legrand LE13289AA UPS Keor Compact User Manual

June 15, 2024
Legrand

legrand-logo

legrand LE13289AA UPS Keor Compact

legrand-LE13289AA-UPS-Keor-Compact-product-image

Product Information

Specifications

  • Item: LE13289AA-11/21-01 WP
  • Model: UPS Keor Compact
  • Language: UK English

Introduction
The UPS Keor Compact is a compact uninterruptible power supply (UPS) designed to provide backup power during electrical outages or fluctuations. This user manual provides detailed information on the installation, operation, and maintenance of the UPS Keor Compact.

Purpose of the Manual
The purpose of this manual is to guide users in the proper installation, operation, and maintenance of the UPS Keor Compact.

Symbols in the Manual
The manual uses the following symbols to convey important information:

  • DANGER: Indicates a high degree of risk that, if not avoided, can lead to death or serious injury.
  • WARNING: Indicates a low level of risk that, if not avoided, can lead to minor or moderate injury or material damage.
  • CAUTION: Indicates a low level of risk that, if not avoided, can lead to minor or moderate injury or material damage.
  • INDICATION: Indicates important information that should be read carefully.

Where and How to Keep the Manual
The manual should be kept in a safe, dry place and be easily accessible for reference. It is recommended to make a copy of the manual and store it in a secure location. When contacting the manufacturer or authorized assistance personnel, refer to the equipment’s rating plate data and serial number.

Update of the Manual
The manual reflects the state of the art when the UPS Keor Compact was released. It may not account for new standards or modifications made to the equipment. In such cases, it is recommended to request a new copy of the manual from the manufacturer, quoting the publication code on the cover.

Regulatory and Safety Requirements
Before installing or operating the UPS Keor Compact, it is important to understand and adhere to the regulatory and safety requirements.

General Notes
Ensure compliance with all relevant regulations and safety guidelines when installing and operating the UPS Keor Compact.

Definitions of Skilled Technician and Operator
In this manual, the terms “Skilled Technician” and “Operator” are defined as follows:

  • Skilled Technician: A person with specialized knowledge and training in electrical systems and equipment.
  • Operator: A person responsible for the day-to-day operation of the UPS Keor Compact.

Personal Protective Equipment
When working with the UPS Keor Compact, it is recommended to use appropriate personal protective equipment (PPE) such as gloves and safety glasses to minimize the risk of injury.

Hazard Signs in the Workplace
The workplace should have hazard signs indicating potential dangers associated with the UPS Keor Compact. Familiarize yourself with these signs and follow the necessary precautions.

Signs on the Equipment
The UPS Keor Compact may have signs indicating specific instructions or warnings. Pay attention to these signs and follow the corresponding instructions.

General Warnings
Read and follow all warnings provided in this manual to ensure safe installation and operation of the UPS Keor Compact.

How to Proceed in an Emergency
In case of an emergency, follow the procedures outlined in this manual. This includes first-aid procedures and fire procedures.

Transportation and Placement
The UPS Keor Compact should be transported and placed in accordance with the guidelines provided in this section.

Installation
Proper installation of the UPS Keor Compact is crucial for its optimal performance. Follow the instructions below for a successful installation.

Rear View
Refer to the rear view diagram for a better understanding of the UPS Keor Compact’s connections and components.

Operations
Learn how to operate the UPS Keor Compact effectively using the instructions provided in this section.

Switching on the UPS
To switch on the UPS Keor Compact, follow these steps:

  1. Ensure the UPS is connected to a power source.
  2. Press the power button located on the front panel of the UPS.
  • Normal Mode
    In normal mode, the UPS Keor Compact operates as a backup power supply, providing continuous power during electrical outages.

  • Cold Start
    In cold start mode, the UPS Keor Compact can be started without being connected to a power source. This is useful when no utility power is available.

  • Start-up in Eco Mode
    Eco mode allows the UPS Keor Compact to operate with maximum energy efficiency, reducing power consumption.

  • Start-up in Converter Mode
    Converter mode enables the UPS Keor Compact to convert power from one form to another, ensuring compatibility with specific equipment.

Switch to Bypass
To switch the UPS Keor Compact to bypass mode, follow these steps:

  1. Access the front panel of the UPS.
  2. Locate the bypass switch and move it to the “ON” position.
  • Front Panel
    The front panel of the UPS Keor Compact contains various sections and features for monitoring and controlling the unit.

  • Touch Screen Sections
    The touch screen sections on the front panel allow users to navigate through different menus and settings.

