eurotech lighting SBSE Square Knockout Emergency LED Bulkhead Installation Guide
- June 15, 2024
- eurotech lighting
Table of Contents
Burly – Square Emergency Bulkhead
Model: SBSE
Installation Instructions
All installations must be carried out by a qualified electrician following
local regulations. Make sure that the power is switched off before
installation. Please read and follow the Installation instructions’ and
Safety instructions’ sections carefully before commencing installation.
Installation of this model can change from time to time please read
instructions every time before installation. For detailed specification,
please go to our website
eurotechlighting.co.nz
Code: | SBSE |
---|---|
Colour: | White |
Dimensions (mm): | 255 x 255 x 85 |
Double Insulated: | Yes |
IP Rating: | IP65 |
Kelvins: | 3000K |
Lumens: | 1500lm |
Material: | Polycarbonate |
Wattage: | 15W |
Product Information
Product Visual
Dimensions
Installation Instructions
- Remove the front diffuser from the base by removing the four diffuser fixing screws and pulling away from the base tray.
- Loosen but do not remove the gear tray retaining screws. Adjust the position of the gear tray to align the hole in the keyhole slots with the retaining screws. Remove the gear tray from the base.
- Select a suitable cable entry point provided or drill out a hole in the base.
- Position and fix the base to a suitable solid surface using the screws provided. Feed the supply cable into the luminaire through a previously selected hole ensuring that the aperture is smooth or use a grommet where possible. Note: If using knock out hole on the side apply silicon to the joint or use IP65 cable gland.
- Ensure that the luminaire has a continuous live supply to L (Unswitch live). The ” Maintained” emergency luminaire can be “switched” via connection Ls (Switched Supply). Ensure battery cells cable is connected.
- Plug in battery, then set colour temperature switch: 1 ON switch 2 OFF switch = 3000K ; 1 ON switch 2 ON switch = 4000K; 1 OFF switch 2 ON switch = 5700K.
- Dress any cables away from the edges of the luminaire and re-align the gear tray. Refit the gear tray using the retaining screws.
- Re-fit the front diffuser to the base using the four diffuser fixing screws. Restore the mains power supply, switch on and test for satisfactory operation.
Emergency luminaire THIS IS A CLASS II PRODUCT
Terminations
L Unswitched Supply
Ls Switched Supply
E
N Neutral
CCT
1
| 2|
---|---|---
ON| OFF|
3000K
ON
| ON| 4000K
OFF| ON|
5700K
Safety Instructions
Read these instructions carefully before commencing installation.
-
The light source contained in this luminaire shall only be replaced by the manufacturer or this service
agent or a similar qualified person. -
This LED luminaire must be installed by a licensed electrician ONLY following all local regulations.
-
Ensure that the cables will not be squeezed or damaged by sharp edges.
-
Clean the light with a soft cloth and a standard PH-neutral detergent.
-
Misuse of/or changes to the appliance shall void all warranties.
-
Do not install on a surface that is not suitable or deformed.
-
Do not install on or above a surface with a high temperature.
-
There should not be any materials that are corrosive, explosive.
For detailed specification, please go to our website eurotechlighting.co.nz
References