MEAN WELL USA Inc SE-1000 Series 1000W Single Output Power Supply User Guide
- June 15, 2024
- MEAN WELL USA Inc
Table of Contents
MEAN WELL USA Inc SE-1000 Series 1000W Single Output Power Supply User
Guide
Features:
- AC input active surge current limiting
- AC input range selected by switch
- Protections: Short circuit / Overload/ Over voltage / Over temperature
- Forced air cooling by built-in DC ball bearing fan
- High power density 7.3w/inch
- With DC_OK signal output
- Built-in remote ON-OFF control
- Built-in remote sense function
- UL/CUL approved
- Low cost
- 2 years warranty
SPECIFICATION
MODEL| SE-1000-5| SE-1000-9| SE-1000-12| SE-1000-15|
SE-1000-24| SE-1000-48
---|---|---|---|---|---|---
**OUTPUT| DC VOLTAGE| 5V| 9V| 12V| 15V|
24V| 48V
RATED CURRENT| 150A| 100A| 83.3A| 66.7A| 41.7A| 20.8A
CURRENT RANGE| 0 ~ 150A| 0 ~ 100A| 0 ~ 83.3A| 0 ~ 66.7A| 0 ~ 41.7A| 0 ~
20.8A
RATED POWER| 750W| 900W| 999.6W| 1000.5W| 1000.8W| 998.4W
RIPPLE & NOISE (max.) **Note.2| 150mVp-p| 150mVp-p| 150mVp-p|
150mVp-p| 200mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 3.3 ~ 5.5V| 7.5 ~ 10V| 10 ~ 13.5V| 13.5 ~ 16.5V| 22
~ 27.5V| 43 ~ 56V
VOLTAGE TOLERANCE Note.3| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 1500ms, 50ms/230VAC 1500ms, 50ms/115VAC
at full load
HOLD UP TIME (Typ.)| 20ms/230VAC 15ms/115VAC at full load
**INPUT| VOLTAGE RANGE| 90 ~ 132VAC / 180 ~ 264VAC
selected by TB2 254 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 81%| 84%| 85%| 86%| 88%| 89%
AC CURRENT (Typ.)| 17.5A/115VAC 10A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC 55A/230VAC
LEAKAGE CURRENT| <2.5mA / 240VAC
****PROTECTION| ****OVERLOAD| 105 ~ 125% rated output power
Protection type : Shut down o/p voltage, re-power on to recover
****OVER VOLTAGE| 5.75 ~ 6.75V| 10.4 ~ 12.2V| 13.8 ~ 16.2V| 18 ~ 21V| 28
~ 32.4V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
****FUNCTION| DC_OK SIGNAL| PSU turn on:3.3V ~ 5.6V
PUS turn off:0 ~ 1V
REMOTE CONTROL| RC+/RC-: 0 ~ 0.8V power on; 4 ~ 10V power off
****ENVIRONMENT| WORKING TEMP.| -20 ~ +60℃ (Refer to
“Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.05%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
****SAFETY & EMC (Note 4)| SAFETY
STANDARDS| UL62368-1, BSMI CNS14336-1, EAC TP TC 004 approved; Design refer
to BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
****EMC EMISSION| Parameter| Standard| Test Level /
Note
Conducted| BS EN/EN55032 (CISPR32)| Class A
Radiated| BS EN/EN55032 (CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| —–
Voltage Flicker| BS EN/EN61000-3-3| —–
****EMC IMMUNITY| BS EN/EN55035, BS EN/EN61000-6-2
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-6-2| 1KV/Line-Line 2KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods,
30% dip 25 periods,>95% interruptions 250 periods
****OTHERS| MTBF| 1273.6K hrs min. Telcordia SR-332
(Bellcore) ; 251.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 27812763.5mm (LWH)
PACKING| 2.5Kg; 6pcs/16Kg/1.38CUFT
NOTE**|
-
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
-
Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
-
Tolerance : includes set up tolerance, line regulation and load regulation.
-
The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com
-
By using UVP circuit, PSU will not turn on direct by in AC continue ON/OFF condition within 5 sec.
-
The ambient temperature derating of 3.5℃/1000m with finless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
-
This power supply does not meet the harmonic current requirements outlined by EN61000-3-2. Please do not use this power supply under the following conditions:
a) the end-devices is used within the European Union, and
b) the end-devices is connected to public mains supply with 220Vac or greater rated nominal voltage, and
c) the power supply is:- installed in end-devices with average or continuous input power greater than 75W, or- belong to part of a lighting system Exception:
Power supplies used within the following end-devices do not need to fulfill EN61000-3-2
a) professional equipment with a total rated input power greater than 1000W;
b) symmetrically controlled heating elements with a rated power less than or equal to 200W
- installed in end-devices with average or continuous input power greater than 75W, or- belong to part of a lighting system Exception:
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification
TB1:AC input terminal
Pin No. | Assignment |
---|---|
1 | AC/L |
2 | AC/N |
3 | FG |
TB2:110/220V Change
Pin No. | 110V | 220V |
---|---|---|
1 | Short | Open |
2
Control Pin (CN3) : JST B6B-XH or equivalent
Pin No. | Assignment | Pin No. | Assignment | Mating Housing | Terminal |
---|---|---|---|---|---|
1 | DC_OK Signal | 4 | +S | JST XHP or equivalent | JST SXH-001Tor equivalent |
2 | DC_OK GND | 5 | RC- | ||
3 | -S | 6 | RC+ |
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
DC_OK Signal
DC_OK Signal is the voltage difference between “DC_OK” and “G” pin output
DC_OK Signal is a TTL level signal
PSU turn on: 3.3 ~ 5.6V
PSU turn off: 0 ~ 1V
Remote Sensing
Between RC+ and RC- | Output |
---|---|
SW OFF(0 ~ 0.8V) | ON |
SW ON(4 ~ 10V) | OFF |
**
**