Danfoss OPTC4 VACON NXP Air Cooled Installation Guide
- June 16, 2024
- Danfoss
Table of Contents
- Danfoss OPTC4 VACON NXP Air Cooled
- GENERAL
- LONWORKS OPTION BOARD TECHNICAL DATA
- LONWORKS FIELDBUS BOARD LAYOUT AND CONNECTIONS
- INSTALLATION OF VACON NX LONWORKS BOARD
- COMMISSIONING
- | Name| Default| Range| Description
- LONWORKS INTERFACE
- FAULT TRACKING
- APPENDIX 1
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Danfoss OPTC4 VACON NXP Air Cooled
GENERAL
Vacon NX frequency converters can be connected to the LonWorks® network using a field bus board. The converter can then be controlled, monitored and programmed from the Host system. The LonWorks® board shall be installed in slot E on the control board of the frequency converter. LONWORKS technology has been developed by Echelon Corporation. LONWORKS network is used in applications like industry and building automation, controlling household electronics, medical instrumentation and many others. The target of the LONWORKS network is to provide a common vendor-independent communication network for intelligent devices. In a LONWORKS network, no central control or master-slave architecture is needed. Nodes on a network communicate with each other using LonTalk® protocol. Interoperable nodes use Standard Network Variable Types (SNVT) for communicating over the network. The definition of an SNVT includes units, a range, and an increment. Vacon option board uses only Standard Network Variable Types for the data types. All network variables are either input (data is coming from the network to the device) or output (data is sent to the network by the device) network variables. When network variables on different nodes on the network have been bound together by an installation tool, the passing of data is automatic between the right nodes. Only the same type of network variables can be bound together, so it is very important to have compatible interfaces.
WARNING!
Internal components and circuit boards are at high potential when the
frequency converter is connected to the power source. This voltage is
extremely dangerous and may cause death or severe injury if you come into
contact with it.
LONWORKS OPTION BOARD TECHNICAL DATA
General
LonWorks
connections
| Interface| Pluggable connector (5 mm)
---|---|---
Communications| Channel type| TP/FT-10
Transfer cable| Twisted pair
Baud rate| 78 Kbit/s
Environment| Ambient operating temperature| –10°C…50°C
Storing temperature| –40°C…70°C
Humidity| <95%, no condensation allowed
Altitude| Max. 1000 m
Vibration| 0.5 G at 9…200 Hz
Safety| | Fulfils EN50178 standard
Physical media and wiring
LONWORKS networks can be implemented on many different physical media. Vacon OPT-C4 option board is equipped with an FT-X1 transceiver supporting the Free Topology transformer coupled network, which allows the network wire to be connected as bus, star, loop or combination of these. This media reaches a communication speed of 78kBits/s. The FT-X1 transceiver is compatible with Echelon’s LPT-10 Link Power Transceiver, and these transceivers can communicate with each other on a single twisted pair cable.
Up to 64 FTT-10 transceiver nodes are allowed per network segment, the individual segments can be connected together by a router. See Table 3-1 for recommended cable types and cable lengths for FTT-10. Even if unshielded cable types are recommended to be used with this type of transceiver, it is still highly recommended to use only shielded cables with frequency converters. Attention should be paid to proper grounding of the shield to ensure bus operation. Grounding of the shield should be done at both ends of the cable.
Cable type
| Max. doubly terminated bus length| Max. free topology wire length| Max.
node-to-node distance
---|---|---|---
Belden 85102 (unshielded)| 2700 m| 500 m| 500 m
Belden 8471
LONAK 2×1,3 (unshielded)
| 2700 m| 500 m| 400 m
Level IV, 22AWG
LONAK 2x2x0,65 (unshielded)
| 1400 m| 500 m| 400 m
JY (St) Y 2x2x0.8mm LONAK 2x2x0,8 (shielded)| 900 m| 500 m| 320 m
Profiles
LonMark Functional Profiles describe in detail the application layer
interface, including the network variables, configuration properties, and
default and power-up behaviours required on LonMark devices for specific,
commonly used control functions.
