Mammoth P6SD-X Package Unit Modulating Economizer Instruction Manual
- June 15, 2024
- MAMMOTH
Table of Contents
- P6SD-X Package Unit Modulating Economizer
- Product Information
- Specifications:
- Package Contents:
- Optional Accessory Kits:
- Unit Dimensions:
- Step 1: Shutdown unit and disconnect from electrical
- Step 2: Remove the return access panel. (Save screws.)
- Step 3: Install the side panel:
- Step 3a: Optional installation of additional kits:
- Step 4: Install the economizer:
- Q: What are the dimensions of the unit?
- Q: Are there any optional accessory kits available?
P6SD-X Package Unit Modulating Economizer
Product Information
Specifications:
-
Model: Downflow Economizer #562533 / 563209
-
Package Equipment Models: 2-5T Convertible Package Units AC, HP
or Gas Electric -
Form Number: 212E-0714 (NEW)
Package Contents:
- Economizer Assembly with Filter installed
- Upper Adaptor Panels (See Table 1 on Page 2)
- Side Adaptor Panel
- Outdoor Air Hood (Attached to Economizer)
- Hardware Package
Optional Accessory Kits:
-
CO2 Sensor Kit, Wall Mount (920317)
-
CO2 Sensor Kit, Duct Mount (920318)
-
Differential Enthalpy Kit (922431)
-
HP Isolation Relay Kit (922598) – for older heat pump
models -
Power Exhaust Kit (547842, 555578)
Unit Dimensions:
| Unit# 562533| Unit# 563209
---|---|---
A| 47.59| 51.03
B| 37.56| 41.06
C| 18.73| 18.75
D| 28.86| 32.29
E| 10.79| 12.54
F| 14.29| 17.34
G| 8.18| 12.54
H| 18.90| –
I| 18.00| –
J| 27.50| 31.08
K| 28.25| 31.83
Product Usage Instructions
Step 1: Shutdown unit and disconnect from electrical
power.
Step 2: Remove the return access panel. (Save screws.)
Step 3: Install the side panel:
Using caution not to puncture coil tubing, align the holes and
place the tab on the side panel on the return side of the divider
wall. Secure with the self-tapping screw provided.
Step 3a: Optional installation of additional kits:
If desired, install the differential enthalpy control and DCV
(CO2) sensor according to the instructions provided in the
respective kit. Refer to the product’s technical service literature
for more information.
Step 4: Install the economizer:
Place the economizer in the unit, attaching only the left and
right side mounting screws. Ensure that the economizer rails sit
flush on the return air opening lip. Use caution not to tear
insulation on the unit’s side wall or floor. Use the screws that
were removed in Step 2. Refer to the attached wiring diagram for
proper installation.
FAQ
Q: What are the dimensions of the unit?
The dimensions of the unit vary depending on the model. Please
refer to the specifications section above for detailed
dimensions.
Q: Are there any optional accessory kits available?
Yes, there are several optional accessory kits available for
this product. These include CO2 Sensor Kits (Wall Mount and Duct
Mount), Differential Enthalpy Kit, HP Isolation Relay Kit (for
older heat pump models), and Power Exhaust Kit. Please refer to the
product information section above for more details.
Package Unit Modulating Economizer Installation Instructions
This product is certified to meet California Title 24, Part 6
Low Leak and FDD requirements
Downflow Unit Warning:
Recognize this symbol as an indication of Important Safety Information! Read
all instructions prior to installation. Disconnect electrical power to the
unit before servicing. Failure to do so can cause electrical shock resulting
in personal injury or death. Improper installation, adjustment, alteration,
service or maintenance can cause injury or property damage. Refer to this
manual. For assistance or additional information consult a qualified installer
or service agency.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
FORM# 212E-0714 (NEW)
Note: Reference Unit Technical Service Literature for application requirements.
Before You Begin: Inspect economizer for shipping damage and correct parts
with list below.
1 – Economizer Assembly w/ Filter installed Upper Adaptor Panels (See Table 1
on Page 2) 1 – Side Adaptor Panel 1 – Outdoor Air Hood (Attached to
Economizer) 1 – Hardware Package
1 – Mixed Air Sensor (MAS) 1 – Mixed Air Sensor Wiring Harness 2 – 8″ Wire Tie
3 – #10 x 16 x ½” Self-Tapping Screws 13 – #10 x 16 x ½” Type A Screws
UPPER PANEL 3 UPPER PANEL 2 UPPER PANEL 1
Note: For rooftop or other installations that requires the economizer to be
lifted or hoisted, always lift economizer with the supplied packaging in place
to prevent damage from lifting and rigging equipment.
