FULHAM FHSHB-347-40W-D High Bay Emergency LED Driver Instruction Manual

June 15, 2024
FULHAM

FULHAM FHSHB-347-40W-D High Bay Emergency LED Driver

Product Information

Specifications

  • Model: FHSHB-347-40W-D
  • Emergency Power Output: 40 Watts (Constant)
  • Output Voltage: 170VDC

Features

  • UL is Listed for the US and CANADA
  • Listed to UL924 and tested to CSA C22.2 NO.141
  • Field or factory installation
  • Low energy consumption
  • CEC Title20 compliance
  • High output voltage
  • Constant output power
  • Self-testing
  • Battery: Over Temperature Protection
  • Over Charge Protection
  • Over-Discharge Protection
  • Remote test: Distance for 98ft (This function is optional)
  • Built-in Integrated junction box for wiring to the LED driver’s input

Product Usage Instructions

Self-Testing
The integrated Self-Diagnostic circuitry will automatically conduct monthly 30-second and annual 90-minute tests to verify proper emergency capability per Life Safety Code requirements. NFPA 101, Life Safety Code outlines the following schedule:

  • Monthly: During AC mode, the system conducts a 30-second self-discharge test of the emergency LED driver every 30 days. It automatically restores to normal charging after 30 seconds of discharging.
  • Annually: During AC mode, the system conducts a 90-minute self-discharge test of the emergency LED driver every 365 days. It automatically restores to normal charging after being fully discharged.

Dimensions
Size: L6.8(173mm)*H5.47(139mm)

Accessories

  • Test Switch Antenna
  • (11) pcs of Wire nuts
  • (1) pc of Safety rope
  • (2) pcs of Chain link connector
  • (1) pc M10 Hanging Hook Bolt
  • (1) pc M10 Hanging Ring Bolt
  • (1) pc of Remote
  • (1) pc of Antenna
  • (2) pcs Connector Suitable for wire diameter 0.118-0.248 (3-6.3mm)
  • (2) pcs Connector Suitable for wire diameter 0.196-0.393 (5-10mm)

FAQ

  • Q: Can the battery be replaced?
  • A: No, the battery used in the FHSHB-347-40W-D is sealed and not field-replaceable. The entire unit needs to be replaced when necessary.
  • Q: How often does the self-testing occur?
  • A: The self-testing occurs monthly for 30 seconds and annually for 90 minutes.
  • Q: What is the output voltage of the emergency LED driver?
  • A: The output voltage is 170VDC.
  • Q: What is the range for remote testing?
  • A: The remote testing function, which is optional, has a distance range of 98ft.
  • Q: What are the dimensions of the FHSHB-347-40W-D?
  • A: The dimensions are L6.8(173mm)*H5.47(139mm).
  • Q: Can I use accessory equipment not recommended by the manufacturer?
  • A: No, using accessory equipment not recommended by the manufacturer may cause an unsafe condition, void the warranty, and result in…

High-Bay Emergency LED Driver

FEATURES

  • UL is Listed for the US and CANADA
  • Listed to UL924 and tested to CSA C22.2 NO.141 Field or factory installation Low energy consumption CEC
  • Title20 compliance
  • High output voltage
  • Constaant output power
  • Self-testing
  • Battery:
    • Over Temperature Protection
    • Over Charge Protection
    • Over Discharge Protection Remote test: Distance for 98ft
  • (This function is optional)
  • Built-in Integrated junction box
  • For wiring to the led driver’s input

SPECIFICATIONS

  • Input Voltage:100-347Vac,50/60Hz
  • Input Current:200mA max.
  • Recharge Power: 12W
  • Output Voltage:170Vdc
  • Emergency Power:40W
  • Recharge Time:24Hrs
  • Discharge Time:1.5H
  • Warranty:5 Years
  • Vaux: 12Vdc … 0.2A
  • Battery: Li-ion
  • Ambient Temp: 32~122°F(0~50°C)
  • Weight:3.96 lbs(1.8kg) max.
  • Surge Protection: Line-Neutral 3KV

SPECIFICATION CHART

The unit of FHSHB-347.40W-D for led lamps less than 320W When the fixture dims to the minimum,

SELF-TESTING
The integrated Self-diagnostic circuitry will automatically conduct monthly 30-second and annual 90-minute tests to verify proper emergency capability per Life Safety Code requirements. NFPA 101, Life Safety Code Outlines the following schedule:

  • Monthly- During AC mode, the system conducts a (30) second self-discharge test of the emergency-led driver every 30 days. And automatically restores to normal charging after (30)seconds dis-charged.
  • Annually- During AC mode, the system conducts a (90) minute self-discharge test of the emergency-led driver every 365 days. And automatically restore to normal charging after fully dis-charged.

