SUNCO LIGHTING White Mounting Bracket for LED Selectable Area Lights Installation Guide

August 6, 2024
Sunco Lighting

White Mounting Bracket for LED Selectable Area Lights

“`html

Specifications:

  • Suitable for wet locations

  • Wattage options: 80W, 100W, 120W, 150W, 170W, 200W, 220W,
    240W

  • Mounting options: Square & Round Pole Mount, Slip Fitter
    Mount, Wall Mount

Product Usage Instructions:

Square & Round Pole Mount:

Step 1: Unscrew the screws of the iron bar with
a screwdriver and adjust the hole spacing of the iron bar according
to the hole position on the Square or Round Pole. Remove the
junction box cover of the Pole Mount bracket.

Step 2: Fix the iron bar to the inside of the
light pole with screws (screw should only be screwed into 1/3 of
its length), and lead out the input wire.

Step 3: Pass the rubber gasket and the Pole
Mount bracket through the screw and input wire on the light pole.
Tighten the screw and then lock the other screw.

Step 4: Run the fixture’s AC input wire through
the bracket. Hang the fixture on the bracket, and tighten the
screws. Bolt torque should be 8.67ft-lb(11.7N.m).

Note: When installing on a round pole, please
remove the rubber gasket.

Slip Fitter Mount:

Step 1: Disassemble the Slip Fitter with a
wrench.

Step 2: Run the fixture’s AC input wire through
the base, then tighten screws to attach the base to the fixture
housing.

FAQ:

Q: Can I modify or alter the product?

A: No, any alteration or modification of this
product is forbidden as it may cause serious personal injury,
death, property damage, and/or product malfunction.

Q: What safety precautions should I take during

installation?

A: Gloves and safety glasses should be worn
while performing the installation. Ensure power is off before
installation or inspection.

“`

ALH AREA LIGHT Installation Instruction

WARNING / ADVERTENCIA / AVERTISSEMENT

To reduce the risk of electrical shock, fire, or injury to persons; read and follow all warnings and installation instructions before installing. All installation should be performed by a qualified electrician.

Para reducir el riesgo de descarga eléctrica incendio o lesiones a personas, lea y siga todes las advertencias e instrucciones de instalación antes de realizerla. Toda instalación debe ser efectuada por un electricista cualificado.

Rick of Electrical Shock
Ensure power is off before installation or inspection. All wirings are performed in accordance with Electrical Code and local electrical code.

Riesgo de descarga eléctrica Asegúrese de desconectar la corriente antes de la instalación o inspección. Todos los cableados se realizan de acuerdo con el Código Eléctrico y el código eléctrico local.

Risk of Fire

Riesgo de incendio

Fixtures are rated for use in 120-277V, 50-60Hz Las luminarias están clasificadas para su

protected circuit and 90°Crated supply wire. uso con 120-277V, circuitos protegidos de

50-60 Hz y cables adecuados para 90°C.

Lisez et suivez les instructions d’installation et les avertissements avant I’installation. Toute I’installation doit être exécutée par un électricien qualifié, pour réduire les risques de choc électrique, de feu ou de blessures corporelles.
Risque de choc électrique Assurez-vous que le courant soit coupé av ant I’installation ou I’inspection et que tout le câblage soit effectué en conformité avec le code d’électricité et le code local d’électric -ité.
Risque de feu Les luminaires sont conçus pour une utilisation de 120 à 277V, pour un circuit protégé de 50 à 60 Hz et pour une source d’alimentation de 90 °C.

FOR YOUR SAFETY
Gloves and safety glasses should be worn while performing the installation.

PARA SU SEGURIDAD

POUR VOTRE SÉCURITÉ

Se deben usar guantes y gafas de seguridad Des gants et des lunettes de sécurité doivent

mientras se realiza la instalación.

être portés lors de l’ installation.

Any alteration or modification of this product is expressly forbidden as it may cause serious personal injury, death, property damage and/ or product malfunction. To prevent product malfunction and/or electrical shock, this product must be properly grounded. To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. Do not alter, relocate, or remove wiring, lampholders, power supply, or any other electrical component.

Cualquier alteración o modificación de este producto está prohibido expresamente, ya que puede causar graveslesiones personales, muerte, daños a la propiedad y/o mal funcionamiento del producto. Para evitar el mal funcionamiento del producto y /o descargas eléctricas, este producto debe estar correctamente conectado a tierra. Para evitar daños en el cableado o abrasiones, no exponga el cableado a hojas de metal laminado u otros objetos cortopunzantes. No altere. reubique o elmine cables, portalámparas, tomacorriente o cualquier otro componente eléctrico.

Toute aletération ou modification de ce produit est expressément interdite car elle peut causer des blessures graves,la mort, des dégâts matériels et / ou un dysfonctionnement du produit.
Pour éviter tout dysfonctionnement du produit et / ou un choc électrique, ce produit doit être correctement mise à la terre
Pour prévenir les dommeges ou l’abrasion, ne pas mettre en contact le câblage avec des bords de plaques de metal ou tout autre oject coupant.
Ne pas modifier, délocaliser ou enlever du câblage, des supports de lampes, une source d’alirmentation ou tout autre composant électrigue.

SUITABLE FOR WET LOCATIONS.

APTO PARA LUGARES HÚMEDOS.

CONVIENT AUX ENDROITS HUMIDES.

INSTALLATION / INSTALACIÓN
Disconnect the power before installation. Exploded view of completed assembly with component call out. 1,2,3,etc. Desconecte la alimentación antes de la instalación, Vista de despiece del conjunto completo con indicación de componentes. 1.2.3.etc Débranchez l’alimentation avant l’installation. Vue en éclaté de I’assemblage complet, avec le nom des composants. 1,2,3,etc.

INSIDE THE BOX
Area Light (Shorting Cap or Twist lock Photocell is optional)

Mounting Arm

80W/ 100W/ 120W/ 150W Wattage Selectable

170W/ 200W/ 220W/ 240W Wattage Selectable

with one of the mounting arms

Square & Round Pole Mount

Slip Fitter Mount

Wall Mount

Photocell Quick-install

Please read this manual carefully before using the product

Remove Shorting Cap

Install Photocell

Square & Round Pole Mount
Step1: Unscrew the screws of the iron bar with a screwdriver, adjust the hole spacing of the iron bar in advance according to the hole position on the Square or Round Pole. Remove the junction box cover of the Pole Mount bracket. hole spacing

Step2: Fix the iron bar to the inside of the light pole with
screws (Note: the screw is only screwed into 1/3 of its length), and lead out the input wire.

1.26″(32mm)

1.26″(32mm)

Iron bar

Junction box cover
Step3: Pass the rubber gasket and the Pole Mount bracket through the screw and input wire on the light pole. Tighten the screw and then lock the other screw.
screw

Step3: Run the fixture’s AC input wire through the bracket. Hang the fixture on the bracket, and tighten the screws.

Bolt torque 8.67ft-lb(11.7N.m)

Note: When installing on a round pole, please remove the rubber gasket.

screw

screw

Step 5: Pull the fixture’s input wire through the wiring hole into the pole and connect the wires inside or pull the wires out from the access panel on the extrusion arm bracket to connect the wires. Close the pole’s top cover or extrusion arm bracket panel.

Connect wires inside square pole

Connect wires inside round pole

Connect wires inside mounting bracket

Wiring Diagram

Connect wires inside mounting bracket

240W/ 260W/ 280W/ 310W Wattage Selectable

Trunnion Mount

Universal Bracket Mount

Adjustable Square & Round Pole Mount

-1-

-2-

ALH AREA LIGHT Installation Instruction

Slip Fitter Mount

Step 1: Disassemble the Slip Fitter with a wrech.

lamp holder

base

Step 2: Run the fixture’s AC input wire through the base, then tighten screws to attach the base to the fixture housing.

Wall Mount
Step 1: Unscrew the screws of the front cover and remove the front cover.

Please read this manual carefully before using the product
Step 2: Install the back housing directly to the wall using the wall anchor holes and appropriate screws.

Bolt torque 17.3ft-lb (23.5N.m)
Step 3: Run the fixture’s input wire through the lamp holder and lock it.

Bolt torque 3.61ft-lb (4.9N.m)

Front Cover

Back Housing

Step 4: Loosen the 4 locking bolts on the Slip Fitter with a wrench. Locking bolt

Step 3: Connect the front case set to the back housing and tighten the screws. Hang the fixture on the Wall Mount bracket and tighten screws.

Step 4: Complete wiring in the wall mount bracket, close the front cover and tighten the 2 screws in the front case.
screw

screw

screw

Step 5: Connect the fixture’s AC input wire to pole-wire with connectors, L to L(black), N to N(White), G to G(Green); If need to connect dimming wires, please also use the connector to connect “Dim+”(purple)to “Dim +”(purple), “Dim-“(gray) to “Dim-“(gray). AC input wire

Step 6: Tighten the 4 locking bolts. Locking bolt
Bolt torque 8.67ft-lb (11.7N.m)

Step 7: Loosen the locking bolt on the Slip Fitter with a wrench to adjust the fixture mounting angle, then tighten the locking bolts. Adjustable angle range ± 90°.
Locking bolt -3-

Trunnion Mount
Step 1: Loosen the screws on both sides of the bracket with a wrench, adjust Trunnion Mount bracket’s angle to keep parallel with its installation surface.

Step 2: Mark the fixing holes locations on the wall with Trunnion Mount bracket, then drill the hole in 10mm diameter with an electric dril.

Installation Surface

1.16″

1.16″

R0.24″

2.58”

electric drill

-4-

ALH AREA LIGHT Installation Instruction

Please read this manual carefully before using the product

Step 3: Knock the two expansion bolts (not included) into wall with a hammer.
expansion bolt hammer

Step 4: Install the Trunnion Mount bracket to the wall with expansion screw by tightening the nut with a wrench. Connecting fixture AC input wire to L N G, then make waterproof processing to joints, put wires into junction box. Note: The adjustable angel range is 0-180°.
Wiring Diagram
180°

Step 5: Pull the fixture’s input wire through the wiring hole into the pole and connect the wires inside or pull the wires out from the access panel on the extrusion arm bracket to connect the wires. Close the pole’s top cover or extrusion arm bracket panel.

Connect wire inside round pole

Connect wire inside square pole

Connect wire inside mounting bracket

Wiring Diagram

Connect wire inside mounting bracket

AUdnjiuvesrtasbaleBSraqcukaerteM&oRunotund Pole Mount

Step 1:

iron bar

base

lamp holder

Disassemble the Slip Fitter with a wrech.

junction box cover
Unscrew the screws, remove the iron bar, open the junction box cover.

Step 2: Run the fixture’s AC input wire through the base, then tighten screws to attach the base to the fixture housing.
Bolt torque 3.61ft-lb (4.9N.m)

Square & Round Pole Mount
Step 3: Put the iron bar inside of pole, fix it with a screw, but reserve gaps of 32mm, pass the Pole Mount bracket through the screw and hang it on the screw, tighten this screw, pass the 2nd screw through the holes of Pole Mount bracket, pole and iron bar, then tighten it with a wrench.

Slip Fitter Mount
Step 1:

base

lamp holder

iron bar

Step 2: Run the fixture’s AC input wire through the base, then tighten screws to attach the base to the fixture housing.

Disassemble the Slip Fitter with a wrech.

junction box cover
Unscrew the screws, remove the iron bar, open the junction box cover.

Step 3: Run the fixture’s input wire through the lamp holder and lock it.

Bolt torque 3.61ft-lb (4.9N.m)

Note: When installing on a round pole, please remove the rubber gasket.

Step 4: Loosen the locking bolt on the Slip Fitter with a wrench to adjust the fixture mounting angle, then tighten the locking bolts. Adjustable angle range ± 90°.

-5-

Step 4: Connect the fixture’s AC input wire to pole-wire with connectors, L to L(black), N to N(White), G to G(Green); If need to connect dimming wires, please also use the connector to connect “Dim+”(purple)to “Dim +”(purple), “Dim-“(gray)to “Dim-“(gray).

Step 5: Tighten the 4 locking bolts. Loosen the locking bolt on the Slip Fitter with a wrench to adjust the fixture mounting angle, then tighten the locking bolts. Adjustable angle range ± 90°.

Wiring Diagram

Locking bolt

-6-

ALH AREA LIGHT Installation Instruction

Adjustable Square & Round Pole Mount

Step 1:
lamp holder

base

iron bar

Step 2: Run the fixture’s AC input wire through the base, then tighten screws to attach the base to the fixture housing.

Connect wire inside mounting bracket

Please read this manual carefully before using the product

Wiring Diagram

Connect wire inside mounting bracket

Disassemble the Slip Fitter with a wrech.

junction box cover
Unscrew the screws, remove the iron bar, open the junction box cover.

Step 3: Adjust the hole spacing of the iron bar in advance according to the hole position on the Square or Round Pole. Fix the iron bar to the inside of the light pole with screws (Note: the screw is only screwed into 1/3 of its length), and lead out the input wire.

hole spacing

1.26″(32mm)

1.26″(32mm)

Iron bar

Bolt torque 3.61ft-lb (4.9N.m)
Step 4: Pass the Pole Mount bracket through the screw and hang it on the screw, tighten this screw, pass the 2nd screw through the holes of Pole Mount bracket, pole and iron bar, then tighten it with a wrench.

Note: When installing on a round pole, please remove the rubber gasket.

Step 5: Loosen the locking bolt on the Slip Fitter with a wrench to adjust the fixture mounting angle, then tighten the locking bolts. Adjustable angle range ± 90°.

TROUBLESHOOTING
1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
2. Is the fixture grounded properly.

Wattage Selectable

1. Unscrew the hatch cover screws 2. Open the driver cover 3. Adjust CCT or Wattage

Step 6: Pull the fixture’s input wire through the wiring hole into the pole and connect the wires inside or pull the wires out from the access panel on the extrusion arm bracket to connect the wires. Close the pole’s top cover or extrusion arm bracket panel.

Connect wire inside round pole

Wiring Diagram

Connect wire inside square pole

CCT Options (30/40/50)K
Wattage Selectable (80/100/120/150)W (170/200/220/240)W (240/260/280/310)W

Wiring Diagram
Live Netrual Ground
120-277Vac 50/60Hz

LED Light

-7-

-8-

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Sunco Lighting User Manuals

Related Manuals