Mammoth Q6SD-X Package Unit Modulating Economizer Instruction Manual
- June 15, 2024
- MAMMOTH
Table of Contents
Package Unit Modulating Economizer
Installation Instructions
DOWNFLOW ECONOMIZER # 562533 / 563209
PACKAGE EQUIPMENT MODELS
2-5T CONVERTIBLE PACKAGE UNITS
AC, HP OR GAS ELECTRIC
FORM# 212E-0714 (NEW)
Q6SD-X Package Unit Modulating Economizer
This product is certified to meet California Title 24, Part 6
Low Leak and FDD requirements
Downflow Unit
Warning:
**** Recognize this symbol as an indication of Important Safety Information!
- Read all instructions prior to installation.
- Disconnect electrical power to the unit before servicing.
- Failure to do so can cause electrical shock resulting in personal injury or death.
- Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer or service agency.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE
Note:
Reference Unit Technical Service Literature for application requirements.
Before You Begin:
Inspect economizer for shipping damage and correct parts with list below.
1 – Economizer Assembly w/ Filter installed Upper Adaptor Panels (See Table 1
on Page 2)
1 – Side Adaptor Panel
1 – Outdoor Air Hood (Attached to Economizer)
1 – Hardware Package
1 – Mixed Air Sensor (MAS)
1 – Mixed Air Sensor Wiring Harness
2 – 8″ Wire Tie
3 – #10 x 16 x ½” Self-Tapping Screws
13 – #10 x 16 x ½” Type A Screws
Note: For rooftop or other installations that requires the economizer to
be lifted or hoisted, always lift economizer with the supplied packaging in
place to prevent damage from lifting and rigging equipment.
Optional Accessory Kits:
CO2 Sensor Kit, Wall Mount (920317)
CO2 Sensor Kit, Duct Mount (920318)
Differential Enthalpy Kit (922431)
HP isolation relay kit (older heat pump models) (922598)
Power Exhaust Kit (547842, 555578)
Unit# | Unit Dimensions | Shipping Information |
---|---|---|
A | B | C |
J | K | Height |
562533 | 47.59 | 37.56 |
28.25 | 35 | 57 ½ |
563209 | 51.03 | 41.06 |
UNIT HEIGHT **(WITH BASE RAILS)*** | UPPER PANEL CLOSE-OFF |
USED w/ UNIT#
---|---|---
35″| PANEL 1 – 22″ x 3″| 562533
39″| PANEL 1 – 22″ x 3″| 563209
43″| PANEL 2 – 22″ x 7″
47″| PANEL 3 – 22″ x 11″
Step 1: Shutdown unit and disconnect from electrical power.
Step 2: Remove the return access panel. (Save screws.)
Step 3: Using CAUTION not to puncture coil tubing, align holes and place
the tab on the side panel on the return side of divider wall and secure with
self-tapping screw provided. Step 3a: (Optional)
Install differential enthalpy control and DCV (CO2) sensor according to that
kit’s instructions. (See products technical service literature.)
Step 4: Install economizer in unit, attaching only left and right side
mounting screws. Ensure economizer rails sit flush on return air opening lip.
Use CAUTION not to tear insulation on unit side wall or floor. (Use screws
that were removed in Step 2.) (See wiring diagram attached.)
Step 5: Screw side panel in place.
Step 6: Remove economizer top pan and face panels. Locate unit economizer
plug (S1) in return air compartment (top right corner). Remove jumper wire and
zip tie it to economizer wiring harness. Connect economizer plug (P1) to unit
plug (S1).
Inspect all wiring and linkage connections for security and proper operation.
Secure all loose wires with a 6” wire tie.
Ensure that wires are protected from all sharp edges, inadvertent grounding,
and will not become entangled with filter or moveable vanes.
Step 6a (Optional)
If installed, make sure differential enthalpy control and DCV (CO2) sensor
wiring connections are made in accordance with that kit’s instructions.
Step 7: Remove unit blower access panel and install mixed air sensor in
appropriate location (as shown in Figure 4) with two #10 Type A screws
provided and then make electrical connection. Replace blower access panel.
Step 8: Return power to unit, Setup and configure economizer. (See
Appendix A on page 5)
Step 9: Install appropriate upper close-off panel and replace face panel
and top panel and secure with screws (See Table 1). Ensure all mounting
screws, panels, and doors are installed.
Note to Installer
- When this economizer is used in conjunction with heat pumps, unit WHITE wire from economizer plug pin #7 MUST be relocated from defrost control board “T1” to low voltage terminal board “A1”.