Variable Speed Drive Profile
Leading manufacturers of drive technology have jointly defined the LonMark
profile. The profile specifies how the drives are to be parameterized and how
the setpoints and actual values are to be transmitted. This enables drives
from different vendors to be exchanged. The profile contains the necessary
specifications for speed control and positioning. It specifies the basic drive
functions while leaving sufficient freedom for application-specific expansions
and further developments.
LONWORKS FIELDBUS BOARD LAYOUT AND CONNECTIONS
Vacon LonWorks Fieldbus Board is connected to the Fieldbus through a 3-pin pluggable bus connector. The communication with the control board takes place through the standard Vacon Interface Board Connector.
LonWorks OPT-C4 option board
Signal | Connector | Description |
---|---|---|
A1 | 21 | Data |
A2 | 22 | Data |
0Shield | 23 | Shield |
Table 3-1. OPT-C4 bus connector signals
Grounding of bus cable shield in OPT-C4
The bus cable shield can be grounded to the frame of the frequency converter
through an RC filter located on the OPT-C4 board.
Note: Normally, the option board has already been installed in slot E of the control board. It is not necessary to detach the whole board for the grounding of the bus cable shield. Just detach the terminal block.
Grounding the bus cable shield directly to the frequency converter frame using the RCfilter
- Strip about 5 cm of the cable as shown in the picture.
- Leave no more than 7 mm of the data cable outside the terminal block (Figure 3-3) and strip the data cables at about 5 mm to fit in the terminals (Figure 3-4).
- Insert the data cables and the shield in their respective terminals. See Table 3-1.
- If the LonWorks board was detached from the control unit place it into slot E of the control board (see board installation on page 12). Otherwise, attach the terminal block. Fix the cable on the frame with the clamp.
Bus termination resistors
To assure a proper data transmission, termination of the network segments is
required. Depending on the type of network, either one or two terminations are
necessary. Free topology network segment requires only one termination whereas
a doubly terminated bus topology requires two. The jumper X5 on the Vacon
LonWorks board must be set accordingly. Use 94-ohm termination resistance when
only one termination is needed and 47-ohm for two terminations.
LED indications
The three LED indications next to the connector show the present statuses of
the Neuron (green H3), the LonWorks board (yellow H2) and the Fieldbus Module
(green H1). From the user’s viewpoint, the first two are the most significant.
Figure 3-8. LED indications on the LonWorks board
Neuron status (H3) GREEN
LED is: | Meaning: | State Code |
---|---|---|
OFF | Configured | 4 |
ON | Applications and Unconfigured | 3 |
Flashing | Unconfigured | 2 |
Board status LED (H2) YELLOW
LED is: | Meaning: |
---|---|
OFF | Option board not activated |
ON | Option board in initialisation state waiting for activation command from |
the frequency converter
Blinking fast (once/1 s)| Option board is activated and in RUN state
Option board is ready for external communication
Blinking slow (once/5 s)| Option board is activated and in FAULT state Internal fault on option board
Bus status LED (H1) GREEN
LED is: | Meaning: |
---|---|
OFF | The Fieldbus module is waiting for parameters from the frequency |
converter No external communication
ON| The Fieldbus module is activated
Parameters received and module activated Module is waiting for messages from the bus
Blinking very fast for 5s (once/0.2
s)
| The Fieldbus module has received a wink request.
Blinking fast (once/1 s)| The module is activated and receiving messages from
the bus
Blinking slow (once/5 s)| The module is in FAULT state
No messages from the Net within the watchdog time Bus broken, and cable loose
INSTALLATION OF VACON NX LONWORKS BOARD
NOTE
MAKE SURE THAT THE FREQUENCY CONVERTER IS SWITCHED OFF BEFORE AN OPTION OR
FIELD BUS BOARD IS CHANGED OR ADDED!
Board information sticker
The LonWorks option board package delivered by the factory includes a sticker
(shown below). Please mark the board type (1), the slot into which the board
is mounted (2) and the mounting date (3) on the sticker. Finally, attach the
sticker on your drive.
