REGENCY Grandview G600EC Gas Fireplace Instruction Manual

June 15, 2024
Regency

REGENCY Grandview G600EC Gas Fireplace

Product Information

  • Model: G600EC Medium DV Gas Fireplace
  • Manufacturer: FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
  • Website: www.regency-fire.com
  • Color: As shown in artwork
  • Dimensions: 5.965″ W x 5.71″ H
  • Gas Type: Indicated on the rating plate (Conversion kit provided)

Manufactured Mobile Home Requirements: This appliance may be installed in an aftermarket permanently located, manufactured (U.S.A. only) or mobile home, where not prohibited by local codes. Ensure that structural members are not cut or weakened during installation.

Carbon Monoxide Poisoning Hazard: Non-metallic venting systems shall not interchange components with another listed or unlisted metallic venting system.

Product Usage Instructions

Owner’s Information:

  • Gas Installation Checklist: Refer to page 9for a detailed checklist to ensure proper installation of the gas fireplace.
  • Before You Start: Before operating the fireplace, review the safety warnings and precautions outlined in the installation and operating instructions accompanying the appliance.
  • Lighting Procedure: Follow the step-by-step lighting procedure provided on page 12 to safely ignite the gas fireplace.
  • Glass Door Installation: Instructions for installing the glass door can be found on page 19. Ensure proper installation for the safety of children and at-risk individuals.

Installer’s Information:

  • Important Message: Read the important message on page 20 for important information regarding installation and safety precautions.
  • General Safety Information: Review the general safety information provided on page 20 to ensure safe installation and operation of the gas fireplace.
  • Installation Checklist: Use the installation checklist on page 21 to ensure all necessary steps are followed during the installation process.
  • Locating Your Gas Fireplace: Follow the guidelines provided on page 21 to determine the appropriate location for installing the gas fireplace.
  • Heatwave Duct System – Optional Kit: If applicable, refer to page 21 for information on installing the optional Heatwave Duct System.

Specifications

  • Model: G600EC
  • Type: Medium DV Gas Fireplace
  • Manufacturer: FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
  • Color: As shown in artwork
  • Dimensions: 5.965″ W x 5.71″ H
  • Gas Type: Indicated on the rating plate (Conversion kit provided)

FAQs

Q: Can I use gasoline or other flammable liquids near the gas fireplace?

A: No, storing or using gasoline or other flammable vapors and liquids in the vicinity of the gas fireplace is strictly prohibited to prevent fire or explosion hazards.

Q: Can children touch the hot glass of the gas fireplace?

A: No, children should never touch the hot glass of the gas fireplace. A barrier is provided with the appliance to reduce the risk of burns, and it must be installed for the protection of children and other at-risk individuals.

Q: How should I clean the burner and control compartment of the gas fireplace?

A: To keep the burner and control compartment clean, refer to the installation and operating instructions accompanying the appliance for specific cleaning instructions.

Grandview® G600EC Gas Fireplace

Owners & Installation Manual
MODEL: G600EC Medium DV Gas Fireplace

www.regency-fire.com
Warning Fire or Explosion Hazard Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electrical switch: do not use any phone in your building.
Leave the building immediately. · Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Tested by:

Certified to/Certifié pour: ANSI Z21.88-2019 CSA 2.33-2019 CSA 2.17-2017

Installer: Please complete the details on the back cover and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.

920-271g

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

01.16.23

To the New Owner:

Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The GrandviewTM G600EC has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The GrandviewTM G600EC has been approved by Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and
the many features of your Regency® FFireropnlatce.

! DANGER

!

HOT GLASS WILL CAUSE BURNS

DO NOT TOUCH GLASS UNTIL COOLED

NEVER ALLOW CHILDREN TO TOUCH GLASS

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and must be installed for the protection of children and other at risk individuals.
CAUTION:
HOT WHILE IN OPERATION. DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP CHILDREN, CLOTHING, FURNITURE, GASOLINE, AND ANY OTHER LIQUIDS WITH FLAMMABLE VAPOURS AWAY.

KEEP BURNER AND CONTROL COMPARTMENT CLEAN.

SEE INSTALLATION AND OPERATING INSTRUCTIONS ACCOMPANYING

APPLIANCE.

920-408

L’écran pare-étincelle contact accidentel ave enfants et des person
ATTENTIO
Risque de brûlures Ne pas toucher l’ap Ne pas laisser les e vêtements, les meu à distance de l’appa S’assurer que le brû Voir les instructions l’appareil.

920-408
4.34.7 Instruction Plate For a glass-fronted gas appliance where the temperature of the glass viewing area outside surface exceeds the limits specified in Clause 5.14.4, the following graphic danger and statements shall be shown on a Class IIIA-2 Permanent Label. 4.34.6 Instruction Plate Each appliance shall bear a Class IIIB marking with letters on a contrasting background, located adjacent to the controlling device or in an equally conspicuous position where the instruction can be easily read.
April 22/14: Created draft Double sided Material: Synthetic Paper Size 5.965″ W x 5.71″ H Color: As shown in artwork

2 | Grandview® G600EC Gas Fireplace

MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Intertek as a Direct Vent Wall Furnace to the following standards: to Vented Gas Fireplace Heaters ANSI Z21.88 · CSA 2.33 and Gas-fired Appliances for Use at High Altitudes CSA 2.17-2017. This Direct Vent System Appliance must be installed in accordance with the manufacturer’s installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada. This appliance installation must comply with the manufacturer’s installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CSA B149.1 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada. This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1. This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes. This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Ensure that structural members are not cut or weakened during installation.
This appliance may be installed in an aftermarket permanently located, manufactured (U.S.A. only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
Grandview® G600EC Gas Fireplace | 3

WARNING CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, CSA B149.1 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. 8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with National Fuel Gas Code, ANSI Z223.1/NFPA and/or Natural Gas and Propane Installation Code, CSA B149.1. 9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace damper and any other gas-fired burning appliance to the previous conditions of use.
Other considerations: Non-metallic venting systems shall not interchange components with another listed or unlisted metallic venting system.
4 | Grandview® G600EC Gas Fireplace

safety decal

This is a copy of the label that accompanies each GrandviewTM G600EC Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
Copy of Safety Decal

Duplicate S/N

543

Listed/Nom: Vented Gas Fireplace Heater / Foyer au gaz à évacuation Certified to/Certifié pour: ANSI Z21.88-2019 · CSA-2.33-2019
CSA 2.17-2017

DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE Serial No./ No de série

C #: 4001172

MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE. Refer to Intertek’s Directory of Building Products for detailed information. Pour plus de détails , se reporter au Répertoire des produits de construction de Intertek.

NATURAL GAS: Model G600EC-NG

Minimum supply pressure 5.0″

Manifold pressure high 3.8″

Manifold pressure low 1.1″

Orifice size

44

Minimum input

11,500

Maximum input

21,000

Altitude

0-4500

WC/C.E. (1.25 kPa)

WC/C.E. (0.94 kPa)

WC/C.E. (0.27 kPa)

DMS

Btu/h 3.37 kWh

Btu/h 6.15 kWh

ft/pi

(0-1372 m)

APPAREIL FONCTIONNANT AU GAZ NATUREL Modèle G600EC-NG Pression d’alimentation minimale Pression manifold – haute Pression manifold – basse Taille de l’orifice Débit calorifique minimal Débit calorifique maximal Altitude

PROPANE GAS: Model G600EC-LP

APPAREIL FONCTIONNANT AU GAZ PROPANE

Modèle G600EC-LP

Minimum supply pressure 11″

WC/C.E. (2.74kPa) Pression d’alimentation minimale

Manifold pressure high 10″

WC/C.E. (2..49kPa) Pression manifold – haute

Manifold pressure low 6.4″

WC/C.E. (1.60kPa) Pression manifold – basse

Orifice size

55 DMS

Taille de l’orifice

Minimum input

16,500 Btu/h

4.84 kWh Débit calorifique minimal

Maximum input

20,500 Btu/h 6.01 kWh Débit calorifique maximal

Altitude

0-4500 ft/pi

(0-1372 m) Altitude

543

Minimum Clearances to Combustibles / Rear Vent–Cool Wall-Clean Front

Dégagements minimaux par rapport aux matériaux combustibles / évacuation

arrière-mur froid-façade épurée

0″ Clearance to combustibles from

Top, sides, and bottom of unit

0.5″ Clearance to combustibles from

D

rear of unit

C

Mantel Clearances from

Fireplace Opening /

(A) 12″ (305 mm) at max. depth

A

Side Wall Clearance from Fireplace

F

Opening /

B

B) Min 6″ (152 mm)

Ceiling from Top of Fireplace

Opening:

C) Min. 44.25″ (1124 mm)

Mantel Depth:

D) Max. 12″ (305 mm)

E

Alcove Clearances:

E) Min. Width 84″ (2134 mm)

DOOR SEAL: Please

F) Max. Depth 36″ (914 mm) Minimum Vent Clearances:

check that the door is properly sealed
(See Instruction Manual for detailed instructions)

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.

This appliance must be installed in accordance with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the

United States, or when such a standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles

This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See

owner’s manual for details. This appliance is not convertible for use with other gases, unless a certified kit is used. (Kit #761-969). Fan Part # 761-917.

Installer l’appareil selon les codes ou règlements locaux, ou, en l’absence de tels règlements, selon les codes d’installation ANSI Z223.1, National Fuel Gas Code ou CSA-B149.1 en vigueur. Installer l’appareil

selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety Standard. Si ces normes

ne sont pas pertinentes, utilisez la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles.

Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U. seulement) installée à demeure

si les règlements locaux le permettent. Voir la notice de l’utilisateur pour plus de renseignements. Cet appareil ne peut pas être utilisé avec d’autres gaz sauf si une trousse de conversion certifiée est

fournie.

This vented gas fireplace heater is not for use with air filters. FOR USE WITH GLASS DOORS CERTIFIED WITH THE APPLIANCE ONLY

Ne pas utiliser de filtre à air avec ce foyer au gaz à évacuation. POUR UTILISATION UNIQUEMENT AVEC LES PORTES EN VERRE CERTIFIÉES AVEC L’APPAREIL

For Use Only with Barrier (Part # 776-109/P)

Utiliser uniquement avec l’écran ( n° 776-109/P)

Part No. 946-556 HeatWave Kit may be used. La trousse HeatWave (pièce no. 946-556) peut être utilisée.

FPI Fireplace Products International Ltd. Delta, BC, Canada

VENTED GAS FIREPLACE HEATER – NOT FOR USE WITH SOLID FUELS. CATEGORY I.

Made in Canada/ Fabriqué au Canada

FOYER AU GAZ À ÉVACUATION – NE PAS UTILISER AVEC UN COMBUSTIBLE SOLIDE. CATÉGORIE I.

EP5011169

CANADIAN ENERGY PERFORMANCE VERIFIED
RENDEMENT ÉNERGÉTIQUE
VÉRIFIÉ

CSA P.4.1 Fireplace Efficiency (FE) /Efficacité énergétique des foyers (EEF) CSA P.4.1 Natural Gas / Gaz naturel : 64.8% Propane Gas / Gaz propane : 67.22%

920-272e

FoPratrht e#:S9t2a0te-2o7f2Me assachusetts, installation

Decal Location

agnaCSsdiozfleriote:utperF:ariEillreivc@meern1uys0tshe0tid%nbgien9b.dtl1aho1cen7k’eC’Woonbmyxgmr6ae.o0yp4nelu5wx’mc’eHeabpletthrwoohrfat

is

highlighted is printed red. DO NOT REMOVE

DECAL

FROM

UNIT.

Massachusetts.

May 04/20 : Created Draft FoSretphteemStbaetre1o0f/M20a:sUsapcdhautesdetttos ,inflceluxdibelekWconm-easurements provided by gas lab. neOcctot.r0s7s/h2a0l:l Unopdt aetxecdeewdith36HienacthWeasvien lkeitnsgttahte. ment.
Mar. 17/21: Updated CSA/ANSI date. FoArutgh1e2S/2t2a:teReovf EMa- sUspadcahtuesdewttosr,dtinhge appli-

ances individual manual shut-off must be a

t-handle type valve.

Remove bottom cover–decal will be on the floor of the unit

The State of Massachusetts requires the installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm with battery back up in the same room where
the gas appliance is installed.

