Schneider Electric ZACC1TO5 Wireless Indication Auxiliary for MCCB Owner’s Manual

June 16, 2024
Schneider Electric

Schneider Electric ZACC1TO5 Wireless Indication Auxiliary for MCCB

IMPORTANT INFORMATIONS

Refer to the gateway or Panel Server user guide to configure your system.
www.se.com

www.se.com/support

Retain instruction sheet for future use.

Visit our website at www.se.com to download other documents.

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
  • All pertinent state, regional, and local safety regulations must be observed when installing and using this product.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, NOM-029-STPS or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Replace all devices, doors, and covers before turning on power to this equipment.
  • Beware of potential hazards, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
    Failure to follow these instructions will result in death or serious injury.

WARNING

HAZARD OF UNINTENDED OPERATION

  • Do not use the wireless indication auxiliary for critical control or protection applications.
  • Do not use the wireless indication auxiliary for early operation indication CAO/CAF.
    Failure to follow these instructions can result in death, serious injury, or equipment damag e.

WARNING: Cancer and Reproductive Harm. www.P65Warnings.ca.gov.

Required for Installation

Description

Wireless Indication Auxiliary

**A**

| Battery cover.
---|---

**B**

| Actuator.

C

| Reset button.

D

| QR code to access device information, including RF-Id address.

**E**

| Status LED.

F

| Label with a detachable adhesive part carrying a QR code and the RF-Id address, useable during commissioning.

Status LED

| Wireless indication auxiliary switched off or not in communication with gateway or Panel Server.
---|---
| Wireless indication auxiliary in pairing mode, searching for a gateway or Panel Server.
| Wireless indication auxiliary in identification mode
| Wireless indication auxiliary in communication. One green flash at each frame sent
| Occasional loss of communication with the gateway or Panel Serve
| Wireless indication auxiliary in setting mode, with LED indication mode set to OFF.
| Wireless indication auxiliary in setting mode, with LED indication mode set to ON.
| Trip indication when wireless indication auxiliary is in SD slot and configured in LED indication mode ON.
| Battery out of power.

Battery Installation

Before Working on Equipment

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Use push-to-trip button to trip the device.
  3. Use a properly rated voltage sensing device to confirm power is off.

Installation

  1. Unscrew the screws of the front cover and remove it as directed in the instruction sheet of the device.
  2. Install the wireless indication auxiliary in the corresponding accessory slot.

The location of the wireless indication auxiliary in the device defines its function:

  • OF: Indication of the open or closed status of the device
  • SD: Indication of the tripped or non-tripped status of the device
  • SDE: Indication of the tripped or non-tripped status of the device due to an electrical fault.
ComPacT NSX100-250 / PowerPacT H-, J-Frame

The installation of wireless indication auxiliary in OF1 slot is not possible if a SDTAM module or SDx module are already installed.

The installation of the wireless indication auxiliary in the SDE slot requires prior installation of the actuator (LV429451), to be ordered separately if required.

ComPacT NSX400-630 / PowerPacT L-Frame
ComPacT NS630b-1600 / PowerPacT M-, P-Frame

Manually Operated

Electrically Operated

Alarm switch (SD) is not available for electrically-operated devices.

ComPacT NS1600b-3200 / PowerPacT R-Frame

Setting LED Indication Mode

Set the LED indication mode of the wireless indication auxiliary to ON to indicate a circuit breaker trip locally when the auxiliary is installed in the SD slot.

The LED indication mode is factory-set to OFF.

| 1 Press the Reset button.
The wireless indication auxiliary status LED blinks
---|---
| 2. Press the Reset button three times in less than two seconds: The auxiliary is in setting mode. Status LED flashes:

  • three times if LED indication mode is OFF
  • six times if LED indication mode is ON.

| 3 Press the Reset button once to change the LED indication mode.

The flashing pattern of the status LED changes according to the new LED indication mode.

| 4. To exit setting mode, press the Reset button for three seconds.

NOTE: If the Reset button is not pressed, the auxiliary exits setting mode after two minutes.