- When this economizer is used with any 2-5 ton package unit (Gas/Electric, A/C, or Heat Pump) WITHOUT A COMMERCIAL THERMOSTAT, the GREEN wire from economizer plug pin #1 MUST be relocated from low voltage terminal board “G” to low voltage terminal board “R” to force dampers to remain in minimum position 100 percent of the time, while in heating mode, to meet the minimum fresh air requirements. When used in conjunction with a commercial thermostat, see Note 2 on wiring diagram.
- Some older 2-5T package heat pumps may not be equipped with a reversing valve isolation relay, required for use with economizers that have a Jade control system. Nordyne kit #922598 is required for these applications.
|
---|---
MAINTENANCE
Return Air Filter Replacement is recommended every 30 days. (16 x 16 x 1)
Step 1: Remove economizer face panel and side screws of top pan.
Step 2: Slide filters out (2) and replace with new filters.
Step 3: Re place face panel and se cure all screws.Fresh air filter clean ing is rec om mended ev ery 3 months.
Step 1: Remove lower section of fresh air hood to access washable filters. (4
screws)
Step 2: Remove filters (2) and clean with water and a mild detergent.
Step 3: Tak ing note of “Air Flow Di rec tion” marking on fil ter frame, re in
stall the filters and fresh air filter access cover, se curing all
screws.
User Interface
The user interface consists of an LCD display and a 4-button keypad on the
front of the Economizer module.
The LCD is a 16 character by 2 line dot matrix display.
Power Up Cycle
All setpoints and advanced settings are restored after any power loss (a power
loss is assumed if voltage falls below 18 Vac). Normal operation is restored
when power returns above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and Economizer W7220
on the second line. After a brief pause, the revision of the software appears
on the first line (second line is blank). It then displays W7220 on the
first line and STATUS on the second line.
Key pad
The four navigation buttons illustrated in Figure 7 are used to scroll through
the menus and menu items, select menu items, and to change parameter and
configuration settings.
Us ing the Key pad with Menus
To use the keypad when working with menus:
- Press the ▲ button to move to the previous menu.
- Press the ▼ button to move to the next menu.
- Press the button (Enter) to display the first item in the currently displayed menu.
- Press the Ó button (Menu up) to exit a menu’s item and return to the list of menus.
Us ing the Key pad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings,
Checkout tests, and Alarms:
- Navigate to the desired menu.
- Press the button (Enter) to display the first item in the currently displayed menu.
- Use the ▲ and ▼ buttons to scroll to the desired parameter.
- Press the ▲ button (Enter) to display the value of the currently displayed item.
- Press the ▼ button to increase (change) the displayed parameter value. a
- Press the button to decrease (change) the displayed parameter value. a
- Press the button to accept the displayed value and store it in non-volatile RAM.
- When the value is accepted, CHANGE STORED is displayed on the LCD.
- Press the button (Enter) to return to the current menu parameter.
- Press the button (MenuUp/Exit) to return to the previous menu.
a When values are displayed, pressing and hold ing the p or q button causes
the display to auto matically in crement.
Menu Struc ture
The following tables illustrate the complete hierarchy of menus and parameters
for the JADE™ Economizer system.
The Menus in display order are:
- STATUS
- SETPOINTS
- SYSTEM SETUP
- ADVANCED SETUP
- CHECKOUT
- ALARMS
IMPORTANT
Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO2) sensor, then none of the DCV
parameters appear and only MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and
low speed) and DCV MAX (high and low speed will appear).
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer module must be setup
and configured for the installed system. Use the System Setup menu, the
Advanced Setup menu (if necessary), and the Setpoints menu to accomplish this.
Time-out and Screen saver
When no buttons have been pressed for 10 minutes, the LCD displays a screen
saver, which cycles through the Status items. Each Status items displays in
turn and cycles to the next item after 5 seconds.
STATUS MENU
Parameter| Parameter Default Value| Parameter Range and
Incre a ment| Notes
---|---|---|---
ECON AVAIL| NO| YES/NO| YES = economizing available; the system can use
Outdoor Air for free cooling when required.
ECONOMIZING| NO| YES/NO| YES = Outdoor Air being used for 1st stage cooling.
OCCUPIED| NO| YES/NO| YES = OCC signal received from space
thermostat or unitary controller. YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP| COOL| COOL/HEAT| Displays COOL or HEAT when SYSTEM is set to heat
pump (non-conventional)
COOL Y1-IN| OFF| ON/OFF| Y1-I signal from space thermostat
input for cooling stage 1 or heat pump heating stage 1. ON = 24 Vac on
terminal Y1-I
OFF = 0 Vac on terminal Y1-I
COOL Y1-OUT| OFF| ON/OFF| Cool Stage 1 Relay Output to stage 1 mechanical
cooling (Y1-OUT terminal).
