SENECA R Series I O with Modbus Tcp Ip and Modbus Rtu Protocol User Manual

June 15, 2024
SENECA

SENECA-logo

SENECA R Series I O with Modbus Tcp Ip and Modbus Rtu Protocol

Product Information

Specifications

Introduction

The R Series I/O is a versatile device that supports both Modbus TCP-IP and Modbus RTU protocols. It is manufactured by SENECA srl and offers various models with different features and capabilities.

R Series Devices

R-32DIDO

The R-32DIDO model is designed for digital input and output operations. It provides a total of 32 digital input and output channels.

Protection of Digital Outputs

The R-32DIDO model includes a chapter in the user manual that explains how to protect the digital outputs to ensure safe and reliable operation.

R-16DI-8DO

The R-16DI-8DO model offers 16 digital input channels and 8 digital output channels.

R-8AI-8DIDO

The R-8AI-8DIDO model combines analog input and output capabilities with digital input and output channels. It features 8 analog input channels and 8 digital input and output channels.

DIP Switch

Meaning of the DIP Switches SW1 for the R-8AI-8DIDO Model

The DIP switches on the R-8AI-8DIDO model, specifically SW1, have specific configurations that determine the device’s behavior.
The user manual provides detailed information on the meaning of each switch position and how it affects the device’s functionality.

Meaning of SW1 DIP-Switches for the R-32DIDO Model

The R-32DIDO model also has DIP switches, and the user manual explains the meaning of each switch position and its impact on the device’s operation.

DIP Switch SW1 for Firmware Revision = 1015

For devices with firmware revision 1015, there is specific information in the user manual about the DIP switch SW1 and its configuration.

Meaning of the SW1 DIP Switches for the R-SG3 Model

The R-SG3 model has its own set of DIP switches, and the user manual provides detailed explanations of each switch position and its function for this particular model.

I/O Copy Using the Peer to Peer Function without Wiring

The user manual includes instructions on how to use the peer to peer function to copy I/O data without the need for wiring connections. This feature allows for easy and efficient data transfer between compatible devices.

FAQs

Q: Can I use the R Series I/O with other protocols besides Modbus TCP-IP and Modbus RTU?

A: No, the R Series I/O is specifically designed to work with Modbus TCP-IP and Modbus RTU protocols only.

Q: How can I protect the digital outputs on the R-32DIDO model?

A: The user manual provides detailed instructions on how to protect the digital outputs to ensure safe operation. Please refer to the corresponding chapter in the manual for step-by-step guidance.

Q: Can I use the analog input and output channels simultaneously on the R -8AI-8DIDO model?

A: Yes, the R-8AI-8DIDO model allows for simultaneous use of analog input and output channels. The user manual provides information on how to configure and utilize these channels effectively.

USER MANUAL
R SERIES I/O WITH MODBUS TCP-IP and MODBUS RTU
PROTOCOL
SENECA S.r.l. Via Austria 26 ­ 35127 ­ Z.I. – PADOVA (PD) – ITALY Tel. +39.049.8705355 ­ 8705355 Fax +39 049.8706287
www.seneca.it

ORIGINAL INSTRUCTIONS

User Manual

R SERIES

Introduction

The content of this documentation refers to products and technologies described in it. All technical data contained in the document may be changed without notice. The content of this documentation is subject to periodic review. To use the product safely and effectively, read the following instructions carefully before use. The product must be used only for the use for which it was designed and manufactured: any other use is under the full responsibility of the user. Installation, programming and set-up are allowed only to authorized, physically and intellectually suitable operators. Set-up must be performed only after correct installation and the user must follow all the operations described in the installation manual carefully. Seneca is not responsible for failures, breakages and accidents caused by ignorance or failure to apply the stated requirements. Seneca is not responsible for any unauthorized modifications. Seneca reserves the right to modify the device, for any commercial or construction requirement, without the obligation to promptly update the reference manuals. No liability for the contents of this document can be accepted. Use the concepts, examples and other content at your own risk. There may be errors and inaccuracies in this document that could damage your system, so proceed with caution, the author(s) will not take responsibility for it. Technical specifications are subject to change without notice.

CONTACT US Technical support Product information

supporto@seneca.it commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 2

User Manual

R SERIES

Document revisions

DATE
10/02/2023

REVISION
0

02/03/2023

1

15/03/2023

2

15/03/2023

3

08/05/2023

5

29/05/2023

6

31/05/2023

7

19/07/2023

8

13/11/2023

9

27/11/2023

10

NOTES
First revision R-32DIDO-1, R-32DIDO-2, R-16DI-8DO, R-8AI-8DIDO
Added Chapter “Protection of digital outputs”
Fix Seneca Discovery Device, Easy Setup 2, Seneca Studio Seneca Studio Fix cross references
Tables translated in English language
Added info about RW register Fix registers info in English language Added R-SG3 device, modified chapter “Factory configuration reset”
Added DIP SWITCH chapter
Fixed ModBUS registers 40044, 40079 and 40080 of R-SG3
Changed old R-8AI-8DIDO with new R-8AI-8DIDO version Deleted -1 R-series HW code Minor fix
Fix R-8AI-8DIDO Modbus table

AUTHOR
MM
MM MM
MM MM
MM MM AZ MM
MM

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 3

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 5

User Manual

R SERIES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 6

User Manual

R SERIES

1. INTRODUCTION
ATTENTION!
This user manual extends the information from the installation manual to the configuration of the device. Use the installation manual for more information.
ATTENTION!
In any case, SENECA s.r.l. or its suppliers will not be responsible for the loss of data/revenue or consequential or incidental damages due to negligence or bad/improper management of the device,
even if SENECA is well aware of these possible damages. SENECA, its subsidiaries, affiliates, group companies, suppliers and distributors do not guarantee that the functions fully meet the customer’s expectations or that the device, firmware and software should
have no errors or operate continuously.

R SERIES DEVICES

The R Series I/O modules are devices designed for flexible cabling needs, reduced installation spaces, high I/O density applications with ModBUS communication (serial and Ethernet). Configuration can be done via dedicated software and/or DIP switches. The devices can be connected in daisy chain mode (without the use of an external switch) and support faultbypass mode to ensure the Ethernet connection even in the event of failure of a module in the chain.
For more information on these protocols, see the website: http://www.modbus.org/specs.php.

R-32DIDO

The devices allow the use of 32 digital channels that can be individually configured for input or output. When a digital channel is configured as an input, a 32-bit counter is also associated with a value saved in non-volatile memory.

CODE R-32DIDO-2

ETHERNET PORT 2 PORTS 10/100 Mbit
(Switch mode)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 7

User Manual

R SERIES

PROTECTION OF DIGITAL OUTPUTS
The outputs are protected against overload and against overtemperature, they open cyclically until the fault is repaired or the output opens. The limit current is between 0.6 and 1.2 A.

R-16DI-8DO The devices allow the use of 16 digital input channels and 8 digital relay output channels.

CODE R-16DI8DO

ETHERNET PORT 2 PORTS 10/100 Mbit
(Switch mode)

R-8AI-8DIDO
The devices allow the use of 8 analog input channels and 8 digital channels that can be individually configured for input or output.

CODE R-8AI-8DIDO-2

ETHERNET PORT 2 PORTS 10/100 Mbit
(Switch mode)

ANALOG INPUT UPDATE TIME Sampling time can be configured from 25ms to 400ms per each channel, in particular:

CHANNEL SAMPLING TIME 25ms 50ms 100ms 200ms 400ms

To calculate the update time of a channel, consider the following example: By activating 8 channels and setting a sampling time of 25 ms, you get an input update every: 25*8 = 200 ms.

Note (only if thermocouple channels are enabled): In the case of a thermocouple input, the Burnout check is carried out every 10 seconds. The duration of this check takes 25ms on each enabled thermocouple channel.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 8

User Manual

R SERIES

For example, with 3 active thermocouples, every 10 seconds the following are used: 25ms x 3 channels = 75 ms for Burnout evaluation.

UPDATE TIME OF DIGITAL INPUTS/OUTPUTS

The update time of the 8 digital inputs/outputs is 25ms. R-SG3

R- SG3 is a load cell converter (strain gauge). The measurement, carried out with the 4 or 6-wire technique, is available via the server TCP-IP Modbus or via RTU slave Modbus protocols The device is equipped with a new noise filter specifically developed to obtain a rapid response time. The device

is also fully configurable via the webserver.

.

CODE

ETHERNET PORT

R-SG3

1 PORT 10/100 Mbit

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 9

User Manual

R SERIES

LOAD CELL CONNECTION
It is possible to connect the converter to the load cell in 4- or 6-wire mode. 6-wire measurement is preferable for measurement accuracy. The load cell power supply is provided directly by the device.
4- OR 6-WIRE LOAD CELL CONNECTION
A load cell can have a four-wire or six-wire cable. In addition to having the +/- excitation and +/- signal lines a six-wire cable also has the +/- sense lines. It is a common misconception to think that the only difference between 4- or 6-wire load cells is the possibility of the latter to measure the actual voltage at the load cell. A load cell is compensated to work within specifications in a certain temperature range (usually -10 – +40°C). Since the cable resistance depends on the temperature, the response of the cable to temperature changes must be eliminated. The 4-wire cable is part of the load cell temperature compensation system. The 4-wire load cell is calibrated and compensated with a certain amount of cable connected. For this reason, never cut the cable of a 4-wire load cell. The cable of a 6-wire cell, on the other hand, is not part of the load cell temperature compensation system. The sense lines are connected to the R-SG3 sense terminals, to measure and adjust the actual voltage of the load cell. The advantage of using this “active” system is the possibility of cutting (or extending) the 6-wire load cell cable to any length. It must be considered that a 6-wire load cell will not reach the performance declared in the specifications if the sense lines are not used.
CHECKING THE LOAD CELL OPERATION
Before starting the configuration of the device it is necessary to verify the correctness of the wiring and the integrity of the load cell.
2.4.3.1. CHECKING CABLES WITH A DIGITAL MULTIMETER
First you need to check with the load cell manual that there are about 5V DC between the +Excitation and ­ Excitation cables. If the cell has 6 wires check that the same voltage is also measured between +Sense and ­ Sense. Now leave the cell at rest (without the tare) and check that the voltage between the +Signal and ­Signal cables is around 0 V. Now unbalance the cell by applying a compression force, checking that the voltage between the +Signal and ­ Signal cables increases until it reaches the full scale (if possible) where the measurement will be approximately:
5 (cell sensitivity) mV.
For example, if the declared cell sensitivity is 2 mV/V, 5
2 = 10 mV must be obtained.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 10

User Manual

R SERIES

In the case of bipolar measurement only (compression/traction) it is necessary to completely unbalance the cell

even in traction, in this case the same value must be measured between the +Signal and ­Signal cables but

with

the

negative

sign:

-5* (cell sensitivity) mV.

CONNECTION OF MORE LOAD CELLS IN PARALLEL

It is possible to connect up to a maximum of 8 load cells (and in any case without ever falling below the minimum 87 Ohms).

It is therefore possible to connect:

IMPEDANCE OF THE STATED LOAD CELL
[Ohm] 350
1000

NUMBER OF LOAD CELLS IN PARALLEL MAXIMUM NUMBER OF CONNECTABLE CELLS IN PARALLEL
4 8

For the connection of 4 load cells Seneca recommends using the SG-EQ4 product.

To connect 2 or more 4-wire cells in parallel with the SG-EQ4 junction box, use the following diagram:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 11

User Manual

R SERIES

To connect 2 or more 6-wire cells in parallel with the SG-EQ4 junction box use the following diagram:

For more details, refer to the SG-EQ4 Junction Box accessory manual.
TRIMMING 4-WIRE LOAD CELLS The figure below shows a diagram of three trimmed load cells.