  • Menu Pages
    The menu pages provide access to various configuration options and settings. Use the touch screen sections to navigate through the menu pages.

  • Parameters Section
    The parameters section allows users to adjust and customize specific settings of the UPS Keor Compact, such as input voltage and output frequency.

  • Mimic Display
    The mimic display provides a visual representation of the UPS Keor Compact’s operating status and conditions.

  • Maintenance
    Regular maintenance is essential for ensuring the optimal performance and longevity of the UPS Keor Compact. Follow the instructions provided in this section.\

  • Preventive Maintenance
    Perform regular preventive maintenance tasks to keep the UPS Keor Compact in good working condition. Refer to the maintenance schedule for specific instructions.

  • Periodical Checks
    Periodically check the UPS Keor Compact for any signs of damage or malfunction. This includes inspecting the connections, cables, and battery status.

  • Warehousing
    Proper warehousing of the UPS Keor Compact and its batteries is important to maintain their quality and performance. Follow the guidelines provided in this section.

  • UPS
    Store the UPS Keor Compact in a clean, dry, and secure location. Protect it from dust, moisture, and extreme temperatures.

  • Batteries
    When storing batteries separately from the UPS Keor Compact, ensure they are kept in a cool and dry environment. Follow the manufacturer’s instructions for battery storage.

  • Dismantling
    If necessary, follow the instructions below for dismantling the UPS Keor Compact or its components.

  • Battery Disposal
    Dispose of batteries in accordance with local regulations and environmental guidelines. Contact the appropriate authorities for proper disposal methods.

  • UPS Dismantling
    If the UPS Keor Compact needs to be dismantled, follow the recommended procedures provided by the manufacturer. This may involve disconnecting power sources and removing specific components.

  • Electronic Component Dismantling
    If individual electronic components of the UPS Keor Compact need to be dismantled, refer to the manufacturer’s instructions for safe and proper procedures.

Technical Data
The following technical data provides detailed specifications of the UPS Keor Compact:

  • Model: UPS Keor Compact
  • Input Voltage:
    • 400 ± 20% at full load
    • 400 – 40% ~ -20% at half load (3F+N+PE)
  • Output Voltage: 380/400/415 ± 1% (with static load) (3F+N+PE)
  • Power Capacity: 20kVA
  • Weight: 176kg
  • Dimensions:
    • Width: 260mm
    • Depth: 850mm
    • Height: 890mm

FAQ (Frequently Asked Questions)

  • Q: How often should I perform preventive maintenance on the UPS Keor Compact?
    A: It is recommended to perform preventive maintenance according to the schedule provided in the manual. This will help ensure the UPS remains in optimal condition.

  • Q: Can I start the UPS Keor Compact without a power source?
    A: Yes, the UPS Keor Compact can be started in cold start mode, which allows it to operate without being connected to a power source.

  • Q: How do I switch the UPS Keor Compact to bypass mode?
    A: To switch to bypass mode, locate the bypass switch on the front panel of the UPS and move it to the “ON” position.

  • Q: What should I do in case of an emergency?
    A: In case of an emergency, follow the emergency procedures outlined in the manual. This includes first-aid procedures and fire procedures.

Introduction

Purpose of the manual

  • The purpose of this manual is to provide the operator (see paragraph 2.2.1) with instructions for safely using the Keor Compact UPS, also called “equipment” in the rest of the manual.
  • Extraordinary maintenance operations are not dealt with because they are the sole preserve of the LEGRAND Technical Support Service.
  • The reading of this manual is essential but does not substitute the skill of technical personnel who must have received adequate preliminary training.
  • The intended use and configurations envisaged for the equipment as shown in this manual are the only ones allowed by the Manufacturer.
  • Any other use or configuration must be previously agreed with the Manufacturer in writing and, in this case, the written agreement will be attached to the installation and user manuals.
  • This manual also refers to laws, directives and standards that the operator is required to be aware of and consult.
  • The original text of this publication, drafted in English, is the only reference for the resolution of disputes of interpretation linked to translations into other languages.

Symbols in the manual
Some operations are shown in graphic symbols that draw the attention of the reader to the danger or the importance they imply:

  • DANGER
    This indication shows a danger entailing a high degree of risk that, if not avoided, will lead to death or serious injury or considerable damage to the equipment and things around it.

  • WARNING
    This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or material damage to the equipment and the things around it.

  • CAUTION
    This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or material damage to the equipment and the things around it.

  • INDICATION
    This symbol indicates important information which should be read carefully.