COOL Y2-IN| OFF| ON/OFF| Y2-I signal from space thermostat
input for second stage cooling or heat pump heating stage 2.
ON = 24 Vac on terminal Y2-I OFF = 0 Vac on terminal Y2-I
COOL Y2-OUT| OFF| ON/OFF| Cool Stage 2 Relay Output to mechanical cooling
(Y2-OUT terminal).
MA TEMP| ._ºF| -40 to 150ºF| Displays value of measured mixed air from MAT
sensor. Displays -.- if not connected, short, or out-of-range.
DA TEMP| ._ºF| -40 to 150ºF| Displays when Discharge Air
Sylk Bus sensor is connected and displays measured discharge air temperature.
Displays -.-°F if sensor sends invalid value, if not connected, short or out-
of-range.
OA TEMP| . ºF| -40 to 140ºF| Displays measured value of outdoor air
temperature. Displays -°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA HUM| %| 0 to 100%| Displays measured value of outdoor humidity from OA
Sylkbus sensor. Displays -% if not connected, short, or out-of-range.
RA TEMP| _.ºF| 0 to 140ºF| If field installed Dual Enthalpy sensor is
connected, displays measured value of return air temperature. Displays -°F if
sensor sends invalid value, if not connected, short or out-of-range.
RA HUM| %| 0 to 100%| If field installed Dual Enthalpy sensor is connected,
displays measured value of return air humidity. Displays -% if sensor sends
invalid value, if not connected, short or out-of-range.
IN CO2| **** ppm| “0 to 2000 (3500) ppm”| If field installed CO2 sensor
is connected, displays value of measured CO2. Invalid if not connected, short
or out-of-range. May be adjusted in Advanced menu by Zero offset and Span.
DCV STATUS| n/a| n/a| If field installed CO2 sensor is connected, displays ON
if above setpoint and OFF if below setpoint.
DAMPER OUT| %| 0 to 100%| Displays output position to the damper actuator.
When used with Honeywell communicating actuator the damper out is in XX.X%
ACT POS.| n/a| 0 to 100%| Displays actual position of actuator.
ACT COUNT| n/a| 1 to 65,535| Displays number of times actuator has cycled. 1
Cycle equals 180° of movement in any direction.
ACTUATOR| n/a| OK/Alarm| Displays Error on ALARM MENU if voltage or torque is
below actuator range.
EXH1 OUT| OFF| ON/OFF| Output of EXH1 terminal. Displays ON
when damper position reaches programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.
EXH2 OUT| OFF| ON/OFF| Output of AUX1 O terminal Displays ON
when damper position reaches programmed percentage setpoint ON = 24 Vac
Output, OFF = No Output; displays only if AUX1 O = EXH2
ERV| OFF| **** ON/OFF| Output of AUX1 O terminal, ON = 24 Vac
Output, OFF = No Output; displays only if AUX1 O = ERV
MECH COOL ON| 0| 0, 1, or 2| Displays number of mechanical cooling stages that
are active.
FAN SPEED| n/a| LOW/HIGH| Displays speed of fan on a 2-speed fan unit
W (HEAT IN)| n/a| ON/OFF| Displays status of heat on a 2-speed fan unit.
a When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.
**Parameter| Parameter Default Value| Parameter Range and
a Increment| ****Notes
---|---|---|---
** MAT SET| 53ºF| 38 to 70ºF; increment by 1| The economizer will
modulate the OA damper to maintain the mixed air temperature at the setpoint.
LOW T LOCK| 32ºF| -45 to 80ºF; increment by 1| Setpoint determines
outdoor temperature when the mechanical cooling cannot be turned on. Commonly
referred to as the Compressor lockout. At or below the setpoint the Y1-O and
Y2-O will not be energized on the controller.
DRYBLB SET| 63ºF| 48 to 80ºF; increment by 1| Setpoint determines
where the economizer will assume outdoor air temperature is good for free
cooling; e.g.; at 63 ºF setpoint unit will economizer at 62 ºF and below and
not economize at 64 ºF and above. There is a a 2 ºF deadband.
ENTH CURVE| ES3| ES1, ES2, ES3, ES4, or ES5| Does not display if a
field installed Dual Enthalpy kit is connected. Enthalpy boundary “curves” for
economizing using single enthalpy comparison between outdoor air enthalpy and
setpoint.
DCV SET| 1100 ppm| 500 to 2000 ppm increment by 100| Displays ONLY
if field installed CO2 sensor is connected. Setpoint for Demand Control
Ventilation of space. Above the setpoint, the OA dampers will modulate open to
bring in additional OA to maintain a space ppm level below the setpoint.