Commissioning

  • The wireless indication auxiliary can be commissioned with the device switched off.
  • Before proceeding with pairing, ensure that the gateway or Panel Server has the latest available firmware version.
    Refer to the user guide of the concerned gateway.
Pairing

Put the wireless indication auxiliary in pairing mode in one of the following ways:

  • If the wireless indication auxiliary is not installed in the circuit breaker, press the Reset button or the actuator.
  • If the wireless indication auxiliary is installed in the OF slot, open and close the circuit breaker.
  • If the wireless indication auxiliary is installed in the SD slot, open, close and action the push-to-trip button on the circuit breaker.
  • If the wireless indication auxiliary is installed in the SDE slot, open, close and trip the circuit breaker electrically.
    Result: The status LED blinks orange. The wireless indication auxiliary stays in pairing mode for three minutes.

|
---|---
Pair the gateway or Panel Server with the wireless indication auxiliary by using EcoStruxure Power Commission software or the webpages of the gateway or Panel Server.
Result: The status LED blinks green to indicate that the auxiliary is paired.|
Configure the wireless indication auxiliary by using EcoStruxure Power Commission software or the webpages of the gateway or Panel Server.|

Change of the Radio Frequency Channel

To change the radio frequency channel used by the gateway or Panel Server to communicate:

  1. Wake up the wireless indication auxiliary in one of the following ways:

    • If the wireless indication auxiliary is not installed in the circuit breaker, press the Reset button or the actuator.
    • If the wireless indication auxiliary is installed in the OF slot, open and close the circuit breaker.
    • If the wireless indication auxiliary is installed in the SD slot, open, close and action the push-to-trip button on the circuit breaker.
    • If the wireless indication auxiliary is installed in the SDE slot, open, close and trip the circuit breaker electrically.
      Result: The wireless indication auxiliary wakes up, and is ready to be configured for three minutes.
  2. Change the radio frequency channel used by the gateway or Panel Server to communicate with the wireless indication auxiliary by using EcoStruxure Power Commission software or the webpages of the gateway or Panel Server. Result: The status LED blinks green to indicate that the auxiliary communicates with the gateway or Panel Server.

Reinstall Front Cover

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Put back the device front cover before energizing device to prevent access to live terminals.
Failure to follow these instructions will result in death or serious injury.
NOTICE

HAZARD OF EQUIPMENT DAMAGE

  • Be careful not to pinch electrical wires when installing front cover.
  • Tighten all front cover screws to stated torque.
  • Do not over torque screws.
  • Do not use power equipment to torque screws. Failure to follow these instructions can result in equipment damage.
  1. Put back front cover as directed in the instruction sheet of the device.
  2. Device is ready to be placed in service.

Unpairing

Press the Reset button for 3 s to unpair the wireless indication auxiliary.

Wireless Indication Auxiliary Removal

Release tab to remove the wireless indication auxiliary.

Radio Frequency Compliance Statements

Europe

EU Declaration of Conformity
Hereby, Schneider Electric Industries SAS, declares that the wireless indication auxiliary LV429454 is in compliance with the essential requirements and other relevant provisions of RED Directive 2014/53/EU. The EU PB21033002 declaration of conformity can be downloaded on www.se.com/docs.

  • IEEE 802.15.4 operating frequency: 2400–2483.5 MHz.
  • Maximum radio-frequency power transmitted: < 10 mW.

United Kingdom

UK Declaration of Conformity

Hereby, Schneider Electric Industries SAS, declares that the wireless indication auxiliary LV429454 is in compliance with the essential requirements and other relevant provisions of the Radio Equipment Regulations SI 2017 No. 1206.
The PB21033002-UK declaration of conformity can be downloaded on www.se.com/uk.

  • IEEE 802.15.4 operating frequency: 2400–2483.5 MHz.
  • Maximum radio-frequency power transmitted: < 10 mW.

USA

Federal Communication Commission Interference Statement

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.

Radiation Exposure Statement
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment.
This equipment should be installed and operated with minimum distance 20 cm between the radiator & your body. This equipment can only be used within Schneider Electric or Square D circuit breaker.

Canada

Industry Canada Statement

This device complies with RSS-247 of the Industry Canada Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Radiation Exposure Statement

This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment.
This equipment should be installed and operated with minimum distance 20 cm between the radiator & your body.
This equipment can only be used within Schneider Electric or Square D circuit breaker.

Mexico

CUSTOMER SERVICES

Schneider Electric Industries SAS 35, rue Joseph Monier
CS 30323 F – 92506 Rueil Malmaison Cedex
www.se.co
© 2021 Schneider Electric – All rights reserved.
Schneider Electric Limited Stafford Park 5 Telford, TF3 3BL United Kingdom
www.se.com/uk

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals