PC104-3 & PC105-3
3-PHASE SOCKET TESTER
Instruction Manual
ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING
Thank you for buying one of our products. For safety and full understanding of
its benefits please read this manual before use.
Technical support is available from +44 (0)1923 441717 and support
@martindale-electric.co.uk.
Safety Information
Always read before proceeding.
REMEMBER: SAFETY IS NO ACCIDENT
These instructions contain both information and warnings that are necessary for the safe operation and maintenance of this product. It is recommended that you read the instructions carefully and ensure that the contents are fully understood. Failure to understand and to comply with the warnings and instructions can result in serious injury, damage or even death.
Particular attention should be paid to the Warnings, Precautions and Technical
Specifications.
Please keep these instructions for future reference. Updated instructions and
product information are available at: www.martindale-
electric.co.uk
1.1 Meaning of Symbols and Markings
| Caution – risk of danger & refer to instructions
---|---
| Caution – risk of electric shock
|
Equipment protected by double or reinforced insulation (Class II)
| Equipment complies with relevant EU Directives
| Equipment complies with relevant UK Conformity Assessed marking
| End of life disposal of this equipment should be in accordance with
relevant EU Directives
| Three-phase alternating current
Measurement Category III (CAT III) is applicable to test and measuring equipment connected to the distribution part of the building’s low-voltage MAINS installation.
1.2 Precautions
This product has been designed with your safety in mind, but please pay
attention to the following warnings and cautions before use.
Warning
In order to avoid the danger of electrical shock, it is important that proper
safety measures are taken when working with voltages exceeding 30V AC rms, 42V
AC peak or 60V DC.
Where applicable other safety measures such as the use of protective gloves,
goggles etc. should be employed.
The product(s) must only be used by a skilled and competent person who is
familiar with the relevant regulations, the safety risks involved and the
consequent normal safe working practices, and under the conditions and for the
purposes for which it has been constructed and specified.
Before use check the unit for cracks or any other damage. Make sure the unit
is free from dust, grease and moisture. Also check any associated leads and
accessories for damage. Do not use if damaged.
Always verify the unit is functioning correctly on a known correctlywired live
socket before and after use. Do not use the unit if the unit does not give the
correct indications.
The socket tester is not intended to determine if circuits being tested are
dead. The correct testing methods should be used to do this.
If the indicators do not illuminate, this does not necessarily mean all three
phases under test are dead. Two phases and the earth/neutral could be open
circuit, but one phase could still be live.
If the equipment is used in a manner not specified by Martindale Electric, the
protection provided by the equipment may be impaired.
Caution
Avoid severe mechanical shock or vibration and extreme temperature.
INTRODUCTION
2.1 Inspection
Examine the shipping carton for any sign of damage. Inspect the unit and any
accessories for damage. If there is any damage then consult your distributor
immediately.
2.2 Description
The PC104 & PC105 are 3-phase socket testers intended to check CEE 4 & 5 pin,
16A, 32A & 63A sockets.
The PC104 checks for phase presence, phase sequence and PE presence.
The PC105 also checks for neutral presence.
The table below shows the model number and the CEE socket type tested.
Model No | Socket Type Tested |
---|---|
PC104-16 | 16A/3P+E |
PC105-16 | 16A/3P+N+E |
PC104-32 | 32A/3P+E |
PC105-32 | 32A/3P+N+E |
PC104-63 | 63A/3P+E |
PC105-63 | 63A/3P+N+E |
2.3 Accessories (included)
Instructions
OPERATION
3.1 Testing a 3-Phase Socket
Plug the PC104 or PC105 into the socket to be tested and refer to the table
below, or the front decal of the unit, to determine the wiring condition of
the socket under test.
PC104 Indication | PC105 Indication | Wiring Condition |
---|---|---|
**Socket is wired correctly. Phase sequence is L.1, L2, L3. PE & Neutral |
are present.**
LI, L2 & L3 flash green in a clockwise direction. PE & N illuminate green.
| | Phases wired incorrectly.
Phase sequence is L.1, L3, L2.
Lt, 12 & L3 flash red in an anti-clockwise direction.
| Phase L.1 is missing. L2 & L3 flash red.
| Phase L2 is missing. LI & L3 flash red.
| Phase L3 is missing. Lt _& _1.2 flash red.
| | PE is missing. PE illuminates red.
(On the now superseded Mk2 versions. PC104-2 and PC105-2. the PE LED is extinguished in the case of missing PE and is not lit red)
NA| | Neutral is missing. N illuminates red.
The PC104 & PC105 also indicate the wiring condition by sounding a buzzer according to the table below:
Condition | Buzzer Indication |
---|---|
Correct socket wiring, phase sequence correct | Continuous tone |
Phases wired incorrectly, phase sequence incorrect | Slow intermittent tone |
Phase, PE or neutral missing | Fast intermittent tone |
Note : The interchanging of the neutral wire (N) with the earth (PE)
cannot be recognised by this device.
Warning
Where a socket is found to have a wiring error, maintenance should only be
carried out by a competent electrician who is familiar with the relevant
regulations and the safety risks involved.
3.2 Wiring Colour Coding
In April 2004 the colour coding of UK wiring was harmonised with the IEC
wiring colour code. Table 2 shows the old UK colour code and the new IEC
colour code.
| Earth| Neutral| Line 1| Line 2| Line 3
---|---|---|---|---|---
Old UK Colours| Green/ Yellow| Black| Red| Yellow| Blue
New IEC| Green/ Yellow| Blue| Brown| Black| Grey
MAINTENANCE
4.1 Cleaning
Warning
To reduce the risk of surface leakage, this instrument must be kept in a clean
condition.
Warning
Prior to cleaning, ensure that the instrument is disconnected from any voltage
source.
If contamination is found, clean with a damp soft cloth and if necessary a mild detergent. Do not use abrasives, abrasive solvents, or detergents which can cause damage to the unit. If a mild detergent is used, the unit should subsequently be thoroughly cleaned with a water dampened soft cloth. After cleaning, dry and allow to remain in a dry environment for 2 hours before use.
4.2 Repair & Service”
There are no user serviceable parts in this unit. Return to Martindale
Electric if faulty. Our service department will quote promptly to repair any
fault that occurs outside the guarantee period.
4.3 Storage Conditions
The instrument should be kept in warm dry conditions away from direct sources
of heat or sunlight, and in such a manner as to preserve the working life of
the unit. It is strongly advised that the unit is not kept in a tool box where
other tools may damage it.
WARRANTY AND LIMITATION OF LIABILITY
This Martindale product is warranted to be free from defects in material and
workmanship under normal use and service. The warranty period is 2 years and
begins on the date of receipt by the end user. This warranty extends only to
the original buyer or enduser customer, and does not apply to fuses,
disposable batteries, test leads or to any product which, in Martindale’s
opinion, has been misused, altered, neglected, contaminated, or damaged by
accident or abnormal conditions of operation, handling or storage.
Martindale authorised resellers shall extend this warranty on new and unused
products to end-user customers only but have no authority to extend a greater
or different warranty on behalf of Martindale.
Martindale’s warranty obligation is limited, at Martindale’s option, to refund
of the purchase price, free of charge repair, or replacement of a defective
product which is returned to Martindale within the warranty period.
This warranty is the buyer’s sole and exclusive remedy and is in lieu of all
other warranties, expressed or implied, including but not limited to any
implied warranty of merchantability or fitness for a particular purpose.
Martindale shall not be liable for any special, indirect, incidental or
consequential damages or losses, including loss of data, arising from any
cause or theory.
Since some jurisdictions do not allow limitation of the term of an implied
warranty, or exclusion or limitation of incidental or consequential damages,
the limitations and exclusions of this warranty may not apply to every buyer.
If any part of any provision of this
warranty is held invalid or unenforceable by a court or other decision- maker
of competent jurisdiction, such holding will not affect the validity or
enforceability of any other provision or other part of that provision.
Nothing in this statement reduces your statutory rights.
Specification
PC104-3 & PC105-3
3-Phase Socket Tester
ELECTRICAL SPECIFICATIONS
Input voltage range: 360 to 440V AC (Phase to Phase)
Un = 400V (+/-10%)
Input frequency: 50Hz or 60Hz
Input current: I = I = I = 15mA max LI L2 L3
GENERAL SPECIFICATIONS
Power: From circuit under test
Dimensions: 152(L) x 81(W) x 35(D) mm
Weight: 240g approx. (without plug)
Includes: Instructions
SAFETY:
BS EN 61010-1, CAT III 300V
Class II Double Insulation
ENVIRONMENTAL:
Suitable for indoor use, and outdoor use in dry weather conditions only
Altitude: Up to 2000m
Operating Temperature: 0°C to + 40°C
Humidity: ≤ 80%RH up to 31°C, decreasing linearly to 50%RH at 40°C
Ingress Protection: IP40
Pollution Degree: 2
EMC:
Conforms to BS EN 61326-1, BS EN 61326-2-2
Check out what else you can get from Martindale:
• 18th Edition Testers | • Safe Isolation Kits |
---|---|
• Accessories | • Multifunction Testers |
• Calibration Equipment | • Non-trip Loop Testers |
• Continuity Testers | • Pat Testers & Accessories |
• Electricians’ Kits | • Phase Rotation Testers |
• Environmental Products | • Proving Units |
• Full Calibration & Repair Service | • Socket Testers |
• Fuse Finders | • Thermometers & Probes |
• Digital Clamp Meters | • Test Leads |
• Digital Multimeters | • Voltage Indicators |
• Labels | • Specialist Metrohm Tester |
• Microwave Leakage Detectors | • Specialist Drummond Testers |
Martindale Electric Co. Ltd. Metrohm House, 12 Imperial Park,
Imperial Way, Watford WD24 4PP. T: +44 (0)1923 441717 F: +44 (0)1923 446900
www.martindale-electric.co.uk sales
@martindale-electric.co.uk
Ver. D1.1
Due to policy of continuous development, Martindale Electric reserves the
right to alter equipment specification and description outlined in this
document without prior notice.
No part of this document shall be deemed to be part of any contract for the
equipment unless specifically referred to as an inclusion within such
contract. © 2023 Martindale
Electric Co. Ltd. Registered in England No. 3387451. LITPC104-105-3