MIN POS| 2.8 V| 2 to 10 Vdc| Displays ONLY if a CO2 sensor
is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed
fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is
2.8V
VENTMAX| 2.8 V| 2 to 10 Vdc| Displays only if a field
installed CO2 sensor is connected. Used for Vbz (ventilation max cfm)
setpoint. VENTMAX is the same setting as MIN POS would be if you did not have
the CO2 sensor.
100 to 9990 cfmincrement by 10| If OA, MA, RA and CO2 sensors are connected
and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM
and displays from 100 to 9990 cfm.
**2 to 10 Vdc| With 2-speed fan units VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is
3.2V and VENTMAX H is 2.8V.
** VENTMIN| 2.25 V| 2 to 10 Vdc| Displays only if field
installed CO2 sensor is connected. Used for Va (ventilation min cfm) setpoint.
This is the ventilation requirement for less than maximum occupancy of the
space.
100 to 9990 cfmincrement by 10| If OA, MA, RA and CO2 sensors are connected
and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM
and displays from 100 to 9990 cfm.
**2 to 10 Vdc| With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for VENTMIN L is
2.5V and VENTMIN H is 2.25V.
b ERV OAT SP| ** 32ºF| 0 to 50ºF; increment by 1| Only when AUX1
O = ERV
EXH1 SET| 50%| 0 to 100%; increment by 1| Setpoint for OA damper
position when exhaust fan 1 is powered by the economizer. With 2-speed fan
units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are
required. Default for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET| 75%| 0 to 100%; increment by 1| Setpoint for OA
damper position when exhaust fan 2 is powered by the economizer. Only used
when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan)
settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.
a b **** When values are displayed, pressing and holding the ▲ or ▼
button causes the display to automatically increment.
ERV Operation: When in Cooling mode AND the conditions are NOT OK for
economizing – the ERV terminal will be energized. In the Heating mode the ERV
terminal will be energized when the OA is below the ERV OAT setpoint in the
setpoint menu.
SYSTEM SETUP MENU
**Parameter| Parameter Default Value| Parameter Range and
a Increment| ****Notes
---|---|---|---
INSTALL| 01/01/2011| | Display order = MM/DD/YY. Setting order = DD, MM, then
YY.
UNITS DEG| ºF| ºF or ºC| Sets economizer controller in degrees Fahrenheit or
Celsius.
** EQUIPMENT| CONV| CONV HP| CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from
thermostat or controller.
**** AUX2 I| **** N/A| Shutdown (SD) Heat (W1) HP(O)HP(B)| In CONV
mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-gram CONV mode for W. Shutdown
is not available in the two-speed fan mode.
In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) =
energize heat pump on Heat.
FAN TYPE| 1 speed| 1 speed/ 2 speed| Sets economizer
controller for operation of 1 speed or 2 speed supply fan. The controller does
not control the fan but positions the OA and RA dampers to the heating or
cooling mode.
NOTE: 2-speed fan option also needs Heat (W1) pro-grammed in AUX 2 In.
**** FAN CFM| **** 5000cfm| 100 to 15000cfm; increment by 100|
This is the capacity of the RTU. The value is found on the label from the
RTU manufacturer. The cfm of the fan is only used with DCV CAL ENABLE AUO
AUX1 OUT| NONE| NONE ERV EXH2 SYS| ● NONE = not configured (output
is not used)
● ERV= Energy Recovery Ventilator
● EXH2 = second damper position relay closure for second exhaust fan.
● SYS = use output as an alarm signal
OCC| INPUT| INPUT or ALWAYS| When using a setback thermostat with
occupancy out (24 Vac), the 24 Vac is input “INPUT” to the OCC terminal. If no
occupancy output from the thermostat then change program to “ALWAYS” OR add a
jumper from terminal R to OCC terminal.
FACTORY DEFAULT| NO| **** NO or YES| Resets all set points to factory
defaults when set to YES. LCD will briefly flash YES and change to NO but all
parameters will change to factory default values.
a When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.
ADVANCE SETUP MENU
**Parameter| Parameter Default Value| Parameter Range and
a Increment| ****Notes
---|---|---|---
** MA LO SET| 45ºF| 35 to 55ºF increment by 1º| Temp to activate
Freeze Protection (close damper or modulate to MIN POS if temp falls below set
value)
FREEZE POS| CLO| CLO MIN| Damper position when freeze
protection is active (closed or MIN POS).
CO2 ZERO| **** 0 ppm| 0 to 500 ppm increment by 10| Displays only if field
installed CO2 sensor is connected. CO2 ppm level to match CO2 sensor start
level.
