Dwyer PMI Series Particulate Matter Transmitter User Manual
- June 4, 2024
- Dwyer
Table of Contents
PMI Series Particulate Matter Transmitter
User Manual
The Series PMI Particulate Matter Transmitter is designed to measure indoor
air quality by detecting particulate matter in an office environment or HVAC
duct. Using laser scattering technology, the Series PMI can measure particles
as small as 0.3 μm, making it an essential component of any indoor air quality
monitoring system.
The optional relay combined with the settable alarm and control parameters
allow the Series PMI to be a stand-alone controller.
BENEFITS/FEATURES
- Maintains healthy air supply with long-term stability and accuracy
- Particulate matter application-independent as duct and wall mount units are available
- Low maintenance with 10 years of service life in auto mode
- Minimal downtime with overvoltage protection
- Easy setup with optional integral display and buttons
- Saves time using a removable terminal block on duct mount model
- Single unit controller with alarm, control modes, and optional relay
APPLICATIONS
- Educational institutions
- Healthcare facilities
- Corporate offices
- Hotels/restaurants
- Air purifiers
SPECIFICATIONS
Sensor: Laser scattering.
Range: PMI-2.5: 0-500 μg/m3, particle size 0.3-2.5 μm; PMI-10: 0-600 μg/m
3, particle size 0.3-10 μm.
Accuracy: ±10 μg/m3 @ 0-100 μg/m 3 ; ±10% reading @ 100-600 μg/m³ @ 25°C, 50%
RH.
Resolution: 1 μg/m3.
Response Time: <10 s, continuous service mode.
Temperature Limits: Operating: 32 to 122°F (0 to 50°C); Storage: -22 to 158°F
(-30 to 70°C).
Humidity Limits: 0-95% RH (non-condensing).
Power Requirements: 16-28 VAC/6-35 VDC.
Load Resistance: Current output: ≤500 Ω; Voltage output: ≥2 kΩ.
Output: Current: 4-20 mA; Voltage: 0-10 VDC; Relay: SPST 3A, 30 VDC/250 VAC;
RS-485/Modbus® (RTU).
Service Life: MTBF more than 3 years in continuous service mode, service life
up to 8-10 years in auto (intermittent) service mode.
Display: Optional 4-digit LCD.
Housing Materials: Wall mount: Polycarbonate (UL 94 V-0); Duct mount: ABS and
polycarbonate (UL 94 V-0).
Enclosure Rating: Wall mount: IP30; Duct mount: IP65 (housing), IP30 (probe).
Weight: Wall mount: 7.05 oz (200 g); Duct mount: 9.5 oz (270 g).
Compliance: CE, UKCA.
INSTALLATION
CAUTION
Hazard of eye injury. This product uses a laser particulate matter sensor and
it is strictly prohibited to disassemble the unit. Direct laser exposure is
hazardous.
NOTICE
Use electrostatic discharge precautions (e.g., use of wrist straps) during
installation and wiring to prevent equipment damage.
NOTICE
Avoid locations where severe shock or vibration, excessive moisture, or
corrosive fumes are present.
This product is suitable for common environment measurement. If it is
installed in an environment exceeding the acceptable measurement range for a
long period of time, it may lead to a decrease in measurement accuracy. In any
environment with high humidity, high temperature, smoke, etc., the performance
of the sensor may also be decreased due to excessive contaminants, such as
dust and oil mist, etc.
Choose a location with good ventilation and without strong light or vibration.
Direct light or vibration can affect the accuracy of the sensor.
The unit should be powered OFF during installation and wiring. When using 24
VAC, it is strongly recommended to power the unit with an independent
transformer. If sharing a 24 VAC transformer with other equipment, such as
controllers, transmitters, or actuators, please make sure the terminals 24 V
and GND are connected correctly to avoid equipment damage that is not covered
under warranty.
Surface Mounting:
The wall mount models should be installed vertically on a flat surface. The
installation site should be far away from any heater, cooler, fan, humidifier,
dehumidifier, and other heat/cool/humidity sources. To mount the transmitter:
- Use a flathead screwdriver and insert it into the snap at the upper side of the housing. Push down gently and then open the front cover.
- Feed the cable into the housing before installing the base on the wall according to the diagram inside the front cover.
- Finish electrical connection according to the wiring diagram in Figure 3.
- Snap the front cover back into place and finish the installation.
Duct Mounting
During assembly, installation, and wiring, all seal rings must be applied
properly and securely to ensure the whole enclosure, including where the probe
and duct meet, will be sealed. This is the only way to prevent leaks from air
sources other than the air sampling vents/holes and maintain the IP65 rating.
NOTICE
To duct mount the transmitter:
-
First, the probe must be attached to the back of the enclosure as shown in Figure 2A by inserting the provided black seal ring in the groove located on the back of the housing. Next, align the probe latches with the cutouts on the back of the housing and gently turn it according to the direction indicated on the probe until it snaps into place.