Dimensions

SIZE : L6.8″(173mm*H5.47″(139mm)

ACCESSORIES

Installation Manual

!!! IMPORTANT SAFEGUARDS !!!
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1. CAUTION: This emergency driver provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit.
  2. CAUTION: Servicing of this equipment should be performed by qualified personnel only.
  3. CAUTION: Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field-replaceable. Replace the entire unit when necessary.
  4. CAUTION: The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void the warranty, and result in non-compliance with UL specifications.
  5. CAUTION: The emergency driver requires an un-switched AC power source of 100-347VAC,50/60Hz. The installer must confirm the fixture’s input voltage. covered 120VAC before installation. It will supply power under an output voltage of 170VDC in emergency mode for at least 90 minutes.
  6. CAUTION: The battery pack should be charged for 24 hours every 6 months during storage.
  7. The battery in this unit may not be fully charged. After electricity is connected to the unit for at least 24 hours, then normal operation of this unit should take effect.
  8. For use in 0℃ minimum, 50℃ maximum ambient temperatures. Suitable for use in wet locations and plenum spaces.
  9. The emergency driver should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
  10. Do not use this equipment for anything other than its intended use. Equipment only used for LED Lighting emergency backup.
  11. Do not mount near gas or electric heaters. Do not let power supply cords touch hot surfaces.
  12. Do not make or leave any other open holes in the wiring enclosure or electrical component enclosure during installation.
  13. This fixture is for use with grounded, UL Listed, this model can be used in wet locations. Not for use in heated air outlets or hazardous locations.
  14. The emergency driver has a battery inside, forbidden for insulation voltage(I/P-O/P) test.
  15. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
  16. The equipment is intended for ordinary locations and for permanent installation into one or more Listed emergency luminaires.
  17. Suitable for a minimum 10W LED lamp.
  18. Maximum installation height: 28.5 feet.
  19. Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
  20. this device may not cause harmful interference, and
  21. this device must accept any interference received, including interference that may cause undesired operation.
  22. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
    • Reorient or relocate the receiving antenna.
    • Increase the separation between the equipment and the receiver.
    • Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
    • Consult the dealer or an experienced radio/TV technician for help.

LUMEN OUTPUT DURING EMERGENCY OPERATION

The luminaire-rated data and maximum mounting height can be found as follows:

  1. Determine the fixture efficacy under normal AC operation, based on fixture manufacturer published data in lumens per watt(LM/W).
  2. Reference DLC QPL (www.designlights.org) and Energy Star QPL (www.energystar.gov) for rated data on fixture efficacy. If fixture is not found on DLC or Energy Star Qualified Product List, contact fixture manufacturer.
  3. Multiply fixture LM/W by rated output power of emergency pack Example ‘model FHSHB-347-40W-D’is 40 W 100 LM/W = 4000 Lumens This product has been designed and tested to be compatible with most led drivers in the market. However, compatibility cannot be guaranteed with all current and future LED drivers or fixtures. So compatibility testing of the end-use system is suggested.

Please contact the factory with any questions.

Caution : Before Installation, Make Certain The A.C. Power is Off!

STEP 1: ASSEMBLING NOTICE

  • Select a suitable location on the hangable device.
  • The Maximum weight of the lighting fixture should be less than 20kg.
  • Turn o the AC power before installing.
  • Assembling the EM backup with the Safety Rope with the chain link connector.
  • Please use waterproof connectors in the position AC input wire interface and Dimming wire interface for application in wet location.

STEP 2: INSTALLING

  • Install the ring M10 Hanging Ring Bolt to the EM backup and fix it with a screw.
  • Install the M10 Hanging Hook Bolt to the EM backup and fix it with a screw.
  • Install the UFO high bay to the Hanging Hook of EM back up and tighten the screws.

STEP 3: WIRING

  • Before wiring, make sure the safety rope is securely locked and make sure all the screws are tight.
  • Open the cover of the junction box.
  • Select the appropriate wiring diagram to connect the emergency driver to the AC driver. For other diagrams, consult the manufacturer.
  • The voltage input to the dimmable wires (DIM+, DIM-) of the emergency LED driver must be less than 20Vdc.
  • Use wire nuts to cover unused wires and make sure all connections are in accordance with the NEC and any local regulations.

STEP 4: TESTING

  • After the wiring is complete, apply A.C. power. Check if the indicator light lights or not, which will indicate the battery’s charging situation.
  • The battery in this unit may not be fully charged. A short-term discharge test may be conducted after the emergency driver has been charging for 1 hour. Charge for 24 hours before conducting a long-term discharge test.

WIRING DIAGRAM

Note : The LED fixture must integrated with a 0-10V driver when LED xture power is more than the Emergency backup unit power.

INSTALLATION INSTRUCTIONS

**OPERATION

**

(INDICATOR STATUS)

WARNING
Risk of Electric Shock

Note : Please press once test switch to make certain the battery is turned off, before installation, maintenance, storage or shipping.

PACKAGE

PACKAGE INFORMATION

Fulham Co. Inc.: 12705 South Van Ness Ave., Hawthorne, CA 90250 Tel.: 1-323-779-2980 Fax.: 1-323-754-9060.
Specifications are subject to change without notice.

order@fulham.com www.fulham.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

FULHAM User Manuals

Related Manuals