CO2 SPAN
| ****
2000 ppm
| 1000 to 3000 ppm; increment by 50| Displays only if field installed CO2
sensor is connected. CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor
output would be 500 CO2 zero and 1000 CO2 span. See note on page 6 for C7632
CO2 sensor.
STG3 DLY| 2.0h| 0 min, 5 min, 15 min, then 15 min intervals. Up to
4h or OFF| Delay after stage 2 for cool has been active. Turns on 2nd stage of
mechanical cooling when economizer is 1st stage call and mechanical cooling is
2nd stage call. Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS| CLO| CLO OPN| Indicates shutdown signal from
space thermostat. When controller receives 24 Vac input on the SD terminal in
conventional mode, the OA damper will open if programmed for OPN and OA damper
will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1,
etc. will shut off.
DCVCAL ENA| MAN| MAN (manual) AUTO| Turns on the DCV automatic
control of the dampers. Resets ventilation based on the RA, OA and MA sensor
conditions. Requires all sensors (RA, OA, MA and CO2).
This operation is not operable with a 2-speed fan unit.
MAT T CAL| 0.0 F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration mixed air temperature sensor.
OAS T CAL| 0.0F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration outdoor air temperature sensor.
OAS H CAL| 0% RH| +/-10% RH| Allows for the operator to adjust for an out of
calibration outdoor air humidity sensor.
RA T CAL| 0.0F°| +/-2.5F°| If field installed Dual Enthalpy sensor is
connected, allows for the operator to adjust for an out of calibration
temperature sensor.
RA H CAL| 0% RH| +/-10% RH| If field installed Dual Enthalpy sensor is
connected, allows for the operator to adjust for an out of calibration
humidity sensor.
DA T CAL| 0.0 F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration Discharge Air Sylk Bus temperature sensor.
2SP FAN DELAY| 5 Minutes| 0 to 20 minutes in 1 minute increments.|
When in economizing mode this is the delay for the high speed fan to try
to satisfy the call for second stage cooling before the first stage mechanical
cooling is enabled.
a When values are displayed, pressing and holding the ▲ or ▼ button causes the display to automatically increment.
CHECKOUT MENUc
**Parameter| Parameter Default Value| Parameter Range and
a Increment| ****Notes
---|---|---|---
DAMPER VMIN-HS| n/a| n/a| Positions damper to VMIN position
DAMPER VMAX-HS| ** n/a| ** n/a| Positions damper to VMAX position.
DAMPER VMAX-LS| With 2-speed fan units the damper will position to VMAX low
speed fan.
** DAMPER OPEN| n/a| n/a| Positions damper to the full open
position. Exhaust fan contacts enable during the DAMPER OPEN test. Make sure
you pause in this mode to allow for exhaust contacts to energize due to the
delay in the system.
DAMPER CLOSE| n/a| n/a| Positions outside air damper to the fully closed
position.
CONNECT Y1-O| n/a| n/a| Closes the Y1-O relay (Y1-O). See CAUTION on below
CONNECT Y2-O| n/a| n/a| Closes the Y2-O relay (Y2-O). See CAUTION on below
CONNECT AUX1-O| n/a| **** n/a| Energizes the AUX1-O output. If
AUX1-O setting is:
● NONE – no action taken
● ERV – 24 Vac out. Turns on or signals an ERV that the conditions are not
good for economizing but are good for ERV operation.b
● SYS – 24 Vac out. Issues a system alarm.
CONNECT EXH1| n/a| n/a| Closes the power exhaust fan 1 relay (EXH1)
a When values are displayed, pressing and holding the p or q button causes the
display to automatically increment.
b ERV Operation: When in Cooling mode AND the conditions are NOT OK for
economizing – the ERV terminal will be energized. In the Heating mode the ERV
terminal will be energized when the OA is below the ERV OAT setpoint in the
setpoint menu.
c After 10 minutes without a command or mode change, the controller will
change to normal operation.
CHECK OUT
Inspect all wiring connections at the Economizer module’s terminals, and
verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and perform the
Checkout tests.
Note: See “Interface Overview” on page 5. for information about menu
navigation and use of the keypad.
WARNING:
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections,
to prevent electrical shock or equipment damage.
If any wiring changes are required, first be sure to remove power from the
Economizer module before starting work.
Pay particular attention to verifying the power connection (24 Vac).
Power Up
After the module is mounted and wired, apply power.
Power Up De lay
Upon power up (or after a power outage or brownout), the W7220 controller
module begins a 5 minute power up delay before enabling mechanical cooling.
Power Loss (Out age or Brown out)
All setpoints and advanced settings are restored a after any power loss or
interruption.