Where and how to keep the manual

  • This manual must be kept in a safe, dry place and must always be available for consultation.
  • It is recommended to make a copy of it and file it away.
  • If information is exchanged with the Manufacturer or the authorized assistance personnel, it is essential to refer to the equipment’s rating plate data and serial number.

INDICATION
The manuals provided with the equipment are an integral part of it and must therefore be kept for its entire lifetime. In case of need (for example in case of damage that even partially compromises its consultation) a new copy must be requested from the Manufacturer, quoting the publication code on the cover.

Update of the manual

  • The manual reflects the state of the art when the equipment was put onto the market. The publication conforms to the directives current on that date. The manual cannot be considered inadequate when new standards come into force or modifications are made to the equipment.
  • Any addition to the manual the Manufacturer considers appropriate to send to the users, must be kept together with the manual of which they will become an integral part.
  • The version of the manual updated to its latest release is available on the Internet at http://www.ups.legrand.com

Manufacturer’s liability and guarantee
The skilled technician and the operator shall scrupulously comply with the precautions and installation instructions indicated in the manuals. They must:

  • always work within the operating limits of the equipment;
  • always carry out constant and careful maintenance through a skilled technician who complies with all the procedures indicated in the installation and maintenance manual.

The Manufacturer declines all indirect or direct responsibility arising from:

  • assembly and cabling made by personnel not fully qualified according to national standards to work on equipment presenting electrical hazards;
  • assembly and cabling made without using safety equipment and tools required by national safety standards;
  • failure to observe the installation and maintenance instructions and use of the equipment which differs from the specifications in the manuals;
  • use by personnel who have not read and thoroughly understood the content of the user manual;
  • use that does not comply with the specific standards used in the country where the equipment is installed;
  • modifications made to the equipment, software, functioning logic unless they have been authorized by the Manufacturer in writing;
  • repairs that have not been authorized by the LEGRAND Technical Support Service;
  • damage caused intentionally, through negligence, by acts of God, natural phenomena, fire or liquid infiltration;
  • damage caused using batteries and protections not specified in the manuals;
  • accidents caused by a wrong assembly of the safety protections or due to the lack of application of the safety labels specified in the installation manual.

The transfer of the equipment to others also requires to hand over all the manuals. Failure to do it will automatically nullify any right of the buyer, including the terms of the guarantee where applicable.
If the equipment is sold to a third party in a country where a different language is spoken, the original owner shall be responsible for providing a faithful translation of this manual in the language of the country where the equipment will be used.

Guarantee terms

  • The guarantee terms may vary depending on the country where the UPS is sold. Check the validity and duration with LEGRAND’s local sale representative.
  • If there should be a fault in the product, contact the LEGRAND Technical Support Service which will provide all the instructions on what to do.
  • Do not send anything back without LEGRAND’s prior authorization.
  • The guarantee becomes void if the UPS has not been brought into service by a properly trained skilled technician (see paragraph 2.2.1).
  • If during the guarantee period the UPS does not conform to the characteristics and performance laid down in this manual, LEGRAND at its discretion will repair or replace the UPS and relative parts.
  • All the repaired or replaced parts will remain LEGRAND’s property.

LEGRAND is not responsible for costs such as:

  • losses of profits or earnings;
  • losses of equipment, data or software;
  • claims by third parties;
  • any damage to persons or things due to improper use, unauthorized technical alterations or modifications;
  • any damage to persons or things due to installations where the full compliance with the standard regulating the specific usage applications have not been guaranteed.

Extension of the guarantee and maintenance contracts

  • The standard guarantee can be consolidated in a single extension contract (maintenance contract).
  • Once the guarantee period has passed, LEGRAND is available for giving a technical assistance service able to meet all requirements, maintenance agreements, 24/7 availability and monitoring.
  • Please, contact the LEGRAND Technical Support Service for further information.

Copyright
The information contained in this manual cannot be disclosed to any third party. Any partial or total duplication of the manual by photocopying or other systems, including electronic scanning, which is not authorized in writing by the Manufacturer, violates copyright conditions and may lead to prosecution.
LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous written authorization.

General UPS description
The UPS systems described in this manual are on-line, double conversion; the inverter included in the UPS always supplies energy to the load, whether the mains is available or not (according to the battery autonomy time).
This configuration guarantees the best service to the user, as it supplies clean power uninterruptedly, ensuring voltage and frequency stabilization at nominal value. Thanks to the double conversion, it makes the load completely immune from micro-interruptions, from excessive mains variations, and prevents damage to critical loads.legrand-LE13289AA-UPS-Keor-Compact-01
\(1\) The UPS uses IGBT technology with a high switching frequency in order to allow a low distortion of the current re-injected into the supply line, as well as high quality and stability of output voltage. The components used assure high reliability, very high efficiency and maintenance easiness.