COMMISSIONING
READ FIRST CHAPTER 8 ‘COMMISSIONING’ IN VACON NX USER’S MANUAL (Document nr. ud00701, please visit http://www.vacon.com/support/documents.html).
Fieldbus board parameters
The Vacon LonWorks board is commissioned with the control keypad by giving
values to appropriate parameters in menu M7 (for locating the expander board
menu, see Vacon NX User’s Manual, Chapter 7).
Expander board menu (M7)
The Expander board menu makes it possible for the user 1) to see what expander
boards are connected to the control board and 2) to reach and edit the
parameters associated with the expander board. Enter the following menu level
(G#) with the Menu button right. At this level, you can browse through slots A
to E with the Browser buttons to see what expander boards are connected. On
the lowermost line of the display you also see the number of parameter groups
associated with the board. If you still press the Menu button right once you
will reach the parameter group level including one parameter (Service pin).
LonWorks parameters
To commission the LonWorks board, enter the parameter G7.5.1.1 from the
Parameters group (G7.5.1). Give the desired value to the LonWorks parameter.
| Name| Default| Range| Description
---|---|---|---|---
1| Service Pin| 0| 0..1| Broadcasts a service pin message to the network.
Table 5-1. LonWorks parameters
Start-up test
Frequency converter application
Choose Fieldbus (Bus/Comm) for the active control place (see Vacon NX User’s
Manual, Chapter 7.3.3).
Master Software
- Write 100.0 1 to nviDrvSpeedStpt.
- The frequency converter status is RUN and the output frequency is 1.00 * nviDrvSpeedScale
- Write 0.0 0 to nviDrvSpeedStpt
- Frequency converter status is STOP.
- If nvoDrvStats bit 3 = 1 Status of the frequency converter is FAULT.
LONWORKS INTERFACE
Features of the LonWorks interface:
- Direct control of Vacon NX (e.g. Run, Stop, Direction, Speed reference, Fault reset)
- Full access to all Vacon NX parameters
- Monitor Vacon NX status (e.g. Output frequency, Output current, Fault code)
General
Input Network Variables
Function | Variable Name | SNVT type | Min. Value | Max. Value |
---|---|---|---|---|
Node Object request | nviRequest | SNVT_obj_request | ||
Driver speed setpoint | nviDrvSpeedStpt | SNVT_switch | n/a | n/a |
Driver set point speed scaling | nviDrvSpeedScale | SNVT_lev_percent | -163.840% |
163.830%
Reset fault| nviRstFault| SNVT_switch| n/a| n/a
Clear kWh trip or Drive total running hours trip counters| nviClrCntr|
SNVT_switch| 1| 2
Process In Data| nviProcessIn1..8| SNVT_lev_percent| 0| 65535
Digital Inputs| nviDigitalIn1..8| SNVT_switch| 0| 4
Parameter Set| nviParCmd| SNVT_preset| n/a| n/a
nviRequest
This input network variable provides the mechanism to request a particular
mode for the Node object or the Variable Speed Motor Drive object within a
node. Supported requests are RQ_NORMAL, RQ_UPDATE_STATUS, RQ_CLEAR_STATUS,
RQ_REPORT_MASK, RQ_DISABLED, RQ_ENABLE and RQ_CLEAR_ALARM.
nviDrvSpeedStpt
This input network variable provides control and a low-resolution speed
setpoint.
state | value | command |
---|---|---|
0 | NA | Stop |
1 | 0 | 0% |
1 | 1 to 200 | 0.5 to 100% |
1 | 201 to 255 | 100.0% |
0xFF | NA | Auto |
nviDrvSpeedScale
This input network variable provides scaling for nviDrvSpeedStpt. Negative
values indicate a motor direction in reverse. For example, if the
nviDrvSpeedStpt value is 50% and nviDrvSpeedScale -150%, then the actual speed
setpoint is –75%, or 0.75 times the nominal speed in the reverse direction.