Optional Accessory Kits: CO2 Sensor Kit, Wall Mount (920317) CO2 Sensor Kit,
Duct Mount (920318) Differential Enthalpy Kit (922431) HP isolation relay kit
(older heat pump models) (922598) Power Exhaust Kit (547842, 555578)
SIDE PANEL Figure 1
H
D
I
E
K
J
F
G
Unit#
562533 563209
A 47.59 51.03
B 37.56 41.06
C 18.73 18.75
D 28.86 32.29
Unit Dimensions
E
F
G
10.79 12.54 14.29 17.34
8.18
C
B A
H 18.90
I 18.00
J 27.50 31.08
K 28.25 31.83
Shipping Information
Height Length Width Weight
35
57 ½ 20 ½
109 112
Figure 2
1
INSTALLATION INSTRUCTION
UNIT HEIGHT
(WITH BASE RAILS)*
35″ 39″ 43″ 47″
UPPER PANEL CLOSE-OFF
PANEL 1 – 22″ x 3″ PANEL 1 – 22″ x 3″ PANEL 2 – 22″ x 7″ PANEL 3 – 22″ x 11″
USED w/ UNIT# 562533
563209
Table 1
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
BLOWER
UNIT ELECTRICAL ACCESS PANEL
UPPER PANEL 3 UPPER PANEL 2 UPPER PANEL 1 ECONOMIZER TOP PAN ECONOMIZER FACE
PANEL
FRESH AIR HOOD
UNIT ECONOMIZER PLUG LOCATION
RETURN ACCESS PANEL
SIDE PANEL
Figure 3
Step 1: Shutdown unit and disconnect from electrical power.
Step 2: Remove the return access panel. (Save screws.)
Step 3: Using CAUTION not to puncture coil tubing, align holes and place the
tab on the side panel on the return side of divider wall and secure with self-
tapping screw provided.
Step 3a: (Optional) Install differential enthalpy control and DCV (CO2) sensor
according to that kit’s instructions. (See products technical service
literature.)
Step 4: Install economizer in unit, attaching only left and right side
mounting screws. Ensure economizer rails sit flush on return air opening lip.
Use CAUTION not to tear insulation on unit side wall or floor. (Use screws
that were removed in Step 2.) (See wiring diagram attached.)
Step 5: Screw side panel in place.
Step 6: Remove economizer top pan and face panels. Locate unit economizer plug
(S1) in return air compartment (top right corner). Remove jumper wire and zip
tie it to economizer wiring harness. Connect economizer plug (P1) to unit plug
(S1). Inspect all wiring and linkage connections for security and proper
operation. Secure all loose wires with a 6″ wire tie. Ensure that wires are
protected from all sharp edges, inadvertent grounding, and will not become
entangled with filter or moveable vanes.
Step 6a (Optional) If installed, make sure differential enthalpy control and
DCV (CO2) sensor wiring connections are made in accordance with that kit’s
instructions.
2
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
Step 7: Remove unit blower access panel and install mixed air sensor in
appropriate location (as shown in Figure 4) with two #10 Type A screws
provided and then make electrical connection. Replace blower access panel.
Step 8: Return power to unit, Setup and configure economizer. (See Appendix A
on page 5)
Step 9: Install appropriate upper close-off panel and replace face panel and
top panel and secure with screws (See Table 1). Ensure all mounting screws,
panels, and doors are installed.
Note to Installer
l When this economizer is used in conjunction with heat pumps, unit WHITE wire
from economizer plug pin #7 MUST be relocated from defrost control board “T1”
to low voltage terminal board “A1”.
l When this economizer is used with any 2-5 ton package unit (Gas/Electric,
A/C, or Heat Pump) WITHOUT A COMMERCIAL THERMOSTAT, the GREEN wire from
economizer plug pin #1 MUST be relocated from low voltage terminal board “G”
to low voltage terminal board “R” to force dampers to remain in minimum
position 100 percent of the time, while in heating mode, to meet the minimum
fresh air requirements. When used in conjunction with a commercial thermostat,
see Note 2 on wiring diagram.
l Some older 2-5T package heat pumps may not be equipped with a reversing
valve isolation relay, required for use with economizers that have a Jade
control system. Nordyne kit #922598 is required for these applications.
MIXED AIR SENSOR Figure 4a – Gas/Electric
Figure 4b – Electric/Electric or Heat Pump
3
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
MAINTENANCE
Return Air Filter Replacement is recommended every 30 days. (16 x 16 x 1)
Step 1: Remove economizer face panel and side screws of top pan.
Step 2: Slide filters out (2) and replace with new filters.
Step 3: Replace face panel and secure all screws.
ECONOMIZER FACE PANEL
ECONOMIZER FACE PANEL REMOVED
Figure 5
Fresh air filter cleaning is recommended every 3 months.
Step 1: Remove lower section of fresh air hood to access washable filters. (4
screws)
Step 2: Remove filters (2) and clean with water and a mild detergent.
Step 3: Taking note of “Air Flow Direction” marking on filter frame, reinstall
the filters and fresh air filter access cover, securing all screws.
FRESH AIR FILTER ACCESS COVER
FILTER ACCESS REMOVED Figure 6
4
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
User Interface
The user interface consists of an LCD display and a 4-button keypad on the
front of the Economizer module. The LCD is a 16 character by 2 line dot matrix
display.
Power Up Cycle
All setpoints and advanced settings are restored after any power loss (a power
loss is assumed if voltage falls below 18 Vac). Normal operation is restored
when power returns above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and Economizer W7220
on the second line. After a brief pause, the revision of the software appears
on the first line (second line is blank). It then displays W7220 on the first
line and STATUS on the second line.
2 LINE LCD
MENU UP (EXIT) BUTTON
SELECT (ENTER) BUTTON SCROLL (UP/DOWN) BUTTON
Figure 7
Keypad
The four navigation buttons illustrated in Figure 7 are used to scroll through
the menus and menu items, select menu items, and to change parameter and
configuration settings.
Using the Keypad with Menus
To use the keypad when working with menus:
l Press the p button to move to the previous menu. l Press the q button to
move to the next menu. l Press the 8 button (Enter) to display the first item
in
the currently displayed menu. l Press the Ó button (Menu up) to exit a menu’s
item
and return to the list of menus. Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings,
Checkout tests, and Alarms:
l Navigate to the desired menu.
l Press the 8 button (Enter) to display the first item in
the currently displayed menu.
l Use the p and q buttons to scroll to the desired parameter.
l Press the 8 button (Enter) to display the value of the currently displayed
item.
l Press the p button to increase (change) the displayed parameter value.a
l Press the q button to decrease (change) the displayed parameter value.a
l Press the 8 button to accept the displayed value and store it in non-
volatile RAM.
l When the value is accepted, CHANGE STORED is displayed on the LCD.
l Press the 8 button (Enter) to return to the current menu parameter.
l Press the Ó button (MenuUp/Exit) to return to the previous menu.
a When values are displayed, pressing and holding the p or q button causes the
display to automatically increment.
Menu Structure
The following tables illustrate the complete hierarchy of menus and parameters
for the JADETM Economizer system.
The Menus in display order are:
l STATUS l SETPOINTS l SYSTEM SETUP l ADVANCED SETUP l CHECKOUT l ALARMS
IMPORTANT Your menu parameters may be different depending on your
configuration.
For example if you do not have a DCV (CO2) sensor, then none of the DCV
parameters appear and only MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and
low speed) and DCV MAX (high and low speed will appear).
SETUP AND CONFIGURATION
Before being placed into service, the JADETM Economizer module must be setup
and configured for the installed system. Use the System Setup menu, the
Advanced Setup menu (if necessary), and the Setpoints menu to accomplish this.
Time-out and Screen saver
When no buttons have been pressed for 10 minutes, the LCD displays a screen
saver, which cycles through the Status items. Each Status items displays in
turn and cycles to the next item after 5 seconds.
5
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
STATUS MENU
Parameter ECON AVAIL ECONOMIZING OCCUPIED HEAT PUMP COOL Y1-IN COOL Y1-OUT
COOL Y2-IN
COOL Y2-OUT MA TEMP
DA TEMP
OA TEMP OA HUM RA TEMP RA HUM IN CO2 DCV STATUS DAMPER OUT ACT POS. ACT COUNT
ACTUATOR EXH1 OUT
EXH2 OUT
ERV MECH COOL ON FAN SPEED W (HEAT IN)
Parameter Default Value
NO
NO
Parameter Range and Incrementa
YES/NO YES/NO
NO
YES/NO
COOL COOL/HEAT
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
OFF ._ºF
ON/OFF -40 to 150ºF
._ºF -40 to 150ºF
._ ºF -40 to 140ºF
%
0 to 100%
._ºF 0 to 140ºF
%
0 to 100%
_ ppm
“0 to 2000 (3500) ppm”
n/a
n/a
% n/a n/a n/a
0 to 100% 0 to 100% 1 to 65,535 OK/Alarm
OFF
ON/OFF
OFF
OFF 0 n/a n/a
ON/OFF
ON/OFF 0, 1, or 2 LOW/HIGH ON/OFF
Notes
YES = economizing available; the system can use Outdoor Air for free cooling
when required.
YES = Outdoor Air being used for 1st stage cooling.
YES = OCC signal received from space thermostat or unitary controller. YES =
24 Vac on terminal OCC No = 0 Vac on terminal OCC.
Displays COOL or HEAT when SYSTEM is set to heat pump (non-conventional)
Y1-I signal from space thermostat input for cooling stage 1 or heat pump
heating stage 1. ON = 24 Vac on terminal Y1-I OFF = 0 Vac on terminal Y1-I
Cool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT terminal).
Y2-I signal from space thermostat input for second stage cooling or heat pump
heating stage 2. ON = 24 Vac on terminal Y2-I OFF = 0 Vac on terminal Y2-I
Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
Displays value of measured mixed air from MAT sensor. Displays -.- if not
connected, short, or out-of-range.
Displays when Discharge Air Sylk Bus sensor is connected and displays measured
discharge air temperature. Displays -.-°F if sensor sends invalid value, if
not connected, short or out-of-range.
Displays measured value of outdoor air temperature. Displays -°F if sensor
sends invalid value, if not connected, short or out-of-range.
Displays measured value of outdoor humidity from OA Sylkbus sensor. Displays
-% if not connected, short, or out-of-range.
If field installed Dual Enthalpy sensor is connected, displays measured value
of return air temperature. Displays -°F if sensor sends invalid value, if not
connected, short or out-of-range.
If field installed Dual Enthalpy sensor is connected, displays measured value
of return air humidity. Displays -% if sensor sends invalid value, if not
connected, short or out-of-range.
If field installed CO2 sensor is connected, displays value of measured CO2.
Invalid if not connected, short or out-of-range. May be adjusted in Advanced
menu by Zero offset and Span.
If field installed CO2 sensor is connected, displays ON if above setpoint and
OFF if below setpoint.
Displays output position to the damper actuator. When used with Honeywell
communicating actuator the damper out is in XX.X%
Displays actual position of actuator.
Displays number of times actuator has cycled. 1 Cycle equals 180° of movement
in any direction.
Displays Error on ALARM MENU if voltage or torque is below actuator range.
Output of EXH1 terminal. Displays ON when damper position reaches programmed
percentage setpoint. ON = 24 Vac Output; OFF = No Output.
Output of AUX1 O terminal Displays ON when damper position reaches programmed
percentage setpoint ON = 24 Vac Output, OFF = No Output; displays only if AUX1
O = EXH2
Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No Output; displays only
if AUX1 O = ERV
Displays number of mechanical cooling stages that are active.
Displays speed of fan on a 2-speed fan unit
Displays status of heat on a 2-speed fan unit.
a When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
6
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
SETPOINTS MENU
Parameter
Parameter Default Value
Parameter Range and Incrementa
Notes
MAT SET
53ºF
38 to 70ºF; The economizer will modulate the OA damper to maintain the mixed air temperature at the increment by 1 setpoint.
LOW T LOCK
32ºF
-45 to 80ºF; increment by 1
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O and Y2-O will not be energized on the controller.
DRYBLB SET
63ºF
48 to 80ºF; increment by 1
Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63 ºF setpoint unit will economizer at 62 ºF and below and not economize at 64 ºF and above. There is a a 2 ºF deadband.
ENTH CURVE
ES3
ES1, ES2, ES3, Does not display if a field installed Dual Enthalpy kit is connected. Enthalpy boundary “curves” ES4, or ES5 for economizing using single enthalpy comparison between outdoor air enthalpy and setpoint.
DCV SET
1100 ppm
500 to 2000 ppm increment by 100
Displays ONLY if field installed CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
MIN POS
2.8 V
2 to 10 Vdc
Displays ONLY if a CO2 sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed
fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is
2.8V
2 to 10 Vdc
Displays only if a field installed CO2 sensor is connected. Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sensor.
VENTMAX
2.8 V
100 to 9990 cfm If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, increment by 10 the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
2 to 10 Vdc
With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
2 to 10 Vdc
Displays only if field installed CO2 sensor is connected. Used for Va (ventilation min cfm) setpoint. This is the ventilation requirement for less than maximum occupancy of the space.
VENTMIN
2.25 V
100 to 9990 cfm If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, increment by 10 the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
2 to 10 Vdc
With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) settings are required. Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
ERV OAT SPb
32ºF
0 to 50ºF; increment by 1
Only when AUX1 O = ERV
EXH1 SET
50%
0 to 100%; increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered by the economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET
75%
0 to 100%; increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.
a b When values are displayed, pressing and holding the p or q button causes
the display to automatically increment.
ERV Operation: When in Cooling mode AND the conditions are NOT OK for
economizing – the ERV terminal will be energized. In the Heating mode the ERV
terminal will be
energized when the OA is below the ERV OAT setpoint in the setpoint menu.
7
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
SYSTEM SETUP MENU
Parameter
Parameter Default Value
Parameter Range and Incrementa
Notes
INSTALL
01/01/2011
Display order = MM/DD/YY. Setting order = DD, MM, then YY.
UNITS DEG
ºF
ºF or ºC
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
CONV HP
CONV = conventional. HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or controller.
AUX2 I
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode. Shutdown (SD)
N/A
Heat (W1) HP(O)
NOTE: If using 2-speed fan mode, you must pro-gram CONV mode for W. Shutdown is not available in the two-speed fan mode.
HP(B)
In HP O/B mode: HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN TYPE
1 speed
1 speed/ 2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or cooling mode.
NOTE: 2-speed fan option also needs Heat (W1) pro-grammed in AUX 2 In.