-
Mount using one of the following ways, ensuring that all sampling holes on the probe are inserted into the duct and that the direction indicated on the front cover is the same as the direction of the airflow inside of the duct.
◦ To install via the flange as shown in Figure 2B, drill a Ø19 mm hole in the duct, and install the seal ring and the flange onto the duct using three of the four provided shorter screws. Then, insert the probe into the duct. Use the last provided short screw to lock the whole enclosure onto the flange.
◦To install the enclosure directly on the duct as shown in Figure 2C, drill a Ø19 mm hole on the duct, insert the probe with the seal ring, and screw the enclosure
on the duct directly using the two longer screws provided. -
Remove the four screws from the front cover and lift to access the wiring. Wire according to the wiring diagram inside the front cover. Once completed, replace the front cover.
ELECTRICAL
Different models have different electrical terminals. Please wire specific
model according to the wiring diagram inside the front cover.
NOTICE
Disconnect power supply before installation to prevent electrical shock and
equipment damage.
CAUTION
Make sure all connections are in accordance with the job wiring diagram and in
accordance with national and local electrical codes. Use copper conductors
only.
Outputs
Shown in Figure 3 below is an example of a communication terminal block.
Analog-only models will not include terminals 5 and 6.
Terminal 3 is the 0-10 V output and terminal 4 is the 4-20 mA output. For
RS-485/Modbus® communication refer to the RS-485 COMMUNICATIONS/Modbus® RTU
section later in the manual.
Terminals 9 and 10 close when relay 1 is on. Terminals 9 and 10 open when
relay 1 is off. For relay output setting, refer to the Setting Parameters
section.
Jumpers
Figure 4 shows the RS-485 terminal resistance jumper J8 description as
follows:
The Series PMI has two working modes, automatic mode (AUTO) and continuous mode (NORMAL). AUTO mode will automatically reduce the measuring time to extend the service life of the sensor when the environment’s dust concentration changes very slightly. Use the MODE jumper shown in Figure 5 to choose the desired mode. The factory default mode is AUTO.
OPERATION
NOTICE
Do not exceed the ratings of this device, permanent damage not covered by
warranty may result.
Mode| Mode Description| Parameter #1| Parameter #2| Parameter #3| Parameter
4| Definition|
---|---|---|---|---|---|---|---
0| Cancel relay alarm function| N/A| N/A| N/A| N/A| RELAY OFF|
|
1| Relay actuate when input is lower than set point| Set point| Deadband|
Start delay| Stop delay| |
2| Relay actuate when input is higher than set point| Set point| Deadband|
Start delay| Stop delay| |
3| Relay actuate between high and low limits| Low limit| High limit| Start
delay| Stop delay| |
LOW LIMIT|
4| Relay actuate outside high and low limits| Low limit| High limit| Start
delay| Stop delay| |
RELAY LOW LIMIT|
Table 1: Relay descriptions
ERROR MESSAGES
The following error messages will appear if an LCD is present and the device
is an error state.
LCD ERROR MESSAGES
Error Code| Possible Problem| Solution
Err
Er4| Button input error Sensor reading is abnormal
reading is abnormal| Try a different input value
Verify sensor is plugged in correctly
RS-485 COMMUNICATIONS/Modbus® RTU
Communication settings:
- Baud rate: 9600
- Data: 8 Bit
- Stop: 1
- Parity: None
- Protocol: Modbus® RTU/RS-485
A typical Modbus® RTU mode message frame is shown below. In Modbus® RTU mode, the messages between frames are separated by no activity of at least the time interval of 3.5 characters. If the no-activity interval between two characters is more than the time of 3.5 characters, the previous character was transferred successfully, and the current character’s transmission starts.
Modbus® message
Modbus® Address
The message’s first frame field is the device’s address. Modbus® can support
up to 256 different addresses, including valid addresses from 1-247. Address 0
is for broadcast and addresses 248-255 are reserved for special addresses.
The slave address can be set with compatible Modbus® RTU software. The default
address is 1. It is suggested each single loop be less than 32 devices.
Modbus® Function
The function code is the second data in the frame. Valid function codes are
from 0-127 (01H-7FH). See the relevant Modbus® standard.
The Series PMI supports 03H/06H function codes, shown as the following Modbus®
Poll software. The detail register addresses are in the General Register Table
found on the next page.
03H Read Holding Register
Example: Use the 03 function code to read the measurement value As shown in
Figure 8:
Slave address: 5
Function: 03
Started register: 40002
Register reading length: 2
Scan rate: 200 ms
Communication codes:
Master/PC to SLAVE: 05 03 00 01 00 02 94 4F
SLAVE to Master/PC: 05 03 04 00 FA 01 F4 9F D5
06H Preset Single Register
Example: restore factory settings.
As shown in Figure 7:
Slave address: 5
Function: 06
Register: 40016
Set value: 21845
Communication code:
Master/PC to SLAVE: 05 06 00 0F 55 55 47 22
SLAVE to Master/PC: 05 06 00 0F 55 55 47 22
Broadcast mode to write data to slave
Using broadcast mode, the user can write data to all slaves connected to the
network.
The address of the broadcast mode to write data is 0.
Example: To change slave address with broadcast mode, the user can set a new
slave address.
Note: Since this operation will modify all the addresses of the slaves to the
same address, it is NOT applicable for a network of more than one slave.
As shown in Figure 9, the slave address is changed to 3 by using broadcast
mode:
Slave address: 0
Function: 06
Register address: 40014
Set value: 3
Communication codes:
Master/PC to SLAVE: 00 06 00 0D 00 03 59 D9
SLAVE to Master/PC: none
Special mode to read data from slave
With the special mode, the user can read the registered data under the
circumstance of NOT knowing the slave’s address.
Address of special mode read data: 255(0xFF)
Note: This operation is applicable for ONLY ONE slave in the network.
As shown in Figure 10 is a special mode to read slave addresses:
Slave address: 255(0xFF)
Function: 03
Started register: 40014
Register reading length: 1
Communication codes:
Master/PC to SLAVE: FF 03 00 0D 00 01 59 D9
SLAVE to Master/PC: FF 03 02 00 01 9F D5
GENERAL REGISTER TABLE
Register Address| R/W| Type| Definition| Remarks
40001, 00000
0×0000
40002,00001
0×0001
40003, 00002
0×0002
40014, 00013
40016, 00015
40017, 00016
40018, 00017
40019, 00018
40020, 00019
40021, 00020
40022, 00021
40029, 00028
40030, 00029| R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W| Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed
Signed| Product code
PM2.5 value
PM10 valueRS-485/Modbus
®
RTU slave address
Function register
Relay control mode
Back up
Set point (mode 1 or 2) low limit (mode 3 or 4) regional
Deadband (mode 1 or 2) high limit (mode 3 or 4)
Start delay
Stop delay
Baud rate
Parity| PMI series product code: 9070
PMI2.5 = Value, ug/m³
PMI10 = Value, ug/m³
Default slave address =1, RTU,9600,n,8,1)
Write 40016=21845 to reset to the factory default setting
0: Off
1: Relay activated below the set point
2: Relay activated higher than set point
3: Relay activated in the set range
4: Relay activated outside the set range
Relay control parameters set
Relay control parameters set
Relay control parameters set
Relay control parameters set
Relay control parameters set
Relay control parameters set
Baud rate: 9600(default) or 4800
Parity: 0: NONE, 1: ODD, 2: EVEN
Note:
- 40001 is PLC mode ADDRESS (BASE 1); 00000 is PROTOCOL ADDRESS (BASE 0).
- Function register 40016: Use the 06 function code to write the password (21845) to register 40016 to return to the factory settings.
MAINTENANCE/REPAIR
Upon final installation of the Series PMI, no routine maintenance is required.
The Series PMI is not fielded serviceable and it is not possible to repair the
unit. Field repair should not be attempted and may void the warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website.
Contact customer service to receive a Return Materials Authorization (RMA)
number before shipping the product back for repair. Be sure to include a
brief description of the problem plus any additional application notes.
MODEL CHART
Model| Particulate Size| Mounting| Output| Relay| LCD Display| Buttons
PMI-2.5WC-N-N
PMI-2.5WC-N-LCD
PMI-10WC-N-N
PMI-10WC-N-LCD
PMI-2.5DC-N-N
PMI-10DC-N-N
PMI-2.5WC-RLY-LCD
PMI-10WC-RLY-LCD
PMI-2.5WC-RLY-B
PMI-10WC-RLY-B
PMI-2.5WA-RLY-B
PMI-10WA-RLY-B
PMI-2.5WC-RLY-N
PMI-10WC-RLY-N
PMI-2.5WA-N-LCD
PMI-10WA-N-LCD
PMI-2.5WA-N-N
PMI-10WA-N-N
PMI-2.5WA-N-B
PMI-10WA-N-B
PMI-2.5WC-N-B
PMI-10WC-N-B
PMI-2.5DA-N-N
PMI-10DA-N-N
PMI-2.5DA-N-LCD
PMI-10DA-N-LCD
PMI-2.5DC-N-LCD
PMI-10DC-N-LCD| PM 2.5
PM 2.5
PM 10
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10
PM 2.5
PM 10| Wall mount
Wall mount
Wall mount
Wall mount
Duct mount
Duct mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Wall mount
Duct mount
Duct mount
Duct mount
Duct mount
Duct mount
Duct mount| Modbus® , 4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V Modbus® , 4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V
Modbus®, 4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V
Modbus® , 4-20 mA, 0-10 V| No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No| No
Yes
No
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes| No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
DWYER INSTRUMENTS, INC.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
P.O. BOX 373
MICHIGAN CITY, INDIANA 46360, U.S.A.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>