Honeywell H-GTW Gateway Control Panel User Guide
- June 15, 2024
- Honeywell
Table of Contents
Honeywell H-GTW Gateway Control Panel
Product Information
Specifications
- Opto-isolated digital input / pulse counter input
- Programmable 4-10 V power output or PWM dimming
- External power supply input: 5…28VDC
- Power negative: GND = negative COM Pin5
- FACP reference TX = transmission with Pin2 RX of the FACP
- RX = Receive with Pin3 TX from FACP
- Micro USB connector for PC communication (configuration utility)
- RS485 / SDI12 bus terminals
- Digital channel inputs (pull up 10K 1%), referred to terminal GND
- Open collector outputs, max. 200mA
Product Usage Instructions
Device Connections
Before powering on the device, make sure all connections are made properly.
Connection i4
AnOut V+ GND RS-232 USB A,B i1,i2,i3 o1..o2
Linking with Exchanges
H-GTW-N ID-3000 (ISO-RS232)
GND 0v TX TX RX RX ID-50/60
Pin 5 Pin 2 Pin 3 AM-8200 (SIB-8200) SNC Terminal 2 Terminal 4 Terminal 5
RS232 Port Speed for Control Panels
FACP ID-3000 (ISO-RS232)
Transmission speed: 4800Bd
Model TPP TPP11 ID-50/60 9600bd TPP11 AM-8200 (SIB-8200) SNC 38400 TPP13 Normal/Special
Control Panel Configuration
ID50/60
- To enable the RS232 port on the control panel, proceed as follows:
- Reposition jumper J9 or MEN at the end of programming.
ID3000
- To enable the RS232 port of the ISO-RS232 option card, follow the steps below in the control panel menu:
- Configuration
- Central configuration
- Conf. Isolated RS232 port
- Integration Protocol 4800 bps Version: 2: 011 (only if Half Duplex is not available)
- Controls: enabled/disabled *1
- Com. monitoring: disabled
- Time monitoring: 0
*1 If the controls are disabled, no commands can be sent to the control panel.
AM-8200
- To enable the RS232 port on the control panel using the SIB-8200 board, proceed as follows:
- Press PRGM (default code 44444)
- Select ‘Program or device configuration’
- Select ‘SIB’
- In Installed, press Enter and use the ‘up/down’ cursor keys to change to ‘YES’
FAQ
Q: How do I enable the RS232 port on the control panel?
A: Please refer to the specific section for your control panel model in the Control Panel Configuration instructions.
Device connections
Before power on the device, make sure all connections are made properly.
Connection | Description |
---|---|
i4 | Opto-isolated digital input / pulse counter input. |
AnOut | Programmable 4-10 V power output or PWM dimming. |
V+ | External power supply input, 5…28VDC . |
GND | Power negative. |
RS- 232
| GND = negative COM Pin5 FACP reference
TX = transmission with Pin2 RX of the FACP
RX= Receive with Pin3 TX from FACP
USB| Micro USB connector for PC communication (configuration utility)
A,B| RS485 / SDI12 bus terminals.
i1,i2,i3| Digital channel inputs (pull up 10K 1%), referred to terminal
GND.
o1..o2| Open collector outputs, max. 200mA.
Links with exchanges
H-GTW- N| ID-3000 (ISO-RS232)| ID-50/60| AM- 8200
(SIB-8200) SNC
---|---|---|---
GND| 0v| Pin 5| Terminal 2
TX| TX| Pin 2| Terminal 4
RX| RX| Pin 3| Terminal 5
RS232 port speed for control panels
FACP| ID- 3000
(ISO-RS232)
| ID-50/60| AM- 8200
(SIB-8200) SNC
---|---|---|---
Transmission speed| 4800Bd| 9600bd| 38400
Model TPP| TPP11| TPP11| TPP13 Normal/Special
Communication via Ethernet
IP address 192.168.1.234 Port 61534 (default)
Installer’s Manual QR
QR Integration Manual
Control panel configuration
ID50/60
To enable the RS232 port on the control panel, proceed as follows:
- Release the control panel programming lock, remove jumper J9 or MEN
- Run the programme and open the programming file.
- If you do not have the programming file, run the programme and click on
- Tools > Receiving Data from Central
- When finished, press Save, specifying a path and a name for the file.
- Click on the Panel icon on the left-hand side of the screen.
- Select the ‘Device Options’ window.
- In the part marked RS232 (right), where it says RS232 Protocol, enter
- Integration
- Under ‘RS232 Options’, select HALF DUPLEX.
- In the section ‘Monitoring the Integration of Communications’, select ‘Cancellation’.
- Save the data, click on Tools>Send to Panel
- When prompted, enter installer code 3333, in order to perform the dump
- Reposition jumper J9 or MEN at the end of programming.
ID3000
To enable the RS232 port of the ISO-RS232 option card, follow the steps below
in the control panel menu (to unlock the keyboard and access the menu, turn
the service button on the front panel, next to the keyboard, a quarter turn to
the right):
- 6. Configuration
- 6. Central configuration
- 18. Conf. Isolated RS232 port
- 3. Integration Protocol 4800 bps
- Version: 2: 011 (only if Half Duplex is not available) Controls: enabled/disabled *1 Com. monitoring: disabled Time monitoring: 0
Mandatory selections are highlighted in bold.
Default password level 3B: 27835
*1 If the controls are disabled, no commands can be sent to the control panel.
AM-8200
To enable the RS232 port on the control panel using the SIB-8200 board,
proceed as follows:
- Press PRGM (default code 44444)
- Select ‘Program or device configuration’.
- Select ‘SIB’.
- In Installed, press Enter and use the ‘up/down’ cursor keys to change to ‘YES’.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>