6 | Grandview® G600EC Gas Fireplace

installer’s information

5.08: Modifications to NFPA-54, Chapter 10

MA Code – CO Detector
(for the State of Massachusetts only)

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipmentat the completion of the installation.
Grandview® G600EC Gas Fireplace | 7

dimensions
Unit Dimensions

14

5 8

372mm

4″
101mm 6(1-56/18872m’6’m34mm” )

16″ 406mm

31

7 8

811mm

OUTSIDE FINISH

28

3 4

729mm

CLEAN FRONT

17

1 4

439mm

16″ 405mm

9

3 4

246mm

1011mm

3 4

21-3/4″ (552 mm)

39

CLEAN FRONT

679mm

OUTSIDE FINISH

758mm

FIREPLACE OPENING

719mm

(6 632235415’87’mm”mm)

GAS INLET

8

3 8

213mm

28

3 8

29

7 8

[8935353371-m112m/m”2m” ]

26

3 4

26-1/8″ (664 mm)

41mm

5 8

1

1

5 8

41mm

[9835353977-m334m/m”4m” ]

ELECTRICAL INLET

7

1 2

191mm

10

1 2

268mm

3304-585/”8″ [878708mmmm]

3304-734/”8″ [878834mmmm]

Finishing Trim

Faceplate

Note: Gas connection is from the left hand side of the appliance & electrical connection on right hand side of the appliance. A metal receptacle box is supplied/installed with the appliance to make all 120 volt electrical connections.

ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY. ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
8 | Grandview® G600EC Gas Fireplace

Gas Installation Checklist

dimensions

This general checklist does not contain all pertinent installation details or specifics and does not supersede the guidelines in this manual. Your Regency dealer/installer should use it in conjunction with manual instructions. Please follow all local codes and jurisdictions in authority.

Customer:

Date Installed:

Install Address: Serial No: Model No:

Location of Fireplace: Installer:

Site Requirements

YES NO

If applicable, are the insulation, vapour barrier, and drywall present if installed on an outside wall or chase?
Does the area have a solid continuous base to support the unit? Will the area accommodate the size of the applliance and all clearances? Are the gas and electrical roughed into the area where the unit is being installed?
In City & Grandview series cool wall applications, is the chase enclosure sealed to prevent heat from escaping? All hot air from the unit must exit via the mandatory ventilation openings. In City & Grandview applications, Is the chase enclosure vented with the mandatory heat ventilation openings? See manual for details. If applicable, is the masonry/factory built freplace in its original condition with no modifications?
If applicable, have the hearth requirements been met?
Unit Setup

YES NO

If applicable, are the standoffs and top nailing flange extensions installed and at the correct depth to accommodate finishing material? See manual for details. If applicable, is the fireplace level and secured, meeting framing clearances? See manual for details. If applicable, is the unit converted to top or rear vent per manual instructions, and the insulation discarded?
Venting

YES NO

Are the venting components approved for the unit installed? Does the venting configuration comply with venting diagrams? Is venting installed and secured, and are clearances for the vent pipe and termination cap maintained? If applicable, was a 1/4″ rise maintained for every foot of horizontal run? Was the termination installed and sealed? Is the direct vent termination at the highest point in the vent assembly? If applicable, are both chimney liners continuous from flue collars to termination? Electrical and Wiring

YES NO

Is the appliance connected to the household’s 110/120v per local codes? Check local codes for receptacle placement. Were the connections in the fireplace tested with a circuit tester? Is the appliance properly grounded? If applicable, is the supplied electrical/gang box affixed to the wall to facilitate the mounting of the receiver/battery box ? Gas

YES NO

Does the supply pressure meet the requirements shown on the rating plate? Was a conversion performed? Was a leak check performed and manifold pressures verified? Is the shut-off valve installed and easily accessible to the customer?

Grandview® G600EC Gas Fireplace | 9

installation
Finishing If applicable, is only noncombustible material installed in the noncombustible areas? Do clearances meet installation and manual requirements? Do the mantels and/or projections comply with the installation manual? If applicable, was the solid fuel fireplace warning plate installed? Appliance Media Setup Do commands from the remote or wall switch light the pilot and main burner? Are the burner media/log set, glass door, and screen installed per instructions in the manual? Was the air shutter on the proper setting after running the unit for 20 minutes? If applicable, were the surround and trims installed according to the manual? Was the operation of the fan, lights (if installed), and flame modulation checked? Customer Tutorial and Presentation Is the customer confident operating the new gas appliance and aware of all the features on the remote? Confirm that the rating and lighting plates are attached to the appliance. Do not remove. Was the customer informed of the location of the rating and lighting plates? Was accessing unit controls in a power outage explained to the customer? Are the model and serial numbers and the date of installation of the unit written in the manual and on the checklist? Were the warranty and unit registration reviewed with the customer? Comments:

YES NO YES NO YES NO

10 | Grandview® G600EC Gas Fireplace

Before You Start

Safe installation and operation of this appliance involves common sense. This is echoed in the reminders the Canadian Safety Standards and ANSI Standards require us to provide you, which follow below.
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.

YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
A BARRIER DESIGNED TO REDUCE THE RISK OF BURNS FROM THE HOT VIEWING GLASS IS PROVIDED WITH THIS APPLIANCE AND SHALL BE INSTALLED FOR THE PROTECTION OF CHILDREN AND OTHER AT-RISK INDIVIDUALS.
ANY SAFETY SCREEN, GUARD, OR BARRIER REMOVED FOR SERVICING THE APPLIANCE, MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
IF THE BARRIER BECOMES DAMAGED, THE BARRIER SHALL BE REPLACED WITH THE MANUFACTURER’S BARRIER FOR THIS APPLIANCE.

owner’s information

Grandview® G600EC Gas Fireplace | 11

owner’s information

Lighting Procedure
IMPORTANT: The battery holder and ON/OFF key on the hand held transmitter of the remote control system supplied with this appliance provides several options for startup/operation.
Prior to operating this appliance, please read the remote control operating instructions provided.
1. Ensure the battery holder switch and/or wall mounted battery holder (if equipped) is in the position.
2. Press and release the ON/OFF button on the remote’s handheld transmitter (see Diagram 1). The receiver should beep. If not using the remote, the unit can also be turned on by sliding the battery holder switch to the position (if equipped).
3. After approximately 4 seconds, the spark ignition system will spark for 60 seconds to light the main burner.

The system will need to be reset as follows:
a) Turn the system off by pressing the ON/OFF button on the remote. b) Wait 5 minutes then repeat from step 2.
Shutdown Procedure
1. Press the ON/OFF button on the remote 2. If service is to be performed- you must disconnect power and shut off
gas to the unit.

ON/OFF Button

Diagram 1 Remote shown in Manual Mode on Hi
4. The unit will turn on.

  • Not offered on all models.

Note: The first try for ignition will last approximately 60 seconds. If there is no flame ignition (rectification) the board will stop sparking for approximately 35 seconds. After wait time , the board will start second try for ignition by sparking for approximately 60 seconds . If there is still no positive ignition the board will go into lock out.

Fan Operation: The standard fan can be operated by using the remote control supplied with this unit. See remote control instructions.
Note: In thermostat mode: When the appliance is turned on, the fan will not come on for the first 5 minutes (if fan is turned on). When the appliance is turned off the fan will not turn off for 12 minutes (if in on position)
Manual mode: Fan will turn on and off immediately using the remote control transmitter if the fan function is in the “on” position.
Continuous Pilot/Intermittent Pilot (CPI/IPI) selection
See remote control instructions for details.

On Demand Pilot (seven day safety timer)
Important information if using the appliance in CPI (continuous pilot mode) only
This appliance is a ProFlame 2 system fitted with the “On Demand” Pilot, a safety feature which will shut down the gas valve completely by extinguishing the pilot light in the event of a continuous full seven days of inactivity. This only applies if the CPI (continuous pilot) switch is in the “on” position in your remote control transmitter.
Each time the main burner shuts down, manually or through the call from the thermostat, the seven day timer starts again.
The seven day inactivity timer is controlled within the circuit board. Therefore, if in CPI mode and when the pilot light is extinguished after seven straight days of inactivity, the CPI setting on the remote control transmitter will remain in the “CPI” (continuous pilot) position. Therefore, all that is required to relight the pilot would be to press the on/off button on the remote control transmitter from “on” to “off” and back to “on”. Once the pilot has re-established operation will resume as normal. There is no requirement to do anything with the IPI/CPI mode on the remote control transmitter. If the unit never goes as long as seven full days without a call for heat, the pilot will remain lit until it is manually shut-off.
If the unit is being operated in IPI (intermittent pilot) mode, neither the above instructions nor the seven day timer will apply.
See the instructions in this manual and on the Lighting Instructions plate on the appliance to light or re-light the pilot.
12 | Grandview® G600EC Gas Fireplace

Copy of Lighting Plate Instructions

owner’s information

FOR YOUR SAFETY READ BEFORE LIGHTING
POUR VOTRE SÉCURITÉ ­ À LIRE AVANT LA MISE EN MARCHE
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or gas supplier.
AVERTISSEMENT : Quiconque ne respecte pas scrupuleusement les instructions de la présente notice risque de déclencher un incendie ou une explosion pouvant entraîner des dégâts matériels ou des blessures pouvant être mortelles. Tout défaut d’installation, de réglage, de modification, de service ou d’entretien peut entraîner des blessures ou des dommages matériels. Reportez-vous au manuel d’utilisation fourni avec cet équipement. Pour obtenir de l’aide ou des informations complémentaires, consulter un installateur ou un service d’entretien qualifié, ou le fournisseur de gaz.
A) This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS – Do not try to light any appliance. – Do not touch any electric switch, do not use any phone in your building. – Leave the building immediately. – Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s instructions. – If you cannot reach your gas supplier, call the fire department.
C) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
A) Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
B) AVANT LA MISE EN MARCHE, reniflez tout autour de l’appareil pour déceler une odeur de gaz. Reniflez au niveau du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ : · Ne tentez pas d’allumer l’appareil · Ne touchez à aucun interrupteur; n’utilisez pas le téléphone se trouvant dans le bâtiment. · Quittez immédiatement le bâtiment. · Appelez immédiatement votre fournisseur de gaz depuis un téléphone extérieur. Suivez les instructions du fournisseur. · Si vous ne pouvez pas rejoindre le fournisseur, appelez le service incendie.
C) N’utilisez pas cet appareil s’il a été plongé dans l’eau, même partiellement. Faites inspecter l’appareil par un technicien qualifié et remplacez tout élément du système de contrôle ou de commande qui a été plongé dans l’eau.
CAUTION: Hot while in operation. Do not touch. Severe burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having flammable vapors away. Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
ATTENTION : Surfaces chaudes lorsque l’appareil est en marche. Ne pas toucher. Risque de brûlures graves. En raison des températures élevées, les enfants, les vêtements et le mobilier, le carburant et tout autre liquide aux vapeurs inflammables doivent être tenus éloignés de l’appareil. Nettoyer régulièrement le brûleur et le compartiment des commandes. Voir les consignes d’installation et d’utilisation fournies avec l’appareil.

OPERATING INSTRUCTIONS

/ CONSIGNES DE FONCTIONNEMENT

  1. STOP! Read the safety information above on this label.

  2. Ensure the Main switch is in the ON position and/or the wall mounted battery holder (if equipped) is in the position.

  3. Press and release the ON/OFF button on the remote handheld transmitter. An audible beep should be heard from the receiver. If not using the remote, the unit can also be turned on by sliding the battery holder switch to the position (if equipped).

  4. After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner.

  5. The unit will turn on. Note: The first attempt to ignition will last approximately 60 seconds. If there is no flame ignition (rectification) the board will stop sparking for approximately 35 seconds. After this wait time, the board will start a second try for ignition by sparking for approximately 60 seconds. If there is still no positive ignition after the second attempt the board will go into lock out. The system will need to be reset as follows (after going into lock out mode):
    a) Wait 5 minutes – turn the system off by pressing the ON/OFF button on the remote. b) After approximately 2 seconds press the ON/OFF button again. c) Unit will repeat step 2. 6) If the appliance will not operate, follow the instructions, “To Turn Off Gas to Appliance” and call your service technician or gas supplier. This appliance is equipped with an on-demand pilot that shuts off after seven days.