A variable resistor, independent of the temperature, or a typically 20 potentiometer is inserted in the +Excitation cable of each load cell. There are two ways to trim the load cells. The first method is to adjust the potentiometers by trial, shifting the calibration weights from one corner to another. All the potentiometers must be adjusted so as to set the maximum sensitivity for each cell, turning them all completely clockwise. Then, once

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 12

User Manual

R SERIES

the angle with the lowest output is located, act on the trimmers of the other cells until obtaining the same minimum output value. This method can be very long, especially for large scales where the use of test weights on the corners is not very practical. In these cases the second, more suitable method is to “pre-trim” the potentiometers using a precision voltmeter (at least 4 1/2 digits). You can use the following procedure: 1) Determine the exact mV/V ratio of each load cell, shown in the calibration certificate of the cell itself. 2) Determine the exact excitation voltage provided by the indicator/meter (for example Z-SG), measuring this voltage with the voltmeter (for example 10.05 V). 3) Multiply the lowest mV/V value found (point 1) by the excitation voltage (point 2). 4) Divide the trimming factor calculated in point 3 by the mV/V value of the other load cells. 5) Measure and adjust the excitation voltage of the other three load cells using the respective potentiometer. Check the results and make a final adjustment by moving a test load from corner to corner.
3. DIP SWITCH
ATTENTION!
THE DIP SWITCH SETTINGS ARE READ ONLY AT THE START. AT EACH CHANGE, IT IS NECESSARY TO RESTART.
ATTENTION!
DEPENDING ON THE MODEL IT MAY BE NECESSARY TO REMOVE THE REAR COVER OF THE DEVICE TO ACCESS THE DIP SWITCHES

MEANING OF THE DIP SWITCHES SW1 FOR THE R-8AI-8DIDO MODEL

Below is the meaning of the SW1 dip switches:

DIP1 DIP2

OFF OFF

ON

ON

OFF

ON

ON

OFF

MEANING Normal operation: The device loads the configuration from the flash.
Resets the device to its factory configuration Disables access to the Web server Reserved

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 13

User Manual

R SERIES

ATTENTION!
ONCE COMMISSIONING HAS BEEN COMPLETED, IN ORDER TO INCREASE THE SECURITY OF THE DEVICE, DISABLE THE WEBSERVER THROUGH THE DIP SWITCHES

MEANING OF SW1 DIP-SWITCHES FOR THE R-32DIDO MODEL

Below is the meaning of the SW1 dip switches for the various firmware revisions:

DIP SWITCH SW1 FOR FIRMWARE REVISION <= 1014

DIP1 DIP2

OFF OFF

ON

ON

OFF

ON

ON

OFF

MEANING Normal operation: The device loads the configuration from the flash.
Resets the device to its factory configuration Only forces the device IP address to the standard value of SENECA Ethernet
products: 192.168.90.101
Reserved

DIP SWITCH SW1 FOR FIRMWARE REVISION >= 1015

DIP1 DIP2

OFF OFF

ON

ON

OFF

ON

ON

OFF

MEANING Normal operation: The device loads the configuration from the flash.
Resets the device to its factory configuration Disables access to the Web server Reserved

ATTENTION!
ONCE COMMISSIONING HAS BEEN COMPLETED, IN ORDER TO INCREASE THE SECURITY OF THE DEVICE, DISABLE THE WEBSERVER THROUGH THE DIP SWITCHES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 14

User Manual

R SERIES

MEANING OF THE SW1 DIP SWITCHES FOR THE R-SG3 MODEL

Below is the meaning of the SW1 dip switches:

DIP1 DIP2

OFF OFF

ON

ON

OFF

ON

ON

OFF

MEANING Normal operation: The device loads the configuration from the flash.
Resets the device to its factory configuration Disables access to the Web server Reserved

ATTENTION!
ONCE COMMISSIONING HAS BEEN COMPLETED, IN ORDER TO INCREASE THE SECURITY OF THE DEVICE, DISABLE THE WEBSERVER THROUGH THE DIP SWITCHES

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 15

User Manual

R SERIES

4. I/O COPY USING THE PEER TO PEER FUNCTION WITHOUT WIRING
The “R” series devices can be used to copy and update in real time an input channel on a remote output channel without the aid of a master controller. For example, a digital input can be copied to a remote digital output device:

Note that no controller is required because the communication is managed directly by the R series devices. It is possible to make a more sophisticated connection, for example it is possible to copy the inputs to different R-series remote devices (from Device 1 Input 1 to Device 2 Output1, Device 1 Input 2 to Device 3 Output 1 etc …) It is also possible to copy an input to an output of multiple remote devices:

Each R-series device can send and receive a maximum of 32 inputs.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 16

User Manual

R SERIES

MODBUS PASSTHROUGH

Thanks to the Modbus Passthrough function it is possible to extend the amount of I/O available in the device via the RS485 port and the Modbus RTU slave protocol, for example by using the Seneca Z-PC series products. In this mode the RS485 port stops working as Modbus RTU slave and the device becomes a gateway from Modbus TCP-IP (ethernet) to Modbus RTU (serial):

Each Modbus TCP-IP request with station address other than that of the R series device is converted into a serial packet on the RS485 and, in the case of a reply, it is turned over to TCP-IP. Therefore, it is no longer necessary to purchase gateways to extend the I/O number or to connect already available Modbus RTU I/O.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 17

User Manual

R SERIES

6. RESETTING THE DEVICE TO FACTORY CONFIGURATION
PROCEDURE FOR RESTORING DEVICES TO THE FACTORY CONFIGURATION
It is possible to reset the device to the factory configuration using the dip- switches (see chapter 3).
7. CONNECTION OF THE DEVICE TO A NETWORK
The factory configuration of the IP address is:
Static address: 192.168.90.101
Therefore, multiple devices must not be inserted on the same network with the same static IP. If you want to connect multiple devices on the same network, you need to change the IP address configuration using Seneca Discovery Device software.
ATTENTION!
DO NOT CONNECT 2 OR MORE FACTORY-CONFIGURED DEVICES ON THE SAME NETWORK, OR THE ETHERNET INTERFACE WILL NOT WORK
(CONFLICT OF IP ADDRESSES 192.168.90.101)
If the addressing mode with DHCP is activated and an IP address is not received within 1 minute, the device will set an IP address with a fixed error:
169.254.x.y Where x.y are the last two values of the MAC ADDRESS. This way it is possible to install more I/O of the R series and then configure the IP with the Seneca Discovery Device software even on networks without a DHCP server.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 18

User Manual

R SERIES

8. WEB SERVER
ACCESS TO THE WEB SERVER
Access to the web server takes place using a web browser and entering the IP address of the device. To know the IP address of the device you can use the Seneca Discovery Device software.
On first access the user name and password will be requested. The default values are:
User Name: admin Password: admin

ATTENTION!
AFTER THE FIRST ACCESS CHANGE USER NAME AND PASSWORD IN ORDER TO PREVENT ACCESS TO THE DEVICE TO UNAUTHORIZED PEOPLE.

ATTENTION!
IF THE PARAMETERS TO ACCESS THE WEB SERVER HAVE BEEN LOST, IT IS NECESSARY TO RESET THE FACTORY-SET CONFIGURATION
ATTENTION!
BEFORE ACCESSING THE WEBSERVER, CHECK THE STATE OF THE DIP-SWITCHES (SEE CHAPTER 3)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 19

User Manual

R SERIES

9. CONFIGURATION OF THE R-32DIDO DEVICE VIA WEB SERVER
SETUP SECTION
DHCP (ETH) (default: Disabled) Sets the DHCP client to get an IP address automatically.
IP ADDRESS STATIC (ETH) (default: 192.168.90.101) Sets the device static address. Careful not to enter devices with the same IP address into the same network.
IP MASK STATIC (ETH) (default: 255.255.255.0) Sets the mask for the IP network.
GATEWAY ADDRESS STATIC (ETH) (default: 192.168.90.1) Sets the gateway address.
PROTECT CONFIGURATION (default: Disabled) Allows you to enable or disable password protection for reading and writing the configuration (including the IP address) using the Seneca Discovery Device software. The password is the same one that allows accessing the web server.
ATTENTION!
IF THE CONFIGURATION PROTECTION IS ENABLED IT WILL BE IMPOSSIBLE TO READ/WRITE THE CONFIGURATION OF THE DEVICE WITHOUT KNOWING THE PASSWORD.
IF THE PASSWORD IS LOST, IT WILL BE POSSIBLE TO RETURN THE DEVICE TO THE FACTORY-SET CONFIGURATION USING THE DIP SWITCHES
MODBUS SERVER PORT (ETH) (default: 502) Sets the communication port for the Modbus TCP-IP server.
MODBUS SERVER STATION ADDRESS (ETH) (default: 1) Active only if Modbus Passthrough is also active, it sets the station address of the modbus TCP-IP server.
ATTENTION!
THE MODBUS SERVER WILL ANSWER ANY STATION ADDRESS ONLY IF THE MODBUS PASSTHROUGH MODE IS DISABLED.
MODBUS PASSTHROUGH (ETH) (default: disabled) Sets the conversion mode from Modbus TCP-IP to Modbus RTU serial (see chapter 5).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 20

User Manual

R SERIES

MODBUS TCP-IP CONNECTION TIMEOUT [sec] (ETH) (default: 60) Sets the TCP-IP connection timeout for the Modbus TCP-IP server and Passthrough modes.
P2P SERVER PORT (default: 50026) Sets the communication port for the P2P server.
WEB SERVER USERNAME (default: admin) Sets the username to access the webserver.
CONFIGURATION/WEB SERVER PASSWORD (default: admin) Sets the password to access the webserver and to read/write the configuration (if enabled).
WEB SERVER PORT (default: 80) Sets the communication port for the web server.
BAUDRATE MODBUS RTU (SER) (default: 38400 baud) Sets the baud rate for the RS485 communication port.
DATA MODBUS RTU (SER) (default: 8 bit) Sets the number of bits for the RS485 communication port.
PARITY MODBUS RTU (SER) (default: None) Sets the parity for the RS485 communication port.
STOP BIT MODBUS RTU (SER) (default: 1 bit) Sets the number of stop bits for the RS485 communication port.
MODBUS PASSTHROUGH SERIAL TIMEOUT (default: 100ms) Active only if passthrough mode is activated, sets the maximum waiting time before sending a new packet from TCP-IP to the serial port. It must be set according to the longest response time of all the devices present on the RS485 serial port.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 21

User Manual

R SERIES

DIGITAL I/O SETUP SECTION This section allows the configuration of the digital I/Os present in the device.
DIGITAL I/O MODE (default Input) Selects whether the selected input will work as an input or output.
DIGITAL INPUT NORMALLY HIGH/LOW (default Normally Low) If selected as digital input, it configures whether the input is normally high or low.
DIGITAL OUTPUT NORMALLY STATE (default Normally Open) If selected as digital output, it configures whether the output is normally open or closed.
DIGITAL OUTPUT WATCHDOG (default Disabled) If selected as digital output, it sets the output watchdog mode. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Modbus Communication” the output goes into “Watchdog state” if there has been no generic Modbus communication within the set time. If “Enabled on Modbus Digital Output Writing” the output goes into “Watchdog state” if there has been no writing of the output within the set time.
DIGITAL OUTPUT WATCHDOG STATE (default Open) Sets the value that the digital output must adopt if the watchdog has been triggered.
DIGITAL OUTPUT WATCHDOG TIMEOUT [s] (default 100s) Represents the watchdog time of the digital output in seconds.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 22

User Manual

R SERIES

SETUP COUNTERS SECTION
COUNTERS FILTER [ms] (default 0) Sets the value in [ms] for filtering all the counters connected to the inputs.
P2P CONFIGURATION
In the P2P Client section it is possible to define which local events to send to one or more remote devices. This way it is possible to send the status of the inputs to the remote outputs and obtain the input-output replication without wiring. It is also possible to send the same input to several outputs simultaneously.
In the P2P Server section it is instead possible to define which inputs must be copied to the outputs.
The “Disable all rules” button places all the rules in a disabled status (default). The “APPLY” button allows you to confirm and then save the set rules in the non-volatile memory.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 23

User Manual

R SERIES

10. CONFIGURATION OF THE R-16DI-8DO DEVICE VIA WEB SERVER
SETUP SECTION

DHCP (ETH) (default: Disabled) Sets the DHCP client to get an IP address automatically.

IP ADDRESS STATIC (ETH) (default: 192.168.90.101) Sets the device static address. Careful not to enter devices with the same IP address into the same network. IP MASK STATIC (ETH) (default: 255.255.255.0) Sets the mask for the IP network.

GATEWAY ADDRESS STATIC (ETH) (default: 192.168.90.1) Sets the gateway address.

PROTECT CONFIGURATION (default: Disabled) Allows you to enable or disable password protection for reading and writing the configuration (including the IP address) using the Seneca Discovery Device software.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 24

User Manual

R SERIES

ATTENTION!
IF THE CONFIGURATION PROTECTION IS ENABLED IT WILL BE IMPOSSIBLE TO READ/WRITE THE CONFIGURATION OF THE DEVICE WITHOUT KNOWING THE PASSWORD.
IF THE PASSWORD HAS BEEN LOST, THE DEVICE CAN BE RETURNED TO ITS DEFAULT SETTINGS BY CONNECTING IT VIA USB TO THE EASY SETUP 2 SOFTWARE
MODBUS SERVER PORT (ETH) (default: 502) Sets the communication port for the Modbus TCP-IP server.
MODBUS SERVER STATION ADDRESS (ETH) (default: 1) Active only if Modbus Passthrough is also active, it sets the station address of the modbus TCP-IP server.

ATTENTION!
THE MODBUS SERVER WILL ANSWER ANY STATION ADDRESS ONLY IF THE MODBUS PASSTHROUGH MODE IS DISABLED.

MODBUS PASSTHROUGH (ETH) (default: disabled) Sets the conversion mode from Modbus TCP-IP to Modbus RTU serial (see chapter 5).

MODBUS TCP-IP CONNECTION TIMEOUT [sec] (ETH) (default: 60) Sets the TCP-IP connection timeout for the Modbus TCP-IP server and Passthrough modes.

P2P SERVER PORT (default: 50026) Sets the communication port for the P2P server.

WEB SERVER USER NAME (default: admin) Sets the user name to access the web server.

CONFIGURATION/WEB SERVER PASSWORD (default: admin) Sets the password to access the webserver and to read/write the configuration (if enabled).

WEB SERVER PORT (default: 80) Sets the communication port for the web server.

BAUDRATE MODBUS RTU (SER) (default: 38400 baud) Sets the baud rate for the RS485 communication port.

DATA MODBUS RTU (SER) (default: 8 bit) Sets the number of bits for the RS485 communication port.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 25

User Manual

R SERIES

PARITY MODBUS RTU (SER) (default: None) Sets the parity for the RS485 communication port.
STOP BIT MODBUS RTU (SER) (default: 1 bit) Sets the number of stop bits for the RS485 communication port.
MODBUS PASSTHROUGH SERIAL TIMEOUT (default: 100ms) Active only if passthrough mode is activated, sets the maximum waiting time before sending a new packet from TCP-IP to the serial port. It must be set according to the longest response time of all the devices present on the RS485 serial port.

ATTENTION!
THE USB PORT CONFIGURATION PARAMETERS CANNOT BE MODIFIED AND ARE BAUDRATE: 115200
DATA: 8 BIT PARITY: NONE
STOP BIT: 1 MODBUS RTU PROTOCOL

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 26

SETUP 2 SECTION

User Manual

R SERIES

COUNTERS FILTER (default: 100ms) Sets the filtering of the counters, the value is expressed in [ms]. The filter cut-off frequency corresponds to:

[] =

1000 2 []

For example, if the filter counter is 100ms the cutting frequency will be:

[] =

2

1000

[]

=

5

So all input frequencies greater than 5 Hz will be cut.