Note: If power goes below 18 Vac, the W7220 controller module assumes a
power loss and the 5 minute power up delay will become functional when power
returns above 18 Vac.
a All settings are stored in non-volatile flash memory.
Sta tus
Use the Status Menu to check the parameter values for the various devices and
sensors configured.
Check out Tests
Use the Checkout Menu to test the damper operation and any configured outputs.
Only items that are configured are shown in the Checkout menu.
To perform a Checkout test:
- Scroll to the desired test in the Checkout menu using the p and q buttons.
- Press the 8 button to select the item.
- RUN? appears on the display.
- Press the 8 button to start the test.
- The unit pauses and then displays TEST RUNNING.
- Press the button Ó (Menu up) to end the test (e.g. turn off the relay). Test stops automatically after 10 minutes without a command or mode change, and will resume normal operation. The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test that the system is operable.
CAUTION
Equipment damage may result.
Be sure to allow enough time for compressor startup and shutdown between
checkout tests so that you do not short-cycle the compressors.
ALARM MENU
**Parameter| Parameter Default Value| Parameter Range
and a Increment| ****Notes
---|---|---|---
MA T SENS ERR| n/a| n/a| ** Alarms display only when they are active. The
menu title “ALARMS (_)”includes the number of active alarms in parenthesis ().
CO2 SENS ERR| n/a| n/a
OA T SENS ERR| n/a| n/a
DA ENTHL ERR| n/a| n/a
SYS ALARM| n/a| n/a| When AUX1 O is set to SYS and there is any alarm (e.g.,
failed sensors, etc.), the AUX1 O terminal has 24 Vac out.
ACT UNDER V| n/a| n/a| Voltage received by Actuator is above expected range
ACT OVER V| n/a| n/a| Voltage received by Actuator is below expected range
ACT STALLED| n/a| n/a| Actuator stopped before achieving commanded position
When values are displayed, pressing and holding the p or q button causes the
display to automatically increment.
Alarms
The Economizer module provides alarm messages that display on the 2-line
LCD.
_ NOTE: Upon power up, the module waits 60 minutes before checking for
alarms. This allows time for all the configured devices (e.g. sensors,
actuator) to become operational. The exception is the MA sensor which will
alarm immediately.
_If one or more alarms are present and there has been no keypad activity for
at least 5 minutes, the Alarms menu displays and cycles through the active
alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g.
replaced faulty sensor), the alarm can be cleared from the display. To clear
an alarm, perform the following:
- Navigate to the desired
- Press the ⮠ button
- ERASE? ? displays.
- Press the ⮠ button
- ALARM ERASED displays.
- Press the button ↑ (MenuUp/Exit) to complete the action and return to the previous
NOTE: If an alarm still exists after you clear it, it redisplays within 5 seconds
SEQUENCE OF OPERATION
Dry Bulb Operation No DCV (CO2 sensor) – 1 Speed Fan.
**DCV| OA Good to economize?| ****Y1-I| ****Y2-I|
****FAN SPD| ****Y1-O| ****Y2-O| ****Occupied|
****Unoccupied
** None| No| Off| Off| High| 0-v/Off| 0-v/Off| MIN POS| Closed
On| Off| High| 24-v/On| 0-v/Off| MIN POS| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS| Closed
None| Yes| Off| Off| High| 0-v/Off| 0-v/Off| MIN POS| Closed
On| Off| High| 0-v/Off| 0-v/Off| MIN POS to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| MIN POS to Full-Open| Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied.
Dry Bulb Operation With DCV (CO2 sensor) – 1 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
Below CO2 set| No| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN| Closed
On| Off| High| 24-v/On| 0-v/Off| VENTMIN| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN| Closed
Yes| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN| Closed
On| Off| High| 0-v/Off| 0-v/Off| VENTMIN to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| VENTMIN to Full-Open| Closed to Full-Open
Above CO2 set| No| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN to VENTMAX|
Closed
On| Off| High| 24-v/On| 0-v/Off| VENTMIN to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN to VENTMAX| Closed
Yes| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN to VENTMAX| Closed
On| Off| High| 0-v/Off| 0-v/Off| VENTMIN to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| VENTMIN to Full-Open| Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied
Enthalpy Operation No DCV (CO2 sensor) – 1 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
None| No| Off| Off| High| 0-v/Off| 0-v/Off| MIN POS| Closed
On| Off| High| 24-v/On| 0-v/Off| MIN POS| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS| Closed
None| Yes| Off| Off| High| 0-v/Off| 0-v/Off| MIN POS| Closed
On| Off| High| 0-v/Off| 0-v/Off| MIN POS to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| a 0-v/Off| MIN POS to Full-Open| Closed to Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied.
