Indicator.
Bracket Mounting
If you are using an optional bracket, start with Step 1.
-
Align the two mounting holes in the Remote Indicator with the two slots in the mounting bracket and assemble the (2) M8 hex cap screws, (2) lock washers and (2) flat washers provided. Rotate Remote Indicator assembly to the desired position and torque the M8 hex cap screws to 27,0 Nm/20,0 Lb-ft maximum.
Pipe Mount Option: Refer to Figure 2
-
Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe, and install a “U” bolt around the pipe and through the holes in the bracket. Secure the bracket with the nuts, flat washers and lock washers provided.
-
Wall Mount Option: Position the bracket on the mounting surface at the desired location and secure the bracket to the mounting surface using the appropriate hardware (Wall mounting hardware requirements to be determined and supplied by the end user)
Figure 2: Pipe Mounting Bracket Secured to a Horizontal or Vertical Pipe
Wiring the RMA805 Enraf FlexLine Remote Indicator
Overview
The Remote Indicator must be connected to the local HART compatible bus of the
Enraf Smart radar FlexLine or the Enraf Smart Servo 954.
The Remote Indicator has 3 terminals. Following table provides the connection details:
Terminal
| Description
---|---
1| Loop +
2| Loop –
3| Not used
The screw terminals are suitable for wirings up to 16AWG (1.3 mm2 ) Shielded, twisted pair cable such as Belden 9318 or equivalent must be used for all wiring. The cable shield must be connected at only one end of the cable. Connect it to the FlexLine Gauge side and leave the shield insulated at the Remote Indicator side.
Note: If solid core wire is used strip insulation 1/4 in (6 mm). Once
inserted under the square washer the stripped portion should be contained
under the square washer. If multi-stranded wire is used, a ferrule is to be
used and the stripped wire should be in the insulated portion of the ferrule.
The ferrule can be also be used on the solid core wire.
Electrical Wiring
The Remote Indicator shall be connected to the Loop + and Loop – terminals of
the FlexLine Gauge. Typically, these are terminals 24 and 25. See the
installation manual of the FlexLine Gauge for more information.
It is possible that other devices such as a VITO temperature convertor and a
pressure transmitter must be connected to the same loop. All devices must be
wired in parallel. Ensure all devices are set to 4 mA digital multi-drop mode
before connecting to the Flex Line Gauge. See Figure 4 for a connection
diagram.
ATTENTION
Wiring must comply with local codes, regulations and ordinances. Grounding may
be required to meet various approval body certifications, for example CE
conformity. Refer to Appendix A of this document for details.
Wiring Procedure
- See Figure 3, for parts locations. Loosen the end cap lock using a 1.5 mm Allen wrench.
- Remove the end cap cover from the terminal block end of the electronics housing.
- Feed loop power leads through one end of the conduit entrances on either side of the electronics housing. The Remote Indicator accepts up to 16 AWG wire.
- Plug the unused conduit entrance with a conduit plug appropriate for the environment.
- Torque terminal screws to 0.6 Nm (5.3 lbf.in) to 0.8 Nm (7.0 lbf.in).
- Connect the Loop Power wiring shield to earth ground only at the power supply side.
- Replace the end cap and secure it in place being careful not to damage the wires.
Explosion-Proof Conduit Seal
WARNING
When installed as explosion proof in a Division 1 Hazardous Location, keep
covers tight while the Remote Indicator is energized. Disconnect power to the
Remote Indicator in the nonhazardous area prior to removing end caps for
service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the Remote Indicator in the non-hazardous area, or determine that the location is nonhazardous before disconnecting or connecting the Remote Indicator wires.
Remote Indicator installed as explosion proof in Class I, Division 1, Group A Hazardous (classified) locations in accordance with ANSI/NFPA 70, the US National Electrical Code, with ½ inch conduit do not require an explosion- proof seal for installation. If ¾ inch conduit is used, a LISTED explosion proof seal must be installed in the conduit, within 18 inches (457.2 mm) of the Remote Indicator.