ATTENTION!
WHEN COUNTER FILTERING IS ACTIVE, THE SAME FILTER IS ALSO OBTAINED ON THE SINGLE DIGITAL INPUTS!

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 27

User Manual

R SERIES

INPUTS TYPE (default: Pnp “Source”) Sets the input/counter operating mode to between npn “Sink” and pnp “Source”.

COUNTER DIRECTION (default: Up) Sets the counting mode of the counters “forward”, up or back “down”. In the “Up” mode when the counter reaches the value:
= 232 – 1 = 4294967295

A subsequent increase will return the value to 0. In the “Down” mode, if the counter value is 0, a subsequent input pulse will return the value to 4294967295.

DIGITAL OUTPUT WATCHDOG (default: Disabled) Set whether the digital output watchdog is to activated. When enabled, if within the timeout time there has been no communication from the master to the device (Modbus serial communication, TCP-IP or USB or P2P communication) the outputs go into a Fail state. This mode makes it possible to obtain a secure system in the event of a master malfunction and its use is recommended in the case of radio type connections.

DIGITAL OUTPUTS WATCHDOG T.OUT [s] (default: 5 s) Sets the watchdog time of the digital outputs (valid only if the DIGITAL OUTPUT WATCHDOG parameter is enabled)

NORMALLY STATE/FAULT (default: normally Normally open (N.O.) and Normally closed (N.C.) state in case of fail They set the states of each of the outputs in normal conditions and in the event of a failure.

In the case of normally open (not energized)

writing in the Modbus “Outputs” register with 0 will cause

the relay not to energize, otherwise, in the case of normally closed (energized)

writing in the Modbus

“Outputs” register with 1 will determine the relay not to be energized.

In the case of “fail” the output will go into the selected configuration between not energized .

or energized

The “Configure” section allows you to save or open a complete configuration of the device. The “Firmware” section allows you to update the device firmware in order to obtain new functions.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 28

User Manual

R SERIES

11. CONFIGURATION OF THE R-8AI-8DIDO DEVICE VIA WEB SERVER
SETUP SECTION
DHCP (ETH) (default: Disabled) Sets the DHCP client to get an IP address automatically.
IP ADDRESS STATIC (ETH) (default: 192.168.90.101) Sets the device static address. Careful not to enter devices with the same IP address into the same network.
IP MASK STATIC (ETH) (default: 255.255.255.0) Sets the mask for the IP network.
GATEWAY ADDRESS STATIC (ETH) (default: 192.168.90.1) Sets the gateway address.
PROTECT CONFIGURATION (default: Disabled) Allows you to enable or disable password protection for reading and writing the configuration (including the IP address) using the Seneca Discovery Device software. The password is the same one that allows accessing the web server.

ATTENTION!
IF THE CONFIGURATION PROTECTION IS ENABLED IT WILL BE IMPOSSIBLE TO READ/WRITE THE CONFIGURATION OF THE DEVICE WITHOUT KNOWING THE PASSWORD.
IN THE EVENT OF LOSING THE PASSWORD IT WILL BE POSSIBLE TO RETURN THE DEVICE TO THE FACTORY CONFIGURATION (SEE CHAPTER 6)
MODBUS SERVER PORT (ETH) (default: 502) Sets the communication port for the Modbus TCP-IP server.
MODBUS SERVER STATION ADDRESS (ETH) (default: 1) Active only if Modbus Passthrough is also active, it sets the station address of the modbus TCP-IP server.

ATTENTION!
THE MODBUS SERVER WILL ANSWER ANY STATION ADDRESS ONLY IF THE MODBUS PASSTHROUGH MODE IS DISABLED.

MODBUS PASSTHROUGH (ETH) (default: disabled) Sets the conversion mode from Modbus TCP-IP to Modbus RTU serial (see chapter 5).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 29

User Manual

R SERIES

MODBUS TCP-IP CONNECTION TIMEOUT [sec] (ETH) (default: 60) Sets the TCP-IP connection timeout for the Modbus TCP-IP server and Passthrough modes.
P2P SERVER PORT (default: 50026) Sets the communication port for the P2P server.
WEB SERVER USERNAME (default: admin) Sets the username to access the webserver.
CONFIGURATION/WEB SERVER PASSWORD (default: admin) Sets the password to access the webserver and to read/write the configuration (if enabled).
WEB SERVER PORT (default: 80) Sets the communication port for the web server.
BAUDRATE MODBUS RTU (SER) (default: 38400 baud) Sets the baud rate for the RS485 communication port.
DATA MODBUS RTU (SER) (default: 8 bit) Sets the number of bits for the RS485 communication port.
PARITY MODBUS RTU (SER) (default: None) Sets the parity for the RS485 communication port.
STOP BIT MODBUS RTU (SER) (default: 1 bit) Sets the number of stop bits for the RS485 communication port.
MODBUS PASSTHROUGH SERIAL TIMEOUT (default: 100ms) Active only if Passthrough mode is activated, sets the maximum waiting time before sending a new packet from TCP-IP to the serial port. It must be set according to the longest response time of all the devices present on the RS485 serial port.
CHANNEL SAMPLE TIME [ms] (default: 100ms) Sets the sampling time of each analog input.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 30

User Manual

R SERIES

ATTENTION!
THE USB PORT CONFIGURATION PARAMETERS CANNOT BE MODIFIED AND ARE BAUDRATE: 115200
DATA: 8 BIT PARITY: NONE
STOP BIT: 1 MODBUS RTU PROTOCOL

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 31

User Manual

R SERIES

SETUP AIN 1. 8 SECTION
This section allows the configuration of the analog inputs present in the device.
ATTENTION!
THE DEVICE CAN DETECT THE COLD JOINT TEMPERATURE FROM THE INTERNAL SENSORS OR FROM ANALOG INPUT 1 (THROUGH EXTERNAL PT100-TYPE SENSOR).
IN THIS CASE ALL THE DETECTIONS OF THE INTERNAL SENSORS WILL BE REPLACED BY THE READING OF ANALOG INPUT 1.
ANALOG INPUT MODE (default +-30V) Set the type of measurement for the selected input.
It is possible to choose between the following types of input:
+-30V +-100mV +-24 mA Thermocouple PT100 2 wires (for use as a cold junction and only for input 1) PT100 3 wires (for use as a cold junction and only for input 1)
If the”IN2..8 CJ PT100″ type of measurement is selected for input 1, this will automatically be used as a measurement of the cold junction for all inputs configured by thermocouple between IN2 and IN8 included.
ANALOG INPUT 1 PT100 WIRE RESISTANCE [Ohm] (default 0 Ohm) (Only for analog input 1) allows to compensate the cable resistance in case of 2-wire connection to the PT100.
ANALOG INPUT TC TYPE (default J) In the case of thermocouple measurement, it allows to select the type of thermocouple between: J, K, R, S, T, B, E, N, L
ANALOG INPUT TEMPERATURE OFFSET (default 0°C) Sets a temperature offset in °C for thermocouple measurements
ANALOG INPUT ONBOARD COLD JUNCTION (default ENABLED) In the case of thermocouple measurement, it enables or disables the automatic cold junction offset of the device. If channel 1 has been configured as PT100 cold junction measurement, this sensor will be used for the offset and not the one inside the instrument.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 32

User Manual

R SERIES

ANALOG INPUT COLD JUCTION VALUE [°C] (default 0°C) In the case of thermocouple measurement, if the automatic measurement of the cold junction has been deactivated, it is possible to manually enter the cold junction temperature.
ANALOG INPUT BURNOUT MODE (default FAIL VALUE) In the case of thermocouple measurement, it selects the behaviour in case of sensor failure: In the case of “Last Value” the value is stopped at the last valid value, in the case of “Fail Value” the “Burnout” value is loaded in the registers.
ANALOG INPUT BURNOUT VALUE (default 10000°C) In the case of thermocouple measurement, if the ANALOG INPUT BURNOUT MODE = “FAIL VALUE” mode is activated and the sensor is in the “burn” state, it allows you to set a value in °C to be taken by the measurement register.
ANALOG INPUT UNIT MEASURE (default °C) In the case of thermocouple measurement, it allows you to set the measurement unit of the measurement register between °C, K, °F and mV.
ANALOG INPUT FILTER [samples] (default 0) Allows you to set the moving average filter with the selected number of samples. If the value is “0” the filter is disabled.
ANALOG INPUT START SCALE Represents the start of the electrical scale of the analog measurement used for the register of the engineering measurement.
ANALOG INPUT STOP SCALE Represents the electrical full scale of the analog measurement used for the engineering measurement register.
ANALOG INPUT ENG START SCALE Represents the value of the engineering measurement register when the input reaches the value shown in the ANALOG INPUT START SCALE parameter. For example if: ANALOG INPUT START SCALE = 4mA ANALOG INPUT STOP SCALE = 20mA ANALOG INPUT ENG STOP SCALE = -200 metres ANALOG INPUT ENG START SCALE = 200 metres
With a 12 mA input the engineering value will be 0 metres.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 33

User Manual

R SERIES

ANALOG INPUT ENG STOP SCALE It represents the value of the engineering measurement register when the input reaches the value shown in the ANALOG INPUT STOP SCALE parameter.
For example if: ANALOG INPUT START SCALE = 4mA ANALOG INPUT STOP SCALE = 20mA ANALOG INPUT ENG STOP SCALE = -200 metres ANALOG INPUT ENG START SCALE = 200 metres
With a 12 mA input the engineering value will be 0 metres.
DIGITAL I/O SETUP SECTION
This section allows the configuration of the digital I/Os present in the device.
DIGITAL I/O MODE (default Input) Selects whether the chosen terminal will work as an input or output.
DIGITAL INPUT NORMALLY HIGH/LOW (default Normally Low) If selected as digital input, it configures whether the input is normally high or low.
DIGITAL OUTPUT NORMALLY STATE (default Normally Open) If selected as digital output, it configures whether the output is normally open or closed.
DIGITAL OUTPUT WATCHDOG (default Disabled) If selected as digital output, it sets the output watchdog mode. If “Disabled”, it disables the watchdog function for the selected output. If “Enabled on Modbus Communication” the output goes into “Watchdog state” if there has been no generic Modbus communication within the set time. If “Enabled on Modbus Digital Output Writing” the output goes into “Watchdog state” if there has been no writing of the output within the set time.
DIGITAL OUTPUT WATCHDOG STATE (default Open) Sets the value that the digital output must adopt if the watchdog has been triggered.
DIGITAL OUTPUT WATCHDOG TIMEOUT [s] (default 100s) Represents the watchdog time of the digital output in seconds.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 34

User Manual

R SERIES

EVENT SETUP SECTION

This section allows the configuration of events to send analog values with the P2P protocol. EVENT AIN MODE (Default: DISABLED) Represents the event condition for sending packets linked to the analog inputs in the P2P protocol. It may be: “Disabled” the sending event of the analog packet is disabled “Event when AIN > HIGH THRESHOLD” the packet sending event occurs when the analog input exceeds the “High” threshold set.
“Event when AIN < LOW THRESHOLD” the packet sending event occurs when the analog input is lower than the “Low” threshold set.
EVENT AIN HIGH THRESHOLD (Default: 0) Threshold value linked to the “High” event.
EVENT AIN LOW THRESHOLD (Default: 0) Threshold value linked to the “Low” event.
EVENT AIN HISTERESYS Hysteresis value for the reset of the “event” condition. For example, if the event is configured in “Event when AIN > HIGH THRESHOLD” mode, when the analog input exceeds the threshold value, the packet will be sent, to send the next packet it will be necessary for the analog value to fall below the value (EVENT AIN HIGH THRESHOLD + EVENT AIN HYSTERESIS) and then to rise above the HIGH value again.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 35

User Manual

R SERIES

12. CONFIGURATION OF THE R- SG3 DEVICE VIA WEB SERVER
SETUP SECTION
DHCP (ETH) (default: Disabled) Sets the DHCP client to get an IP address automatically.
IP ADDRESS STATIC (ETH) (default: 192.168.90.101) Sets the device static address. Careful not to enter devices with the same IP address into the same network.
IP MASK STATIC (ETH) (default: 255.255.255.0) Sets the mask for the IP network.
GATEWAY ADDRESS STATIC (ETH) (default: 192.168.90.1) Sets the gateway address.
MODBUS SERVER PORT (ETH) (default: 502) Sets the communication port for the Modbus TCP-IP server.
MODBUS SERVER STATION ADDRESS (ETH) (default: 1) Active only if Modbus Passthrough is also active, it sets the station address of the modbus TCP-IP server.

ATTENTION!
THE MODBUS SERVER WILL ANSWER ANY STATION ADDRESS ONLY IF THE MODBUS PASSTHROUGH MODE IS DISABLED.

MODBUS PASSTHROUGH (ETH) (default: disabled) Sets the conversion mode from Modbus TCP-IP to Modbus RTU serial (see chapter 5).

MODBUS TCP-IP CONNECTION TIMEOUT [sec] (ETH) (default: 60) Sets the TCP-IP connection timeout for the Modbus TCP-IP server and Passthrough modes.

P2P SERVER PORT (default: 50026) Sets the communication port for the P2P server.

WEB SERVER USERNAME (default: admin) Sets the username to access the webserver.