  6. STOP! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.

  7. S’assurer que le commutateur principal est en position ON et/ou que le bloc-piles mural (le cas échéant) est en position . 3) Appuyer sur la touche ON/OFF de la télécommande puis relâcher. Un bip sonore retentira depuis le récepteur. Si vous n’utilisez pas la
    télécommande, l’appareil peut également être allumé en faisant glisser le commutateur du bloc-piles sur la position (le cas échéant). 4) Après environ 4 secondes, le système d’allumage produira une étincelle pendant 60 secondes pour allumer le brûleur principal. 5) L’appareil s’allumera. Remarque : Au premier allumage, le système tente d’allumer les flammes pendant 60 secondes. Si l’essai est infructueux, le système fera une pause de 35 secondes. C’est ce qu’on appelle l’étape de rectification. Ce délai écoulé, le système tente à nouveau d’allumer les flammes en produisant des étincelles pendant 60 secondes. Si les flammes ne s’allument toujours pas, le système se met en mode verrouillage. Il faut alors le réinitialiser en suivant les étapes ci-dessous (pour le déverrouiller) :
    a) Attendre 5 minutes et éteindre l’appareil en appuyant sur la touche ON/OFF de la télécommande. b) Attendre 2 secondes et appuyer encore une fois sur la touche ON/OFF. c) L’appareil répètera l’étape 2. 6) Si l’appareil ne fonctionne pas, suivez les instructions “Pour couper le gaz au niveau de l’appareil” et appelez un technicien qualifié ou votre fournisseur de gaz. Cet appareil est équipé d’une veilleuse sur demande qui s’éteint après sept jours.
    TO TURN OFF GAS TO APPLIANCE / POUR COUPER LE GAZ AU NIVEAU DE L’APPAREIL

  8. Press the ON/OFF button on the remote or slide the wall mount switch to the “OFF” position. 2) If service is to be performed­you must disconnect power and shut off gas to the unit. 1) Appuyer sur la touche ON/OFF de la télécommande ou faites glisser l’interrupteur mural sur la position “OFF”. 2) Lors de l’entretien de l’appareil, vous devez débrancher l’alimentation électrique et couper le gaz alimentant l’appareil.

DO NOT REMOVE THIS INSTRUCTION PLATE

NE PAS ENLEVER CETTE ÉTIQUETTE D’INSTRUCTIONS

919-649b

Grandview® G600EC Gas Fireplace | 13

owner’s information

Proflame II Remote Control Operating instructions

IMPORTANT:The Proflame Transmitter 2 is an integrated part of the Proflame 2 System, which consists of these elements: · Proflame 2 Transmitter, to be used in conjunction with: · Integrated Fireplaces Control (Proflame 2 IFC)
The Proflame 2 Transmitter provides for controlling the following hearth appliance functions:
1. Main Burner On/Off 2. Main Burner flame modulation (6 levels) 3. Choice of standing or intermittent pilot (CPI/IPI) 4. Thermostat and Smart thermostat functions 5. Accent light modulation (6 levels) 6. Split flow valve 7. Comfort Fan speed modulation (6 levels)
This feature is not available on any Hampton models.
The Proflame Transmitter uses a streamline design with a simple button layout and informative LCD display (Fig. 1). A Mode Key is provided to index between the features and a Thermostat Key is used to turn on/ off or index through Thermostat functions (Fig. 1 & 2). Additionally, a Key Lock feature is provided (Fig. 22).

TECHNICAL DATA REMOTE CONTROL

Supply Voltage

4.5V (three 1.5V AAA batteries)

Ambient temperature ratings

0 – 50oC (32 – 122oF)

Radio Frequency

315 MHZ

WARNING: THE TRANSMITTER AND IFC ARE RADIO FREQUENCY DEVICES.

ATTENTION!
– Turn “OFF” the main gas supply of the appliance during installation or maintenance of the IFC.
– Turn “OFF” main gas supply to the appliance prior to removing or reinserting the batteries.
– In case of remote control malfunction, turn off the IFC device using the “ON/OFF” main switch.
– For installation / maintenance, switch off the IFC device removing main power supply plug.

Figure 1: Proflame Transmitter

OPERATING PROCEDURE
Pairing the remote control to remote receiver/battery holder (if required)
Power the receiver. Press the PRG button located on the top right hand corner of receiver. The receiver will beep three times to indicate that it is ready to synchronize with a transmitter. Install the 3 AAA type batteries in the transmitter battery bay, located on the base of the transmitter (fig. 3). With the batteries already installed in the transmitter, opush the ON button. The receiver’s command is accepted and sets to the particular code of that transmitter. The system is now initialized.
(*) The receiver may be independent or integral jto the IFC hearth appliance control module. The receiver instruction may not be independent when part of the IFC.

Figure 2: Transmitter LCD Display

14 | Grandview® G600EC Gas Fireplace

Figure 3: Battery Compartment

Temperature indication Display
With the system in the “OFF” position, press the Thermostat Key and the Mode Key at the same time. Look at the LCD screen on the transmitter to verify that a C or F is visible to the right of the room temperature display (Figures 4 & 5).

owner’s information
Remote-Flame Control
The Proflame has six (6) flame levels. With the system on, and the flame level at the maximum in the appliance, pressing the Down Arrow Key once will reduce the flame height by one step until the flame is turned off. The Up Arrow Key will increase the flame height each time it is pressed. If the Up Arrow Key is pressed while the system is on but the flame is off, the flame will come on in the high position. ( Fig. 7 & 8 ) A single “beep” will confirm reception of the command.

Figure 4: Remote Control display in Farenheit.

Figure 5: Remote Control display in Celsius.

Fig. 7

Turn on the Appliance
With the system OFF, press the ON/OFF Key on the Transmitter. The Transmitter display will show some other active Icons on the screen. At the same time the IFC will activate the appliance. A single “beep” from the IFC will confirm reception of the command.
Figure 6: Remote Control display
Turn off the Appliance
With the system ON, press the ON/OFF Key on the Transmitter. The Transmitter LCD display will only show the room temperature (Fig. 6). At the same time the IFC will turn off the appliance. A single “beep” from the IFC confirms reception of the command.

Fig. 8
Room Thermostat (Transmitter Operation)
The Remote Control can operate as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in a room. To activate this function, press the Thermostat Key (Fig. 1). The LCD display on the Transmitter will change to show that the room thermostat is “ON” and the set temperature is now displayed (Fig. 9). To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.

Figure 9

Figure 10

Grandview® G600EC Gas Fireplace | 15

owner’s information
Smart Thermostat (Transmitter Operation)
The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actual room temperatures. As the room temperature gets closer to the set point the Smart Function will modulate the flame down. To activate this function, press the Thermostat Key (Fig. 1) until the word “SMART” appears to the right of the temperature bulb graphic (Fig. 11). To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter (Fig. 12). Note. When Smart Thermostat is activated, manual flame height adjustment is disabled.

Remote Dimmer Control (Bottom Ember Lights)
The bottom ember lights are located near the dimmable light control. To activate this function use the Mode Key (fig. 1) to index to light bulb (fig. 15 & 16). The intensity of the output can be adjusted through six (6) levels. Use the Up/Down Arrow Keys (Fig.1) adjust the output level (Fig. 16). A single “beep” will confirm reception of the command.
Note: This function is available only with the IFC Control Module.

Figure 11: Smart Flame Function

Figure 12

Fan Speed Control**

If the appliance is equipped with a hot air circulating fan, the speed of the fan can be controlled by the Proflame system. The fan speed can be adjusted through six (6) speeds. To activate this function use the Mode Key (fig.1) to index to the fan control icon (Fig. 13). Use the Up/Down Arrow Keys (fig.1) to turn on, off or adjust the fan speed (fig. 14). A single “beep” will confirm reception of the command.

Figure 15

Figure 16

Remote top light control (top light)
The auxiliary function controls the top light. To activate this function use the Mode Key (fig. 1) to index to the AUX icon (fig. 17 & 18). Pressing the Up Arrow Key will activate the outlet. Pressing the Down Arrow Key will turn the outlet off. A single “beep” will confirm the reception of the command.

Figure 13

Figure 14

Figure 17

Figure 18

Split Flow Control
(
Not available on this model)

The secondary burner is controlled by the split Flow. To activate this
function use the Mode Key (fig. 1) to index to the SPLIT FLOW mode icon (fig. 19 & 20).

Pressing the Up Arrow Key will activate the secondary burner. Pressing the Down Arrow Key will turn the secondary burner off. A single “beep” will confirm the reception of the command.

16 | Grandview® G600EC Gas Fireplace

Figure 19

Figure 20

Continuous Pilot/Intermittent Pilot (CPI/ IPI) selection
Note: Power vent models do not have a Continuous Pilot option.
With the system in “OFF” position press the Mode Key (fig. 1) to index to the CPI mode icon (fig. 21 & 22). Pressing the Up Arrow Key will activate the Continuous Pilot Ignition mode (CPI). Pressing the Down Arrow Key will return to IPI. A single “beep” will confirm the reception of the command.

owner’s information
4.The screen will show either “Clr” or “Set” as the first option available is to disable or enable a mode.
5. “Clr” will remove a mode–use the up or down arrow while holding down ON/OFF and MODE (mode icon will disappear once removed).
6. Use the “MODE” button to move to the next function. 7. “Set” will add a mode –use the up or down arrow while holding
down ON/OFF and MODE (mode icon will appear when added). 8. Use the “MODE” button to move to the next function.
Note: You should never program out the fan (if installed) or CPI/IPI mode on the remote.
Key Lock
This function will lock the keys to avoid unsupervised operation. To activate this function, press the MODE and UP Keys at the same time (fig. 23). To de- activate this function, press the MODE and UP Keys at the same time.

Figure 21

Figure 22

CPI/IPI Switch

This appliance comes equipped with a CPI/IPI switch. The functions of both the CPI/IPI switch are as follows: Continuous pilot (CPI) – A pilot that when in operation, is intended to remain continuously ignited until it is manually interrupted.
Intermittent pilot (IPI) – A pilot that is automatically ignited when an appliance is called on to operate and which remains continuously ignited
during each period of main burner operation. The pilot is automatically
extinguished when each main burner operating cycle is completed. The
mode of the fireplace is easily changed from an intermittent pilot ignition system (IPI) to a continuous pilot ignition system (CPI) by using remote control as noted above.
The benefits of having as CPI are as follows: -Keeps venting primed for trouble free start-up under colder weather conditions or inversions.
-Keeps the unit glass warm, which decreases the amount of condensation on start-up
-Provides owners with flexibility to choose a traditional continuous pilot. The primary benefit of having the IPI function is a significant savings on fuel as the pilot will only run when there is a call for heat.
Thermostat Icon: If the thermostat icon is not present on the remote transmitter, follow instructions noted below: 1.Remove one battery from the remote.
2. Press and hold down the Thermostat button on the remote.
3. Reinstall the battery(removed in Step 1) while still holding down thermostat button.
4. If you see “Set” the thermostat option is now enabled. If you see “Clr” the thermostat option is now disabled.
5. Repeat the procedure if the “Set” or “Clr” to remove or add the option back to the remote did not appear.
Enable all other functions if not present on the remote transmitter, follow instructions noted below:
1. Remove one battery from remote.
2. Press and hold both the ON/OFF and MODE button at the same time . 3. Reinstall battery removed in Step 1 while holding both buttons–
keep holding buttons, then release the MODE button only.

Figure 23
Low Battery Power Detection Transmitter
The life span of the remote control batteries depends on various factors: quality of the batteries used, the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Transmitter batteries are low, a Battery Icon will appear on the LCD display of the Transmitter (Fig. 24) before all battery power is lost. When the batteries are replaced this Icon will disappear.
Figure 24
Grandview® G600EC Gas Fireplace | 17

owner’s information
Proflame II Battery Holder Battery Replacement & Battery Pack up if 120 Volt Power is lost

How to replace/add the batteries on battery holder (Proflame 2).

Note : If a wall switch cover plate is installed, first remove cover plate by removing 2 small phillips head screws

STEP 1

Move both the left/right slides as shown below.

The battery compartment will be pushed out slightly, to allow to easily extract it

STEP 2

Extract the battery compartment from the remote receiver/battery holder

Replace 4 x AA batteries and insert the battery compartment back into remote receiver/battery holder

STEP 3

Keeping the battery compartment pressed in, close the left slide

Close the right slide

STEP 4 Reinstall wall cover plate with 2 Phillips head screws.
18 | Grandview® G600EC Gas Fireplace

Safety Screen Removal
1. Slide screen up.
2. Slide screen right.

owner’s information
Glass Door Removal
1. To remove the glass door – place both hands on either side of the latch. Pull forward then up to unlock, repeat on opposite side. Important: After releasing the latches, support the weight of the door.
Latch locations

3. Lower screen down.

2. With both latches released, support the door with both hands and tilt out to approximately a 60 degree angle.
3. Lift the door up and out of lower slots to remove.

4. Swing screen outwards while
keeping the
screen level
and remove.

Glass Door Installation
To install the door–Reverse steps above.

Safety Screen Installation
To install the safety screen–Reverse steps above.

Grandview® G600EC Gas Fireplace | 19

installer’s information

Important Message
SAVE THESE INSTRUCTIONS
The G600EC Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the “authority having jurisdiction” to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with manufacturer’s instructions and all applicable codes.
General Safety Information

9. Wear gloves and safety glasses for protection while doing required maintenance.
10. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11. Under no circumstances should this appliance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12. Installation and any repairs to this appliance should be done by a qualified service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.

1. The appliance installation must conform with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2. The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.

13. Do not slam shut or strike the glass door.
14. Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15. The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).

3. See general construction and assembly instructions. The appliance and vent should be enclosed.
4. This appliance must be connected to the specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per Venting instructions.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

5. Inspect the venting system annually for blockage and any signs of deterioration.

6. Venting terminals shall not be recessed into a wall or siding.

7. Any safety glass removed for servicing must be replaced prior to operating the appliance.

8. To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.

20 | Grandview® G600EC Gas Fireplace

Installation

1. Locate appliance a) Room location (Refer to “Locating Your Gas fireplace” section) b) Clearances to Combustibles (Refer to “Clearances” section) c) Mantle Clearances (Refer to “Combustible Mantel Clearances” section) d) Framing & Finishing Requirements (Refer to “Framing & Finishing” section) e) Venting Requirements (Refer to “Venting” section)
2. Assemble Top Standoffs and Top Facing Support and Side Nailing Strips (Refer to “Unit Assembly Prior to Installation” Section). NOTE: Must be done before installing unit into place.
IMPORTANT: If installing the fan kit or chan-ging this from top vent to rear vent, this must be completed prior to installing the appliance into the framed opening.
3. Install vent (Refer to “Venting” sections).
4. Make gas connections. Test the pilot. Must be as per Diagram (Refer to “Pilot Adjustment” section).
Convert to propane if desired (Refer to “Gas Line Installation” and “Conversion Kit from NG to LPG” sections).
5. Make electrical connections to receptacle supplied with unit (recommended).
6. Install standard and optional features. Refer to the following sections:
a. Standard Glass Door b. Top to rear vent conversion c. Coolwall conversion d. Fan Installation (Optional) e. Nailing flange installation f. Electrical access/120 volt power installa-
tion by others g. Wall Mount On/OFF Switch + Battery
Holder Installation h. Coolwall Clearances/Framing/Finishing i. Clean Front Clearance/Framing/Finishing j. Outside Finish Clearance/ Framing/Fin-
ishing k. LP Conversion (optional) l. Inner Panels or Brick Panels (Must
install one of the options) m. Log Set Installation OR n. Crystal Media Tray o. HeatWave Kit
7. Final check.

This includes: 1. Clocking the appliance to ensure the correct
firing rate (rate noted on label 21,000 Btu/h for natural gas and 20,500 Btu/h for propane), after burning appliance for 15 minutes. 2. If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize. CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
Locating Your Gas Fireplace
1. When selecting a location for your fireplace, ensure that the clearances are met.
2. The appliance must be installed on a flat, solid, continuous surface For example a wood, metal or concrete floor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3. The G600EC Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner

installer’s information
4. This appliance is Listed for bedroom installations using the standard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5. The G600EC Gas Fireplace are approved for alcove installations, see “Clearances” section for details.
6. We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Heatwave Duct System – Optional Kit
The HeatWave Air Duct Kit increases the effectiveness of your fireplace by dispersing warm air from the fireplace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.

Grandview® G600EC Gas Fireplace | 21

installation
Clearance/Framing and Venting Configurations
The G600EC is designed to allow for unique installation options–depending on the desired finish. Please review the options and follow the specific clearance, framing, and finishing options for that application. The applications are as follows: Cool Wall installation-Clean Front & Outside Finish: combustible materials can be installed right up to the fireplace opening with this option. Non Combustible Installation-Clean Front & Outside Finish Applications: non-combustible required when installing materials right to the fireplace opening with this option. Note: The topics listed below can be found in the pages that follow.
· Cool Wall Installation (Combustible Finishing)………………………………………………………………….20 · Non Combustible Installation……………………………………………………………………………………….20 · Unit Assembly Prior to Installation (Nailing Flange Installation) ……………………………………………21 · Nailing Flange Installation …………………………………………………………………………………………..22 · Cool Wall Clearances …………………………………………………………………………………………………24 · Cool Wall Mantel Clearances………………………………………………………………………………………..25 · Cool Wall Mantel Leg Clearances ………………………………………………………………………………….25 · Cool Wall Installation – Framing ……………………………………………………………………………………26 · Cool Wall Installation – Cool Wall Conversion …………………………………………………………………..27 · Chase Venting ………………………………………………………………………………………………………….28 · Chase Vent Installation – Cool Wall ………………………………………………………………………………29 · Clean Front Installation (Non Cool Wall) – Clearances ………………………………………………………..30 · Clean Front Installation (Non Cool Wall) – Mantel Clearances ………………………………………………31 · Clean Front Installation (Non Cool Wall) – Mantel Leg Clearances…………………………………………32 · Clean Front Installation (Non Cool Wall) – Non-Combustible Requirements……………………………..32 · Clean Front Installation – Framing (Non Cool Wall)……………………………………………………………33 · Clean Front Installation………………………………………………………………………………………………34 · Outside Finish Installation (Non Cool Wall) – Clearances …………………………………………………….35 · Outside Finish Installation (Non Cool Wall) – Mantel Clearances …………………………………………..36 · Outside Finish Installation (Non Cool Wall) – Mantel Leg Clearances ……………………………………..36 · Outside Finish Installation (Non Cool Wall) – Framing ………………………………………………………..37 · Outside Finish Finishing …………………………………………………………………………………………….38 · Faceplate Installation (Part # 776-922, 776-924, 776-926)…………………………………………………39 · Finishing Trim Installation (Part #776-928) …………………………………………………………………….40
22 | Grandview® G600EC Gas Fireplace

Cool Wall Installation (Combustible Finishing)
Cool Wall Install: · Vented chase · Combustible material can be used all around the fireplace · Combustible framing

installation

Clean Front
Clean Front Non Combustible Installation
Install: · Non-vented chase · Non-combustible board required · Combustible framing

Outside Finish w/ Finishing Trim

Clean Front

Outside Finish w/ Faceplate Grandview® G600EC Gas Fireplace | 23

installation

Unit Assembly Prior to Installation (Nailing Flange Installation)

After the framing has been built, the nailing Flanges will need to be set depending on the depth of finishing material being used. Up to 1-1/4″ (32 mm) total material thickness can be used, including the backing material. The depth of finishing material can be adjusted in 1/4″ (6 mm) increments.

Left Nailing Flange Right Nailing Flange

1. If venting the unit in a top vent configuration, first intall the top vent heat shield with two screws, as shown.
2. Determine the required depth setting for the materials being used.
3. Once the setting has been chosen, install the Left and Right Nailing Flanges with 2 screws on each Flange.

Header Deflector
Top Nailing Flange
Nailing Flange Parts

24 | Grandview® G600EC Gas Fireplace

Nailing Flange Installation

Finishing

Material

@
11/4″

Depth @

Flush

3/4″

1/4″ Setting

@

@ Front of Fireplace

installation

———-
—–
—–

—–
..
··

-.:– ··-…..
‘f,1′->
\It’ / ._..,.,,,,.
·-

– ‘c::::i’– — — – – – – – · – – – – –
4. Screw one screw into the rear hole on each Side Nailing Flange. 5. Install the Top Nailing Flange with 4 screws.

I I

——–

0
·

· I

0 0
– ···-·-·- ···-··· ····· ··· Top Nailing Flange

– – ·······–··–··- ·- ······–········· ·.·.·.·.·

0

·
0 0

————-

0

————————–

0 0

Grandview® G600EC Gas Fireplace | 25

installation
6. Slot the Header Deflector onto the back screws, then secure the with a screw through the remaining front hole on each flange.
Header Deflector

CLEAN FRONT

OUTSIDE FINISH
Distance to combustible material varies with install

Backing Material (Drywall etc.) Finishing Material
Flush Finishing Material

1-1/4″ (32 mm) Max.

Backing Material (Drywall etc.) Finishing Material

Total Material
Maximum Depth: 1-1/4″ (32 mm)

26 | Grandview® G600EC Gas Fireplace

installation

Cool Wall Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

CAUTION WARNING

· The top, back and sides of the fireplace are
defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

· Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of the greatest importance that this fireplace and vent system be installed in accordance with these instructions.

G600EC Clearance Requirements–Cool Wall Installations

Clearance:

Cool Wall – Clean Front

Measured From:

A: Mantel Height (min.)

1″ (25 mm)**

Top of Fireplace Opening

B: Sidewall

6″ (152 mm)

Side of Fireplace Opening

C: Ceiling

44-1/4″ (1124 mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12″ (305 mm)

Front of Fireplace Opening

E: Alcove Width

84″ (2134 mm)

Wall to Wall (Minimum)

F: Alcove Depth

36″ (914 mm)

Front to Back Wall (Maximum)

G: Convection Air Outlet

58 in2 (374 cm2)*

Top/Front of Enclosure

H: Convection Air Outlet Opening Offset

0-2″ (0-51 mm)

*Top of Chase Enclosure

K: Chase Enclosure (Min.)

74-1/2″ (1892 mm)

From Base of Appliance Floor

L: Clearance to Sprinkler Head (Min.)

36″ (914 mm)

Perpendicular From Chase Grill

Notes:

0″

No Hearth Required

IMPORTANT – *A minimum of 58 square inches (374 cm2) of open area, not lower than 0″-2″ (0 – 51 mm) from top of enclosure, required for all cool wall installations — this can be achieved by having an open area in front. See manual for details. ** An extra 3/4″ (19 mm) of mantel height is required when using a faceplate.

The HeatWave Duct
Kit has different clearance and framing re-
quirements, check the HeatWave manual
for details.

H G

C

K

D

F

A

E
E
F

Sprinkler
L
Chase grill
Side view

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

Alcove

Grandview® G600EC Gas Fireplace | 27

installation
Cool Wall Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram below.
Mantel Clearances
14 12 10 8 6 4 2

0

10

12″ (305 mm)

5 0
Inches

7″ (178 mm)
B

C

1″ (51 mm)

D

A
To Floor

Top of Fireplace Opening

Combustible

Mantel Clearances G600EC
From Top of Fireplace Opening

A
29 3/8″ (746 mm)

B
9-1/4″ (235 mm)

C
5-1/2″ (140 mm)

D
1″ (25 mm)

Note: Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour.
*Note: When the clean-finish and optional faceplate are chosen, overall width changes from 28-3/4″ (730 mm) to 33″ (838mm), and to 32″ (819 mm) when the clean-finish and optional finishing trim are chosen.

Cool Wall Mantel Leg Clearances

TopView

2″ (51 mm)

MMaanntteell lleegg Mantel leg

Side opening of fireplace

28-3/4″ (729 mm) overall fireplace width (*see note above) Clean Finish

1-3/4″ (44 mm)

3″ (76 mm)

6″ (152 mm)

5″ (127 mm)
Allowable mantel leg projection

See framing dimensions on next page.

28 | Grandview® G600EC Gas Fireplace

installation

Cool Wall Installation – Framing

Framing Dimensions M N* O P Q R S (Rear Vent) S (Top Vent) T U V W

Description Framing Width Framing Height Framing Depth Corner Facing Wall Width Corner Facing Wall Width Framed Chase Ceiling Enclosure Vent Centerline Height – Rear Vent Centerline Height – Top Gas Connection Height Gas Connection Inset Gas Connection Width Clearance to Corner of Unit

Cool Wall 33-1/2″ (851mm) 40″ (1016mm) 15″ (381mm) 37-1/4″ (946mm) 52-1/2″ (1334mm) 74-1/2″ (1892mm) 25″ (635mm) 39-1/2″ (1003mm) 1-7/8″ (48mm) 8-3/8″ (213mm) 3-1/2″ (89mm) 1/2″ (13mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.
    Note: The 2 standoffs at the rear of the appliance may be removed as these are not required in this application. Ensure that any screws that are removed are reinstalled. The 2 standoffs can be recycled/discarded.

R

Combustible header
N **M

Top Vent

Rear Vent

** O
S S

P W

T
Q
VU
**The framing depth/width does not take into account dry wall/wood or similar materials against the back /side wall. The framing depth will need to change based on the thickness of the material: (example: M – 33-1/2″ framing width +1/2″ drywall = 34″) (example: O – 15″ framing depth +1/2″ drywall = 15-1/2″)
Grandview® G600EC Gas Fireplace | 29

installation
Cool Wall Installation – Cool Wall Conversion
1. Remove safety screen from unit as per manual. 2. Remove the three screws from the top of the unit, holding the top
cover in place.

6. Remove the inner cover piece and secure it to the left rear side of the unit with one screw as shown.

3. Remove the top cover piece and secure it to the rear right side of the unit with one screw as shown.

7. Loosen the two outermost screws which are accessed through the
holes in the locations show below. NOTE: Do not remove these two screws; loosen them.

4. Remove the strip of insulation.

8. Reach underneath the top of the unit and locate the lower sliding portion of the cool wall assembly. Push this piece toward the back
of the unit as far as it will go to open the cool wall air channel.

