Features
- Universal AC input / Full range (up to 305VAC)
- Built-in active PFC function
- No load power consumption <0.5W at remote OFF
- High efficiency up to 96%
- Fanless design, cooling by free air convection
- -40 ~ + 70°C wide operating rang1e
- Aluminum case and filling with heat-conducted glue
- Withstand 1 OG vibration test
- Output voltage and output current can be adjusted through internal potentiometer
- Protections: Short circuit / Over current / Over voltage I Over temperature
- LED indicator for power on
- Operating altitude up to 5000 meters (Note. 7)
- 6 years warranty
Applications
- Outdoor telecommunication equipment
- Outdoor electronic signage and billboard
- Petroleum plant or mine shaft facility
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
HEP-600 is a 600W industrial AC/DC power supply featuring the outstanding
capability to operate under
high ly humid, dusty , oily , and high-vibration harsh environment. The entire
series is housed with the aluminum case and fully potted with heat-conducted
silicone. Thanks to state-of-the-art design, the working efficiency is up to
96%, enabling HEP-600 perfectly work between -40°C and +70°C under free air
convection.
Model Encoding
SPECIFICATION
MODEL| HEP-600-12| HEP-600-15| HEP-600-20| HEP-600-24| HEP-600-30| HEP-600-36|
HEP-600-42| HEP-600-48| HEP-600-54
---|---|---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 15V| 20V| 24V| 30V| 36V| 42V| 48V| 54V
RATED CURRENT| 40A| 36A| 28A| 25A| 20A| 16.7A| 14.3A| 12.5A| 11.2A
RATED POWER| 480W| 540W| 560W| 600W| 600W| 601.2W| 600.6W| 600W| 604.8W
RIPPLE & NOISE (max.) Note.2| 150mVp-p| 150mVp-p| 150mVp-p| 150mVp-p|
200mVp-p| 250mVp-p| 250mVp-p| 250mVp-p| 350mVp-p
VOLTAGE ADJ. RANGE| 10.2 ~ 12.6V| 12.7 ~ 15.8V| 17 ~ 21V| 20.4 ~ 25.2V| 25.5 ~
31.5V| 30.6 ~ 37.8V| 35.7 ~ 44.1V| 40.8 ~ 50.4V| 45.9 ~ 56.7V
CURRENT ADJ. RANGE| Can be adjusted by internal potentiometer
20 ~ 40A| 18 ~ 36A| 14 ~ 28A| 12.5 ~ 25A| 10 ~ 20A| 8.3 ~ 16.7A| 7.1 ~ 14.3A|
6.2 ~ 12.5A| 5.6 ~ 11.2A
VOLTAGE TOLERANCE Note.3| ±3.0%| ±2.0%| ±1.5%| ±1.0%| ±1.0%| ±1.0%| ±1.0%|
±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±2.0%| ±1.5%| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME Note.5| 500ms, 80ms at full
load 230VAC /115VAC
HOLD UP TIME (Typ.)| 15ms at full load 230VAC /115VAC
INPUT| VOLTAGE RANGE Note.4| 85~264VAC(277VAC
operational) 120~370VDC(390VDC operational)
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.98/115VAC, PF>0.95/230VAC, PF>0.93/277VAC at full
load
EFFICIENCY (Typ.)| 93%| 94%| 95%| 95%| 95.5%| 95.5%| 96%| 96%| 96%
AC CURRENT (Typ.)| 7A / 115VAC 3.3A / 230VAC 2.9A / 277VAC
INRUSH CURRENT(Typ.)| COLD START 70A(twidth=1000μs measured at 50% Ipeak) at
230VAC
LEAKAGE CURRENT| <0.75mA / 277VAC
PROTECTION| OVER CURRENT| 105 ~ 125%
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
SHORT CIRCUIT| Constant current limiting, recovers automatically after fault
condition is removed
46 ~ 50V 59 ~ 63V
OVER VOLTAGE| 13 ~ 16V| 16.5 ~ 20.5V| 22 ~ 26V| 26 ~ 30V| 32.5 ~ 36.5V| 39.5 ~
43.5V| | 52.5 ~ 56.5V|
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
FUNCTION| REMOTE ON/OFF CONTROL| Power on : “Hi” >2 ~ 5V or Open circuit
Power off : “Low” <0 ~ 0.5V or Short circuit
5V STANDBY| 5VSB : 5V@0.5A ; tolerance ±5%, ripple : 100mVp-p(max.)
ENVIRONMENT| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| 20 ~ 500Hz, 10G 12min./1cycle, period for 72min. each along X, Y, Z
axes
SAFETY & EMC (Note.6)| SAFETY STANDARDS| UL62368-1,TUV BS EN/EN62368-1, EAC TP
TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS
EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035,
heavy industry level, EAC TP TC 020
OTHERS| MTBF| 914.7K hrs min. Telcordia SR-332 (Bellcore) ; 76.9K hrs
min. MIL-HDBK-217F (25℃)
DIMENSION| 28014448.5mm (LWH)
PACKING| 3.9Kg; 4pcs/16Kg/0.9CUFT
NOTE|
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- Derating may be needed under low input voltages. Please check the static characteristics for more details.
- Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
- The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1 mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power SIUpplies.” (as available on http://www.meanwell.com)
- The ambient temperature derating of 3.5°C/1 000m with fanless models and of 5°C/1 000m with fan models for operating altitude higher than 2000m(6500ft). * Product Liability Disclaimer :
For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Case No. 228A Unit:mm
T case: Max. Case Temperature.
Output voltage and constant current level can be adjusted through internal potentiometer. (Can access by removing the rubber stopper on the case.)
AC Input Terminal Pin No. Assignment
Pin No. | Assignment |
---|---|
1 | FG |
2 | AC/L |
3 | AC/N |
DC Output Terminal Pin No. Assignment
Pin No. | Assignment | Pin No. | Assignment |
---|---|---|---|
1 | RC+ | 4,5 | -V |
2 | RC- & GND | 6,7 | +V |
3 | +5VSB |
Installation Manual
Please refer to: http: //www.meanwell.com/manual.html
Customer Support
File Name:HEP-600-SPEC 2022-08-08
Downloaded from Arrow.com.