CONFIGURATION/WEB SERVER PASSWORD (default: admin) Sets the password to access the webserver and to read/write the configuration (if enabled).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 36

User Manual

R SERIES

WEB SERVER PORT (default: 80) Sets the communication port for the web server.
BAUDRATE MODBUS RTU (SER) (default: 38400 baud) Sets the baud rate for the RS485 communication port.
DATA MODBUS RTU (SER) (default: 8 bit) Sets the number of bits for the RS485 communication port.
PARITY MODBUS RTU (SER) (default: None) Sets the parity for the RS485 communication port.
STOP BIT MODBUS RTU (SER) (default: 1 bit) Sets the number of stop bits for the RS485 communication port.
MODBUS PASSTHROUGH SERIAL TIMEOUT (default: 100ms) Active only if Passthrough mode is activated, sets the maximum waiting time before sending a new packet from TCP-IP to the serial port. It must be set according to the longest response time of all the devices present on the RS485 serial port.

LOAD CELL SETUP SECTION
FUNCTION MODE It allows to configure the basic operation of the device, can be set to factory calibration or to Calibration with standard weight.
FACTORY CALIBRATION It is used when a load cell with declared sensitivity is available. In this mode, calibration only consists in acquiring the tare directly in the field with a direct measurement. If it is not possible to acquire the tare with a direct measurement (for example in the case of an already filled silo) it is possible to manually enter the tare value in the desired unit of measurement (kg, t, etc.).
CALIBRATION WITH STANDARD WEIGHT It is used when a sample weight is available (as far as possible towards the load cell full scale). In this mode the calibration consists in acquiring both the tare and the sample weight directly on the field.
MEASURE TYPE It allows to configure the operation of the device between:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 37

User Manual

R SERIES

BALANCE (UNIPOLAR) It is used when a scale is being created in which the load cell is only compressed, in this case the maximum resolution of the compression measurement is obtained.

COMPRESSION AND TRACTION (BIPOLAR) It is used when a measurement system (typically of force) is being created that can both compress and extend the load cell. In this case the direction of the force can also be decided, if compression the measurement will have the + sign, if traction it will have the – sign. A typical case of use is to link the direction of the force to the analog output so that, for example, 4mA correspond to the maximum traction force and 20mA correspond to the maximum compression force (in this case the cell at rest will provide 12Ma).

MEASURE UNIT Sets the unit of measurement for the weighing in g, Kg, t etc.

CELL SENSITIVITY It is the declared cell value sensitivity expressed in mV/V (in most cells it is 2mV/V).

CELL FULL SCALE It is the full scale value of the cell expressed in the selected unit of measurement.

STANDARD WEIGHT VALUE It represents the value of the sample weight that will be used in the calibration if the operating mode with standard weight has been chosen.

NOISE FILTER Enables or disables measurement filtering.

FILTER LEVEL Allows you to set the measurement filter level according to the following table:

FILTER LEVEL 0 1 2 3 4 5 6
ADVANCED

RESPONSE TIME [ms] 2 6.7 13 30 50 250 850
Configurable

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 38

User Manual

R SERIES

The higher the filter level the more stable (but slow) the weight measurement will be.
If you select the advanced filtering level (Advanced), the configuration will allow you to select the following parameters:
ADC SPEED Selects the ADC acquisition speed from 4.7 Hz to 960 Hz
NOISE VARIATION It is the variation in ADC points due to noise alone (represents the measurement uncertainty due to noise) or how much we expect the measurement to vary (the unit of measurement is in raw ADC points).
FILTER RESPONSE SPEED Represents a parameter related to the filter response speed, it can vary from 0.001 (slowest response) to 1 (fastest response). Represents the variance of the process.
NET WEIGHT RESOLUTION It is the resolution with which the value of the net weighing is represented, it can be worth:
MAXIMUM RESOLUTION It will represent the net weight with the highest possible resolution
MANUAL It will represent the net weight with the manual resolution set (in engineering units). For example, by setting 0.1 Kg you will get that the net weight can only vary by multiples of 100g.
AUTOMATIC RESOLUTION It will represent the net weight with a calculated resolution of about 20000 points. Unlike Maximum or Manual resolution, this setting limits also the ADC value and therefore affects all measurements.

CAUTION
Keep in mind that in the “Calibration with sample weight” mode, using the “Manual Resolution”, the correct sample weight value may not be perfectly represented:

Cell full scale 15000 g Sample weight 14000 g Manual Resolution 1.5 g

For example, you have:

The value of the sample weight (14000 g) cannot be represented with the resolution in 1.5g steps (14000/1.5g = 9333.333 is not an integer value) so it will be represented as: 9333*1.5g = 13999.5g To avoid this effect, use a resolution that allows the value to be represented (for example 1g or 2g).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 39

User Manual

R SERIES

SAMPLE PIECE WEIGHT

Sets the weight of a single piece in technical units for the mode. By setting the net weight of a single element in this register, the converter will be able to indicate the number of pieces present in the scales special register according to the relation:

=

AUTOMATIC TARE TRACKER It allows you to enable or disable the automatic tare reset.
ADC VALUE It allows to set the number of ADC points within which to reset the tare automatically. If after 5 seconds of stable weighing condition the ADC value of the net weight deviates by less than this value then a new tare is acquired.

I/O SETUP SECTION
DIGITAL I/O MODE Configures the digital I/O of the device
DIGITAL INPUT If the nth IO is configured as an input, it is possible to choose its function from:
FUNCTION DIGITAL INPUT The input is configured as a digital input whose value can be read from the appropriate register.
FUNCTION ACQUIRE TARE In this mode, if the digital input is activated for a time longer than 3 seconds, a new tare value is acquired (in RAM, then it is lost upon restart). It is equivalent to sending the command 49594 (decimal) in the command register.

DIGITAL OUTPUT If the nth IO is configured as an output, it is possible to choose its function from:

DIGITAL OUTPUT MODE The output can be configured as normally open (Normally Open) or as normally closed (Normally Close).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 40

User Manual

R SERIES

DIGITAL OUTPUT CONFIGURATION Here you can choose the behaviour of the digital output:

STABLE WEIGHT The stable weighing condition is used to indicate that the net weight measurement is stable if:

The net weight remains within the weight _ over time or if the

slope of the curve drawn by the net weight is less than

_

:

You will be prompted to enter Delta Net Weight (Delta Weight) (in engineering units) and Delta Time (Delta Time) (in 0.1 seconds).
THRESHOLD AND STABLE WEIGHT
In this mode, the output activates when the net weight reaches the threshold and the weigh is in a stable weighing condition.

STABLE WEIGHT

In this mode the output is activated if the weighing is in the stable weighing condition.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 41

User Manual

R SERIES

COMMANDABLE FROM MODBUS In this mode the output can be controlled by the modbus register.
THRESHOLD WITH HYSTERESIS In this mode the output is activated when the net weight reaches the threshold, the alarm is cancelled when the net weight falls below the Threshold-Hysteresis value:

STABLE WEIGHT CONDITION

The stable weighing condition is used to indicate that the net weight measurement is stable if:

The net weight remains within the weight _ (DELAT WEIGHT) over time (DELTA TIME)

or if the slope of the curve drawn by the net weight is less than

_

:

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 42

User Manual

R SERIES

TEST AND LOAD CELL CALIBRATION SECTION
In this section it is possible to calibrate the cell and carry out the tests. For more information on cell calibration refer to the Cell Calibration chapter of this manual.
P2P CONFIGURATION
In the P2P Client section it is possible to define which local events to send to one or more remote devices. This way it is possible to send the status of the inputs to the remote outputs and obtain the input-output replication without wiring. It is also possible to send the same input to several outputs simultaneously.
In the P2P Server section it is instead possible to define which inputs must be copied to the outputs.
The “Disable all rules” button places all the rules in a disabled status (default). The “APPLY” button allows you to confirm and then save the set rules in the non-volatile memory.

LOAD CELL CALIBRATION THROUGH THE WEB SERVER
To calibrate the load cell, access the “TEST AND LOAD CELL CALIBRATION” section of the web server. Depending on the two modes chosen between factory calibration or with standard weight, it will be possible to proceed with the calibration.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 43

User Manual

R SERIES

CELL CALIBRATION WITH FACTORY PARAMETERS
In cell calibration with factory parameters it is not necessary to use a standard weight as reference is made to the parameters acquired in the factory. The necessary data are:
-The cell sensitivity -The cell full scale
For the cell calibration procedure it is necessary to acquire the tare. The tare can be entered manually in technical units (if known) or it can be acquired from the field.
ATTENTION!
TO OBTAIN A BETTER MEASUREMENT ACCURACY ACQUIRE THE TARE FROM THE FIELD
12.6.1.1. MANUAL ENTRY OF THE TARE VIA WEB SERVER
It is not always possible to acquire the tare value from the field (for example in the case of already filled silos), in these cases it is possible to introduce the tare weight in technical units.

To acquire the tare value, press the “SET MANUAL TARE (FLASH)” button
12.6.1.2. ACQUISITION OF THE TARE FROM THE FIELD VIA WEB SERVER

  1. Enter the “Test and load cell calibration” web server page 2) Replace the tare on the cell 3) Wait for the measurement to stabilize 4) Press the “TARE ACQUISITION (FLASH)” button

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 44

User Manual

R SERIES

CELL CALIBRATION WITH A SAMPLE WEIGHT In cell calibration with a standard weight it is necessary to know: -The cell sensitivity -The cell full scale -A standard weight (so that Standard weight + Tare are as close as possible to the cell full scale)

  1. Enter the “Test and load cell calibration” web server page 2) Replace the tare on the cell 3) Wait for the measurement to stabilize 4) Press the “TARE ACQUISITION (FLASH)” button 5)
  2. Replace the Tare + Standard Weight 7) Wait for the measurement to stabilize
  3. Press the “STANDARD WEIGHT ACQUISITION (FLASH)” button

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 45

13. P2P CLIENT

User Manual

R SERIES

The “Automatic configuration” button allows you to prepare the rules for sending all the inputs available in the device in use.

En. Selects whether the copy rule is active or not.

Loc. Ch. Selects the status of which channel should be sent to the remote device(s).

Remote IP Selects the IP address of the remote device to which the status of that input channel is to be sent. If the channel has to be sent simultaneously to all the devices (broadcast), enter the broadcast address (255.255.255.255) as the IP address.

Remote Port Selects the communication port for sending the status of the inputs. It must coincide with the P2P SERVER PORT parameter of the remote device.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 46

User Manual

R SERIES

En Selects operation in “Only Timed” or “Timed+Event” mode. In “Only Timed” mode, the status of the inputs is sent on each “tick [ms]” and then refreshed continuously (cyclic sending). In the “Timed+Event” mode, the status of the inputs is sent to a digital event (change of status).
Tick [ms] Sets the cyclical sending time of the input status.
ATTENTION!
IN CASE OF ENABLED WATCHDOG OF DIGITAL OUTPUTS THE RULE’S TICK TIME MUST BE LOWER THAN THE WATCHDOG TIMEOUT SET
ATTENTION!
IT IS ALSO POSSIBLE TO COPY SOME I/O OF THE SAME DEVICE (FOR EXAMPLE, COPY THE I01 INPUT TO D01) BY ENTERING THE IP OF THE DEVICE AS REMOTE IP

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 47

14. P2P SERVER

User Manual

R SERIES

The “Automatic configuration” button allows you to prepare the rules to receive all the inputs on the outputs of the device in use.
En. Selects whether the copy rule is active or not.
Rem. Ch. Selects the status of which remote channel should be received by the local device.
Remote IP Selects the IP address of the remote device from which to receive the input status. If the channel must be received simultaneously by all the devices (broadcast), enter the broadcast address (255.255.255.255) as the IP address.
Loc. Ch. Selects the copy destination of the remote input value.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 48

User Manual

R SERIES

ATTENTION!
IT IS ALSO POSSIBLE TO COPY SOME I/O OF THE SAME DEVICE (FOR EXAMPLE, COPY THE I01 INPUT TO D01) BY ENTERING THE IP OF THE DEVICE AS REMOTE IP. HOWEVER, THE ETHERNET
PORT MUST BE CORRECTLY CONNECTED.
P2P CONFIGURATION EXAMPLE
In the following example we have No.2 devices and we want to copy the status of digital input 1 of the first to the digital output of the second. The IP address of Device 1 is 192.168.1.10 The IP address of Device 2 is 192.168.1.11
Let’s move to device 1 with IP address 192.168.1.10 and select the sending of digital input 1 to the remote address 192.168.1.11 of device 2 this way:
DEVICE 1

Now let’s move on to device 2 and first configure the P2P server communication port on 50026:

And we now configure the P2P server, the channel to be received from 192.168.1.10 is Di_1 and must be copied to Do_1:
DEVICE 2

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 49

User Manual

R SERIES

With this configuration, each time digital input 1 of device 1 (192.168.1.10) changes status, a packet will be sent to device 2 (192.168.1.11) which will copy it to digital output 1. After 1 second, the same packet will be sent cyclically.
P2P EXECUTION TIME The switching time depends on the client device model and the server device model in addition to the congestion of the ethernet network. For example, for the R-16DI8DO model, the switching time of the remote digital output as a response to an incoming event into another R-16DI8DO is about 20 ms (daisy chain connection of 2 devices, 1 set rule). As regards the analog models, the refresh time of the digital inputs/outputs and analog inputs typical of the device must also be considered.
15. MODBUS PASSTHROUGH
Thanks to the Modbus Passthrough function it is possible to extend the amount of I/O available in the device via the RS485 port and the Modbus RTU slave protocol, for example by using the Seneca Z-PC series products. In this mode the RS485 port stops working as Modbus RTU slave and the device becomes a Modbus TCP-IP gateway to Modbus RTU serial:

Each Modbus TCP-IP request with station address other than that of the R series device is converted into a serial packet on the RS485 and, in the case of a reply, it is turned over to TCP-IP. Therefore, it is no longer necessary to purchase gateways to extend the I/O number or to connect already available Modbus RTU I/O.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 50