Jumper Settings
On the Remote Indicator there is a failsafe jumper and a write protect jumper behind the display on the Communication Module. The top jumper is the failsafe jumper. It is highly recommended to put the failsafe jumper to DOWN (Downscale). The bottom jumper sets the write protect.
| ATTENTION: Electrostatic Discharge (ESD) hazards. Observe precautions
for handling electrostatic sensitive devices.
---|---
Step| Action
1| Ensure the Enraf FlexLine Gauge is switched off or that the Remote
Indicator is disconnected.
2| Loosen the end-cap lock, and unscrew the end cap from the Electronics
side of the Transmitter housing.
3| Carefully depress the tabs on the sides of the Display Module and pull it
off.
4| Set the write protect jumper and the failsafe jumper to the desired
behavior. See Table 1 for jumper positioning.
5| Reinstall the Display Module. Carefully line up the display and interface
connector and snap it into place. Verify that the two tabs on the sides of the
display latch.
6| Screw on the end cap and tighten the end-cap lock.
7| Reconnect the Remote Indicator or switch on the Enraf FlexLine Gauge.
Configuration Guide
The Remote Indicator 3-button interface provides user interface and operation
capability without opening the Remote Indicator.
The user must press button to call up the Main Menu. To exit the Main Menu
and return to the PV display screen, select .
Use the button to scroll through the list of menu items. Press the button
to select an item for data entry or activation. When an item is selected for
data entry or activation, the cursor is positioned over the left-most digit to
allow editing of the value. No action is taken against a menu item until the
button is pressed.
Table 1: Jumper settings
Image | Description |
---|---|
Failsafe = DOWN (3.8mA)Write Protect = OFF (Not Protected) | |
Failsafe = UP (21.8mA) NOT RECOMMEND Write Protect = OFF (Not Protected) | |
Failsafe = DOWN (3.8mA) Write Protect = ON (Protected) | |
Failsafe = UP (21.8mA) NOT RECOMMEND Write Protect = ON (Protected) |
Table 2: Main Menu Structure
Level 1 | Level 2 | Level 3 |
---|---|---|
< Exit> | n/a | n/a |
Diagnostics | Critical Non-Critical | For details see table 6 |
Display Setup | LCD Contrast | For details see table 5 |
Device Setup | HART Setup Parameters | For details see table 4 |
Information | Display COMM Module | For details see table 3 |
Table 3: Display Setup Menu
< Return> Return to the Level 1 menu
LCD Contrast| < Return>
Set Contrast| 0 – 9Default: 5| Adjust the LCD contrast level.| Press ¿ to
edit, or ¯ to select number and ¿ to enter.
Table 4: Device Setup Menu
< Return> Return to the Level 1 menu
| < Return>
HART Address| 7 or 8Default:7| HART polling address| Press ¿ to edit, or ¯ to
select number and ¿ to enter.
Parameters| Standby Time| 0 – 15Default: 5| Enter the time in minutes until
the device automatically goes online once in standby.0 means the device does
NOT automatically goon line.| Press ¿ to edit, or ¯ to select number and ¿ to
enter.
Table 5: Information Menu
< Return> Return to the level 1 menu
Display| < Return>|
Firmware Version| The firmware version of the Display Module| Read Only
COMM Module| < Return>|
Firmware Version| The firmware version of the Communication Module| Read Only
Table 6: Diagnostic Menu
< Return> Return to the Level 1 menu
Critical| < Return>
COMM Module| OK FAULT| FAULT: There is a problem with the Communications
Module.
Non- Critical| < Return>
Supply Voltage| OK LOW HIGH| LOW: Supply voltage is below the low
specification limit HIGH: Supply voltage is above the high specification
limit.
Comm Module Temp| OKOVER TEMP| OVER TEMP: Communications Module temperature is
greater than 85°C.
Display Setup| OK NVMCORRUPT| NVM CORRUPT: The Display setup memory is
corrupted.
