Mammoth P6SD-X36 Packaged Air Conditioning Owner’s Manual
- June 15, 2024
- MAMMOTH
Table of Contents
P6SD Series
13 SEER, Three Phase, Packaged
Air Conditioning
3-5 Ton Units
TECHNICAL SPECIFICATIONS
The P6SD Series packaged units are high efficiency self contained cooling units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed. The unit is truly designed with the contractor and the end user in mind.
WARRANTY
- One Year Commercial Parts Warranty
- 5 year limited Compressor Warranty
FEATURES and BENEFITS
- State-of-the-art Copeland Scroll compressor is standard equipment.
- Proven, Industry Standard Components Easier service and availability.
- TXV Externally equalized. Provides precise refrigerant control under varying load conditions.
- High Pressure Switch Protects against abnormally high system pressures.
- Liquid Line Filter/Drier Insures clean and dry refrigeration system.
- Externally Accessible Service Ports Quick access to refrigerant system without disrupting operation.
- Compact Footprint Easy to handle and transport.
- Convertible Air Delivery Horizontal or downflow to accommodate rooftop or horizontal application.
- Heavy-Gauge, Full Perimeter Base Rails Facilitates forklift handling and curb mounting.
- Galvanized Steel Cabinet with polyurethane finish provides 950 hour salt spray protection.
- Wire Guard Coated with Earth Friendly Epoxy and Plastic Mesh Hail Guard will never rust and protect the coil from being damaged by balls, lawnmowers, hail etc.
- Corrosion-Resistant Drain Pan Quickly drains away evaporator condensate.
- Quiet Operation Low Vibration. 20″ fan blade combined with custom venture condenser fan opening.
- Access to Controls and Major Components Easy in and out service.
- Service Access Panels To all major components and the compressor. Designed to make servicing easier for the Contractor.
- Factory Installed Filter Rack 1″ or 2″ Capable.
- Easy to Install Electric heat strip provides 9 or 15 KW of heat output.
- Accessories Roof curbs, economizers, fresh air dampers and more.
MODEL IDENTIFICATION CODE
DIMENSIONS
P6SD models
Model Number
P6SD-| Unit Weight| Center of Gravity| Height (in inches)
C
---|---|---|---
A| B
with base rails
X36| 405.00| 29.50| 26.00| 35.30
X48| 415.00| 29.50| 26.50| 35.30
X60| 480.00| 30.00| 27.50| 39.30
SPECIFICATIONS
P6SD models – 208/230V Three Phase
Model Number | P6SD |
---|---|
X36C | X48C |
Performance | |
Capacity -Cooling BTUH | 34,200 |
Efficiency – SEER | 13.30 |
EER (Btuh/watt) | 11. |
Electrical Rating – 60 Hz | |
Phase | 3 |
Operating Voltage Range | 187 – 253 |
Compressor Data | |
Volts | 208 / 230 |
Rated Load Amps | 12. |
Lock Rotor Amps | 73 |
Indoor Blower | |
Type | DD / 3 |
Motor – HP / RPM | 1/4 – 1075 |
Motor – Amps | 1. |
Outdoor Fan | |
Motor – HP / RPM | 1/4 – 1100 |
Motor – Amps | 1. |
Fan Diameter / CFM | 20/3600 |
Refrigerant Charge – Oz. R-410A | 110 |
Net Weight lbs. | 405 |
Shipping Weight lbs. | 415 |
Filters (Field Installed) | |
Style | Disposable |
Size (Qty) | 16 x 25 x 1 (2) |
Field convertible to two inches |
BLOWER PERFORMANCE
P6SD models
Model Number
P6SD-| External Static Pressure Drop – inches water column
---|---
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
X36
*| High| 1610| 1562| 1504| 1442| 1365| 1295| 1214| 1109
Medium| 1367| 1320| 1271| 1205| 1138| 1065| 968| 845
Low| 1153| 1102| 1043| 990| 912| 831| 731| 618
X48| High| 2361| 2278| 2218| 2141| 2066| 1976| 1870| 1758
Medium| 2026| 1982| 1935| 1889| 1822| 1744| 1660| 1554
Low| 1584| 1568| 1532| 1489| 1445| 1387| 1322| 1236
-
- X60 *| Tap T1| 1515| 1450| 1380| 1350| 1300| 1250| 1200| 1160
Tap T2| 1580| 1520| 1460| 1400| 1360| 1300| 1260| 1230
Tap T3| 1740| 1690| 1650| 1600| 1540| 1500| 1460| 1390
Tap T4| 1960| 1910| 1840| 1820| 1780| 1740| 1700| 1600
Tap T5| 2090| 2050| 2010| 1975| 1940| 1900| 1850| 1790
- X60 *| Tap T1| 1515| 1450| 1380| 1350| 1300| 1250| 1200| 1160
-
Denotes factory set cooling speed
Denotes factory set electric heating speed
NOTE:** Airflow performance is with a dry coil
SPECIFICATIONS
P6SD models – 460V Three Phase
Model Number | P6SD |
---|---|
X36D | X48D |
Performance | |
Caoacitv -Coolina BTUH | 34,200 |
Efficiencv – SEER | 13.30 |
EER <Btuh/watt) | 11.2 |
Electrical Ratina – 60 Hz | |
Phase | 3 |
Ooeratina Voltaae Ranae | 414 – 506 |
Comoressor Data | |
Volts | 460 |
Rated Load Amos | 6.4 |
Lock Rotor Amos | 38 |
Indoor Blower | |
Tvoe | DD / 3 |
Motor – HP I RPM | 1/4 – 1075 |
Motor – Amos | 0.8 |
Outdoor Fan | |
Motor – HP I RPM | 1/4 – 1100 |
Motor – Amos | 0.6 |
Fan Diameter I CFM | 20/3600 |
Refriaerant CharQe – Oz. R-410A | 110 |
Net Weiaht lbs. | 405 |
ShloolnnWelaht lbs. | 415 |
Filters <Field Installed) | |
Stvle | Disoosable |
Size <Otv) | 16 x 25 x 1 (2) |
Field convertible to two inches |
AIR CONDITIONER ELECTRICAL DATA
P6SD SERIES – 208/230V – 3 PHASE MODELS
MODEL NUMBER P6SO-| HEATER
INSTALLED NOMINAL KW| SINGLE CIRCUIT
---|---|---
MCA| MOP
X36C| 0| 17.0| 25
9| 26.7| 30
15| 46.8| 50
X48C| 0| 21.6| 35
9| 28.7| 35
15| 46.8| 50
X60C| 0| 29| 45
9| 29| 45
15| 46.7| 50
P6SD SERIES – 460V – 3 PHASE MODELS
MODEL NUMBER P6SD-| HEATER
INSTALLED NOMINAL KW| SINGLE CIRCUIT
---|---|---
MCA| MOP
X360| 0| 9.4| 15
9| 15.1| 15
15| 24.5| 25
X48D| 0| 10.9| 15
9| 16.2| 15
15| 25.7| 30
X60D| 0| 14.6| 15
9| 14.9| 15
15| 24.3| 25
NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different circuits when adding a heater kit.
HEATER APPLICATION MATRIX
TONNAGE
& PHASE| UNIT| NOMINAL KW| HEATER KIT MODEL| HEATER KIT
PART NUMBER| BREAKERS REQUIRED
---|---|---|---|---|---
3,4,& 5 TON
3 Phase 208/230V| P6SD| 9| H3HK 0090·016| 9038546| None
15| H3HK-015Q-016| 9038556| None
3,4,& 5 TON
3 Phase 460V| P6SD| 9| H3HK-009S-016| 9038506| None
15| H3HK-015S-016| 9038516| None
MODEL IDENTIFICATION CODE
P6SD ACCESSORIES
Description | Part Number |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14”) | 547831 |
Roof Curb (18”) | 547850 |
Roof Curb (24”) | 547851 |
Supply/return transition, 16” | 547834 |
Supply/return transition, 18” | 547835 |
Concentric diffuser, flush, 16” | 547836 |
Concentric diffuser, flush, 18” | 547837 |
Concentric diffuser, step down 16” | 547838 |
Concentric diffuser, step down 18” | 547839 |
Manual Fresh Air Damper | 547832 |
Motorized Fresh Air Damper | 547840 |
Economizer, downflow w/filter modulating, enthalpy controlled | 558870 |
Economizer, horizontal modulating, enthalpy controlled | 547841 |
Power Exhaust for use with downflow economizer (208/230 3 Phase) Special
Order| 555578
Power Exhaust for use with horizontal economizer (208/230 3 Phase) Special
Order| 555580
Power Exhaust for use with downflow economizer (460V 3 Phase) Special Order|
555579
Power Exhaust for use with horizontal economizer (460V 3 Phase) Special Order|
555581
HOOD TYPE HAIL GUARD 34” X 76” (3 or 4 Ton)| 547846
HOOD TYPE HAIL GUARD 38” X 76” (5 Ton)| 547847
Differential enthalpy sensor kit| 920233
Control, CO2 sensor, wall mount| 547848
Duct Smoke Detector Photo Elec| 558863
Multi Signal Control| 558866
Sampling Tube DST 3, 2-4′| 558864
Sampling Tube DST 5, 4-8′| 558865
Low Pressure Switch Kit| 913551
Low Ambient Kit| 918837
Freezestat| 917108
Duct Adaptor, 14″ Round (2 each)| 913812A
Outdoor Thermostat Kit| 913852
Circuit Breaker, Three Phase (3-Pole)| 913740
P6SD EXPANDED RATINGS
GENERAL TERMS OF LIMITED WARRANTY
Nortek Global HVAC, LLC will furnish a replacement for any part of this
product which fails in normal use and service within the terms and conditions
of the warranty.
For complete details of the Limited Warranty, including applicable terms and
conditions, see your local installer or contact the Nortek Global HVAC, LLC
warranty department for a copy.
Before purchasing this appliance, read important energy cost and efficiency
information available from your retailer. Specifications and illustrations
subject to change without notice and without incurring obligations. Printed in
U.S.A (10/2015)
716C-1014 (Replaces 716C-0910)
www.mammothlc.com
Trademark Mammoth® used under license. © Nortek Global HVAC, LLC. All Rights
Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>