5. Remove the three screws from the inner cover piece in the locations shown.

30 | Grandview® G600EC Gas Fireplace

9. Tighten the two outer screws that were loosened to secure the sliding piece in place.

installation
Chase Venting
Note: The enclosure opening cannot be any lower than 0-2″ (0-51mm) from the top of the enclosure for all installations. Minimum height of enclosure from base of appliance is 74-1/2″ (1892 mm).
iAncmluindiimngumthe58eixn5a2m8oppleensinsghoinwnthbeeelonwcl.osure is required to maintain safe opeating temperatures. This can be achieved in a number of ways
Warning: DO NOT cover or place objects in front of the air outlets.

Regency Chase Vent

Custom Chase Vent

Reveal at the Chase Top

Grandview® G600EC Gas Fireplace | 31

installation

(1073 mm)

Chase Enclosure (Cool Wall)
When choosing to install the ventilation openings from the front, the top of the ventilation opening cannot be any lower than 0-2″ (51mm) from the top of the chase enclosure for all installations.
Minimum h(e1ig0h2t omf emncloxs1ur1e 4frommmba)se of appliance is 74-1/2″ (1892mm).
A minimum 58in2 opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including the examples shown in this manual.
IMPORTANT: Exterior wall/Alcove enclosure: When installing into an exterior cavity or alcove enclosure (ceiling, back and sides), regardless of where appliance is placed within the home, requires the use of either drywall or other means such as plywood, wood studs, etc. to prevent heat from escaping anywhere above /through the enclosure other than the required grill / ventilation opening. Internal chase: When installing as an internal chase framing installation ,regardless of where appliance is placed within the home, requires the use of either drywall or other means such as plywood, on the rear wall of the chase to eliminate heat escaping into the rear wall cavity. If the chase is extended to the ceiling ,the ceiling will also need to be finished in a manner to prevent heat escaping into floor joist/attic space.
One of the following methods must be used to prevent the heat from escaping. a. If choosing drywall, ensure that the drywall is butt up tight with no gaps. b. Plywood, wood studs, etc. installed tightly with no gaps.
As this appliance has been designed with all hot air escaping through the chase enclosure ventilation/grill openings only, if hot air is trapped as a result of the hot air escaping through joints, crevasses, open studs, or other openings within the enclosure above, this will change the clearances within the enclosure causing the enclosure to overheat. It is vital that all the hot air from within the enclosure exits through the ventilation openings only. Ensure that the ventilation openings are made as such to prevent debris, objects from falling into the enclosure. Warning: DO NOT cover or place objects in front of the ventilation opening air outlet(s).

MMaaxx. 32″” ((5716mmmm))

Stud

Top of chase enclosure
Ceiling

M40in”i(m1u0m165m8smq). CinhcahsoepVeennintg

Stud

MMaaxx.32″” (7561mmmm))

Stud

Ceiling ToTpopofocfhcahsaeseenecnlocslousruere
M40in”im(1u0m165m8smq.) CinhchasoepVeennintg

Stud

In the example above, the ceiling does not meet the requirement as it is higher than
the specified minimum. Top of chase enclosure is sealed off to meet the 0-2” (51mm) requirement.

32 | Grandview® G600EC Gas Fireplace

installation
Chase Vent Installation – Cool Wall
(Part #776-941) Framed opening must be at least 2 3/8″ (60 mm) tall, and at least 29 3/8″ (746 mm) wide to accomodate the chase vent. The top of the chase vent opening must be 2″ (51 mm) or less from the top of the chase enclosure. Fasten the chase vent with screws and construction adhesive. If the chase vent is not being used, a minimum 58 in2 (374 cm2) opening in the enclosure is required to maintain safe operating temperatures. This can be achieved in a number of ways including a reveal at the top of the chase.
29
(746 mm)
(60 mm)

Ceiling

Side View

Top of enclosure
Max 2″ (51 mm)

Ceiling

Max 2″ (51 mm)

Grandview® G600EC Gas Fireplace | 33

installation

Clean Front Installation (Non Cool Wall) – Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements
The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING
Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these
instructions.

G600EC Clearance Requirements

Clearance:

Dimension

A: Mantel Height (min.)

14″ (356 mm)

B: Sidewall

25″ (635 mm)

C: Ceiling

36″ (914 mm)

D: Mantel Depth (max.)

17″ (432 mm)

E: Alcove Width

84″ (2134 mm)

F: Alcove Depth

36″ (914 mm)

Notes:

0″

Measured From: Top of Fireplace Opening
Side of Fireplace Opening Top of Fireplace Opening Front of Fireplace Opening
Wall to Wall (Minimum) Front to Back Wall (Maximum) No Hearth Required

The HeatWave Duct
Kit has different clearance and framing re-
quirements, check the HeatWave manual
for details.

C D F
A
E
E
F
Alcove
34 | Grandview® G600EC Gas Fireplace

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

installation

Clean Front Installation (Non Cool Wall) – Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the Diagram on the right.

Note: Ensure the paint that is used on the mantel and the facing is “High Quality” or the paint may discolour.

Mantel Clearances

15

10

5

0

25

17″ (432 mm)

20

12″ (305 mm)

Combustible

15
B

10

C

5

5″ (127 mm) 1″ (25 mm)
Min.
D

Non-Combustible Material Min. 13″ H (330mm)

0
Inches

Top of Fireplace Opening

A To Floor

Mantel Clearances G600EC
From Top of Fireplace Opening

A

B

C

D

28-3/8″ (721 mm)

23″ (584 mm)

19-1/4″ (489 mm)

14″ (356 mm)

Grandview® G600EC Gas Fireplace | 35

installation
Clean Front Installation (Non Cool Wall) – Mantel Leg Clearances

TopView
Side opening of fireplace

Allowable mantel leg projection

(38mm)

4-1/4″ (108mm)

2″ (51mm)

*3228–13//24″”((872269mmmm) ) OverallOFvireerpallal FceireWpiladcthe (wCildetahn Finish)

Mantel Leg Mantel leg

1-1/2″ (38mm)

5″
3″ (76mm)

6-7/8″ (175mm)

Clean Front Installation (Non Cool Wall) – Non-Combustible Requirements
33-1/2″ [851mm]

No Combustible Materials in this Area

13″ [331 mm]

NO FACING OR FINISHING MATERIAL
IN THIS AREA

26-3/4″ [679 mm]

3″ [76mm]

3″ [76mm]

28-3/4″ [730mm]

3″ [76mm]

1-5/8″ (41 mm)

36 | Grandview® G600EC Gas Fireplace

See framing dimensions on next page.

installation

Clean Front Installation – Framing (Non Cool Wall)

Framing Dimensions M
N* O

Description Framing Width Framing Height Framing Depth

G600EC – Non Cool Wall 33-1/2″ (851 mm) 40″ (1016 mm) 16-3/4″ (452 mm)

P (Top Vent Only) Q (Top Vent Only) R (Top Vent) R (Rear Vent) S (Rear Vent) S1 (Top Vent) T
U V
W

Corner Facing Wall Width Corner Facing Wall Width Framed Chase Ceiling Framed Chase Ceiling Vent Centerline Height-Rear Vent Centerline Height – Top Gas Connection Height Gas Connection Inset Gas Connection Width Clearance to corner of unit

40″ (1016 mm) 57″ (1448 mm) 60″ (1524 mm) 43-1/2″ (1105 mm) 25″ (635 mm) 39-1/2″ (1003 mm) 1-7/8″ (48 mm) 8-3/8″ (213 mm) 3-1/2″ (89 mm)
2” (51 mm)

**Non-combustible Facing Height

13″ (330 mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth. ** See previous page for details on non-combustible facing requirements above appliance.

R

Combustible header
N **M

Top Vent

Rear Vent

**O

S1 S

S

P W
T
Q
VU
**The framing depth/width does not take into account dry wall/wood or similar materials against the back /side wall. The framing depth will need to change based on the thickness of the material: (example: M – 33-1/2″ framing width +1/2″ drywall = 34″) (example: O – 16-3/4″ framing depth +1/2″ drywall = 17-1/4″)
Grandview® G600EC Gas Fireplace | 37

installation
Clean Front Installation
CLEAN FRONT TRIM INSTALL INSTRUCTIONS:
1. Install the nailing flanges, see manual for instructions.
2. Loosen the four (4) screws that secure the left and right nailing flanges to the unit.
3.Slide the left and right tiling flanges onto the front of the fireplace. Use the slots to center, with the screw securing the nailing flanges (Diagram 1).
4. Tighten screws.
5. Slide the bottom tiling flange against the bottom of the fireplace. Secure with a screw on each side.
6. Finishing material can now be pressed against the flat edge created by the clean front trim (Diagram 2).

26-3/4″ (679 mm)

28-3/4″ (730 mm)

Diagram 1: Exploded View
NOTE: Do NOT finish beyond the dimensions in Diagram 2.

2″ (51 mm)mmaaxx..
Diagram 2: Finishing Dimensions
38 | Grandview® G600EC Gas Fireplace

installation

Outside Finish Installation (Non Cool Wall) – Clearances

The clearances listed below are minimum distances unless otherwise stated.

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Caution Requirements
The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.

WARNING
Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and vent system be installed only in accordance with these
instructions.

G600EC Outside Finish Clearance Requirements

Clearance:

Dimension

Measured From:

A: Mantel Height (min.)

12″ (305 mm)

Top of Fireplace Opening

B: Sidewall

25″ (635 mm)

Side of Fireplace Opening

C: Ceiling

36″ (914 mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

17″ (432 mm)

Top of Fireplace Opening

E: Alcove Width

84″ (2134 mm)

Wall to Wall (Minimum)

F: Alcove Depth Notes:

36″ (914 mm) 0″

Front to Back Wall (Maximum) No Hearth Required

C D F
A
E
E
F
Alcove

Minimum Vent Clearances to Combustibles

Horizontal Top Horizontal Side Horizontal Bottom Vertical Vent

2″ (51 mm) 1-1/2 ” (38 mm) 1-1/2″ (38 mm) 1-1/2″ (38 mm)

Grandview® G600EC Gas Fireplace | 39

installation

Outside Finish Installation (Non Cool Wall) – Mantel Clearances
Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the Diagram below.

Mantel Clearances

15

10

5

0

20

17″ (432 mm)

12″ (305 mm)
15

Combustible

10 B
C
5

5″ (127 mm)
D

Non-Combustible Material Min. 10 1/2″ H (267mm)

0
Inches

A
To Floor

Top of Fireplace

Mantel Clearances G600EC
From Top of Fireplace

A
30″ (762 mm)

B
19-1/2 (495 mm)

C
15-3/4″ (400 mm)

D
10-1/2″ (267 mm)

Note: Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour. **The non combustible board supplied with the appliance is 13″ (330mm) high. This may be cut to size if desired.

Outside Finish Installation (Non Cool Wall) – Mantel Leg Clearances

Mantel Leg Mantel Leg
3 ”

TopView

Side opening of fireplace

4-1/4″ (108mm)

1-1/2″

32″ (813 mm) Overall Fireplace Width (Outside Finish)

6-7/8″ (175mm)
Allowable mantel leg projection

40 | Grandview® G600EC Gas Fireplace

installation

Outside Finish Installation (Non Cool Wall) – Framing

Framing Dimensions

Description

Outside Finish

M

Framing Width

33-1/2″ (851 mm)

N* O P (Top Vent Only) Q (Top Vent Only) R (Top Vent) R (Rear Vent) S (Rear Vent) S1 (Top Vent) T U V W

Framing Height Framing Depth Corner Facing Wall Width Corner Facing Wall Width Framed Chase Ceiling Framed Chase Ceiling Vent Centerline Height – Rear Vent Centerline Height – Top Gas Connection Height Gas Connection Inset Gas Connection Width Clearance to Corner of Unit Non-combustible Height

40″ (1016 mm) 16-3/4″ (425 mm)
40″ (1016 mm) 57″ (1448 mm) 60″ (1524 mm) 43-1/2″ (1105 mm) 25″ (635 mm) 39-1/2″ (1003 mm) 1-7/8″ (48 mm) 8-3/8″ (213 mm) 3-1/2″ (89 mm)
2″ (51 mm) 10-1/2″ (267 mm)

  • Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.

R

Combustible header
N **M

Top Vent

Rear Vent

** O

S1 S

S

P W

T

Q
Corner=Top Vent Only

VU

IMPORTANT: Corner applications are vented from the top only – rear venting cannot be used.