Appendix A. PRODUCT CERTIFICATIONS
A1. Hazardous Locations Certifications
MSG CODE| AGENCY| TYPE OF PROTECTION| Electrical
Parameters| Ambient Temperature
---|---|---|---|---
C| ATEX| Flame-proof and Dust: II 2 G Ex db IIC T6..T5 Gb II 2 D Ex tb
IIIC T 95°C Db| Note 1| T6: -50°C to 65°C T95°C, T5: -50°C to 85°C
Intrinsically Safe: II 1 G Ex ia IIC T4 Ga| Note 2| -50°C to 70°C
Non-IncendiveII 3 G Ex ec IIC T4 Gc| Note 1| -50°C to 85°C
Enclosure: Type IP66/IP67| ALL| ALL
STANDARDS: EN 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN60079-31:
2014; EN 60079-7: 2015/A1: 2018;
D| IECEx| Flame-proof: Ex db IIC T6..T5 Gb Ex tb IIIC T 95°C Db| Note 1|
T6: -50°C to 65°C T95°C, T5: -50°C to 85°C
Intrinsically Safe: Ex ia IIC T4 Ga| Note 2| -50°C to 70°C
Non-Incendive Ex ec IIC T4 Gc| Note 1| -50°C to 85°C
Enclosure: IP66/ IP67| ALL| ALL
STANDARDS: IEC 60079-0: 2017 IEC 60079-1: 2014;IEC 60079-11: 2011; IEC
60079-7: 2015/A1: 2018; IEC 60079-31: 2013
MSG CODE| AGENCY| TYPE OF PROTECTION| Electrical
Parameters| Ambient Temperature
---|---|---|---|---
K| cCSAus| Explosion proof: Class I, Division 1, Groups A, B, C, D;T6..T4
Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T4Class I Zone
1 Ex db IIC T4 Gb Ex db IIC T4 Gb
Zone 21 Ex tb IIIC T 95°C Db Ex tb IIIC T 95°C Db| Note 1| T6: -50°C to +65°C
T4 T5: -50°C to 85°C
Intrinsically Safe: CSA 14.2689056Class I, II, III, Division 1, Groups A, B,
C, D, E, F, G; T4Ex ia IIC T4 Ga| Note 2| -50°C to 70°C
Non-Incentive Class I, Division 2, Groups A, B, C, D; T4Class I Zone 2 Ex nA
IIC T4 Gc Ex nA IIC T4 Gc| Note 1| 50°C to 85°C
Enclosure: 4X/ IP66/ IP67| ALL| ALL
Standards: CSA C22.2 No. 0: 2015; CSA C22.2 No. 30: 2016; CSA C22.2 No.
94-M91; CSA C22.2 No. 25: 2017; CSA C22.2 No. 61010-1: 2017; CSA-C22.2No.157:
2016; C22.2 No. 213: 2017; C22.2 No. CSA 60079-0:2015;C22.2 No. 60079-1: 2016;
C22.2 No. 60079-11: 2014; C22.2 No. 60079-15:2016; C22.2 No. 60079-31:
2015;ANSI/ ISA12.12.01-2017; ANSI/ ISA 61010-1: 2016; ANSI/ UL 60079-0:
2013;ANSI/ UL 60079-1: 2015; ANSI/ UL 60079-11: 2014; ANSI/ UL 60079-15:2013;
ANSI/ UL 60079-31: 2015;FM 3600: 2011; FM 3615: 2006; FM Class 3616: 2011;
ANSI/ UL 913: 2015;UL 916: 2015; ANSI/ UL 12.27.01: 2017; ANSI/UL 50E: 2015
MSG CODE| AGENCY| TYPE OF PROTECTION| Electrical Parameter
s| Ambient Temperature
---|---|---|---|---
G| NEPSI| Flame-proof:Ex d IIC Ga/Gb T4 Ex tb IIIC Db T 85°C| Note 1| -20°C to
85°C
Intrinsically Safe: Ex ia IIC Ga T4| Note 2| -20°C to 70°C
Nonincendive: Ex nA IIC Gc T4| Note 1| -20°C to 85°C
Enclosure: IP 66/67| All| All
Notes
- Operating Parameters: Voltage= 12 to 42 V Current= 25 mA
- Intrinsically Safe Entity Parameters For details see Control Drawing, 50089981.
EU DECLARATION OF CONFORMITY
We
Honeywell International Inc.
