Wengart TP808 Low Voltage Thermostat User Guide
- June 16, 2024
- WENGART
Table of Contents
**Wengart TP808 Low Voltage Thermostat User Guide
**
About your new thermostat
This thermostat is used to control up to 3 stages heating and 2 stages cooling system with 8 types control system, EM heat activation, adjustable compressor delay time and O/B changeover. It is with tempered touch sensitive button, quick connecting terminals to save installer’s time. 7 days programmable and four modes everyday make users’ life convenient and comfortable.
Thermostat passed FCC standard.
Thermostat box you will find
Thermostat | Manual | Screws | QC pass certificate |
---|---|---|---|
Service
We offer the warranty of 18 months from the sales day. If it is not the problem of quality or beyond the warranty time, we will charge for the after- sale service
Technical Data of your thermostat
Sensor :NTC3977 10K Accuracy:±1℉
Temp. Range :41℉ -95℉ Power Consumption:<1.5W
Timing error :<1%
Power Supply :AC24V, 50 ~60Hz
Shell Material :PC (Fireproof)
Dimension :132x90x23.5mm
Installation boxfuls Standard box
Ambient Temp.:0 ℉~ 113℉, 5 ~ 95%RH(Non condensing)
Storage Temp :-41℉~ 140℉
Features of your thermostat
- Apply with various kind of heating and cooling system. Including Single stage, Multi-stage And Heat Pump (Up to 3-stage heat, 2-stage cool, with Aux. Or Emergency heat)
- 4″ LCD display with backlight
- 7days 4 time periods scheduling. Set the target heating and cooling temperature respectively.
- Both Vacation mold and hold duration mode available for comfort and energy saving
- Temperature display of Celsius or Fahrenheit scale
Home screen quick reference
Operation
: Switching System Mod e
Short press button to select system mode: HEAT, COOL, AUTO, EMER, OFF.
: Confirm button
Press this button to confirm your settings. Press again select Schedule
Permanent Hold and Energy saving
Fan Mode
Press this button to select fan on, auto and cycle
Setting the time
When connecting the thermostat to Wi-Fi, the
time will sync automatically. If not connecting to Wi-Fi, Press to set second-
hour-week
Auto Mode
Short press button to select Auto. Short press bettor to enter AUTO mode
:Setting the Lock
Press and hold button at the same time over 7 seconds to lock/unlock your
thermostat
WIFI reset
Long press seconds to reset WIFI when power off
Check external sensor temperature
(external sensor only)
Press and to check external sensor temperature
Setting a Schedule
Thermostat passed FCC standard. When connecting the thermostat to Wi-Fi, the
schedule is programmed based on time and temperature set points from the Sense
app. If you are not connecting to Wi-Fi, follow these steps to set a basic 7
day schedule with 4 mandatory set points. Long press button above 7secends to
enter weekly program funtion.Short press button to set week-hour-cool
temperature-heat temperature ,Short press to return back.Press to set the
parameters Long press at the same time over 7seconds to go back factory weekly
program settings
Example Schedule
Week Period | Get up | Go outside | Go home | Sleep |
---|---|---|---|---|
**** Mon-Sun | Time | 6:00 | 8:00 | 18:00 |
Cool Temp | 79℉ | 83℉ | 79℉ | 83℉ |
Heat Temp | 72℉ | 61℉ | 72℉ | 61℉ |
Wiring Diagram
RH : Power for heating, 24V
RC : Power for cooling, 24V
G : Indoor blower (fan)
S : Connect to S on C-wire adapter
O/B : Changeover (reverse valve) connection for heat pump or zone panel
systems
Y : First outdoor stage cooling on conventional systems or first heat
and cool on heat pump systems
Y2 : Second outdoor stage cooling on conventional systems or second heat
and cool on two stage heat pump systems or humidifier
NTC +: Outer Sensor+
NTC -: Outer Sensor: Common wire, 24V
W /AUX : First indoor stage heat on conventional systems or first stage
auxiliary
W2/E : Secondary indoor heat for conventional systems emergency heat on
heat pump systems
Vocation function
Long press fan button over 7seconds to enter Vocation mode. Short press fan
button check days->cool temp ->heat templon press button for 7 ed.When you see
the parameter flash. Short press fan button to set the paremeters.Short press
to excite
Setting Energy Saving Mode
Short press button to enter energy saving. The LCD will show on. If you need
change energy saving temp. Long press button and button at the same time over
7seconds.Short press time button to set The order is ECO cool temp->ECO heat
temp
Configuration Menu
No. | Menu item | Short Icon | Selection Range | Notes | Default |
---|---|---|---|---|---|
1 | Set Up HVAC Equipment (Outdoor) | OUT | Outdoor Setup AC1/AC2/HP1/HP2/None |
AC2
2| Set Up HVAC Equipment (Indoor)| IND| Indoor Setup GA1/GA2/EL1/EL2/None|
When you select heat pump (AUX) GA1/EL1/NON option| EL2
3| Outdoor equipment 1| INE| When you select heat pump (EMER) GA1/EL1/NON
option| Only Item 1 select OUT:HP1 HP2 workable| NON
4| Circulation fan switch| FA1| ON/OFF| | ON
5| Circulation fan Setting range| FA2| **** 10%-100%|
If you set the Circulating Fan to 50%, the fan will run 30 minutes every hour.