FAN CFM
5000cfm
100 to 15000 cfm;
increment by 100
This is the capacity of the RTU. The value is found on the label from the RTU manufacturer. The cfm of the fan is only used with DCV CAL ENABLE AUO
AUX1 OUT
NONE
NONE ERV EXH2 SYS
l NONE = not configured (output is not used) l ERV= Energy Recovery Ventilator l EXH2 = second damper position relay closure for second exhaust fan. l SYS = use output as an alarm signal
OCC
INPUT
INPUT or ALWAYS
When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS” OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and change to NO but all parameters will change to factory default values.
a When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
8
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
ADVANCE SETUP MENU
Parameter
Parameter Default Value
Parameter Range and Incrementa
Notes
MA LO SET
45ºF
35 to 55ºF Temp to activate Freeze Protection (close damper or modulate to MIN POS if temp falls increment by 1º below set value)
FREEZE POS
CLO
CLO MIN
Damper position when freeze protection is active (closed or MIN POS).
CO2 ZERO
0 ppm
0 to 500 ppm Displays only if field installed CO2 sensor is connected. CO2 ppm level to match CO2 sensor increment by 10 start level.
CO2 SPAN
1000 to 3000 Displays only if field installed CO2 sensor is connected. CO2 ppm span to match CO2
2000 ppm
ppm;
sensor; e.g.; 500-1500 sensor output would be 500 CO2 zero and 1000 CO2 span. See note
increment by 50 on page 6 for C7632 CO2 sensor.
STG3 DLY
0 min, 5 min, 15 Delay after stage 2 for cool has been active. Turns on 2nd stage of mechanical cooling when
2.0h
min, then 15 economizer is 1st stage call and mechanical cooling is 2nd stage call. Allows three stages of min intervals. cooling, 1 economizer and 2 mechanical.
Up to 4h or OFF OFF = no Stage 3 cooling.
SD DMPR POS
CLO
CLO OPN
Indicates shutdown signal from space thermostat. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off.
DCVCAL ENA
MAN
MAN (manual) AUTO
Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions. Requires all sensors (RA, OA, MA and CO2). This operation is not operable with a 2-speed fan unit.
MAT T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration mixed air temperature sensor.
OAS T CAL
0.0F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration outdoor air temperature sensor.
OAS H CAL
0% RH
+/-10% RH Allows for the operator to adjust for an out of calibration outdoor air humidity sensor.
RA T CAL
0.0F°
+/-2.5F°
If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration temperature sensor.
RA H CAL
0% RH
+/-10% RH
If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration humidity sensor.
DA T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration Discharge Air Sylk Bus temperature sensor.
2SP FAN DELAY
5 Minutes
0 to 20 minutes in 1 minute
When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled.
increments.
a When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
9
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
CHECKOUT MENUc
Parameter
Parameter Parameter Range Default Value and Incrementa
Notes
DAMPER VMIN-HS
n/a
n/a
Positions damper to VMIN position
DAMPER VMAX-HS n/a
DAMPER VMAX-LS
Positions damper to VMAX position. n/a
With 2-speed fan units the damper will position to VMAX low speed fan.
DAMPER OPEN
n/a
Positions damper to the full open position. Exhaust fan contacts enable during the
n/a
DAMPER OPEN test. Make sure you pause in this mode to allow for exhaust contacts
to energize due to the delay in the system.
DAMPER CLOSE
n/a
n/a
Positions outside air damper to the fully closed position.
CONNECT Y1-O
n/a
n/a
Closes the Y1-O relay (Y1-O). See CAUTION on below
CONNECT Y2-O
n/a
n/a
Closes the Y2-O relay (Y2-O). See CAUTION on below
CONNECT AUX1-O
n/a
Energizes the AUX1-O output. If AUX1-O setting is:
l NONE no action taken
n/a
l
ERV 24 Vac out. Turns on or signals an ERV that the conditions are not good for economizing but are good for ERV operation.b
l SYS 24 Vac out. Issues a system alarm.
CONNECT EXH1
n/a
n/a
Closes the power exhaust fan 1 relay (EXH1)
a b When values are displayed, pressing and holding the p or q button causes
the display to automatically increment.
ERV Operation: When in Cooling mode AND the conditions are NOT OK for
economizing – the ERV terminal will be energized. In the Heating mode the cERV
terminal will be energized when the OA is below the ERV OAT setpoint in the
setpoint menu.
After 10 minutes without a command or mode change, the controller will change
to normal operation.
CHECKOUT
Inspect all wiring connections at the Economizer module’s terminals, and
verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and perform the
Checkout tests.
Note: See “Interface Overview” on page 5. for information about menu
navigation and use of the keypad.
WARNING: Electrical Shock Hazard. Can cause severe injury, death or property
damage. Disconnect power supply before beginning wiring or making wiring
connections, to prevent electrical shock or equipment damage.
If any wiring changes are required, first be sure to remove power from the
Economizer module before starting work. Pay particular attention to verifying
the power connection (24 Vac).