The valid range is –163,840% to 163,830. The value 0x7FFF (+163,835%) will be
handled as an invalid value. The default value is determined by
nciDrvSpeedScale. This value will be adopted at power-up and in case of not
receiving an update within the specified Receive Heartbeat time.
nviRstFault
This input network variable provides a fault reset. Setting value 1 for State
and a non-zero value for Value will reset an active fault in Vacon NX. Default
value is 0; 0.
State | Value | Command |
---|---|---|
0 | any | no action (0; 0) |
1 | 0 | no action (0; 1) |
1 | > 0 | reset fault (200 ; 0) |
-1 (0xFF) | any | invalid (no action) |
nviClrCntr
This input network variable provides a mechanism to clear the kWh trip
counter or the Drive total running hours trip counter.
- MWh trip counter
- Operation day trip counter
nviProcessIn1..8
These input network variables are sent directly to the application (see more
detailed explanation in chapter 6.5 Process data) The valid range is 0 to
65535 (-163,840 to 163,835).
nviDigitalIn1..8
These input network variables are sent directly to the application (see more
detailed explanation in chapter 6.5 Process data) Default value is 0; 0.
state | value | command |
---|---|---|
0 | any | off (0; 0) |
1 | 0 | off (0; 1) |
1 | > 0 | on (200; 1) |
-1 (0xFF) | any | invalid (no action) |
nviParCmd
This input network variable is used to read and write the parameters. The
parameter addresses are determined in the application. Every parameter and
actual value has been given an ID number in the application. The ID numbering
of the parameter as well as the parameter ranges and steps can be found in the
application manual in question. The parameter value must be given without
decimals. Find the ID numbers of each parameter/actual value in the
application manual. The ID numbers are grouped as follows:
Parameter ID | Group | Description |
---|---|---|
0 | Not used | |
1 … 98 | Actual Values | |
99 | Active Fault Code | |
100 | Not Used | |
101… 899 | Parameter | |
900 … 999 | Reserved | Reserved for LonWorks board internal usage |
1000 | Not Used | |
1001…1999 | Parameter |
Examples
Data format in examples is: – learn selector <byte(3) byte(2) byte(1)
byte(0)> day hour minute second-millisecond x = meaningless.
Example1
Write to parameter number 102 (Max frequency “Basic Application par. ID102”)
value 4500 (45Hz). Write a command to nviParSet
-
LN_LEARN_CURRENT 102 <x x 11 94> x x x x
If the write command is successful then the nvoParOut value is -
LN_LEARN_CURRENT 102 <0 0 11 94> 0 0 0 0
If the write command fails then the nvoParOut value is -
LN_NUL 102 <0 0 11 94> 0 0 0 0
Example2
Read parameter number 112 (Nominal speed of the motor “Basic Application par.
ID112”) default value 1440 (1440 rpm). Read command to nviParSet
- LN_RECALL 112
x x x x - If the read command is successful then the nvoParOut value is
- LN_RECALL 112 <0 0 5 A0> 0 0 0 0
- If the read command fails then the nvoParOut value is
- LN_ LN_NUL 112 <0 0 0 0> 0 0 0 0
Output Network Variables
Function | Variable Name | SNVT type | Min. | Max. Value |
---|---|---|---|---|
Node Object status | nvoStatus | SNVT_obj_status | ||
Drive speed feedback | nvoDrvSpeed | SNVT_lev_percent | -163.840% | +163.830% |
Actual motor current | nvoDrvCurnt | SNVT_amp | 0.0A | 3276.7A |
Actual drive power | nvoDrvPwr | SNVT_power_kilo | 0,0 kW | 6553,5 kW |
Drive total | nvoDrvRunHours | SNVT_time_hour | 0 h | 65535 |
Status word | nvoDrvStatus | SNVT_state | n/a | n/a |
kWh trip counter | nvoDrvEnrgy | SNVT_elect_kwh | 0kWh | 65535kWh |
Active fault code | nvoActFault | SNVT_count | 0 | 41 |
Process Out | nvoProcessOut1..8 | SNVT_ lev_percent | 0 | 65535 |
Digital Out | nvoDigitalOut1..8 | SNVT_switch | 0 | 4 |
Parameter Out | nvoParResp | SNVT_preset | – | – |
NvoStatus
This output network variable reports the status for the Node object or
Variable Speed Motor Drive object.
Field | Description |
---|---|
object_id | ID of an object within the node |
invalid_id | 1 means the requested ID is not implemented in this node |
invalid_request | 1 means request for an unimplemented function |
disabled | 1 means the object disabled |
electrical_fault | 1 means drive is faulted |
in_alarm | 1 means the drive is in alarm |
report_mask | 1 means status is an event mask |
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage
of the nominal speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
nvoDrvRunHours
This output network variable provides the drive resettable operation time
counter for the motor in running hours. The maximum value for used SNVT is
65535 h. On the frequency converter, the value can go much higher. If the
counter exceeds the SNVT’s maximum value, the network variable stays at its
maximum. In such cases the real value can be seen on Vacon NX’s operating
keypad.
nvoDrvStatus
This output network variable provides the drive status.
Bit | Description |
---|---|
Value = 0 | |
0 | Not Ready |
1 | FC stopped |
2 | Clockwise |
3 | No fault |
4 | No warning |
5 | Reference ¹ Actual value |
nvoDrvEnrgy
This output network variable provides the drive resettable energy
consumption counter. The maximum value for used SNVT is 65535 kWh. On the
frequency converter, the value can go much higher. If the counter exceeds the
SNVT’s maximum value, the network variable stays at its maximum. In such
cases, the real value can be seen on Vacon NX’s operating keypad.
nvoActFault
This output network variable provides the drive active fault code. If the
value is 0 the frequency converter has no fault. See the fault code list in
the Vacon NX Frequency Converter User’s Manual for fault identification.
nvoProcessOut1..8
These output network variables are sent directly from the application (see
more detailed explanation in chapter 6.5 Process data) The valid range is 0 to
65535 (-163,840 to 163,835).
nvoDigitalOut1..8
These output network variables are sent directly from the application (see
more detailed explanation in Chapter 6.5 Process data).
state | value | command |
---|---|---|
0 | 0 | off (0; 0) |
1 | 200 (0xC8) | on (200; 1) |
-1 (0XfF) | any | invalid (NULL) |
nvoParResp
explained in chapter nviParSet.
Network Configuration Variables
Function | Variable Name | SNVT type |
---|---|---|
Maximum motor speed | nciMaxSpeed | SCPTmaxSetpoint |
Minimum motor speed | nciMinSpeed | SCPTminSetpoint |
Receive heartbeat time | nciRcvHrtBt | SCPTmaxRcvTime |
Send heartbeat time | nciSndHrtBt | SCPTmaxSndTime |
Minimum output time | nciMinOutTime | SCPTminSndTime |
Nominal motor speed in RPM | nciNmlSpeed | SCPTnomRPM |
Nominal motor frequency | nciNmlFreq | SCPTnomFreq |
Minimum ramp-up time | nciRampUpTm | SCPTrampUpTm |
Minimum ramp-down time | nciRampDownTm | SCPTrampDownTm |
Default value for nviDrvSpeedScale | nciDrvSpeedScale | SCPTdefScale |
nciMaxSpeed
This configuration property is used to define the maximum speed of a motor.
The value is entered as a percentage of nominal speed in RPM, as defined by
the Nominal Speed (nciNmlSpeed) configuration value. The value of the maximum
speed must be validated against the value of the minimum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciMinSpeed
This configuration property is used to define the minimum speed of the motor.