**The framing depth/width does not take into account dry wall/wood or similar materials against the back /side wall. The framing depth will need to change based on the thickness of the material:
(example: M – 33-1/2″ framing width +1/2″ drywall = 34″) (example: O – 16-3/4″ framing depth +1/2″ drywall = 17-1/4″)

Grandview® G600EC Gas Fireplace | 41

installation
Outside Finish Finishing
Finishing material may be brought to the top and side edges of the fireplace, as show below.
29-7/8″ (758 mm)
31-7/8″ (81 mm)
42 | Grandview® G600EC Gas Fireplace

Faceplate Installation (Part # 776-922, 776-924, 776-926)
A 1/2″ (13 mm) gap must be maintained on the sides of the fireplace to allow the Face Plate to be installed and removed.
Do NOT finish past the front face of the fireplace.
3 ” (19 mm) 4

Mounting Tab Folded Forward

Framing

Nailing Flange folded forward
Face Plate

Nailing Flange Tabs folded forward
Mounting Tabs folded forward

installation

30-7/8″ (784 mm)
33-3/4″ (857 mm)

33″ (838 mm)

Install the faceplate by resting the arms on the Face Plate on top of the mounting tabs.
Adjust left and right to center the Face Plate.

Critical Finishing Gap

NOTE: Do not touch the faceplate without clean, soft, gloves. Dirt or oils can be transferred onto the finish and become permanent.

Grandview® G600EC Gas Fireplace | 43

installation
Finishing Trim Installation (Part #776-928)
The finishing trim can be installed to upgrade the look of the fireplace or to cover facing material edges. 1. Lay the parts on a soft surface, painted side down. 2. Insert the tab on the left side in to the slot on the top. 3. Fold the tabs down to secure. 4. Insert the tab on the top into the slot on the right. 5. Fold the tab down to secure.
See section: Nailing Flange Install for Nailing Flange Depth Settings.

Left Side Right Side

Finishing Trim Install Instructions:
.
1. Bend the four tabs on the outer box front forward. There are two tabs per side. These tabs are the mounts for the faceplate or finishing trim.
tabs
2. Bend the two tabs on the top nailing flange down.
3. Bend the tabs on the left and right nailing flages forward. There are two tabs per nailing flange.

44 | Grandview® G600EC Gas Fireplace

Top and Side Nailing Flange Tabs

A 1Fi/n2is”h(in1g3Trmimm- F)ingisahpingm: ust be maintained on the sides anAd1t/o2″pgoapf mthuestfbireempalainctaeinteod oanllothwe stihdees fainndisthopinogf tthreimfiretpolabcee instotaallleowd tahne dFirneismhinogvTeridm.Ttohbee fininstiaslhleidnagntdrirmemhoavesda. Tdhjeusfintmisheinngt fortrmimahtaesraiadljutsotmpernot tfrour dmeateurpialttoo p1r/o4tr”u(d6e umpmto)1p/4a” spat stthtehefrfroonntt of othf tehefifinniisshhininggtritmri.m.
1. IInnsstatlal tlhl ethfaecefipnlaistehbinygretsrtiinmg tbhye arermsstinongththeefinaisrhminsg torifmthone the tfoinp iosfhthinegmotruinmtinogntabtos.p of the mounting tabs.
2. AAddjujsutsletftleafntdaringdht rtoigchetntteor tchee nfinteisrhitnhgetrifmin. ishing trim.

installation

30-5/8″ (778 mm)

Side View
33″ (838 mm)

Top Nailing Flange Tabs folded down
Nailing Flange Tabs folded forward
Mounting Tabs folded forward
Top View
3″ 43/4″
(19 mm)

30-1/4″ (768 mm)

Mounting Tab Folded forward

33-1/2″ (851 mm)

Critical Finishing Gap

Critical Finishing Gap

Finishing Trim

Nailing Flange folded forward

Grandview® G600EC Gas Fireplace | 45

installation
Wall Board/Drywall Installation G600EC
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified. Finishing Instructions: It is important to follow the framing and finishing instructions to ensure proper placement of fireplace into the surrounding framing/finishing materials. Wall board materials 1/2in. (13mm) thick are specified in this installation manual to properly align with the optional finishing methods offered with this appliance. The G600EC may be finished to the appliance opening with 1/2 inch (13mm) thick drywall or non combustible material depending on the application and requirements. The nailing flanges allow for adjustments up to 1-1/4″ (32mm) thickness of material. · Ensure that the back and side clearances are maintained. WARNING! Risk of Fire! Maintain specified air space clearances to combustibles. Inadequate air space could cause overheating and fire. The appliance is designed to be used with 1/2in. (13mm) wall sheathing materials such as drywall, plywood, wood composites, or non-combustible materials. Thicker materials may be used. Refer to facing and finishing details in this manual. Facing Material · Facing and/or finishing materials must never overhang into the glass opening. · Facing materials may be combustible or non-combustible WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation. PAINTING If desired finishing includes a painted wall, 100% acrylic latex, oil-based or standard acrylic paints may be used. Follow paint manufacturer’s instructions for paint and primer application.
NO SCREW ZONE
46 | Grandview® G600EC Gas Fireplace

installation

Conversion to Rear Vent
Note: This conversion must be done prior to the unit being placed in position.
The unit comes equipped as a top vent unit. These instructions are to be used only if the unit is going to be rear vented. 1. Remove the collar trim piece from the unit by removing 6 screws.
Hidden screw

Diagram 5

4. Remove the intake collar from the top by removing 4 screws.

Hidden screw

Hidden screw

Collar trim piece

Diagram 1
2. Remove the intake cover plate from the rear by removing the top 2 screws and loosening the bottom 2 screws.

Diagram 6

Diagram 2

Diagram 7
5. Remove the exhaust collar from the top by removing the front 4 screws and loosening the screws closest to the back of the unit.

Diagram 3
3. Remove the exhaust cover plate from the rear by removing the top 4 screws and loosening the bottom 2 screws.

Diagram 8

Diagram 4

Diagram 9
Grandview® G600EC Gas Fireplace | 47

installation

6. Install the exhaust cover plate on top using the same screws that previously 8. Install the intake cover plate on top using the same screws that previously

held the exhaust collar.

held the intake collar.

Diagram 10

Diagram 13

7. Install the first piece of supplied insulation by inserting into the area on top of the exhaust cover plate. Position it forward so that the insulation is
held in place by the bend on the exhaust cover plate.

9. Install the second piece of supplied insulation by inserting into the area on top of the intake cover plate.

Diagram 11

Diagram 14

Diagram 12

Push insulation toward front of unit

48 | Grandview® G600EC Gas Fireplace

Diagram 15

10. Install the exhaust collar onto the rear. Hang the collar onto the 2 previ-
ously loosened bottom screws, secure in place with the 4 top screws, and then tighten the 2 bottom screws.

12. Reinstall the collar trim with 6 screws.

installation

Diagram 16

Diagram 19

Hidden screw

Diagram 17
11. Install the intake collar onto the rear. Hang the collar onto the previously loosened bottom screws, secure in place with the 2 top screws, and then tighten the 2 bottom screws.

Diagram 18

Grandview® G600EC Gas Fireplace | 49

installation
Vent Restrictor Installation (Part # 776-027)
1. Determine the venting configuration.
2. Go to venting arrangements section (in the manual) to determine if a vent restrictor setting is required. (If required, proceed to Step 3).
3. Loosen the two screws that secure the top heat deflector and remove top heat deflector (diagram 1).
4. Align the vent restrictor plate (found in the manual package) to the required vent restrictor position, per the diagrams below.
5. Once the vent restrictor plate is in the required position, secure with 2 – 1/4″ (57 mm) x 1/2″ (13mm) screws. Ensure all screws are tight.

Diagram 1: Top baffle

Restrictor Plate

Set 3, 1-1/2″ (38 mm) open

Restrictor plate for Set 1, 2″ (51mm) open

Diagram 2: Vent restrictor located on top exhaust assembly

Set 4, 1-1/4″ (32mm) open

Venting Introduction
The G600EC uses the “balanced flue” technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it’s own separate vent system. Common vent systems are prohibited.

Set 2, 1-3/4″ (44mm) open

Set 5, 1″ (25mm) open

50 | Grandview® G600EC Gas Fireplace

Exterior Vent Termination Requirements

installation

Minimum Clearance Requirements

Canada1

USA2

A Clearance above grade, veranda, porch, deck, or balcony

12″(30cm)

12″(30cm)

B Clearance to window or door that may be opened C Clearance to permanently closed window

12″(30cm) *

9″ (23cm) *

D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code)

24″(60cm)

24″(60cm)

E Clearance to unventilated soffit

19″(48cm)

19″(48cm)

F Clearance to outside corner: with AstroCap Termination Cap.

13″(33cm)

13″(33cm)

Clearance to outside corner: with all other approved Termination Caps.

13″(33cm)

13″(33cm)

G Clearance to inside corner: with AstroCap Termination Cap

11″(28cm)

11″(28cm)

Clearance to inside corner: with all other approved Termination Caps. H Clearance to each side of center line extended above meter/regulator assembly

11″(28cm) 36″(90cm)a

11″(28cm) *

J Clearance to service regulator vent outlet

36″(90cm)

K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance L Clearance to a mechanical air supply inlet

3′ (91cm) above if within 10′ (3m) horizontally.

12″(30cm) 72″(1.8m)

9″ (23cm) 36″(90cm)b

M Clearance above paved sidewalk or a paved driveway located on public property

84″(2.1m)

N Clearance under veranda, porch, deck, or balcony

12″(30cm)

1 In accordance with current CSA B149.1, Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor

  • a

Clearance in accordance with local 3 feet (91cm) within a height of 15

installation codes and the requirements of the gas feet (4.5m) above the meter / regulator assembly

supplier

b 3 feet (91cm) above – if within 10 feet (3m) horizontally

Grandview® G600EC Gas Fireplace | 51

installation
4″ (102 mm) x 6-5/8″ (168 mm) Rigid Pipe – Cross Reference Chart Only
Components from different Manufacturers may not be mixed. Not all Rigid Pipe components are available directly from FPI. Non-metallic venting systems shall not interchange components with another listed or unlisted metallic vent system. Note: Olympia Ventis DV is only approved for certain models. See list of approved models in cross-reference chart.

Description
6″ Pipe Length-Galvanized 6″ Pipe Length-Black 7″ Pipe Length-Galvanized 7″ Pipe Length-Black 9″ Pipe Length-Galvanized 9″ Pipe Length-Black 12″ Pipe Length-Galvanized 12″ Pipe Length-Black 18″ Pipe Length-Galvanized 18″ Pipe Length-Black 24″ Pipe Length-Galvanized 24″ Pipe Length-Black 36″ Pipe Length- Galvanized 36″ Pipe Length-Black 48″ Pipe Length-Galvanized 48″ Pipe Length- Black 60″ Pipe Length-Galvanized 60″ Pipe Length-Black

Simpson Direct Vent Pro®
46DVA-06 46DVA-06B N/A N/A 46DVA-09 46DVA-09B 46DVA-12 46DVA-12B 46DVA-18 46DVA-18B 46DVA-24 46DVA-24B 46DVA-36 46DVA-36B 46DVA-48 46DVA-48B 46DVA-60 46DVA-60B

*Selkirk Direct TempTM
4DT-6 4DT-6B N/A N/A 4DT-9 4DT-9B 4DT-12 4DT-12B 4DT-18 4DT-18B 4DT-24 4DT-24B 4DT-36 4DT-36B 4DT-48 4DT-48B 4DT-60 4DT-60B

*American Metal Products® Amerivent Direct N/A N/A 4D7 4D7B N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

*Metal-FabTM Sure Seal
4D6 4D6B N/A N/A N/A N/A 4D12 4D12B 4D18 4D18B 4D24 4D24B 4D36 4D36B 4D48 4D48B N/A N/A

Adjustable Length 3″-10″-Galvanized N/A

N/A

Adjustable Length 3″-10″-Black

N/A

N/A

Adjustable Length 7)-Galvanized

N/A

N/A

Adjustable Length 7″-Black

N/A

N/A

Extension Pipe 8-1/2″-Galvanized

46DVA-08A

N/A

Extension Pipe 8-1/2″-Black

46DVA-08AB

N/A

Adjustable Length 12″-Galvanized N/A

N/A

Adjustable Length 12″-Black

N/A

N/A

Extension Pipe 16″-Galvanized

46DVA-16A

N/A

Extension Pipe 16″-Black

46DVA-16AB

N/A

N/A N/A 4D7A 4D7AB N/A N/A 4D12A 4D12A N/A N/A

4DAL 4DALB N/A N/A N/A N/A N/A N/A N/A N/A

45º Elbow-Galvanized 45º Elbow-Black 45º Elbow Swivel-Galvanized 45º Elbow Swivel-Black 90º Elbow-Galvanized 90º Elbow-Black 90º Elbow, Swivel-Galvanized 90º Elbow, Swivel-Black 90º Starter Elbow, Swivel-Galvanized Adaptor*