Power Up
After the module is mounted and wired, apply power.
Power Up Delay
Upon power up (or after a power outage or brownout), the W7220 controller
module begins a 5 minute power up delay before enabling mechanical cooling.
Power Loss (Outage or Brownout) All setpoints and advanced settings are
restoreda after any power loss or interruption.
Note: If power goes below 18 Vac, the W7220 controller module assumes a power
loss and the 5 minute power up delay will become functional when power returns
above 18 Vac.
a All settings are stored in non-volatile flash memory.
Status
Use the Status Menu to check the parameter values for the various devices and
sensors configured.
Checkout Tests
Use the Checkout Menu to test the damper operation and any configured outputs.
Only items that are configured are shown in the Checkout menu.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the p and q buttons.
2. Press the 8 button to select the item. 3. RUN? appears on the display.
4. Press the 8 button to start the test. 5. The unit pauses and then displays
TEST RUNNING. 6. Press the button Ó (Menu up) to end the test (e.g. turn
off the relay). Test stops automatically after 10 minutes without a command or
mode change, and will resume normal operation.
The checkout tests can all be performed at the time of installation or any
time during the operation of the system as a test that the system is operable.
CAUTION Equipment damage may result. Be sure to allow enough time for
compressor startup and shutdown between checkout tests so that you do not
short-cycle the compressors.
10
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
ALARM MENU
Parameter
Parameter Default Parameter Range
Value
and Incrementa
Notes
MA T SENS ERR
n/a
n/a
CO2 SENS ERR
n/a
OA T SENS ERR
n/a
n/a
Alarms display only when they are active. The menu title “ALARMS (_)”includes
n/a
the number of active alarms in parenthesis ().
DA ENTHL ERR
n/a
n/a
SYS ALARM
n/a
n/a
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the AUX1 O terminal has 24 Vac out.
ACT UNDER V
n/a
n/a
Voltage received by Actuator is above expected range
ACT OVER V
n/a
n/a
Voltage received by Actuator is below expected range
ACT STALLED
n/a
n/a
Actuator stopped before achieving commanded position
a When values are displayed, pressing and holding the p or q button causes the display to automatically increment.
Alarms
The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms.
This allows time for all the configured devices (e.g. sensors, actuator) to
become operational. The exception is the MA sensor which will alarm
immediately.
If one or more alarms are present and there has been no keypad activity for at
least 5 minutes, the Alarms menu displays and cycles through the active
alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g.
replaced faulty sensor), the alarm can be cleared from the display. To clear
an alarm, perform the following:
1. Navigate to the desired alarm. 2. Press the 8 button. 3. ERASE? displays.
4. Press the 8 button. 5. ALARM ERASED displays. 6. Press the button Ó
(MenuUp/Exit) to complete the action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5
seconds.
11
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
SEQUENCE OF OPERATION
Dry Bulb Operation No DCV (CO2 sensor) – 1 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off 0-v/Off MIN POS
Closed
None
No
On
Off
High
24-v/On 0-v/Off MIN POS
Closed
On
On
High
24-v/On 24-v/On MIN POS
Closed
Off
Off
High
0-v/Off 0-v/Off MIN POS
Closed
None
Yes
On
Off
High
0-v/Off 0-v/Off MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On 0-v/Offa MIN POS to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Dry Bulb Operation With DCV (CO2 sensor) – 1 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off 0-v/Off VENTMIN
Closed
No
On
Off
High
24-v/On 0-v/Off VENTMIN
Closed
Below CO2 set
On
On
High
24-v/On 24-v/On VENTMIN
Off
Off
High
0-v/Off 0-v/Off VENTMIN
Closed Closed
Yes
On
Off
High
0-v/Off 0-v/Off VENTMIN to Full-Open Closed to Full-Open
On
On
High
24-v/On 0-v/Offa VENTMIN to Full-Open
Closed to Full-Open
Off
Off
High
0-v/Off 0-v/Off VENTMIN to VENTMAX Closed
No
On
Off
High
24-v/On 0-v/Off VENTMIN to VENTMAX Closed
Above CO2 set
On
On
High
24-v/On 24-v/On VENTMIN to VENTMAX Closed
Off
Off
High
0-v/Off 0-v/Off VENTMIN to VENTMAX Closed
Yes
On
Off
High
0-v/Off 0-v/Off VENTMIN to Full-Open Closed to Full-Open
On
On
High
24-v/On 0-v/Offa VENTMIN to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Enthalpy Operation No DCV (CO2 sensor) – 1 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off 0-v/Off MIN POS
Closed
None
No
On
Off
High
24-v/On 0-v/Off MIN POS
Closed
On
On
High
24-v/On 24-v/On MIN POS
Closed
Off
Off
High
0-v/Off 0-v/Off MIN POS
Closed
None
Yes
On
Off
High
0-v/Off 0-v/Off MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On 0-v/Offa MIN POS to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage
of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
12
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
Enthalpy Operation With DCV (CO2 sensor) – 1 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
High
0-v/Off 0-v/Off VENTMIN
Closed
No
On
Off
High
24-v/On 0-v/Off VENTMIN
Closed
Below set
On
On
High
24-v/On 24-v/On VENTMIN
Off
Off
High
0-v/Off 0-v/Off VENTMIN
Closed Closed
Yes
On
Off
High
0-v/Off 0-v/Off VENTMIN to Full-Open
Closed to Full-Open
On
On
High
24-v/On 0-v/Offa VENTMIN to Full-Open
Closed to Full-Open
Off
Off
High
0-v/Off 0-v/Off VENTMIN to VENTMAX
Closed
No
On
Off
High
24-v/On 0-v/Off VENTMIN L to VENTMAX Closed
On
On
High
24-v/On 24-v/On VENTMIN H to VENTMAX Closed
Above set
Off
Off
High
0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
Yes
On
Off
High
0-v/Off 0-v/Off VENTMIN to Full-Open
Closed to Full-Open
On
On
High
DELAY (b) 24-v/On
0-v/Offa
VENTMIN to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied.