Enthalpy Operation With DCV (CO2 sensor) – 1 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
Below set| No| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN| Closed
On| Off| High| 24-v/On| 0-v/Off| VENTMIN| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN| Closed
Yes| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN| Closed
On| Off| High| 0-v/Off| 0-v/Off| VENTMIN to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| VENTMIN to Full-Open| Closed to Full-Open
Above set| No| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN to VENTMAX| Closed
On| Off| High| 24-v/On| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H to VENTMAX| Closed
Yes| Off| Off| High| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| High| 0-v/Off| 0-v/Off| VENTMIN to Full-Open| Closed to Full-Open
On| On| High| DELAY (b)24-v/On| a 0-v/Off| VENTMIN to Full-Open| Closed to
Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied.
Dry Bulb Operation No DCV (CO2 sensor) – 2 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
None| No| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 24-v/On| 0-v/Off| MIN POS L| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS H| Closed
None| Yes| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| MIN POS L to Full-Open| Closed to Full-Open
On| On| High| b DELAY 24-v/On| a 0-v/Off| MIN POS H to Full-Open| Closed to
Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage
of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there
is a delay for the high speed fan to try to satisfy the call for second stage
cooling by turning on the fan to high and opening the OA damper 100% before
the first stage mechanical cooling is enabled
Dry Bulb Operation With DCV (CO2 sensor) – 2 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
Below set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| VENTMIN H to Full-Open| Closed to Full-Open
Above set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H to VENTMAX| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to Full-Open| Closed to Full-Open
On| On| High| b DELAY 24-v/On| a 0-v/Off| VENTMIN H to Full-Open| Closed to
Full-Open
aWith stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of
mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there
is a delay for the high speed fan to try to satisfy the call for second stage
cooling by turning on the fan to high and opening the OA damper 100% before
the first stage mechanical cooling is enabled.
Enthalpy Operation No DCV (CO2 sensor) – 2 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
NO CO2 SENSOR| No| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 24-v/On| 0-v/Off| MIN POS L| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| MIN POS L to Full-Open| Closed to Full-Open
On| On| High| b DELAY 24-v/On| a 0-v/Off| MIN POS H to Full-Open| Closed to
Full-Open
a With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage
of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
b With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there
is a delay for the high speed fan to try to satisfy the call for second stage
cooling by turning on the fan to high and opening the OA damper 100% before
the first stage mechanical cooling is enabled.
Dry Bulb Operation With DCV (CO2 sensor) – 2 Speed Fan.
DCV| OA Good to economize?| Y1-I| Y2-I| FAN SPD|
Y1-O| Y2-O| Occupied| Unoccupied
Below set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to Full-Open| Closed to Full-Open
On| On| High| 24-v/On| 0-v/Offa| VENTMIN H to Full-Open| Closed to Full-Open
Above set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H to VENTMAX| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to Full-Open| Closed to Full-Open
On| On| High| b DELAY 24-v/On| a 0-v/Off| VENTMIN H to Full-Open| Closed to
Full-Open
Single Enthalpy and Dual Enthalpy High Limit Curves
Enthalpy Curve| Temp. Dry-Bulb (°F)| Temp. Dewpoint
(°F)| Enthalpy btu/lb/da)| Point P1| Point P2
Temp. °F| Humidity %RH| Temp. °F| Humidity %RH
ES1| 80.0| 60.0| 28.0| 80.0| 36.8| 66.3| 80.1
ES2| 75.0| 57.0| 26.0| 75.0| 39.6| 63.3| 80.0
ES3| 70.0| 54.0| 24.0| 70.0| 42.3| 59.7| 81.4
ES4| 65.0| 51.0| 22.0| 65.0| 44.8| 55.7| 84.2
ES5| 60.0| 48.0| 20.0| 60.0| 46.9| 51.3| 88.5
HL| 86.0| 66.0| 32.4| 86.0| 38.9| 72.4| 80.3
Enthalpy Settings
When the OA temperature, enthalpy and dew point are below the respective
setpoints, the Outdoor Air can be used for economizing. Fig. 18 shows the new
single enthalpy boundaries in the W7220. There are 5 boundaries (setpoints ES1
through ES5), which are defined by dry bulb temperature, enthalpy and dew
point.
Refer to Table above for the ENTH CURVE setpoint values.
To use enthalpy the W7220 must have a C7400S Sylkbus sensor for OA. The W7220
calculates the enthalpy and dew point using the OA temperature and humidity
input from the OA sensor. When the OA temperature, OA humidity and OA dew
point are all below the selected boundary, the economizer sets the economizing
mode to YES, economizing is available.
When conditions are above the selected boundary, the conditions are not good
to economize and the mode is set to NO.
Figure ## shows the 5 current boundaries. There is also a high limit boundary
for differential enthalpy. The high limit boundary is ES1 when there are no
stages of mechanical cooling energized and HL when a compressor stage is
energized. The table above provides the values for each boundary limit.
Two-Speed Fan Operation
The later versions of the W7220 Jade controller have the capability to work
with a system using a 2-speed supply fan The W7220 does not control the supply
directly but uses the following input status to determine the speed of the
supply fan and controls the OA damper to the required position.
State | Fan Speed |
---|---|
OCC | Low |
Y1 | Low |
Y2 | High |
W | High |
The W (heating mode) is not controlled by the W7220 but it requires the status
to know where to position the OA damper for minimum position for the fan
speed.
The 2 speed fan delay is available when the system is programmed for 2 speed
fan (in the System Setup menu item). The 2 speed fan delay is defaulted to 5
minutes and can be changed in the Advanced Setup menu item. When the unit has
a call for Y1 In and in the free cooling mode and there is a call for Y2 In,
the 2-speed fan delay starts and the OA damper will modulate 100% open, the
supply fan should be set to high speed by the unit controller. After the delay
one of two actions will happen:
-
The Y2 In call will be satisfied with the damper 100% open and fan on high speed and the call will turn off
OR -
If the call for additional cooling in the space has not been satisfied then the first stage of mechanical cooling will be enabled through Y1 Out or Y2
Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS3103J or MS3105J communicating actuators.
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1 O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE EXH1 OR AUX10 TERMINAL IS ENERGIZED AND THE 2-POS DAMPER GOES OPEN. IF USING THE AUX10 TERMINAL PROGRAM AUX1 O FOR EXH2.
HARNESS ENDS AT P1| COMPONENT CODE
Nordyne# Honeywell# Description
622754 MS3105J3030 Damper Actuator 24v 626621 W7220A1000 Logic
Module626622 C7400S1000 Fresh Air Enthalpy Sensor 626623 C7250A1001
Mixed Air Temperature Sensor
———- P1 Male Interface Unit Plug———- S1 Male Interface Unit Plug|
WIRE COLOR CODE
BLK Black BLU Blue BRN Brown GRN Green GRY Gray ORG Orange PNK Pink RED
Red TAN Tan VIO Violet WHT White YEL Yellow| Revision| Change|
Date
---|---|---|---|---|---
| |
| |
| |
| |
| |
| |
| |
| |
Notes:
1. Unit wiring shown as reference only. Check unit wiring for actual unit
wiring.
2. Standard connection shown. When this economizer is used in conjunction
with a commercial thermostat that has an OCC connection, unplug white wire
with insulated terminal from pin # 1 and plug into white wire from pin # 7.
Connect the thermostat OCC output to A1 terminal on the unit low voltage
terminal board. (On older models without A1 terminal connection a field
supplied wire can be routed and connected to the unplugged white wire from Pin
1 to JADE OCC)
3. Economizer pin location S1-2 connected to the following: Package
Gas/Electrics – “W1” or Gas valve Package Air Conditioners – “W1”
Package Heat Pumps – “O” for Cooling mode of operation
4. For mechanical cooling (compressor) to energize during economizer cooling
mode of operation, a thermostat “Y2” call must be present. A 2 stage cooling
thermostat is required for this operation.
5. See unit low voltage wiring instruction changes required for economizers
equipped with the Honeywell W220 JADE control module and Page 3 of these
instructions. www.mammothlc.com Trademark
Mammoth® use| DOWNFLOW ECONOMIZER # 562533 / 563209 PACKAGE EQUIPMENT
MODELS
2-5T CONVERTIBLE PACKAGE UNITS AC, HP OR GAS ELECTRIC
162 Diplomat Drive
Carrollton, Texas 75006
Phone: 972-247-7447
PRE RTPA DAP ISA
dunder license. © Nortek Global HVAC, LLC
| Date: February 18, 2015
Supersedes:
Drawn by: MGL
Unit #: 47-366-06
Diagram#: 4736606W
.AAlpl RpirgohvtseRdebsye:rved.
Trademark Mammoth® used under license. © Nortek Global HVAC, LLC. All Rights Reserved.
SUPERSEDES 12-10-14
FEBRUARY 18, 2015
Documents / Resources
|
Mammoth Q6SD-X Package Unit Modulating
Economizer
[pdf] Instruction Manual
Q6SD-X Package Unit Modulating Economizer, Q6SD-X, Package Unit Modulating
Economizer, Unit Modulating Economizer, Modulating Economizer, Economizer
---|---