User Manual

R SERIES

16. UPDATING THE FIRMWARE AND SAVING/OPENING A CONFIGURATION
The firmware update can be performed via the web server in the appropriate section. Via the web server it is possible to save or open a saved configuration.
ATTENTION!
NOT TO DAMAGE THE DEVICE DO NOT REMOVE THE POWER SUPPLY DURING THE FIRMWARE UPDATE OPERATION.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 51

User Manual

R SERIES

17. MODBUS RTU/ MODBUS TCP-IP REGISTERS

The following abbreviations are used in the register tables:

MS LS MSBIT LSBIT MMSW MSW LSW LLSW RO RW
RW*
UNSIGNED 16 BIT SIGNED 16 BIT
UNSIGNED 32 BIT SIGNED 32 BIT
UNSIGNED 64 BIT SIGNED 64 BIT
FLOAT 32 BIT
BIT

Most Significant Least Significant Most Significant Bit Least Significant Bit “Most” Most Significant Word (16bit) Most Significant Word (16bit) Least Significant Word (16bit) “Least” Least Significant Word (16bit) Read Only Register in RAM or Fe-RAM Writable infinite times. Flash Read-Write: REGISTERS CONTAINED IN THE FLASH MEMORY: WRITABLE AT THE MAXIMUM ABOUT 10000 TIMES. Unsigned integer register that can take values from 0 to 65535 Signed integer register that can take values from -32768 to +32767 Unsigned integer register that can take values from 0 to +4294967296 Signed integer register that can take values from -2147483648 to 2147483647 Unsigned integer register that can take values from 0 to 18.446.744.073.709.551.615 Signed integer register that can take values from -2^63 to 2^63-1 Single-precision, 32-bit floating point register (IEEE 754) https://en.wikipedia.org/wiki/IEEE_754 Boolean register, which can take values 0 (false) or 1 (true)

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 52

User Manual

R SERIES

NUMBERING OF “0-BASED” OR “1-BASED” MODBUS ADDRESSES
According to the Modbus standard the Holding Registers are addressable from 0 to 65535, there are 2 different conventions for numbering the addresses: “0-BASED” and “1-BASED”. For greater clarity, Seneca shows its register tables in both conventions.

ATTENTION!
CAREFULLY READ THE DOCUMENTATION OF THE MODBUS MASTER DEVICE IN ORDER TO UNDERSTAND WHICH OF THE TWO CONVENTIONS THE MANUFACTURER HAS DECIDED TO USE
NUMBERING OF MODBUS ADDRESSES WITH “0-BASED” CONVENTION
The numbering is:

HOLDING REGISTER MODBUS ADDRESS (OFFSET) 0 1 2 3 4

MEANING
FIRST REGISTER SECOND REGISTER THIRD REGISTER FOURTH REGISTER
FIFTH REGISTER

Therefore, the first register is at address 0. In the following tables, this convention is indicated with “ADDRESS OFFSET”.

NUMBERING OF MODBUS ADDRESSES WITH “1 BASED” CONVENTION (STANDARD) The numbering is that established by the Modbus consortium and is of the type:

HOLDING REGISTER MODBUS ADDRESS 4x 40001 40002 40003 40004 40005

MEANING
FIRST REGISTER SECOND REGISTER THIRD REGISTER FOURTH REGISTER
FIFTH REGISTER

In the following tables this convention is indicated with “ADDRESS 4x” since a 4 is added to the address so that the first Modbus register is 40001.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 53

User Manual

R SERIES

A further convention is also possible where the number 4 is omitted in front of the register address:

HOLDING MODBUS ADDRESS WITHOUT 4x 1 2 3 4 5

MEANING
FIRST REGISTER SECOND REGISTER THIRD REGISTER FOURTH REGISTER
FIFTH REGISTER

BIT CONVENTION WITHIN A MODBUS HOLDING REGISTER A Modbus Holding Register consists of 16 bits with the following convention:
BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
For instance, if the value of the register in decimal is 12300 the value 12300 in hexadecimal is: 0x300C

the hexadecimal 0x300C in binary value is: 11 0000 0000 1100

So, using the above convention, we get:

BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1 0 0
MSB and LSB BYTE CONVENTION WITHIN A MODBUS HOLDING REGISTER
A Modbus Holding Register consists of 16 bits with the following convention:

BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

LSB Byte (Least Significant Byte) defines the 8 bits ranging from Bit 0 to Bit 7 included, we define MSB Byte (Most Significant Byte) the 8 bits ranging from Bit 8 to Bit 15 inclusive:

BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

BYTE MSB

BYTE LSB

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 54

User Manual

R SERIES

REPRESENTATION OF A 32-BIT VALUE IN TWO CONSECUTIVE MODBUS HOLDING REGISTERS
The representation of a 32-bit value in the Modbus Holding Registers is made using 2 consecutive Holding Registers (a Holding Register is a 16-bit register). To obtain the 32-bit value it is therefore necessary to read two consecutive registers: For example, if register 40064 contains the 16 most significant bits (MSW) while register 40065 contains the least significant 16 bits (LSW), the 32-bit value is obtained by composing the 2 registers:
BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
40064 MOST SIGNIFICANT WORD
BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
40065 LEAST SIGNIFICANT WORD
32 = + ( 65536)
In the reading registers it is possible to swap the most significant word with the least significant word, therefore it is possible to obtain 40064 as LSW and 40065 as MSW.

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 55

User Manual

R SERIES

TYPE OF 32-BIT FLOATING POINT DATA (IEEE 754)
The IEEE 754 standard (https://en.wikipedia.org/wiki/IEEE_754) defines the format for representing floating
point numbers.
As already mentioned, since it is a 32-bit data type, its representation occupies two 16-bit holding registers. To obtain a binary/hexadecimal conversion of a floating point value it is possible to refer to an online converter at this address:
http://www.h-schmidt.net/FloatConverter/IEEE754.html

Using the last representation the value 2.54 is represented at 32 bits as:
0x40228F5C
Since we have 16-bit registers available, the value must be divided into MSW and LSW:
0x4022 (16418 decimal) are the 16 most significant bits (MSW) while 0x8F5C (36700 decimal) are the 16 least significant bits (LSW).

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 56

User Manual

SUPPORTED MODBUS COMMUNICATION PROTOCOLS

The Modbus communication protocols supported are:
Modbus RTU Slave (from the RS485 port) Modbus TCP-IP Server (from Ethernet ports) 8 clients max

SUPPORTED MODBUS FUNCTION CODES

The following Modbus functions are supported:

Read Holding Register Read Coil Status Write Coil Write Multiple Coil Write Single Register Write Multiple Registers

(function 3) (function 1) (function 5) (function 15) (function 6) (function 16)

ATTENTION!
All 32-bit values are contained in 2 consecutive registers

R SERIES

ATTENTION!
Any registers with RW* (in flash memory) can be written up to 10000 times The PLC/Master Modbus programmer must not exceed this limit

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 57

User Manual

R SERIES

18. MODBUS REGISTER TABLE FOR THE R-32DIDO PRODUCT

R-32DIDO: MODBUS 4X HOLDING REGISTERS TABLE (FUNCTION CODE 3)

ADDRESS OFFSET

(4x)

(4x)

REGISTER

CHANNEL

DESCRIPTION

W/R

TYPE

40001

0

MACHINE-ID

Device identification

RO

UNSIGNED 16 BIT

40002

1

FW REVISION (Maior/Minor)

Fw Revision

RO

UNSIGNED 16 BIT

40003

2

FW REVISION (Fix/Build)

Fw Revision

RO

UNSIGNED 16 BIT

40004

3

FW CODE

Fw Code

RO

UNSIGNED 16 BIT

40005

4

RESERVED

RO

UNSIGNED 16 BIT

40006

5

RESERVED

RO

UNSIGNED 16 BIT

40007

6

BOARD-ID

Hw Revision

RO

UNSIGNED 16 BIT

40008

7

BOOT REVISION (Maior/Minor)

Bootloader Revision

RO

UNSIGNED 16 BIT

40009

8

BOOT REVISION (Fix/Build)

Bootloader Revision

RO

UNSIGNED 16 BIT

40010

9

RESERVED

RO

UNSIGNED 16 BIT

40011

10

RESERVED

RO

UNSIGNED 16 BIT

40012

11

RESERVED

RO

UNSIGNED 16 BIT

40013

12

COMMAND_AUX _3H

Aux Command Register

RW

UNSIGNED 16 BIT

40014

13

COMMAND_AUX _3L

Aux Command Register

RW

UNSIGNED 16 BIT

40015

14

COMMAND_AUX 2

Aux Command Register

RW

UNSIGNED 16 BIT

40016

15

COMMAND_AUX 1

Aux Command Register

RW

UNSIGNED 16 BIT

40017

16

COMMAND

Aux Command Register

RW

UNSIGNED 16 BIT

40018

17

STATUS

Device Status

RW

UNSIGNED 16 BIT

40019

18

RESERVED

RW

UNSIGNED 16 BIT

40020

19

RESERVED

RW

UNSIGNED 16 BIT

40021

20

DIGITAL I/O

16..1

Digital IO Value [Channel 16…1]

RW

UNSIGNED 16 BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 58

User Manual

R SERIES

ADDRESS OFFSET

(4x)

(4x)

40022

21

REGISTER DIGITAL I/O

CHANNEL

DESCRIPTION

W/R

TYPE

32..17

Digital IO Value [Channel 32…17]

RW

UNSIGNED 16 BIT

ADDRESS OFFEST

REGISTER

CHANNEL

DESCRIPTION

W/R

TYPE

(4x)

(4x)

40101 40102

100

COUNTER MSW DIN

101

COUNTER LSW DIN

1

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40103 40104

102

COUNTER MSW DIN

103

COUNTER LSW DIN

2

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40105 40106

104

COUNTER MSW DIN

105

COUNTER LSW DIN

3

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40107 40108

106

COUNTER MSW DIN

107

COUNTER LSW DIN

4

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40109 40110

108

COUNTER MSW DIN

109

COUNTER LSW DIN

5

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40111 40112

110

COUNTER MSW DIN

111

COUNTER LSW DIN

6

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40113 40114

112

COUNTER MSW DIN

113

COUNTER LSW DIN

7

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40115 40116

114

COUNTER MSW DIN

115

COUNTER LSW DIN

8

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40117 40118

116

COUNTER MSW DIN

117

COUNTER LSW DIN

9

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40119 40120

118

COUNTER MSW DIN

119

COUNTER LSW DIN

10

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 59

User Manual

R SERIES

ADDRESS OFFEST

REGISTER

CHANNEL

DESCRIPTION

W/R

TYPE

(4x)

(4x)

40121 40122

120

COUNTER MSW DIN

121

COUNTER LSW DIN

11

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40123 40124

122

COUNTER MSW DIN

123

COUNTER LSW DIN

12

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40125 40126

124

COUNTER MSW DIN

125

COUNTER LSW DIN

13

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40127 40128

126

COUNTER MSW DIN

127

COUNTER LSW DIN

14

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40129 40130

128

COUNTER MSW DIN

129

COUNTER LSW DIN

15

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40131 40132

130

COUNTER MSW DIN

131

COUNTER LSW DIN

16

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40133 40134

132

COUNTER MSW DIN

133

COUNTER LSW DIN

17

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40135 40136

134

COUNTER MSW DIN

135

COUNTER LSW DIN

18

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40137 40138

136

COUNTER MSW DIN

137

COUNTER LSW DIN

19

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40139 40140

138

COUNTER MSW DIN

139

COUNTER LSW DIN

20

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40141 40142

140

COUNTER MSW DIN

141

COUNTER LSW DIN

21

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

40143

142

COUNTER MSW DIN

22

CHANNEL COUNTER VALUE

RW

UNSIGNED 32 BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 60

User Manual

R SERIES

ADDRESS (4x)
40144

OFFEST (4x)
143

40145

144

40146

145

40147

146

40148

147

40149

148

40150

149

40151

150

40152

151

40153

152

40154

153

40155

154

40156

155

40157

156

40158

157

40159

158

40160

159

40161

160

40162

161

40163

162

40164

163

40165

164

40166

165

40167

166

40168

167

REGISTER
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
COUNTER MSW DIN
COUNTER LSW DIN
PERIOD
PERIOD

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

CHANNEL

DESCRIPTION

W/R

TYPE

RW

23

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

24

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

25

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

26

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

27

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

28

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

29

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

30

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

31

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

32

CHANNEL COUNTER RW UNSIGNED

VALUE

RW

32 BIT

RW

1

PERIOD [ms]

FLOAT 32 BIT

RW

RW

2

PERIOD [ms]

FLOAT 32 BIT

RW

www.seneca.it

Doc: MI-00604-10-EN

Page 61

User Manual

R SERIES

ADDRESS (4x) 40169 40170 40171 40172 40173 40174 40175 40176 40177 40178 40179 40180 40181 40182 40183 40184 40185 40186 40187 40188 40189 40190 40191 40192 40193 40194 40195 40196 40197 40198 40199 40200 40201 40202 40203 40204 40205 40206 40207 40208 40209

OFFEST (4x) 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208

REGISTER PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

CHANNEL 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

DESCRIPTION PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms]

W/R

TYPE

RW FLOAT 32 BIT
RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW FLOAT 32 BIT

www.seneca.it

Doc: MI-00604-10-EN

Page 62

User Manual

R SERIES

ADDRESS (4x) 40210 40211 40212 40213 40214 40215 40216 40217 40218 40219 40220 40221 40222 40223 40224 40225 40226 40227 40228 40229 40230 40231 40232 40233 40234 40235 40236 40237 40238 40239 40240 40241 40242 40243 40244 40245 40246 40247 40248 40249 40250

