ipd MS116-10 Manual Motor Starter
FEATURES
- Compact design, ideal for installations with limited space
- Provides reliable protection against short-circuits, overload and phase failures
- High breaking capacity
- Features a lockable rotary handle with clear switch position indication
- Suitable for both 3 phase and single phase applications
Specification
General Information
Brand| ABB
Product Type| Manual Motor Starter
Technical Attributes
Design of Control Element| Turn Button
Breaking Capacity 400V AC – Icu (kA)| 75
Main Circuit Electrical Connection| Screw Connection
No. of Poles| 3
Overload Release Current Setting (A)| 6.3
Phase Failure Sensitive| Yes
Power Loss (W)| 7.2
Rated Instantaneous Short-Circuit Current – Ii (A)| 150
Rated Insulation Voltage (V)| 690
Rated Operational Current (A)| 10
Rated Operational Power AC-3 400V (kW)| 4
Rated Operational Voltage (V)| 690
Rated Uninterrupted Current – Iu (A)| 10
Switching Type| Thermomagnetic
Terminal Type| Screw Terminals
Thermal Current Setting Range (A)| 6.30 – 10.0
Thermal Overload Protection| Yes
Dimensions
Dimensions (mm)| 45W x 90H x 85.6D
Protection & Standards
Degree of Protection| IP20