Dry Bulb Operation No DCV (CO2 sensor) – 2 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off 0-v/Off MIN POS L
Closed
None
No
On
Off
Low
24-v/On 0-v/Off MIN POS L
Closed
On
On
High
24-v/On 24-v/On MIN POS H
Closed
Off
Off
Low
0-v/Off 0-v/Off MIN POS L
Closed
None
Yes
On
Off
Low
0-v/Off 0-v/Off MIN POS L to Full-Open Closed to Full-Open
On
On
High
DELAYb 24-v/On
0-v/Offa
MIN POS H to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied. b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is
a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Dry Bulb Operation With DCV (CO2 sensor) – 2 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L
Closed
No
On
Off
Low
24-v/On 0-v/Off VENTMIN L
Closed
Below set
On
On
High
24-v/On 24-v/On VENTMIN H
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L
Closed Closed
Yes
On
Off
Low
0-v/Off 0-v/Off VENTMIN L to Full-Open Closed to Full-Open
On
On
High
24-v/On 0-v/Offa VENTMIN H to Full-Open Closed to Full-Open
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
No
On
Off
Low
24-v/On 0-v/Off VENTMIN L to VENTMAX Closed
On
On
High
24-v/On 24-v/On VENTMIN H to VENTMAX Closed
Above set
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
Yes
On
Off
Low
0-v/Off 0-v/Off VENTMIN L to Full-Open Closed to Full-Open
On
On
High
DELAYb 24-v/On
0-v/Offa
VENTMIN H to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied. b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is
a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
13
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
Enthalpy Operation No DCV (CO2 sensor) – 2 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off 0-v/Off MIN POS L
Closed
No
On
Off
Low
24-v/On 0-v/Off MIN POS L
Closed
NO CO2 SENSOR
Yes
On
On
High
24-v/On 24-v/On MIN POS H
Closed
Off
Off
Low
0-v/Off 0-v/Off MIN POS L
Closed
On
Off
Low
0-v/Off 0-v/Off MIN POS L to Full-Open Closed to Full-Open
On
On
High
DELAYb 24-v/On
0-v/Offa
MIN POS H to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied. b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is
a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Dry Bulb Operation With DCV (CO2 sensor) – 2 Speed Fan.
DCV
OA Good to economize?
Y1-I
Y2-I FAN SPD Y1-O
Y2-O
Occupied
Unoccupied
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L
Closed
No
On
Off
Low
24-v/On 0-v/Off VENTMIN L
Closed
Below set
On
On
High
24-v/On 24-v/On VENTMIN H
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L
Closed Closed
Yes
On
Off
Low
0-v/Off 0-v/Off VENTMIN L to Full-Open Closed to Full-Open
On
On
High
24-v/On 0-v/Offa VENTMIN H to Full-Open Closed to Full-Open
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
No
On
Off
Low
24-v/On 0-v/Off VENTMIN L to VENTMAX Closed
Above set
On
On
High
24-v/On 24-v/On VENTMIN H to VENTMAX Closed
Off
Off
Low
0-v/Off 0-v/Off VENTMIN L to VENTMAX Closed
Yes
On
Off
Low
0-v/Off 0-v/Off VENTMIN L to Full-Open Closed to Full-Open
On
On
High
DELAYb 24-v/On
0-v/Offa
VENTMIN H to Full-Open
Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 O after the delay if the call for Y1-I and Y2-I
have not been satisfied. b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is
a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
14
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
Enthalpy Curve
ES1 ES2 ES3 ES4 ES5 HL
Temp. Dry-Bulb (°F)
80.0 75.0 70.0 65.0 60.0 86.0
Single Enthalpy and Dual Enthalpy High Limit Curves
Temp. Dewpoint (°F)
Enthalpy (btu/lb/da)
Point P1
Temp. °F
Humidity %RH
60.0
28.0
80.0
36.8
57.0
26.0
75.0
39.6
54.0
24.0
70.0
42.3
51.0
22.0
65.0
44.8
48.0
20.0
60.0
46.9
66.0
32.4
86.0
38.9
Point P2
Temp. °F
Humidity %RH
66.3
80.1
63.3
80.0
59.7
81.4
55.7
84.2
51.3
88.5
72.4
80.3
Enthalpy Settings
When the OA temperature, enthalpy and dew point are below the respective
setpoints, the Outdoor Air can be used for economizing. Fig. 18 shows the new
single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1
through ES5), which are defined by dry bulb temperature, enthalpy and dew
point.