OFFEST (4x) 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249

REGISTER
PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD PERIOD FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

CHANNEL
24 25 26 27 28 29 30 31 32 1 2 3 4 5 6 7 8 9 10 11

DESCRIPTION
PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] PERIOD [ms] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz]

W/R

TYPE

RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW

www.seneca.it

Doc: MI-00604-10-EN

Page 63

User Manual

R SERIES

ADDRESS (4x) 40251 40252 40253 40254 40255 40256 40257 40258 40259 40260 40261 40262 40263 40264 40265 40266 40267 40268 40269 40270 40271 40272 40273 40274 40275 40276 40277 40278 40279 40280 40281 40282 40283 40284 40285 40286 40287 40288 40289 40290 40291

OFFEST (4x) 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290

REGISTER FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

CHANNEL 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

DESCRIPTION FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz] FREQUENCY [Hz]

W/R

TYPE

RW FLOAT 32 BIT
RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW
FLOAT 32 BIT RW RW FLOAT 32 BIT

www.seneca.it

Doc: MI-00604-10-EN

Page 64

User Manual

R SERIES

ADDRESS OFFEST

REGISTER

CHANNEL

DESCRIPTION

W/R

TYPE

(4x)

(4x)

40292

291

RW

R-32DIDO: TABLE OF MODBUS REGISTERS 0x COIL STATUS (FUNCTION CODE 1)

ADDRESS (0x) ADDRESS (0x) OFFSET REGISTER CHANNEL DESCRIPTION W/R

1

0

DIGITAL I/O

1

DIGITAL I/O RW

2

1

DIGITAL I/O

2

DIGITAL I/O RW

3

2

DIGITAL I/O

3

DIGITAL I/O RW

4

3

DIGITAL I/O

4

DIGITAL I/O RW

5

4

DIGITAL I/O

5

DIGITAL I/O RW

6

5

DIGITAL I/O

6

DIGITAL I/O RW

7

6

DIGITAL I/O

7

DIGITAL I/O RW

8

7

DIGITAL I/O

8

DIGITAL I/O RW

9

8

DIGITAL I/O

9

DIGITAL I/O RW

10

9

DIGITAL I/O

10

DIGITAL I/O RW

11

10

DIGITAL I/O

11

DIGITAL I/O RW

12

11

DIGITAL I/O

12

DIGITAL I/O RW

13

12

DIGITAL I/O

13

DIGITAL I/O RW

14

13

DIGITAL I/O

14

DIGITAL I/O RW

15

14

DIGITAL I/O

15

DIGITAL I/O RW

16

15

DIGITAL I/O

16

DIGITAL I/O RW

17

16

DIGITAL I/O

17

DIGITAL I/O RW

18

17

DIGITAL I/O

18

DIGITAL I/O RW

19

18

DIGITAL I/O

19

DIGITAL I/O RW

20

19

DIGITAL I/O

20

DIGITAL I/O RW

21

20

DIGITAL I/O

21

DIGITAL I/O RW

22

21

DIGITAL I/O

22

DIGITAL I/O RW

23

22

DIGITAL I/O

23

DIGITAL I/O RW

24

23

DIGITAL I/O

24

DIGITAL I/O RW

25

24

DIGITAL I/O

25

DIGITAL I/O RW

26

25

DIGITAL I/O

26

DIGITAL I/O RW

27

26

DIGITAL I/O

27

DIGITAL I/O RW

28

27

DIGITAL I/O

28

DIGITAL I/O RW

29

28

DIGITAL I/O

29

DIGITAL I/O RW

30

29

DIGITAL I/O

30

DIGITAL I/O RW

31

30

DIGITAL I/O

31

DIGITAL I/O RW

32

31

DIGITAL I/O

32

DIGITAL I/O RW

TYPE BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 65

User Manual

R SERIES

R-32DIDO: TABLE OF MODBUS REGISTERS 1x INPUT STATUS (FUNCTION CODE 2)

ADDRESS (1x) ADDRESS (0x) OFFSET REGISTER CHANNEL DESCRIPTION W/R

10001

0

DIGITAL I/O

1

DIGITAL I/O RW

10002

1

DIGITAL I/O

2

DIGITAL I/O RW

10003

2

DIGITAL I/O

3

DIGITAL I/O RW

10004

3

DIGITAL I/O

4

DIGITAL I/O RW

10005

4

DIGITAL I/O

5

DIGITAL I/O RW

10006

5

DIGITAL I/O

6

DIGITAL I/O RW

10007

6

DIGITAL I/O

7

DIGITAL I/O RW

10008

7

DIGITAL I/O

8

DIGITAL I/O RW

10009

8

DIGITAL I/O

9

DIGITAL I/O RW

10010

9

DIGITAL I/O

10

DIGITAL I/O RW

10011

10

DIGITAL I/O

11

DIGITAL I/O RW

10012

11

DIGITAL I/O

12

DIGITAL I/O RW

10013

12

DIGITAL I/O

13

DIGITAL I/O RW

10014

13

DIGITAL I/O

14

DIGITAL I/O RW

10015

14

DIGITAL I/O

15

DIGITAL I/O RW

10016

15

DIGITAL I/O

16

DIGITAL I/O RW

10017

16

DIGITAL I/O

17

DIGITAL I/O RW

10018

17

DIGITAL I/O

18

DIGITAL I/O RW

10019

18

DIGITAL I/O

19

DIGITAL I/O RW

10020

19

DIGITAL I/O

20

DIGITAL I/O RW

10021

20

DIGITAL I/O

21

DIGITAL I/O RW

10022

21

DIGITAL I/O

22

DIGITAL I/O RW

10023

22

DIGITAL I/O

23

DIGITAL I/O RW

10024

23

DIGITAL I/O

24

DIGITAL I/O RW

10025

24

DIGITAL I/O

25

DIGITAL I/O RW

10026

25

DIGITAL I/O

26

DIGITAL I/O RW

10027

26

DIGITAL I/O

27

DIGITAL I/O RW

10028

27

DIGITAL I/O

28

DIGITAL I/O RW

10029

28

DIGITAL I/O

29

DIGITAL I/O RW

10030

29

DIGITAL I/O

30

DIGITAL I/O RW

10031

30

DIGITAL I/O

31

DIGITAL I/O RW

10032

31

DIGITAL I/O

32

DIGITAL I/O RW

TYPE BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 66

User Manual
19. MODBUS REGISTER TABLE FOR THE R-16DI-8DO PRODUCT

R SERIES

R-16DI-8DO: MODBUS 4X HOLDING REGISTERS TABLE (FUNCTION CODE 3)

ADDRESS OFFSET ADDRESS

(4x)

(4x)

40001

0

40002

1

REGISTER
MACHINE-ID FIRMWARE REVISION

CHANNEL –

DESCRIPTION DEVICE
IDENTIFICATION FIRMWARE REVISION

W/R TYPE

UNSIGNED

RO

16

UNSIGNED

RO

16

ADDRESS (4x) 40017 40018 40019 40020
40021
40022
40023

OFFSET ADDRESS (4x) 16 17 18 19
20
21
22

REGISTER COMMAND RESERVED RESERVED RESERVED
DIGITAL INPUT [16…1] RESERVED
DIGITAL OUT [8…1]

CHANNEL DESCRIPTION W/R TYPE


[1…16] [8…1]

COMMAND REGISTER

RW

UNSIGNED 16

RESERVED

RO

UNSIGNED 16

RESERVED

RO

UNSIGNED 16

RESERVED

RO

UNSIGNED 16

DIGITAL INPUTS

[16… 1] THE

LEAST

SIGNIFICANT BIT

IS RELATIVE TO

I01

EXAMPLE: 5 decimal =

RO

UNSIGNED 16

0000 0000 0000

0101 binary =>

I01 = High, I02 =

LOW, I03 =

HIGH, I04… I16

= LOW

RESERVED

RO

UNSIGNED 16

DIGITAL

OUTPUTS [8… 1]

THE LEAST

SIGNIFICANT BIT IS RELATIVE TO

RW

UNSIGNED 16

D01

EXAMPLE:

5 decimal =

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 67

User Manual
0000 0000 0000 0101 binary =>
D01=High, D02=LOW, D03=HIGH, D04…D08=LOW

R SERIES

ADDRESS (4x)
40101
40102 40103 40104 40105 40106 40107 40108 40109 40110 40111 40112 40113 40114 40115 40116 40117 40118 40119 40120 40121 40122 40123 40124 40125

OFFSET ADDRESS (4x)

REGISTER

CHANNEL

RESET_COUNTE

100

R

16..1

[1..16]

101

RESERVED

102

COUNTER

1

103

104

COUNTER

2

105

106

COUNTER

3

107

108

COUNTER

4

109

110

COUNTER

5

111

112

COUNTER

6

113

114

COUNTER

7

115

116

COUNTER

8

117

118

COUNTER

9

119

120

COUNTER

10

121

122

COUNTER

11

123

124

COUNTER

12

DESCRIPTION

W/ R

RESET A BIT OF THE i-TH

COUNTER

THE LEAST SIGNIFICANT

BIT RELATES

TO COUNTER 1 EXAMPLE:

RW

5 decimal = 0000 0000

0000 0101 binary =>

Resets the value of

counters 1 and 3

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

TYPE
UNSIGNED 16
UNSIGNED 16
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 68

User Manual

R SERIES

40126

125

40127

126

40128

127

40129

128

40130

129

40131

130

40132

131

40133

132

40134

133

COUNTER

13

COUNTER

14

COUNTER

15

COUNTER

16

MSW
LSW MSW LSW MSW LSW MSW LSW MSW

RW

UNSIGNED 32

RW UNSIGNED

RW

32

RW UNSIGNED

RW

32

RW UNSIGNED

RW

32

RW UNSIGNED

RW

32

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER

CHANNEL

DESCRIPTION

W/ R

Integer

40201

200

measure of Tlow in [ms]

RO

INT MEASURE TLOW

1

LSW Integer

40202

201

measure of Tlow in [ms]

RO

MSW

Integer

40203

202

measure of Tlow in [ms]

RO

INT MEASURE TLOW

2

LSW Integer

40204

203

measure of Tlow in [ms]

RO

MSW

Integer

40205

204

measure of Tlow in [ms]

RO

INT MEASURE TLOW

3

LSW Integer

40206

205

measure of Tlow in [ms]

RO

MSW

Integer

40207

206

measure of Tlow in [ms]

RO

INT MEASURE TLOW

4

LSW Integer

40208

207

measure of Tlow in [ms]

RO

MSW

40209

208

INT MEASURE TLOW

5

Integer measure of

RO

TYPE
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 69

User Manual

R SERIES

40210 40211 40212 40213 40214 40215 40216 40217 40218 40219 40220 40221

Tlow in [ms]

LSW

Integer

209

measure of Tlow in [ms]

RO

MSW

Integer

210

measure of Tlow in [ms]

RO

INT MEASURE TLOW

6

LSW Integer

UNSIGNED 32

211

measure of Tlow in [ms]

RO

MSW

Integer

212

measure of Tlow in [ms]

RO

INT MEASURE TLOW

7

LSW Integer

UNSIGNED 32

213

measure of Tlow in [ms]

RO

MSW

Integer

214

measure of Tlow in [ms]

RO

INT MEASURE TLOW

8

LSW Integer

UNSIGNED 32

215

measure of Tlow in [ms]

RO

MSW

Integer

216

measure of Tlow in [ms]

RO

INT MEASURE TLOW

9

LSW Integer

UNSIGNED 32

217

measure of Tlow in [ms]

RO

MSW

Integer

218

measure of Tlow in [ms]

RO

INT MEASURE TLOW

10

LSW Integer

UNSIGNED 32

219

measure of Tlow in [ms]

RO

MSW

220

INT MEASURE TLOW

11

Integer measure of

RO

UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 70

40222 40223 40224 40225 40226 40227 40228 40229 40230 40231 40232

User Manual

R SERIES

Tlow in [ms]

LSW

Integer

221

measure of Tlow in [ms]

RO

MSW

Integer

222

measure of Tlow in [ms]

RO

INT MEASURE TLOW

12

LSW Integer

UNSIGNED 32

223

measure of Tlow in [ms]

RO

MSW

Integer

224

measure of Tlow in [ms]

RO

INT MEASURE TLOW

13

LSW Integer

UNSIGNED 32

225

measure of Tlow in [ms]

RO

MSW

Integer

226

measure of Tlow in [ms]

RO

INT MEASURE TLOW

14

LSW Integer

UNSIGNED 32

227

measure of Tlow in [ms]

RO

MSW

Integer

228

measure of Tlow in [ms]

RO

INT MEASURE TLOW

15

LSW Integer

UNSIGNED 32

229

measure of Tlow in [ms]

RO

MSW

Integer

230

measure of Tlow in [ms]

RO

INT MEASURE TLOW

16

LSW Integer

UNSIGNED 32

231

measure of Tlow in [ms]

RO

MSW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 71

User Manual

R SERIES

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER

40233 40234

232
INT MEASURE THIGH
233

40235 40236

234
INT MEASURE THIGH
235

40237 40238

236
INT MEASURE THIGH
237

40239 40240

238
INT MEASURE THIGH
239

40241 40242

240
INT MEASURE THIGH
241

40243 40244

242
INT MEASURE THIGH
243

CHANNEL 1 2 3 4 5 6

DESCRIPTION W/R TYPE

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

Integer

measure of Thigh in [ms]

RO

LSW

UNSIGNED

Integer

32

measure of Thigh in [ms]