Honeywell Field Solutions Fort Washington, PA 19034 USA
Virginia Drive declare under our sole responsibility that the following products
RMA800-Smart Series Remote Meter Series
RMA803 Foundation Fieldbus Series
RMA801 Analog/DE Series
RMA805 with ENRAF FLEXLINE Communication Series
to which this declaration relates, is in conformity with the provisions of the European Community Directives, including the latest amendments, as shown in the attached schedule.
Assumption of conformity is based on the application of the harmonized standards and when applicable or required, a European Community notified body certification, as shown in the attached schedule
The authorized signatory to this declaration, on behalf of the manufacturer, and the Responsible Person is identified below.
Owen 1. Mürphy.
Product Safety & Approvals Engineering
Issue Date: 31 July 2020
EMC Directive (2014/30/EU)
EN 61326-1:2013: Electrical Equipment for Measurement, Control and
Laboratory Use-EMC Requirements.
Overview of EMC Testing
Equipment Tested (EUT): RMAB03 Foundation Fieldbus RMA801 Analog/DE
Summary of Tests Performed:
PORT| TEST| STANDARD| CRITERIA
(ICC 613261)| RESULTS
---|---|---|---|---
| Radiated Emission| CRP 11| Groupl, Class A
30 – 230 MHz: 4008
230 -1030 MHz: 47 dg| PASS
Enclosure ESO Immunity| IIC610004.2| ./. 4XV act I.
8ContKV Mr| PASS
EM Field- RE Radiated Susceptibility| tEC6100044| 10 V/m• SO MHz to 2611:
1 V/m- 2.0 OW to 2.7 Gelz| PASS
PASS
S0111/60Hz Magnetk Field Immunity| ICC 610044| 30 Alin| II/A1
DC POwe r| EFITB) Immunity| 1E06100044| q. 1KV| PASS
Surge immunity| IEC610004•| · /• 1KV| PASS
RF Conducted Susceptibility| IEC61000-44| 10 V/m ISO Id to 130Mhz| PASS
I/0 SIvial/ Control(1nCluding tutu Lines)| &T(Bunt) Immunity| IEC6100044| et,
1KV| 2
Surge Immunity| IEC610004•| · /• 1KV| 2
RF Conducted Susceptibility| IEC6100044| 10 V/m 150 kHz to 80 Pau| 2
AC Power| Voltage Dip| IEC61000-441| 0% during I Cycle
4096during 10-12 Cycles
70% during 25•30 Cycles| N/A’
PORT| TEST| STANDARD| OLITERIA
KC 61326-1)| RESULTS
---|---|---|---|---
| Short Interruptions| IEC610004.11| 0% during 250-300 Cycles| N/A1
EFT(Burst) Immunity| IEC61000-4-4| 2KV| N/A3
Surge Immunity| IEC61000-4-5| 1KW 2KV| N/A’
RF Conducted Susceptibility| IEC61000-4-6| MI| N/A1
- There is no magnetic sensitive circuitry.
- Done as part of the DC Power Testing.
- Product is DC Powered.
ATEX Directive (2014/34/EU)
Protection: Intrinsically Safe, and Flameproof
EU-Type Certificate No: SIRA 14ATEX2147X
Equipment Group II Category 1 G
Ex ia IIC T4 Ga (Ta=-20°C TO +70°C)
FISCO Field Device (RMA803 Series only)
Ex ia IIC T4 Ga (Ta-20°C TO +70°C)
Equipment Group II Category 2 GD
Ex db IIC T6..15 Gb (T6-20°C TO +65°C; TS-20°C TO +85°C)
Ex tb 18C T95°C Db (Ta-20°C TO +85°C)
Harmonized Standards:
EN 60079-1: 20014
EN 60079-11: 2012
EN 60079-0: 2018
EN 60079-31: 2014
Type Certificate No: SIRA 14ATEX4148X
Protection: Non Sparking
Equipment Group II Category 3 G Ex ec IIC T4 Gc (Ta= -20°C TO +85°C)
Ex ic IIC T4 Ga (Ta-20°C TO +70°C)
FISCO Field Device (RMA803 Series only)
Ex ic IIC T4 Ga (Tam-20°C TO +70°C)
Harmonized Standards:
EN 60079-0: 2018
EN 60079-7: 2015/A1:2018
EN 60079-11: 2012
ATEX Notified Body for EC Type Certificates
CSA Group Netherlands B.V., [Notified Body Number: 2813] Utrechtseweg 310
(842).