Refer to Table above for the ENTH CURVE setpoint values.
To use enthalpy the W7220 must have a C7400S Sylkbus sensor for OA. The W7220
calculates the enthalpy and dew point using the OA temperature and humidity
input from the OA sensor. When the OA temperature, OA humidity and OA dew
point are all below the selected boundary, the economizer sets the economizing
mode to YES, economizing is available.
When conditions are above the selected boundary, the conditions are not good
to economize and the mode is set to NO.
Figure ## shows the 5 current boundaries. There is also a high limit boundary
for differential enthalpy. The high limit boundary is ES1 when there are no
stages of mechanical cooling energized and HL when a compressor stage is
energized.
The table above provides the values for each boundary limit.
Two-Speed Fan Operation
The later versions of the W7220 Jade controller have the capability to work
with a system using a 2-speed supply fan The W7220 does not control the supply
directly but uses the following input status to determine the speed of the
supply fan and controls the OA damper to the required position.
State OCC
Y1 Y2 W
Fan Speed Low Low High High
The W (heating mode) is not controlled by the W7220 but it requires the status to know where to position the OA damper for minimum position for the fan speed.
The 2 speed fan delay is available when the system is programmed for 2 speed fan (in the System Setup menu item). The 2 speed fan delay is defaulted to 5 minutes and can be changed in the Advanced Setup menu item. When the unit has a call for Y1 In and in the free cooling mode and there is a call for Y2 In, the 2-speed fan delay starts and the OA damper will modulate 100% open, the supply fan should be set to high speed by the unit controller. After the delay one of two actions will happen:
l The Y2 In call will be satisfied with the damper 100% open and fan on high speed and the call will turn off
OR
l If the call for additional cooling in the space has not been satisfied then the first stage of mechanical cooling will be enabled through Y1 Out or Y2 Out.
15
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
APPENDIX A
Figure 8 Economizer with Sylk Bus sensors for enthalpy configuration with a
Honeywell MS3103J or MS3105J communicating actuators.
Figure 9 2-position actuator
16
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
17
INSTALLATION INSTRUCTION
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
SUPERSEDES 12-10-14 FEBRUARY 18, 2015
NEIGEJ06
18
HARNESS ENDS AT P1
COMPONENT CODE
Revision
Change
Date
Nordyne# Honeywell# 622754 MS3105J3030 626621 W7220A1000 626622 C7400S1000 626623 C7250A1001 ———- P1 ———- S1
Description Damper Actuator 24v Logic Module Fresh Air Enthalpy Sensor Mixed Air Temperature Sensor Male Interface Unit Plug Male Interface Unit Plug
WIRE COLOR CODE
BLK Black BRN Brown GRY Gray PNK Pink TAN Tan WHT White
BLU Blue GRN Green ORG Orange RED Red VIO Violet YEL Yellow
Notes: 1. Unit wiring shown as reference only. Check unit wiring for actual
unit wiring. 2. Standard connection shown. When this economizer is used in
conjunction with a commercial thermostat that has an OCC
connection, unplug white wire with insulated terminal from pin # 1 and plug
into white wire from pin # 7. Connect the thermostat OCC output to A1 terminal
on the unit low voltage terminal board. (On older models without A1 terminal
DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
connection a field supplied wire can be routed and connected to the unplugged white wire from Pin # 1 to JADE OCC) 3. Economizer pin location S1-2 connected to the following:
Date: February 18, 2015
Package Gas/Electrics “W1” or Gas valve
Supersedes:
Package Air Conditioners “W1” Package Heat Pumps “O” for Cooling mode of operation
Drawn by: MGL
4. For mechanical cooling (compressor) to energize during economizer cooling
mode of operation, a thermostat “Y2” call must be present. A 2 stage cooling
thermostat is required for this operation.
5. See unit low voltage wiring instruction changes required for economizers
equipped with the Honeywell W220 JADE control
Unit #: 47-366-06 Diagram#: 4736606W
module and Page 3 of these instructions.
www.mammothlc.com
Approved by: Trademark Mammoth® used under license.© Nortek Global HVAC, LLC.All Rights Reserved.
Powered by TCPDF (www.tcpdf.org)