RO

MSW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 72

User Manual

R SERIES

40245 40246 40247 40248 40249 40250 40251 40252 40253 40254 40255 40256

Integer

244

measure of Thigh in [ms]

RO

INT MEASURE THIGH

7

LSW Integer

UNSIGNED 32

245

measure of Thigh in [ms]

RO

MSW

Integer

246

measure of Thigh in [ms]

RO

INT MEASURE THIGH

8

LSW Integer

UNSIGNED 32

247

measure of Thigh in [ms]

RO

MSW

Integer

248

measure of Thigh in [ms]

RO

INT MEASURE THIGH

9

LSW Integer

UNSIGNED 32

249

measure of Thigh in [ms]

RO

MSW

Integer

250

measure of Thigh in [ms]

RO

INT MEASURE THIGH

10

LSW Integer

UNSIGNED 32

251

measure of Thigh in [ms]

RO

MSW

Integer

252

measure of Thigh in [ms]

RO

INT MEASURE THIGH

11

LSW Integer

UNSIGNED 32

253

measure of Thigh in [ms]

RO

MSW

Integer

254

measure of Thigh in [ms]

RO

INT MEASURE THIGH

12

LSW Integer

UNSIGNED 32

255

measure of Thigh in [ms]

RO

MSW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 73

40257 40258 40259 40260 40261 40262 40263 40264

User Manual

R SERIES

Integer

256

measure of Thigh in [ms]

RO

INT MEASURE THIGH

13

LSW Integer

UNSIGNED 32

257

measure of Thigh in [ms]

RO

MSW

Integer

258

measure of Thigh in [ms]

RO

INT MEASURE THIGH

14

LSW Integer

UNSIGNED 32

259

measure of Thigh in [ms]

RO

MSW

Integer

260

measure of Thigh in [ms]

RO

INT MEASURE THIGH

15

LSW Integer

UNSIGNED 32

261

measure of Thigh in [ms]

RO

MSW

Integer

262

measure of Thigh in [ms]

RO

INT MEASURE THIGH

16

LSW Integer

UNSIGNED 32

263

measure of Thigh in [ms]

RO

MSW

ADDRESS (4x) OFFSET ADDRESS (4x)

40265

264

40266

265

40267

266

40268

267

REGISTER
INT MEASURE PERIOD
INT MEASURE PERIOD

CHANNEL DESCRIPTION W/R TYPE

Integer Period

Measure [ms] RO

1

LSW Integer Period

UNSIGNED 32

Measure [ms] RO

MSW

Integer Period

Measure [ms] RO

LSW

2

Integer Period

UNSIGNED 32

Measure [ms] RO

MSW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 74

User Manual

R SERIES

40269 40270 40271 40272 40273 40274 40275 40276 40277 40278 40279 40280 40281 40282 40283 40284

Integer Period

268

Measure [ms] RO

INT MEASURE PERIOD

3

LSW Integer Period

UNSIGNED 32

269

Measure [ms] RO

MSW

Integer Period

270

Measure [ms] RO

INT MEASURE PERIOD

4

LSW Integer Period

UNSIGNED 32

271

Measure [ms] RO

MSW

Integer Period

272

Measure [ms] RO

INT MEASURE PERIOD

5

LSW Integer Period

UNSIGNED 32

273

Measure [ms] RO

MSW

Integer Period

274

Measure [ms] RO

INT MEASURE PERIOD

6

LSW Integer Period

UNSIGNED 32

275

Measure [ms] RO

MSW

Integer Period

276

Measure [ms] RO

INT MEASURE PERIOD

7

LSW Integer Period

UNSIGNED 32

277

Measure [ms] RO

MSW

Integer Period

278

Measure [ms] RO

INT MEASURE PERIOD

8

LSW Integer Period

UNSIGNED 32

279

Measure [ms] RO

MSW

Integer Period

280

Measure [ms] RO

INT MEASURE PERIOD

9

LSW Integer Period

UNSIGNED 32

281

Measure [ms] RO

MSW

Integer Period

282

Measure [ms] RO

INT MEASURE PERIOD

10

LSW Integer Period

UNSIGNED 32

283

Measure [ms] RO

MSW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 75

40285 40286 40287 40288 40289 40290 40291 40292 40293 40294 40295 40296

User Manual

R SERIES

Integer Period

284

Measure [ms] RO

INT MEASURE PERIOD

11

LSW Integer Period

UNSIGNED 32

285

Measure [ms] RO

MSW

Integer Period

286

Measure [ms] RO

INT MEASURE PERIOD

12

LSW Integer Period

UNSIGNED 32

287

Measure [ms] RO

MSW

Integer Period

288

Measure [ms] RO

INT MEASURE PERIOD

13

LSW Integer Period

UNSIGNED 32

289

Measure [ms] RO

MSW

Integer Period

290

Measure [ms] RO

INT MEASURE PERIOD

14

LSW Integer Period

UNSIGNED 32

291

Measure [ms] RO

MSW

Integer Period

292

Measure [ms] RO

INT MEASURE PERIOD

15

LSW Integer Period

UNSIGNED 32

293

Measure [ms] RO

MSW

Integer Period

294

Measure [ms] RO

INT MEASURE PERIOD

16

LSW Integer Period

UNSIGNED 32

295

Measure [ms] RO

MSW

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER CHANNEL

DESCRIPTION

W/R TYPE

40297

296

INT MEASURE 1
FREQ

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

40298

297

INT MEASURE
FREQ

2

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

40299

298

INT MEASURE
FREQ

3

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 76

User Manual

R SERIES

40300 40301 40302 40303 40304 40305 40306 40307 40308 40309 40310 40311 40312

299

INT MEASURE
FREQ

4

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

300

INT MEASURE
FREQ

5

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

301

INT MEASURE
FREQ

6

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

302

INT MEASURE
FREQ

7

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

303

INT MEASURE
FREQ

8

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

304

INT MEASURE
FREQ

9

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

305

INT MEASURE
FREQ

10

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

306

INT MEASURE
FREQ

11

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

307

INT MEASURE
FREQ

12

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

308

INT MEASURE
FREQ

13

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

309

INT MEASURE
FREQ

14

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

310

INT MEASURE
FREQ

15

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

311

INT MEASURE
FREQ

16

Integer measure of the frequency in [Hz]

RO

UNSIGNED 16

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER CHANNEL DESCRIPTION W/R TYPE

40401 40402

400

Floating point measure

FLOAT TLOW 1

of Tlow in [ms] (LSW) RO FLOAT 32

401

Floating point measure of Tlow in [ms] (MSW) RO

40403

402

FLOAT TLOW

2

Floating point measure of Tlow in [ms] (LSW)

RO

FLOAT 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 77

User Manual

R SERIES

40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420 40421 40422 40423 40424 40425

403

Floating point measure of Tlow in [ms] (MSW) RO

404

Floating point measure

FLOAT TLOW 3

of Tlow in [ms] (LSW) RO FLOAT 32

405

Floating point measure of Tlow in [ms] (MSW) RO

406

Floating point measure

FLOAT TLOW 4

of Tlow in [ms] (LSW) RO FLOAT 32

407

Floating point measure of Tlow in [ms] (MSW) RO

408

Floating point measure

FLOAT TLOW 5

of Tlow in [ms] (LSW) RO FLOAT 32

409

Floating point measure of Tlow in [ms] (MSW) RO

410

Floating point measure

FLOAT TLOW 6

of Tlow in [ms] (LSW) RO FLOAT 32

411

Floating point measure of Tlow in [ms] (MSW) RO

412

Floating point measure

FLOAT TLOW 7

of Tlow in [ms] (LSW) RO FLOAT 32

413

Floating point measure of Tlow in [ms] (MSW) RO

414

Floating point measure

FLOAT TLOW 8

of Tlow in [ms] (LSW) RO FLOAT 32

415

Floating point measure of Tlow in [ms] (MSW) RO

416

Floating point measure of Tlow in [ms] (LSW) RO

FLOAT TLOW 9

FLOAT 32

417

Floating point measure of Tlow in [ms] (MSW) RO

418

Floating point measure

FLOAT TLOW 10

of Tlow in [ms] (LSW) RO FLOAT 32

419

Floating point measure of Tlow in [ms] (MSW) RO

420

Floating point measure

FLOAT TLOW 11

of Tlow in [ms] (LSW) RO FLOAT 32

421

Floating point measure of Tlow in [ms] (MSW) RO

422

Floating point measure

FLOAT TLOW 12

of Tlow in [ms] (LSW) RO FLOAT 32

423

Floating point measure of Tlow in [ms] (MSW) RO

424

FLOAT TLOW

13

Floating point measure of Tlow in [ms] (LSW)

RO

FLOAT 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 78

User Manual

R SERIES

40426 40427 40428 40429 40430 40431 40432

425

Floating point measure of Tlow in [ms] (MSW) RO

426

Floating point measure

FLOAT TLOW 14

of Tlow in [ms] (LSW) RO FLOAT 32

427

Floating point measure of Tlow in [ms] (MSW) RO

428

Floating point measure

FLOAT TLOW 15

of Tlow in [ms] (LSW) RO FLOAT 32

429

Floating point measure of Tlow in [ms] (MSW) RO

430

Floating point measure of Tlow in [ms] (LSW) RO

FLOAT TLOW 16

FLOAT 32

431

Floating point measure of Tlow in [ms] (MSW) RO

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER CHANNEL

40465 40466

464 FLOAT THIGH 1
465

40467 40468

466 FLOAT THIGH 2
467

40469 40470

468 FLOAT THIGH 3
469

40471 40472

470 FLOAT THIGH 4
471

40473 40474

472 FLOAT THIGH 5
473

DESCRIPTION
Floating point measure of Thigh in
[ms] (LSW) Floating point measure of Thigh in [ms] (MSW) Floating point measure of Thigh in
[ms] (LSW) Floating point measure of Thigh in [ms] (MSW) Floating point measure of Thigh in
[ms] (LSW) Floating point measure of Thigh in [ms] (MSW) Floating point measure of Thigh in
[ms] (LSW) Floating point measure of Thigh in [ms] (MSW) Floating point measure of Thigh in
[ms] (LSW) Floating point measure of Thigh in [ms] (MSW)

W/R TYPE RO FLOAT 32 RO RO FLOAT 32 RO RO FLOAT 32 RO RO FLOAT 32 RO RO FLOAT 32 RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 79

User Manual

R SERIES

40475 40476 40477 40478 40479 40480 40481 40482 40483 40484 40485 40486 40487 40488 40489 40490

Floating point

474

measure of Thigh in

FLOAT THIGH 6

[ms] (LSW) Floating point

RO FLOAT 32

475

measure of Thigh in

[ms] (MSW)

RO

Floating point

476

measure of Thigh in

FLOAT THIGH 7

[ms] (LSW) Floating point

RO FLOAT 32

477

measure of Thigh in

[ms] (MSW)

RO

Floating point

478

measure of Thigh in

FLOAT THIGH 8

[ms] (LSW) Floating point

RO FLOAT 32

479

measure of Thigh in

[ms] (MSW)

RO

Floating point

480

measure of Thigh in

FLOAT THIGH 9

[ms] (LSW) Floating point

RO FLOAT 32

481

measure of Thigh in

[ms] (MSW)

RO

Floating point

482

measure of Thigh in

FLOAT THIGH 10

[ms] (LSW) Floating point

RO FLOAT 32

483

measure of Thigh in

[ms] (MSW)

RO

Floating point

484

measure of Thigh in

FLOAT THIGH 11

[ms] (LSW) Floating point

RO FLOAT 32

485

measure of Thigh in

[ms] (MSW)

RO

Floating point

486

measure of Thigh in

FLOAT THIGH 12

[ms] (LSW) Floating point

RO FLOAT 32

487

measure of Thigh in

[ms] (MSW)

RO

Floating point

488

measure of Thigh in

FLOAT THIGH 13

[ms] (LSW) Floating point

RO FLOAT 32

489

measure of Thigh in

[ms] (MSW)

RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 80

40491 40492 40493 40494 40495 40496

User Manual

R SERIES

Floating point

490

measure of Thigh in

FLOAT THIGH 14

[ms] (LSW) Floating point

RO FLOAT 32

491

measure of Thigh in

[ms] (MSW)

RO

Floating point

492

measure of Thigh in

FLOAT THIGH 15

[ms] (LSW) Floating point

RO FLOAT 32

493

measure of Thigh in

[ms] (MSW)

RO

Floating point

494

measure of Thigh in

FLOAT THIGH 16

[ms] (LSW) Floating point

RO FLOAT 32

495

measure of Thigh in

[ms] (MSW)

RO

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER CHANNEL DESCRIPTION W/R TYPE

Floating point

40529

528

measure of the

FLOAT PERIOD 1

Period in [ms] (LSW) Floating point

RO FLOAT 32

40530

529

measure of the

Period in [ms] (MSW) RO

Floating point

40531

530

measure of the

FLOAT PERIOD 2

Period in [ms] (LSW) Floating point

RO FLOAT 32

40532

531

measure of the

Period in [ms] (MSW) RO

Floating point

40533

532

measure of the

FLOAT PERIOD 3

Period in [ms] (LSW) Floating point

RO FLOAT 32

40534

533

measure of the

Period in [ms] (MSW) RO

Floating point

40535

534

measure of the

FLOAT PERIOD 4

Period in [ms] (LSW) Floating point

RO FLOAT 32

40536

535

measure of the

Period in [ms] (MSW) RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 81

User Manual

R SERIES

40537 40538 40539 40540 40541 40542 40543 40544 40545 40546 40547 40548 40549 40550 40551 40552