If any heat/cool cycles occur duringthe hour, their runtime is subtracted from
the overall fan run time.| 30%
6| Auto Mode| AUT| ON/OFF| | ON
7| Compressor 1 delay| CO1| 1-5min| | 3
8| Compressor 2 delay| CO2| 1-5min| | 3
9| Reversing Valve Position| OB| O/B O:Cool B:Heat| Only Item 1 select out.
HP1/HP2 workable| 0
10| External sensor| SEN| ON/OFF| | OFF
**** 11| **** Both AUX/EMER| **** APU| ****
ON/OFF| Onset “EITHER AUX/iControl the same takeoffs: if you want to setup and
control of Auxiliary and Emergency heating separately . This item is only
display yes if Item1 is set to Heat Pump AND if item 2 GA1/EL1.Item3 GA1/EL1
Aux/E stages =| **** OFF
12| AUX lockout| APL| ON/OFF| Item 1 should be HP1/HP2 Item
2 should be GA1/EL1 Item10 should ON.Only all of three items workable|
OFF
13| AUX lockout Temp| AO| – 15~20 , 5-68| Item 1
should be HP1/HP2 Item 2 should be GA1/EL1 Item10 should ON. Item 12 ON. Only
all of four items workable| 36
14| Heat Pump Lockout| COL| ON/OFF| Item 1 should be HP1/HP2
Item 2 should be GA1/EL1 Item 10 should ON.Only all of three items workable|
OFF
15| Heat Pump Lockout Temp| AC| – 15~20 , 5-68| Item 1
should be HP1/HP2 Item 2 should be GA1/EL1Item10 should ON. Item 13 ON. Only
all of four items workable| **** 32
16| Temperature Compensation| CL| – 9~9| | 0
17| C/F selectable| FC| F/C| | F
18| Maximum TemperatureRange| AH| 20-50℃ ,68-95℉| | 95
19| Minimum Temperature Range| AL| 5-20℃ ,41-68℉| | 41
20| Time| TI| 12 24| | 12
21| UV Reminder time setting| UU| 0-36| | 12
22| Chagas Reminder Time Setting| PAD| 0-36| | 12
23| ChagFilter Reminder Time Setting| FIL| 0-36| | 12
Note:
Item 4: Circulating fan
Short press fan button to select cycle.Press to confirm this function running.
If you want to circulate the air in your home using your indoor blower fan,
you can set this feature at the thermostat. A percentage is selected to
indicate how often the fan should run each hour, You can set 5% increments
from 10% – 100%.
EXAMPLE :
If you set the Circulating Fan to 50%, the fan will run 30 minutes every hour.
If any heat/cool cycles occur during the hour, their runtime is subtracted
from the overall fan run time
Item 21 Select UV lamp replacement run time
This is the reminder to change UV lamp . Select starts to counting for 0 day
to 360 days. The thermostat will display “Chg. UV” when UV time (Days). APP
will also reminder
item 22 Chg. pad replacement run time
This is the reminder of replacement run time of Chabad . Select starts to
counting for 0 day to 360 days.
The thermostat will display “Chg. Pad” when Chg. pad (Days).LCD will
display.APP will also reminder
item 23 Chg. Filter replacement run time
This is the reminder of replacement run time of Chg. Filter . Select starts to
counting for 0 day to 360 days.
The thermostat will display “Chg. Filter” when Chg. Filter (Days).LCD
wildisplay.APP will also reminder All these three items you could check
according to bellow steps.
Long press Menu button over 7seconds to enter check page. Short press menu
button to next item. Press+ and – button over 7seconds to reset.
Sensor broken
Er1:Inner sensor broken or not work
Er2:External sensor broken or not work
Installing your thermostat
This product is suitable for US standard wall box.
-
Connect the wire of power and other equipment into the terminals. Fix the wall plate into the wall box by a screwdriver.
-
Connect the LCD board into the wall plate
WARNING : Please arrange the professional technician to install this
product according to installation drawing and instruction.
RISK OF ELECTRICAL SHOCK. Disconnect power supply before making
electrical connection. Contact with components carrying hazardous voltage can
cause electrical shock and may result in severe personal injury or
death.instruction.