The value is entered as a percentage of nominal speed in RPM, as defined by
the Nominal Speed (nciNmlSpeed) configuration value. The value of the minimum
speed must be validated against the value of the maximum speed as follows:
-163.840 < minimum speed < maximum speed < 163.830
nciRcvHrtBt
This configuration property is used to control the maximum time that elapses
after the last update of the network variables nviDrvSpeedStpt or
nviDrvSpeedScale before the VSD object starts to use the default values.
nciSndHrtBt
This configuration property defines the maximum period that expires before the
network variables nvoDrvSpeed, nvoDrvCurnt and nvoDrvPwr are automatically
updated.
nciMinOutTime
This configuration property defines the minimum period of automatic network
variable transmission.
nciNmlSpeed
This configuration property is used to provide the nominal speed of the motor
in RPM. This value is necessary to determine the minimum and maximum speeds
for the motor, based on the configuration properties nciMinSpeed, and
nciMaxSpeed (entered as a percentage of nominal speed).
nciNmlFreq
This configuration property is used to provide the nominal frequency for the
motor.
nciRampUpTm
Defines the acceleration time for Vacon NX. The valid range is 0.0 to 6,553.4
sec (0.1 sec).
nciRampDownTm
Defines the deceleration time for Vacon NX. The valid range is 0.0 to 6,553.4
sec (0.1 sec).
nciDrvSpeedScale
This configuration property is used as the default value for nviDrvSpeedScale.
This value will be adopted at power-up and in case no input variable within
the specified Receive Heartbeat time is received.
Process data
FAULT TRACKING
The table below presents the faults related to the LonWorks option board. For more information, see also Vacon NX User’s Manual, Chapter 9. The LonWorks option board status LEDs are described in more detail in Chapter 3.4.
Fault code | Fault | Possible cause | Correcting measures |
---|---|---|---|
37 | Device change | Option board changed. | Reset |
38 | Device added | Option board added. | Reset |
39 | Device removed | The option board was removed. | Reset |
40 | Device unknown | Unknown option board. | |
53 | Fieldbus fault | The received heartbeat time has expired. | Check the |
installation.
If installation is correct contact the nearest Vacon distributor.
54| Slot fault| Defective option board or slot| Check the board and slot. Contact the nearest Vacon distributor.
Table 7-1. LonWorks option board faults
You can define with parameters how the frequency converter shall react to
certain faults:
Code | Parameter | Min | Max | Unit | Step | Default | ID | Note |
---|
P2.7.22
|
Response to fieldbus fault
|
0
|
3
| |
1
|
0
|
733
| 0=No response 1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
P2.7.23
|
Response to slot fault
|
0
|
3
| |
1
|
0
|
734
| 0=No response 1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
APPENDIX 1
Process Data OUT
The nodes can read the frequency converter’s actual values using process data
variables. Basic, Standard, Local/Remote, Multi-Step, PID control and Pump and
fan control applications use process data as follows:
Data | Value | Unit | Scale |
---|---|---|---|
Process data OUT 1 | Output Frequency | Hz | 0,01 Hz |
Process data OUT 2 | Motor Speed | rpm | 1 rpm |
Process data OUT 3 | Motor Current | A | 0,1 A |
Process data OUT 4 | Motor Torque | % | 0,1 % |
Process data OUT 5 | Motor Power | % | 0,1 % |
Process data OUT 6 | Motor Voltage | V | 0,1 V |
Process data OUT 7 | DC link voltage | V | 1 V |
Process data OUT 8 | Active Fault Code | – | – |
The Multipurpose Control Application has a selector parameter for every Process Data. The monitoring values and drive parameters can be selected using the ID number (see NX All in One Application Manual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN
- Process Data is used with All-inOne applications as follows:
- Basic, Standard, Local/Remote, Multi-Step applications
Data | Value | Unit | Step |
---|---|---|---|
PD1 – PD8 | Not used | – | – |
Multipurpose control application
Data | Value | Unit | Step |
---|---|---|---|
Process Data IN1 | Torque Reference | % | 0.1% |
Process Data IN2 | Free Analogue INPUT | % | 0.01% |
Process Data IN3 | Adjust Input | % | 0.01% |
PD3 – PD8 | Not Used | – | – |
PID control and Pump and fan control applications
Data | Value | Unit | Step |
---|---|---|---|
Process Data IN1 | Reference for PID controller | % | 0.01% |
Process Data IN2 | Actual Value 1 to PID controller | % | 0.01% |
Process Data IN3 | Actual Value 2 to PID controller | % | 0.01% |
PD4–PD8 | Not Used | – | – |