46DVA-E45

4DT-EL45

46DVA-E45B

4DT-EL45B

See 46DVA-E45 N/A

See 46DVA-E45B N/A

46DVA-E90

4DT-EL90S

46DVA-E90B

4DT-EL90SB

See 46DVA-E90 N/A

See 46DVA-E90B N/A

N/A

N/A

N/A

N/A

4D45L 4DT-EL45B N/A N/A 4DT-EL90S 4DT-EL90SB N/A N/A N/A N/A

N/A N/A 4D45L 4D45LB N/A N/A 4D90L 4D90LB 4D90A 4D90L

Ceiling Support Cathedral Support Box Wall Support/Band Offset Support Wall Thimble-Black Wall Thimble Cover/Ceiling Support Firestop Spacer Trim Plate- Black * Not available from Regency

N/A 46DVA-CS 46DVA-WS 46DVA-ES 46DVA-WT 46DVA-DC 46DVA-FS N/A

52 | Grandview® G600EC Gas Fireplace

4DT-CS 4DT-CSS 4DT-WS/B 4DT-OS 4DT-WT N/A 4DT-FS 4DT-TP

4DSP 4DRSB 4DWS N/A 4DWT N/A 4DFSP 4DFPB

4DFSP 4DRS 4DWS N/A 4DWT N/A 4DFS 4DcP

*Security

*ICC Excel

Secure- Vent® Direct

SV4L6 SV4LB6 N/A N/A N/A N/A SV4L12 SV4LB12 SV4LA SV4LA SV4L24 SV4LB24 SV4L36 SV4LB36 SV4L48 SV4LB48 N/A N/A

TC-4DL6 TC-4DL6B N/A N/A TC-4DL9 TC-4DL9B TC-4DL1 TC-4DL1B TC-4DL18 TC-4DL18B TC-4DL2 TC-4DL2B TC-4DL3 TC-4DL3B TC-4DL4 TC-4DL4B N/A N/A

N/A N/A N/A N/A N/A N/A SV4LA12 SV4LBA12 N/A N/A

TC-4DLT TC-4DLTB N/A N/A N/A N/A TC-4dLSI TC-4dLSIB N/A N/A

N/A N/A SV4E45 SV4EB45 N/A SV4EBR90-1 SV4E90-1 wSV4EB90-1 N/A N/A

TE-4DE45 TE-4DE45B N/A N/A TE-4DE90 TE-4DE90B N/A N/A N/A N/A

SV4SD SV4CSB SV4BM SV4SU SV4RSM SV4PF SV4BF SV4LA

TM4-RDS TM4-SDS TM-SWS TM-SOS N/A N/A TM-4CS TM-4TP

*Olympia Ventis DV***
VDV-0406 VDVB-0406 N/A N/A VDV-0409 VDVB-0409 VDV-0412 VDVB-0412 VDV-0418 VDVB-0418 VDV-0424 VDVB-0424 VDV-0436 VDVCB-0436 VDV-0448 VDVB-0448 N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
VDV-EL0445 VDVB-EL0445 N/A N/A VDV-EL0445 VDVB-EL0445 N/A N/A N/A VDV-UAA04
VDV-SCR04 VDV-CSS04 VDV-WS04 N/A VDV-WPT04 N/A VDV-FS04 VDV-WTC04

installation

Description

Simpson Direct Vent Pro®

Attic Insulation Shield 12″

46DVA-IS

Attic Insulation Shield – Cold Climates 36″ N/A

*Selkirk Direct TempTM
N/A N/A

*American Metal Products® Amerivent Direct
4DAIS12
4DAIS12

*Metal-FabTM Sure Seal
4DIS N/A

*Security Secure- Vent®
SV4RSA N/A

*ICC Excel Direct
N/A TM-4AS

*Olympia Ventis DV***
VDV-AIS04 N/A

Basic Horizontal Termination Kit (A) Horizontal Termination Kit (B) Vertical Termination Kit

46DVA-KHA N/A N/A

4DT-HKA 4DT-HKB 4DT-VKC

4DHTK2 4DHTK1 4DHTK

4DHTKA 4DHTKB 4DHTK

SV-SHK SV-HK SV-FK

TM4-HTK TM4-HTK N/A

VDV-KW04 VDV-K04 N/A

High Wind Vertical Cap High Wind Horizontal Cap
Horizontal Square Termination Cap Vertical Termination Cap Storm Collar

46DVA-VCH N/A
46DVA-HC 46DVA-VC 46DVA-SC

N/A N/A
4DT-HHC 4DT-HVC 4DT-SC

N/A N/A
4DHC 4DVC 4DSC

N/A N/A
4DHT 4DVT 4DSC

N/A N/A
SV4CHC-1 SV4CGV-1 SV4FC

TM-4VT TM-4DHT
TM-4HT N/A TM-SC

VDV-VCHW04 N/A
VDV-HC04 N/A VDV-SC04

Flashing – Flat Roof Adjustable Flashing 0/12-6/12 Adjustable Flashing 6/12-12/12
Vinyl Siding Standoff Vinyl Siding Shield Plate

46DVA-FF 46DVA-F6 46DVA-F12
46DVA-VSS N/A

N/A 4DT-ST14 4DT-ST36
4DT-VS 4DT-VSP

N/A 4D12S 4D36S
N/A N/A

N/A 4DF 4DF-12
4DVS N/A

N/A SV4STC14 SV4STC36
SV4VS SV4VS

N/A TF-4FA TF-4FB
TM-VSS N/A

N/A VDV-F0406 VDV-SSO
N/A N/A

Snorkel Termination 14″ Snorkel Termination 36″

46DVA-SNK14

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

TM-4ST14 N/A TM-4ST36 N/A

Wall Firestop

46DVA-WFS

N/A

N/A

N/A

N/A

TM-4TR

VDV-FS04

  • Not available from Regency
    ***Olympia Ventis DV application for the following units only when using 4″ x 6-5/8″ vent system: B36XTE, B36XTCE, all City Series 40 models, CV72E/CB72E (power-vented models only), G600C, G600C-1, G600EC, G800C, G800C-1, G800EC, P36, P36E, and RC500E.

FPI 946-506/P **510-994 640-530/P

Vent Guard (Optional) for AstroCap Rigid Pipe Adaptor (Must use with all rigid piping) Riser Vent Terminal

946-205 946-208/P 946-523/P 946-206

Vinyl Siding Shield for Riser Vent Terminal Vent Guard (Optional) for Riser Vent Terminal AstroCap Horizontal Cap Vinyl Siding Standoff for AstroCap

**The rigid pipe adaptor is not required on the C34, C34E, U39, U39E, H15, H27, H35 & RC500E. Note: When using Metal-Fab Sure Seal Rigid Piping – please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Offset Pipe Selection: Use this table to determine offset pipe lengths.

Pipe Length (L)

4″ x 6-5/8″ Venting

Run (X)

Rise (Y)

For specific instructions on venting components – visit the manufacturers website listed below.

0″ (0mm)

4-7/8″ (124mm)

13-7/8″ (340mm)

Simpson Direct Vent Pro: www.duravent.com

6″ (152mm)

8″ (203mm)

16-1/2″ (419mm)

Selkirk Direct-Temp: www.selkirkcorp.com

9″ (229mm)

10-1/8″ (257mm)

18-5/8″ (473mm)

American Metal Products: www.americanmetalproducts.com

12″ (305mm)

12-1/4″ (311mm)

20-3/4″ (527mm)

Metal-Fab Sure Seal: www.mtlfab.com

24″ (610mm)

20-5/8″ (524mm)

29-1/8″ (740mm)

Security Secure Vent: www.securitychimneys.com

36″ (914mm)

29″ (737mm)

37-1/2″ (953mm)

Industrial Chimney Company: www.icc-rsf.com

48″ (1219mm) 37-7/16″ (951mm)

45-15/16″ (1167mm)

Olympia Ventis DV: www.olympiachimney.com

Note: Horizontal runs of vent must be level, or have a 1/4″ rise for every 1 foot of run towards the termination. Never allow the vent to run downward – this could cause high temperatures and may present a possible fire hazard.

Olympia Ventis DV: www.olympiachimney.com
Grandview® G600EC Gas Fireplace | 53

installation

Venting Arrangements for Horizontal Terminations – Flex Vent or Rigid Pipe 4″ (102mm) x 6-5/8″ (168mm)
The Diagrams show all allowable combinations of vent runs with 4″ (102 mm) x 6-5/8″ (168 mm) venting using the Regency direct vent system or rigid vent system. A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent maximum horizontal length of 3ft (0.9m).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe vent systems.
· Maintain clearance to combustibles. · Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall.

Vertical Height (Feet)
Rigid 39-1/2″ (1.1 m) Flex 39-1/2″ (1.1 m)
25″ (0.64 m)

Horizontal (Feet)

2

4

6

8

0

12

10

8

Set 2

Set 1

6

4

2 Max. 36″ (0.9 m)
0
Top Vented Set #1: 2″ (51mm) open between 1-3′ (0.3 – 0.91 m) hori-
zontal Set #2: 1-3/4″ open (44mm) less than 1′ (0.3 m) horizontal

24″ (0.61 m)
Rear Vented Factory Setting – 2-1/2″ (64mm)

54 | Grandview® G600EC Gas Fireplace

installation

Rigid Pipe Venting Systems – Horizontal or Vertical Terminations
The minimum components required for a basic horizontal termination are:

1 Horizontal Termination Cap 1 90o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.

Flat Wall Installation

Wall Thickness (inches)

Vent Length Required (inches)

4″ (102mm) – 5-1/2″ (140mm)

6″ (152mm)

7″ (178mm) – 8-1/2″ (216mm)

9″ (229mm)

10″ (254mm) – 11-1/2″ (292mm)

12″ (305mm)

9″ (229mm) – 14-1/2″ (368mm)

11″ (279mm) – 14-5/8″ (371mm) Adj. Pipe

15″ (381mm) – 23-1/2″ (597mm)

17″ (432mm) – 24″ (610mm) Adj. Pipe

Corner Installation

Wall Thickness (inches)

Vent Length Required (inches)

3-1/4″ (83mm) – 6-3/4″ (171mm)

11″ (279mm) – 14-5/8″ (371mm) Adj. Pipe

7-3/4″ (197mm) – 16-1/4″ (413mm)

17″ (432mm) – 24″ (610mm) Adj. Pipe

7-1/4″ (184mm) – 8-3/4″ (222mm)

6″ (152mm) + 12″ (305mm) 9″ (229mm) + 9″ (229mm)

4-1/4″ (108mm) – 5-3/4″ (146mm)

6″ (152mm) + 9″ (229mm)

Vertical Termination
Cap Storm Collar
Flashing
Ceiling Firestop
Pipe Length

Vinyl Siding Standoff (Optional)

Horizontal Termination
Cap

Wall Thimble
Adj.Pipe Length 11″ – 14-5/8″
90o Elbow

24″ Pipe Length
Rigid Pipe Adaptor

Alternate Horizontal Termination
Caps
WARNING: Do not combine venting components from different venting systems. However use of the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with DuraVent Direct Vent, Selkirk Direct-Temp, Ameri Vent Direct venting, Olympia Ventis DV and Security Secure Vent systems. Use of these systems with the Rigid Pipe Adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.

The FPI AstroCapTM and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent , American Metal Products, Olympia Ventis DV, Security Secure Vent®, AmeriVent Direct Vent. AstroCapTM is the proprietary trademark of FPI Fireplace Products
International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.

Grandview® G600EC Gas Fireplace | 55

installation
Venting Arrangements – Horizontal Termination – Rigid Pipe and FPI Direct Vent System (Flex) (Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow). Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems.

Horizontal (Feet)

2

4

6

8

10

12

14

16

18

20

0

18

16
Set #2 (1-3/4″ open)
14

12

Vertical Height (Feet)

10

8
Set #1 (2″ open)
6

4

2

39-1/2″ (1.1 m) Minimum Height

Requirement

0

· Maintain clearances to combustibles.
· Horizontal vent must be supported every 3 feet. · Firestops are required at each floor level and whenever passing through a wall.

All Rigid Pipe System 4″ (102 mm) inner diameter 6-5/8″ (168 mm) outer diameter
FPI Flex Vent 4″ (102 mm) inner diameter 6-7/8″ (175 mm) outer diameter
Note: A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Note: FPI Direct Vent Flex System Part #:946-513 (2 foot / 0.61 m), 946-515 (4 foot / 1.22 m) and 946-516 (10 foot / 3.05 m) only are approved for horizontal terminations.

56 | Grandview® G600EC Gas Fireplace

installation

Venting Arrangements – Vertical Termination – Rigid Pipe System and Vertical Flex Kit to Same
Limitations (Propane & Natural Gas)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with rigid pipe vent systems for Propane and Natural Gas.

Horizontal (Feet)

0

3

6

9

12

Horizontal (Feet)

0

2

4

6

8

10

12

37

35

33

31

Set #4

29

(1-1/4″ open)

27

25

37

35

33

31

29

27

Set #5

25

(1″ open)

Vertical Height (Feet) Vertical Height (Feet)

23

23

21 19 17

15 13

11 9

7

8′ V

Min.

5

3

1 0

Set #3 (1-1/2″ open)
Set #1 (2″ open)
39-1/2″ (1.1 m) Minimum Height Requirement

21

19 17

15

13

Set #4

(1-1/4″ open)

11

9

7

8′ V

Min.

5

3
1 0

· Vent must be supported at offsets. · Firestops are required at each floor level and whenever passing through a wall. · Maintain clearances to combustibles.
Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part

510-994).

Grandview® G600EC Gas Fireplace | 57

installation
Horizontal Terminations – Two 90°Elbows

One 90o elbow = Two 45o elbows.

Option V

H + H1

With these options, maximum

A) 0′ Min.

2′ (0.61 m) Max.

total pipe length is 30 feet (9.14 m) with minimum of 6 feet (1.82

B) 1′ (0.3 m) Min. 3′ (0.91 m) Max. m) total vertical and maximum

H1

C)

2′ (0.61 m) Min.

4′ (1.22 m) Max.

8 feet (2.44 m) total horizontal. Please note minimum 1

D) 3′ (0.91 mm) Min. 5′ (1.52 m) Max. foot (0.3 m) between 90o elbows is required.
E) 4′ (1.22 m) Min. 6′ (1.82 m) Max.

F) 5′ (1.52 m) Min. 7′ (2.13 m) Max.

G) 6′ (1.82 m) Min. 8′ (2.44 m) Max

Restrictor Set #1 – 2″ (51 mm) open. Lengths do not include elbows indicated. *Required when using rigid venting.

H

V

Horizontal Terminations Three 90o Elbows

One 90o elbow = Two 45o elbows.

Option A) B) C) D) E) F)
G)

V 0′ Min. 1′ (0.3 m) Min. 2′ (0.61 m) Min. 3′ (0.91 m) Min. 4′ (1.22 m) Min. 5′ (1.52 m) Min.
6′ (1.82 m) Min.

H 1′ (0.3 m) Max. 2′ (0.61 m) Max. 2′ (0.61 m) Max. 2′ (0.61 m) Max. 3 (0.91 m) Max. 4′ (1.22 m) Max.
5′ (152 m) Max.

V + V1
1′ (0.3 m) Min. 3′ (0.91 m) Min. 5′ (1.52 m) Min.
7′ (2.13 m) Min. 9′ (2.74 m) Min. 10′ (3.04 m) Min.
11′ (3.35 m) Min.

H + H1 2′ (0.61 m) Max. 3′ (0.91 m) Max. 4′ (1.22 m) Max. 5′ (1.52 m) Max. 6′ (1.82 m) Max. 7′ (2.13 m) Max.
8′ (2.44 m) Max.

With these options, max. total pipe length is 30 feet (9.14 m) with min. of 12 feet (3.66 m) total vertical and max. 9 feet (2.79 m) total horizontal.
Please note
min. 1 foot (0,3 m) between 90o elbows is required.

H) 7′ (2.13 m) Min. 6′ (1.82 m) Max. 12′ (3.66 m) 9′ (2.74 m) Max. Min.

Restrictor Set #1 – 2″ (51 mm) open. Lengths do not include elbows included. *Required when using rigid venting

H1 V1

H V

58 | Grandview® G600EC Gas Fireplace

Vertical Venting With Two 90o Elbows

One 90o elbow = Two 45o elbows.

Option

V

H

V + V1

With these

A)

0′ Min.

2′ (0.61 m) Max.

1′ (0.3 m) Min.

options, maximum total

B)

1′ (0.3 m) Min. 4′ (1.22 m) Max. 3′ (0.91 m) Min. p i p e l e n g t h

C)

2′ (0.61 m) Min.

5′ (1.52 m) Max.

4′ (1.22 m) Min.

is 30 feet
(9.14 m)with minimum of 7

V1

D)

3′ (0.91 m) 6′ (1.82 m) Max. 5′ (1.52 m) Min. feet (2.13 m)

Min.

total vertical

and maximum

E)

4′ (1.22 m) 7′ (2.13 m) Max. 6′ (1.82 m) Min. 8 feet (2.44 m)

Min.

total horizontal.

F)

5′ (1.52 m) 8′ (2.43 m) Max. 7′ (2.13 m) Min. Please note

Min.

minimum

1 foot between 90o

elbows is

required.

Restrictor Set #1 – 2″ (51 mm) open Lengths do not include elbow indicated.
*Required when using rigid venting

installation

H

V

Vertical Venting With Three 90o Elbows

One 90o elbow = Two 45o elbows.

Option

V

H + H1

V + V1

With these options,

A)

0′ Min.

2′ (0.61 m) Max.

2′ (0.61 m) Min.

maximum total pipe length is 30 feet (9.14

B)

1′ (0.3 m) Min. 2′ (0.61 m) Max. 3′ (0.91 m) Min. m) with minimum

C)

2′ (0.61 m) Min.

3′ (0.91 m) Max.

4′ (1.22 m) Min.

of 10 feet (3.05 m) total vertical

V1

D)

3′ (0.91 m) Min. 4′ (1.22 m) Max. 6′ (1.82 m) Min. and maximum 8

E)

4′ (1.22 m) Min.

5′ (1.52 m) Max.

7′ (2.13 m) Min.

feet (2.44 m) total horizontal.

F)

5′ (1.52 m) Min. 6′ (1.82 m) Max. 8′ (2.44 m) Min.

G)

6′ (1.82 m) Min. 7′ (2.13 m) Max. 9′ (2.74 m) Min. P l e a s e n o t e

H1

minimum 1

H)

7′ (2.13 m) Min. 8′ (2.44 m) Max. 10′ (3.043 m) Min. foot between

90o elbows is

required.

Restrictor Set #1 – 2″ (51 mm) open Lengths do not include elbow indicated.
*Required when using rigid venting

H

V

Grandview® G600EC Gas Fireplace | 59

installation
Venting Arrangements with Co-linear Flex System in a Masonry Chimney Application
IMPORTANT: As shown below, the unit can only be vented from the top, not from the rear.

THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.

Masonry chimneys may take various contours which the flexible liner will accommodate. However, keep the flexible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.

This appliance is designed to be attached to two 3″ (76mm) co-linear aluminium flex running the full length of the chimney. See the Venting Arrangements on next page for minimum and maximum
heights.

Required Parts:

Part # 946-529 948-305 946-563
510-994

Description
Co-linear DV Vertical Termination Cap 3″ (76 mm) Flex – 35 ft. (10.67 m) Co- Axial to Co-Linear Adapter Kit which contains the following: Co-linear Flex Adapter Outer Pipe Inner Pipe Adapter Rigid Pipe Adapter

Co-linear DV Vertical Termination
Cap # 946-529
A maximum of two certified
joiner kits may be used
per length. #948-305 (35 ft)

Flex Liner

Exhaust Flue

Alternate Approved Caps
46dva-VC Vertical Termination Cap 46dva-VCH High Wind Cap 46dva-GK 3″ (76 mm) Co-linear Adapter with
flashing

Outer Pipe with Kit# 946-563

NOTE: See detailed venting arrangements, vertical terminations, co-linear flex system into masonry fireplaces in this manual.

Pipe Length

Rigid Pipe Adapter # 510-994
Top exit only. Cannot be vented from the rear.

90 Degree Elbow Inner Pipe Adapter with Kit# 946-563

Air Intake
Co-Linear Flex
Adapter with Kit# 946-563

60 | Grandview® G600EC Gas Fireplace

installation
Venting Arrangements – Vertical Terminations – Co-linear Flex System Into Masonry Fireplaces FOR BOTH RESIDENTIAL & MANUFACTURED HOMES
IMPORTANT: As shown below, the unit can only be vented from the top, not from the rear. Restrictor at Set #1 (2″ open)

30

30

30

6′ (1.82 m) max. Combined min. of 8′ (2.44 m) Combined max. of 30′ (9.14 m)

Vertical Height (feet)

30′ (9.14 m) Max.

Vertical Height (feet)

30′ (9.14 m) Max.

Vertical Height (feet)

2′ (0.61 m) max.

39-1/2″ 8′ (2,44 m) Min.
1003 mm

2′ (0,61 m) max.

8′ (2,44 m) Min.

39-1/2″ 1003 mm

40″ 1016 mm

Horizontal Distance (Feet)

Horizontal Distance (Feet)

Horizontal Distance (Feet)

Grandview® G600EC Gas Fireplace | 61

installation

Unit Installation With Horizontal Termination
Install the vent system according to the manufacturer’s instructions included with the components.
1. Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.
2. Direct Vent pipe and fittings are designed with special twist-lock connections to connect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent system.
3. Put a bead of Mill-Pac inside the outer section of the adapter and on the inner collar. Slip the adapter over the existing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
4. Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Notes: a) Twist-lock procedure: Four indentations, located on the female ends of pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends, Diagram 1. Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fittings. They may be located by examining the inside of the female ends.
Diagram 1
NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty.
62 | Grandview® G600EC Gas Fireplace

b) Horizontal runs of vent must be supported every three feet. Wall straps are available for this purpose.
5. Mark the wall for a 10″ x 10″ (3.04 m x 3.04 m) square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, i.e. masonry block or concrete, a 7″(178 mm) dia. (7-1/2″ / 191 mm dia. for flex) hole is acceptable.
Note: With Dura-Vent, the minimum height is achieved by installing a 90o elbow directly to the rigid pipe adaptor. Notes:
a) The horizontal run of vent must be level, or have a 1/4 inch (6 mm) rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see Exterior Vent Termination Location.
c) Snorkel Terminations: For installations requiring a vertical rise on the exterior of the building, 14 inch (356 mm) and 36 inch (914 mm) tall Snorkel Terminations are available, as well as the standard Riser Vent. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.
Below Grade Installation
If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Diagram 4. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.
Diagram 2

Note: Riser Vent is only for use in above grade terminations.
Diagram 3 *Diagrams 3 & 4: As specified in CSA B149.1 Installation Code. Local codes or regulations may require different clearances. 6) The arrow on the vent cap should be
pointing up. Insure that the 1-1/2″ (38 mm) clearances to combustible materials are maintained (Diagram 4). Install the termination cap.
Diagram 4 NOTE: For Snorkel terminations in
ABOVE grade installations, follow national or local code requirements.

Diagram 5
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
7. Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe.
8. Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32 mm). Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe.

Unit Installation With Vertical Termination

1. Maintain the 1-1/4″ (32mm) clearances (air spaces) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible
surfaces. Do not pack air
spaces with insulation. Check
for the maximum vertical rise
of the venting system and the
maximum horizontal offset limitations.

2. Set the gas appliance in

its desired location. Drop

a plumb bob down from

the ceiling to the position

of the appliance flue exit,

and mark the location Diagram 1

where the vent will penetrate the ceiling.

Drill a small hole at his point. Next, drop

a plumb bob from the roof to the hole

previously drilled in the ceiling, and mark

the spot where the vent will penetrate

the roof. Determine if ceiling joists,

roof rafters or other framing

will obstruct

the

venting system.

You may wish to relocate

plumber’s tape

the appliance or to offset,

connected to wall strap

as shown in Diagram 2 to

wall strap

avoid cutting

45o Elbows

load bearing

members.

Firestop

Spacer

Diagram 2

installation
4. Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
5. Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/2″ (38 mm). Slip the flashing under the shingles (shingles should overlap half the flashing) as per Diagram 4.
Diagram 4: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed. This allows for
small adjustments. 6. Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (0.91m), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (Diagram 2).
Galvanized pipe is desirable above the roof line due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in Diagram 5 or local codes. Note that for steep roof pitches, the vertical height must be increased.

Diagram 6
Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.
9. Install wall thimble in the center of the 10″ (254 mm) square and attach with wood screws (Diagram 7).

Diagram 7

NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. 3. A Firestop spacer must be installed in the
floor or ceiling of every level. To install the Firestop spacer in a flat ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the firestop.
Diagram 3

Diagram 5

Roof Pitch
flat to 7/12 over 7/12 to 8/12 over 8/12 to 9/12 over 9/12 to 10/12 over 10/12 to 11/12 over 11/12 to 12/12 over 12/12 to 14/12 over 14/12 to 16/12 over 16/12 to 18/12 over 18/12 to 20/12 over 20/12 to 21/12

Minimum Vent Height

Feet

Meters

2

0.61

2

0.61

2

0.61

2.5

0.76

3.25

0.99

4

1.22

5

1.52

6

1.83

7

2.13

7.5

2.29

8

2.44

Grandview® G600EC Gas Fireplace | 63

installation

A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem. 7. Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic. 8. Install the vertical termination cap by twistlocking it. Note: Any

References