Floating point

536

measure of the

FLOAT PERIOD 5

Period in [ms] (LSW) Floating point

RO FLOAT 32

537

measure of the

Period in [ms] (MSW) RO

Floating point

538

measure of the

FLOAT PERIOD 6

Period in [ms] (LSW) Floating point

RO FLOAT 32

539

measure of the

Period in [ms] (MSW) RO

Floating point

540

measure of the

FLOAT PERIOD 7

Period in [ms] (LSW) Floating point

RO FLOAT 32

541

measure of the

Period in [ms] (MSW) RO

Floating point

542

measure of the

FLOAT PERIOD 8

Period in [ms] (LSW) Floating point

RO FLOAT 32

543

measure of the

Period in [ms] (MSW) RO

Floating point

544

measure of the

FLOAT PERIOD 9

Period in [ms] (LSW) Floating point

RO FLOAT 32

545

measure of the

Period in [ms] (MSW) RO

Floating point

546

measure of the

FLOAT PERIOD 10

Period in [ms] (LSW) Floating point

RO FLOAT 32

547

measure of the

Period in [ms] (MSW) RO

Floating point

548

measure of the

FLOAT PERIOD 11

Period in [ms] (LSW) Floating point

RO FLOAT 32

549

measure of the

Period in [ms] (MSW) RO

Floating point

550

measure of the

FLOAT PERIOD 12

Period in [ms] (LSW) Floating point

RO FLOAT 32

551

measure of the

Period in [ms] (MSW) RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 82

40553 40554 40555 40556 40557 40558 40559 40560

User Manual

R SERIES

Floating point

552

measure of the

FLOAT PERIOD 13

Period in [ms] (LSW) Floating point

RO FLOAT 32

553

measure of the

Period in [ms] (MSW) RO

Floating point

554

measure of the

FLOAT PERIOD 14

Period in [ms] (LSW) Floating point

RO FLOAT 32

555

measure of the

Period in [ms] (MSW) RO

Floating point

556

measure of the

FLOAT PERIOD 15

Period in [ms] (LSW) Floating point

RO FLOAT 32

557

measure of the

Period in [ms] (MSW) RO

Floating point

558

measure of the

FLOAT PERIOD 16

Period in [ms] (LSW) Floating point

RO FLOAT 32

559

measure of the

Period in [ms] (MSW) RO

ADDRESS (4x) OFFSET ADDRESS (4x) REGISTER CHANNEL DESCRIPTION W/R TYPE

Floating point

40593

592

measure of the Frequency in [Hz]

FLOAT FREQUENCY 1

(LSW) Floating point

RO FLOAT 32

40594

593

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

40595

594

measure of the Frequency in [Hz]

FLOAT FREQUENCY 2

(LSW) Floating point

RO FLOAT 32

40596

595

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

40597

596

FLOAT FREQUENCY

3

measure of the Frequency in [Hz]

FLOAT 32

(LSW)

RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 83

User Manual

R SERIES

40598 40599 40600 40601 40602 40603 40604 40605 40606 40607 40608 40609

Floating point

597

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

598

measure of the Frequency in [Hz]

FLOAT FREQUENCY 4

(LSW) Floating point

RO FLOAT 32

599

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

600

measure of the Frequency in [Hz]

FLOAT FREQUENCY 5

(LSW) Floating point

RO FLOAT 32

601

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

602

measure of the Frequency in [Hz]

FLOAT FREQUENCY 6

(LSW) Floating point

RO FLOAT 32

603

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

604

measure of the Frequency in [Hz]

FLOAT FREQUENCY 7

(LSW) Floating point

RO FLOAT 32

605

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

606

measure of the Frequency in [Hz]

FLOAT FREQUENCY 8

(LSW) Floating point

RO FLOAT 32

607

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

608

FLOAT FREQUENCY

9

measure of the Frequency in [Hz]

FLOAT 32

(LSW)

RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 84

User Manual

R SERIES

40610 40611 40612 40613 40614 40615 40616 40617 40618 40619 40620 40621

Floating point

609

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

610

measure of the Frequency in [Hz]

FLOAT FREQUENCY 10

(LSW) Floating point

RO FLOAT 32

611

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

612

measure of the Frequency in [Hz]

FLOAT FREQUENCY 11

(LSW) Floating point

RO FLOAT 32

613

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

614

measure of the Frequency in [Hz]

FLOAT FREQUENCY 12

(LSW) Floating point

RO FLOAT 32

615

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

616

measure of the Frequency in [Hz]

FLOAT FREQUENCY 13

(LSW) Floating point

RO FLOAT 32

617

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

618

measure of the Frequency in [Hz]

FLOAT FREQUENCY 14

(LSW) Floating point

RO FLOAT 32

619

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

620

FLOAT FREQUENCY

15

measure of the Frequency in [Hz]

FLOAT 32

(LSW)

RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 85

40622 40623 40624

User Manual

R SERIES

Floating point

621

measure of the Frequency in [Hz]

(MSW)

RO

Floating point

622

measure of the Frequency in [Hz]

FLOAT FREQUENCY 16

(LSW)

RO

FLOAT 32

Floating point

623

measure of the Frequency in [Hz]

(MSW)

RO

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 86

User Manual

R SERIES

R-16DI-8DO: CONSECUTIVE REGISTERS MODBUS 4x COPY (WITH INTEGER MEASURE REGISTERS)

OFFSET ADDRESS ADDRESS (4x)
(4x)

REGISTER

48001

8000

DIGITAL INPUT [16…1]

48002

8001

DIGITAL OUT [8…1]

48003 48004 48005 48006 48007 48008 48009 48010 48011

8002 8003 8004 8005 8006 8007 8008 8009 8010

COUNTER COUNTER COUNTER COUNTER COUNTER

CHANNEL
[1…16] [8…1] 1 2 3 4 5

W/ DESCRIPTION
R

DIGITAL

INPUTS [16…

1] THE LEAST

SIGNIFICANT

BIT IS

RELATIVE TO

I01

EXAMPLE: 5 decimal =

RO

0000 0000

0000 0101

binary => I01 =

High, I02 =

LOW, I03 =

HIGH, I04… I16

= LOW

DIGITAL OUTPUTS [8… 1] THE LEAST SIGNIFICANT
BIT IS RELATIVE TO
D01 EXAMPLE: 5 decimal = RW 0000 0000 0000 0101 binary => D01=High, D02=LOW, D03=HIGH, D04…D08=LO
W

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

TYPES

UNSIGNED 16
UNSIGNED 16
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 87

User Manual

R SERIES

48012
48013 48014 48015 48016 48017 48018 48019 48020 48021 48022 48023 48024 48025 48026 48027 48028 48029 48030 48031 48032 48033 48034
48035
48036

8011
8012 8013 8014 8015 8016 8017 8018 8019 8020 8021 8022 8023 8024 8025 8026 8027 8028 8029 8030 8031 8032 8033
8034
8035

COUNTER

6

COUNTER

7

COUNTER

8

COUNTER

9

COUNTER

10

COUNTER

11

COUNTER

12

COUNTER

13

COUNTER

14

COUNTER

15

COUNTER

16

INT

MEASURE

1

TLOW

48037 48038

8036 8037

INT

MEASURE

2

TLOW

48039 48040 48041

8038 8039 8040

INT

MEASURE

3

TLOW

INT

MEASURE

4

TLOW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

LSW

RW

MSW

RW

Tlow Integer measure RO
[x 50us] LSW

Tlow Integer measure RO
[x 50us] MSW

Tlow Integer measure RO
[x 50us] LSW Tlow Integer measure [ms] RO
MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer measure [ms] RO
LSW

UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

Doc: MI-00604-10-EN

Page 88

User Manual

R SERIES

48042

8041

48043 48044

8042 8043

INT

MEASURE

5

TLOW

48045 48046

8044 8045

INT

MEASURE

6

TLOW

48047 48048

8046 8047

INT

MEASURE

7

TLOW

48049 48050

8048 8049

INT

MEASURE

8

TLOW

48051 48052

8050 8051

INT

MEASURE

9

TLOW

48053 48054

8052 8053

INT

MEASURE

10

TLOW

48055 48056 48057

8054 8055 8056

INT

MEASURE

11

TLOW

INT

MEASURE

12

TLOW

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Tlow Integer measure RO
[x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer measure [ms] RO
MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer measure [ms] RO
LSW

UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

Doc: MI-00604-10-EN

Page 89

User Manual

R SERIES

48058

8057

48059 48060

8058 8059

INT

MEASURE

13

TLOW

48061 48062

8060 8061

INT

MEASURE

14

TLOW

48063 48064

8062 8063

INT

MEASURE

15

TLOW

48065 48066

8064 8065

INT

MEASURE

16

TLOW

48067 48068

8066 8067

INT

MEASURE

1

THIGH

48069 48070

8068 8069

INT

MEASURE

2

THIGH

48071 48072 48073

8070 8071 8072

INT

MEASURE

3

THIGH

INT

MEASURE

4

THIGH

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Tlow Integer measure RO
[x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer measure [ms] RO
MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Tlow Integer
measure RO [x 50us] LSW Tlow Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer measure [ms] RO
MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW

UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

Doc: MI-00604-10-EN

Page 90

User Manual

R SERIES

48074

8073

48075 48076

8074 8075

INT

MEASURE

5

THIGH

48077 48078

8076 8077

INT

MEASURE

6

THIGH

48079 48080

8078 8079

INT

MEASURE

7

THIGH

48081 48082

8080 8081

INT

MEASURE

8

THIGH

48083 48084

8082 8083

INT

MEASURE

9

THIGH

48085 48086

8084 8085

INT

MEASURE

10

THIGH

48087 48088 48089

8086 8087 8088

INT

MEASURE

11

THIGH

INT

MEASURE

12

THIGH

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Thigh Integer measure RO
[x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer measure [ms] RO
MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW Thigh Integer
measure RO [x 50us] MSW Thigh Integer
measure RO [x 50us] LSW

UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32
UNSIGNED 32

Doc: MI-00604-10-EN

Page 91

User Manual

R SERIES

48090 48091 48092 48093 48094 48095 48096 48097 48098 48099 48100 48101 48102 48103 48104 48105

8089 8090 8091 8092 8093 8094 8095 8096 8097 8098 8099 8100 8101 8102 8103 8104

INT MEASURE
THIGH
INT MEASURE
THIGH
INT MEASURE
THIGH
INT MEASURE
THIGH
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD

Thigh Integer

measure RO

[x 50us] MSW

Thigh Integer

measure [ms] RO

13

LSW Thigh Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Thigh Integer

measure RO

14

[x 50us] LSW Thigh Integer

UNSIGNED 32

measure [ms] RO

MSW

Thigh Integer

measure RO

15

[x 50us] LSW Thigh Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Thigh Integer

measure RO

16

[x 50us] LSW Thigh Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

1

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

2

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

3

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

4

Period Integer measure RO
[x 50us] LSW

UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 92

User Manual

R SERIES

48106 48107 48108 48109 48110 48111 48112 48113 48114 48115 48116 48117 48118 48119 48120 48121

8105 8106 8107 8108 8109 8110 8111 8112 8113 8114 8115 8116 8117 8118 8119 8120

INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD

Period Integer

measure RO

[x 50us] MSW

Period Integer

measure RO

5

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

6

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

7

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

8

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

9

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

[x 50us] LSW

10

Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

11

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

12

Period Integer measure RO
[x 50us] LSW

UNSIGNED 32

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 93

48122 48123 48124 48125 48126 48127 48128 48129 48130 48131 48132 48133 48134 48135 48136

8121 8122 8123 8124 8125 8126 8127 8128 8129 8130 8131 8132 8133 8134 8135

User Manual

R SERIES

INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE PERIOD
INT MEASURE
FREQ INT MEASURE FREQ INT MEASURE FREQ INT MEASURE FREQ INT MEASURE FREQ INT MEASURE FREQ

Period Integer

measure RO

[x 50us] MSW

Period Integer

measure RO

13

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

14

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

15

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

Period Integer

measure RO

16

[x 50us] LSW Period Integer

UNSIGNED 32

measure RO

[x 50us] MSW

1

Frequency Integer
Measure [Hz]

RO

UNSIGNED 16

Frequency

2

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

3

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

4

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

5

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

6

Integer

RO

UNSIGNED 16

Measure [Hz]

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 94

48137 48138 48139 48140 48141 48142 48143 48144 48145 48146

8136 8137 8138 8139 8140 8141 8142 8143 8144 8145

User Manual

R SERIES

INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ
INT MEASURE
FREQ

Frequency

7

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

8

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

9

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

10

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

11

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

12

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

13

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

14

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

15

Integer

RO

UNSIGNED 16

Measure [Hz]

Frequency

16

Integer

RO

UNSIGNED 16

Measure [Hz]

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 95

User Manual

R SERIES

R-16DI-8DO: TABLE OF MODBUS REGISTERS 0x COIL STATUS (FUNCTION CODE 1)

ADDRESS (0x) OFFSET ADDRESS (0x)

1

0

2

1

3

2

4

3

5

4

6

5

7

6

8

7

9

8

10

9

11

10

12

11

13

12

14

13

15

14

16

15

REGISTER
DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT

CHANNEL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

DESCRIPTION DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT DIGITAL INPUT

W/R TYPE RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT RO BIT

ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED WITHOUT PRIOR PERMISSION.

www.seneca.it

Doc: MI-00604-10-EN

Page 96

User Manual

R SERIES

ADDRESS (0x) 33 34 35 36 37 38 39 40

OFFSET ADDRESS (0x) 32 33 34 35 36 37 38 39

REGISTER DIGITAL OUT DIGITAL OUT DIGITAL OUT DIGITAL OUT DIGITAL OUT DIGITAL OUT DIGITAL OUT DIGITAL OUT

CHANNEL 1 2 3 4 5 6 7 8

DESCRIPTION DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT DIGIT

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals