dormakaba SVI Emergency Escape Lock Instructions
- June 16, 2024
- dormakaba
Table of Contents
SVI 2xxx
Commissioning instructions
Information about this document
1.1 Contents and purpose
This document supplements the SVA/SVI locks’ assembly instructions and
contains technical information for the mounting and commissioning of a SVI
2xxxF lock.
1.2 Target group
The locks may only be mounted by technical specialists who have been trained
for this purpose by dormakaba.
1.3 Other applicable documents
- SVA/SVI locks assembly instructions
- Manual for the connecting cable SVP-A 1100/2100
- Technical documents for the selected control unit
- Commissioning instructions for the SVA lock
- Bolt contact switch SVA/SVI assembly instructions
- Assembly instructions for the fittings used, e.g. door handles, panic bar or knob.
1.4 Abbreviations
SVA| Active, self-locking (anti-)panic lock for the active door leaf in 2-leaf
door units
---|---
SVI| Inactive, self-locking (anti-)panic lock for the passive door leaf in
2-leaf door units
2xxx/2xxxF| All versions of a lock; the exact lock type is marked with 3
digits instead of xxx.
G| Active door leaf
S| Passive door leaf
1.5 Symbols used
1.5.1 Hazard categories
WARNING
This signal word indicates a possible hazardous situation that may result in
death or serious injury if not averted.
ATTENTION
This signal word indicates a possible hazardous situation that may result in
damage to property or the environment if not averted.
1.5.2 More symbols
NOTE
This signal word indicates useful information for efficient and trouble-free
operation.
① ② Item numbers used in image caption
Safety
2.1 Intended use
The SVI 2xxxF is a motor lock for the passive door leaf on 2-leaf door units.
The door unit’s active door leaf must be equipped with a dormakaba SVA 2xxx or
SVA 2xxxF lock.
-
Only use the components approved by dormakaba for mounting.
-
Only mount combinations of lock and fitting that have been tested and approved in accordance with EN 179 or EN 1125. The list of approved components can be found in the constancy of performance certificate at www.dormakaba.com. Other
combinations on request. -
Mounting on fire and smoke protection doors is only permitted if the usability certificates for these doors provide for this mounting and if the requirements are followed.
-
The SVI 2xxxFis suitable for use on fire and smoke protection doors.
2.2 Non-intended use
- The lock must not be opened by third parties. If the lock is opened by a third party, there is a risk that safety-relevant functions (e.g. escape/panic functions) will no longer exist.
- The identification plate on the lock contains important information required by law and must not be damaged or obscured.
2.3 Reasonably foreseeable misuse
- Cannot be combined with SVP locks.
- Do not make any changes to the door unit that are not described in this manual.
- If door seals (e.g. profile seals, floor seals) are used, they must not impede the intended function.
Product description
The SVI lock on the passive door leaf serves as a strikbox for the SVA lock.
The SVI lock locks automaticallyby extending the espagnolette bolt as soon as
the passive door leaf is closed. In case of emergency, the door can be opened
in the escape direction at any time. The SVI 2xxxF can query the status of the
espagnolette bolt and the door handle/panic bar.
The SVI 2xxxF contains an integrated Power Reserve module.
The functions are controlled electronically. Control is via the control unit
of the SVA 2xxx or SVA 2xxxF active door leaf lock.
Automatically opening installation example
- Active door leaf with SVA 2xxx/2xxxF
- Passive door leaf with SVI 2xxxF
- Panic door fitting
- Cable transfer CT, cable spiral CS and if necessary detachable cable transfer DT
- Connecting cable SVP-A 1100/2100
- Operator inc. control unit (e.g. ED100/250)
- Sequential locking control
- Door contact TK (optional)
- Carry bar
- Access control components
3.1 Parts included
- SVI lock
- Forend (pre-mounted if necessary)
- Screws required for mounting
- Commissioning instructions SVI 2xxxF
3.2 Variants
Variants for rebated solid doors
235 x 20 mm with angled forend 12 mm Rear backset: 33 mm
- SVI 2071F: Backset 65 mm, DIN left
- SVI 2072F: Backset 65 mm, DIN right
- SVI 2081F: Backset 80 mm, DIN left
- SVI 2082F: Backset 80 mm, DIN right
- SVI 2091F: Backset 100 mm, DIN left
- SVI 2092F: Backset 100 mm, DIN right
Variants for solid butt doors
235 x 24 with lipped or flat forend Rear backset: 33 mm
- SVI 2077F: Backset 65 mm, DIN left/right
- SVI 2087F: Backset 80 mm, DIN left/right
- SVI 2097F: Backset 100 mm, DIN left/right
Variants for tubular frame doors
380 x 24 with lipped or flat forend Rear backset: 15 mm
- SVI 2119F: Backset 35 mm, DIN left/right
- SVI 2129F: Backset 40 mm, DIN left/right
- SVI 2139F: Backset 45 mm, DIN left/right
- Further versions available on request
3.3 Door fittings required
Inner side of the door: Door handle or panic bar Outer side of the door:
without door fitting Locking pin: 9 mm square for passive door leaf set (half
pin)
3.4 Technical data
Temperature range: | -25°C to +70°C |
---|---|
Relative humidity: | up to 95 % at 55°C; no condensation |
Supply voltage: | 24 V DC stabilized (+/- 10%) |
Max. power consumption: | 0.5 A |
Quiescent current consumption: | 0.08 A |
Bolt contact’s contact load capacity:* | 0.5 A at max. 30 V DC |
“Locked” signal: | output switches to GND, 30 mA at max. 30 V DC |
- only for special items
3.5 Integrated Power Reserve module
The integrated Power Reserve module is tested 5 mins after the power is turned
on and then every 48 hrs. If the test completes with an error, the
corresponding flashing code appears once according to the error messages (see
Chapter 6). The test is then performed a second time after a further 5
minutes. If this test is also negative, the flashing code is permanently
displayed.
3.6 LED display
With the SVI 2xxxF, colored light signals in the area around the latch holder
indicate general operational readiness. In addition, the LED display shows the
errormessages (see Chapter 6).
LED display | Color | Duration |
---|---|---|
Ready for operation | 2xxx s |
3.7 Classification
3.7.1 Tubular frame locks
**** | dormakaba Deutschland GmbH DORMA Platz 1 – 58256 Ennepetal |
---|---|
0432-CPR-00026-11 | 18 |
--- | --- |
SVI 2xxxF RR | EN 179:2008 |
DOP_0166
| 0432-CPR-00026-01| 18
---|---|---
SVI 2xxxF RR| EN 1125:2008| 3| 7| 7| B| 1| 4| 2| 1/2| A/B| C
DOP_0167
3.7.2 Solid door locks
**** | dormakaba Deutschland GmbH DORMA Platz 1 – 58256 Ennepetal |
---|---|
0432-CPR-00026-11 | 18 |
--- | --- |
SVI 2xxxF VB | EN 179:2008 |
DOP_0162
| 0432-CPR-00026-02| 18
---|---|---
SVI 2xxxF VB| EN 1125:2008| 3| 7| 7| B| 1| 4| 2| 1/2| A/B| C
DOP_0163
Cable color SVP-A 1100/2100| Connection / function
---|---
Black| GND
Red| not in use
White| +24 V DC
Brown| not in use
Violet| Locked, output switches to
GND, 30 mA at max. 30 V DC
Red-blue| not in use
Blue| not in use
Green| not in use
Gray-pink| Bolt contact
Yellow| Bolt contact
Gray| RS485 N1
Pink| RS485 P1
1Only in combination with SVA 2xxx/SVA 2xxxF
Optional, see bolt contact switch manual SVA/SVI, WN 059826
Pin assignment
Note
For earthed door frames, the bridge on the SVP-A x100 connection cable’s plug
must be disconnected.
4.1 Block diagram SVI 2xxxF with SVA 2xxx
Mounting
See SVA/SVI assembly instructions.
https://techdoc.dormakaba.com/cds/go/SVA-SVI
SVA commissioning instructions
https://techdoc.dormakaba.com/cds/go/SVA
060654-45532 – 05/2023
Error messages
LED display | Cause | Activity |
---|---|---|
Voltage supply outside the tolerance range (24 V DC +/- 10%) | Check power |
supply unit.
| Power reserve function test is faulty| Replace lock.
| Unlocking/locking not successful| Test, bolt, or espagnolette bolts are
blocked from outside the lock. If not, call dormakaba Service
| General error| Disconnect and reactivate the power supply for the door. If
the error persists, call dormakaba Service.
| SVA-SVI bus connection interrupted| Check correct wiring, especially the
wiring of the SVA and SVI lock.
Disassembly and disposal
Disassembly is carried out in reverse order of the mounting instructions.
**** The product must not be disposed of in domestic waste.
Dispose of the product in an environmentally friendly manner at the arranged
acceptance and collection points.
Refer to the statutory regulations for your country.