6812 Arnhem
Netherlands
ATEX Notified Body for Quality Assurance
DEKRA Certification B.V. [Notified Body Number: 0344)
Meander 1051
6825 MJ Arnhem
The Netherlands
Restriction of Hazardous Substances Directive (RoHS) (2011/65/EU)
EN50581: 2012 Technical documentation for the assessment of electrical and
electronic products with respect to the restriction of hazardous substances
A2 Marking ATEX Directive
a. General
The following information is provided as part of the labeling of the Remote
Indicator: Name and Address of the manufacturer
The serial number of the Remote Indicator is located on the Meter Body data-
plate. The first two digits of the serial number identify the year (12) and
the second two digits identify the week of the year (23); for example,
1223xxxxxxxx indicates that the product was manufactured in 2012, in the 23rd
week.
b. Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the
equipment. The user shall then check the box [ ] adjacent to the type of
protection used on the equipment certification nameplate. Once a type of
protection has been checked on the nameplate, the equipment shall not then be
reinstalled using any of the other certification types.
C. WARNINGS and Cautions
Non-Incendive / Non-Sparking (Division 2 and Zone 2 Environments):
WARNING-EXPLOSION HAZARD-SUBSTITUTION OF COMPONENTS MAY
IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2
Intrinsically Safe (Divisions 1. Zone 1 and Zone 2 Environments):
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY
IMPAIR
INTRINSIC SAFETY. WARNING-DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS
PRESENT.
Explosion-Proof (Division 1 and Zone 1 Environments):
WARNING-DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS
PRESENT.
WARNING-DO NOT OPEN WHEN ENERGIZED
“OPEN CIRCUIT BEFORE REMOVING COVER”
Flameproof (Division 1 and Zone 1 Environments):
WARNING – DO NOT OPEN WHEN ENERGIZED
General Requirements / Increased Safety (Zone 1):
WARNING DO NOT OPEN WHEN ENERGIZED
WARNING-OPEN CIRCUIT BEFORE REMOVING COVER
All Protective Measures:
WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60°C USE WIRE RATED 105°C
A.3 Conditions of Use” for Ex Equipment”, Hazardous Location Equipment or
“Schedule of Limitations”:
a. Consult the manufacturer for dimensional information on the flameproof
joints for repair.
b. Painted surface of the RMA 800 series may store electrostatic charge
and become a source of ignition in applications with a low relative humidity
less than approximately30% relative humidity where the painted surface is
relatively free of surface contamination such as dirt, dust or oil. Cleaning
of the painted surface should only be done with a damp cloth.
c. The ambient temperature range and applicable temperature class of the
equipment is as follows: RMA805 series: T4 for -50˚C < Ta < 70˚C
d. The RMA800 series enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction. Care must be
considered during installation and use to prevent impact or friction to avoid
impact.
e. If a charge-generating mechanism is present, the exposed metallic part
on the enclosure is capable of storing a level of electrostatic charge that
could become incendive for IIC gases. Therefore, the user/installer shall
implement precautions to prevent the buildup of electrostatic charge, e.g.
earthing the metallic part. This is particularly important if the equipment is
installed in a zone 0 location.
f. On installation, the RMA800 series shall be provided with supply
transient protection external to the apparatus such that the voltage at the
supply terminals of the RMA800 series does not exceed 140% of the voltage
rating of the equipment. However when an RMA805 is connected to a Smart Radar
FlexLine or to a Smart Servo 954 the supply transient protection is included
in the Smart Radar FlexLine or Smart Servo 954.
Control Drawing
COPYRIGHT 2019, HONEYWELL INTERNATIONAL INC. NEITHER THIS DOCUMENT NOR THE INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED, USED OR DISCLOEED TO OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE. DUPLICATION OR DISCLOSURE OF THIS DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A WRITTEN AGREEMENT NOTHING CONTAINED HEREIN SHALL BE CONSTRUED AS CONFERRING BY IMPLICATION, ESTOPPEL, OR OTHERWISE ANY LICENSE TO ANY PATENT, TRADEMARK, COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT OF HONEYWELL OR ANY THIRD PARTY
RMA 800 Series Remote Meter
Analog, DE Communications, Foundation Fieldbus and ENRAF FLEXLINE Communications
-
Intrinsically safe installation shall be in accordance with
a. FM (USA): ANSI/NFPA 70, NEC Articles 504 and 505.
b. CSA (Canada): Canadian Electrical Code (CEC), part 1, section 1
c. CATEX: Requirements of EN 60079-14, 12.3 (See also 5.2.4).
d. IECEx Requirements of IEC 60079-14, 12.3 (See also 5.2.4). -
ENTITY approved equipment shall be installed in accordance with the manufacturer’s Intrinsic Safety Control Drawing.
-
The Intrinsic Safety ENTITY concept allows the interconnection of two ENTITY Approved intrinsically safe devices with ENTITY parameters not specifically examined in combination as a system when:
Uo, Voc, or Vt Uior Vmax; lo, Isc, or It Sli or Imax; Ca or Co2GCcable, La or LoLitcable, Po Pi Where two separate barrier channels are required, one dual- channel or two single-channel barriers may be used, where in either case, both channels have been Certified for use together with combined entity parameters that meet the aliove equations. -
System Entity Parameters:
RMA 800 Remote Meter: Vmax Voc or Uo, Imax Isc or lo;
RMA 800 Remote Meter: Ci RMA 800 Remote Meter: Li Ccable s Control Apparatus Ca, Lcables Control Apparatus La. -
When the electrical parameters of the cable are unknown, the following values may be used:
Capacitance: 197pF/m (60 pF/ft) Inductance: 0.66µH/m (0.020H/ft). -
Control equipment that is connected to Associated Equipment must not use or generate more than 250 V.
-
Associated equipment must be FM, CSA ATEX or IECEx (depending on location) listed. Associated equipment may be installed in a Class I, Division 2 or Zone 2 Hazardous (Classified) location if so approved.
-
Non-Galvanically isolated equipment (grounded Zener Barriers) must be connected to a suitable ground electrode per:
a. FM (USA): NFPA 70, Article 504 and 505. The resistance of the ground path must be less than 1.0 ohm. b. CSA (Canada): Canadian Electrical Code (CEC), part 1, section 10.
c. ATEX: Requirements of EN 60079-14, 12.2.4.
d. IECEx: Requirements of IEC 60079-14, 12.2.4. -
Intrinsically Safe DIVISION 1/ Zone 0 WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS.
-
Division 2/ Zone 2: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT.
-
NO REVISION OF THIS CONTROL DRAWING IS PERMITTED WITHOUT AUTHORIZATION FROM THE AGENCIES listed.
-
For release approvals see ECO-0103558.
MASTER FILE TYPE: MS WORD | DRAWN | Honeywell | ||
---|---|---|---|---|
CHECKED | CONTROL DRAWING RMA 800 SERIES REMOTE METER DIVISIONS 1 AND |
2/ZONE O AND 2
DEV ENG| | | 50089981
MFG ENG| |
QA ENG| |
TOLERANCE UNLESS NOTED| | A/A4
ANGULAR DIMENSION| SCALE: None| USED ON| SH. 1 OF 4
RMA801, Analog/DE Communications
ENTITY PARAMETERS “Ex ia” and Ex ic” | Associated Apparatus |
---|---|
Ui or Vmax 26 and ≤30V | Uo. Voc or Vt 26 and≤30V |
Il or Imax 225 mA | lo (Isc or it) s 225 mA |
Pi or Pmax IW | Pes 1W |
Ci 28,2nF | Ca or Co2 C + Сама 200 |
Li= 4µH | La or Lo 2 L + Lava |
Note: No Change in Parameters when Terminal 9, DE Communications is connected
NON-HAZARDOUS LOCATION
HAZARDOUS (CLASSIFIED) LOCATION
CLASS I CLASS II, DIVISION 1, GROUPS A, B, C, D, E, F & G; ZONE O IIC & ZONE 2
IIC, CLASS I DIVISION 2, GROUPS A, B, C, D,
POSITIVE SIDE OF LOOP
WHEN SHIELD IS USED, GROUND AT THIS END ONLY
ASSOCIATED EQUIPMENT NOT REQUIRED FOR DIV 2/ZONE 2 Exec or AEx nA INSTALLATIONS CONTROL EQUIPMENT PARAMETERS WHEN NO ASSOCIATED EQUIPMENT Umax- Ui- 42V, 25 mA, Po ≤ 1W
NEGATIVE SIDE OF LOOP
Honeywell | A/A4 | 50089981 |
---|---|---|
SCALE: None | REVE DATE 5/26/2020 | SH.2of4 |
RMA803, Foundation Fieldbus
ENTITY PARAMETERS “Ex ia” and Ex ic” | Associated Apparatus |
---|---|
Ui or Vmax ≤ 30V | Uo, Voc or Vt ≤30V |
li or Imax 180 mA | lo (Isc or it) s 180 mA |
Pi or Pmax = 1W | Po≤ 1W |
Ci= 0 nF | Ca or Co 2 Ccable + Савла 800 |
Li=9 µH | La or Lo 2 Lable + LaMA 800 |
FISCO Parameters
ENTITY PARAMETERS “Ex ia” and Ex ic”
Ui or Vmax = 17.5V
li or Imax ≤ 380 mA
Pi or Pmax ≤ 5.32W
Li = 9 µH
Ci = 0 nF
NON-HAZARDOUS LOCATION
HAZARDOUS (CLASSIFIED) LOCATION
CLASS I, CLASS II, DIVISION 1, GROUPS A, B, C, D, E, F & G; ZONE O IIC & ZONE
2 IIC, CLASS I DIVISION 2, GROUPS A, B, C, D;
ASSOCIATED EQUIPMENT NOT REQUIRED FOR DIV 2/ZONE 2 Ex ec or AEx nA
INSTALLATIONS
CONTROL EQUIPMENT PARAMETERS WHEN NO ASSOCIATED EQUIPMENT Umax Ui 32V, 28 mA, Pos1W
Honeywell | A /A4 | 50089981 |
---|---|---|
SCALE None | REV | DATE 5/26/2020 |
RMA805, ENRAF FLEXLINE COMMUNICATIONS
ENTITY PARAMETERS | Associated Apparatus |
---|---|
Ui or Vmax < 30V | Uo, Voc or Vt ≤ 30V |
li or Imax 225 mA | lo (Isc or It) ≤ 225 mA |
Pi or Pmax=0.9W | Pos 0.9 W |
Ci= 3.9 nF | Ca or Co 2 Cable CST 800/ ST 700 |
Li=0 uH | La or Lo 2 L + LST 800/ST 700 |
NON-HAZARDOUS LOCATION
HAZARDOUS (CLASSIFIED) LOCATION
CLASS I, DIVISION 1, GROUPS A, B, C, D, E, F & G; ZONE O IIC & ZONE 2 IIC,
CLASS I DIVISION 2, GROUPS A, B, C, D
ASSOCIATED EQUIPMENT NOT REQUIRED FOR DIV 2/ZONE 2 INSTALLATIONS
CONTROL EQUIPMENT PARAMETERS WHEN NO ASSOCIATED EQUIPMENT
Umax Ui42V, 4-20 mA, Pos 1W
Honeywell | A/A4 | 50089981 |
---|---|---|
SCALE: None | REV F DATE 5/26/2020 | SH. 4 of 4 |
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
Honeywell Pte Ltd.
17 Changi Business Park Central 1Singapore 486073
Phone : +65 6355 2828
Email: (Sales)
Email :enraf-sg@honeywell.com
or (TAC)
hfs-tac-support@honeywell.com
Web
Knowledge Base search
engine http://bit.ly/2N5Vldi
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and
the Honeywell web site, it is up to the customer to determine the suitability
of the product in the application.