  • Rectifier [3]
    It converts the three-phase voltage of the AC mains into continuous DC voltage using a three-phase fully controlled IGBT bridge with a low harmonic absorption.
    The control electronics uses a microprocessor of latest generation that allows to reduce the distortion of the current absorbed by mains (THDi) to less than 5%. This ensures that the rectifier does not distort the supply mains, with regard to the other loads. It also avoids cable overheating due to the harmonics circulation.

  • Battery charger / Booster [6]
    A bi-directional DC/DC converter is placed between the battery and the DC bus.
    The converter has a double function. When the mains is present and the rectifier operational the converter works as battery charger, restoring the energy lost by the battery and keeping it in floating charge. In case of mains or rectifier failure the battery supplies energy to the inverter through the converter, which works as booster stage.
    As the mains is back the rectifier provides energy to the inverter and the converter restores its function as battery charger.

  • Inverter [4]
    It converts the direct voltage coming from the rectifier or from the DC battery into alternating AC voltage stabilized in amplitude and frequency.
    The fully digital control of the output sinewave allows to achieve high performances, among which a very low voltage distortion even in presence of high-distorting loads.

  • Battery
    The battery can be installed inside or outside the UPS.
    The battery is charged every time it has been partially or completely discharged. When its full capacity is restored, it is kept floating to compensate for any self-discharge.

  • Static bypass [5]
    The static bypass allows to transfer the load between Inverter and Bypass and vice-versa, in a very short time, and uses SCR’s as power commutation elements.

  • Maintenance bypass [2]
    The maintenance bypass is used to cut off the UPS completely, supplying the load directly from the input mains in case of maintenance or serious failure

UPS operating modes

The UPS has four main operating modes.

Normal operation

  • During normal operation all the circuit breakers/isolators are closed, except for MBP (maintenance bypass).
  • The rectifier is supplied by the AC three-phase input voltage, feeds the inverter and compensates mains voltage as well as load variations, keeping the DC voltage constant. The battery charger keeps the battery charged (floating or boost charge depending on the battery type). The inverter converts the DC voltage into an AC sinewave with stabilized voltage and frequency and supplies the load via its static switch SSB.legrand-LE13289AA-UPS-Keor-Compact-01 \(2\)

Bypass operation
The load can be switched to bypass either automatically or manually. The manual changeover can be performed by display forcing the load to bypass. In case of failure of the bypass line, the load is switched back to inverter without interruption.legrand-LE13289AA-UPS-Keor-Compact-01
\(3\) Battery operation

  • In case of power failure or rectifier fault, the battery feeds the inverter without interruption through the booster converter. The battery voltage drops based on the amplitude of the discharging current. The voltage drop has no effect on the output voltage, which is kept constant by changing the PWM modulation. An alarm is activated when the battery is near the minimum discharge value.
  • In case the supply is restored before the battery is completely discharged, the system will be switched back to normal operation automatically. In the opposite case, the inverter shuts down and the load is switched to the bypass line. If the bypass line is not available or is out of tolerance, the loads supply is interrupted as soon as the battery reaches the discharge limit threshold (black-out).
  • As soon as the supply is restored, the battery charger will recharge the battery. In the standard configuration, the loads are supplied again via static switch SSB when mains is available again. The inverter is restarted when the battery has partially restored its capacity.legrand-LE13289AA-UPS-Keor-Compact-01-21

Maintenance mode
The maintenance bypass operation is necessary whenever the UPS functionality is tested, or during maintenance or repair work. During this mode, the UPS is completely shut down and the load is directly supplied by the bypass line .legrand-LE13289AA-UPS-Keor-Compact-01-22

Regulatory and safety requirements

DANGER
Before carrying out any operation on the equipment, it is necessary to read the entire manual carefully, especially this chapter.

General notes
The equipment has been made for the applications given in the manual. It may not be used for purposes other than those for which it has been designed, or differently from those specified in this manual.
The various operations must be carried out according to the criteria and the chronology described in this manual.

Definitions of “Skilled Technician” and “Operator”

  • Skilled Technician
    The professional that will carry out the installation, start up and ordinary maintenance is called “Skilled Technician”. This definition refers to people qualified by LEGRAND who have the specific technical qualification and are aware of the method of installing, assembling, repairing, bringing online and using the equipment safely.
    In addition to the requirements listed in the paragraph below for a general operator, the Skilled Technician is qualified according to national safety standards to work under dangerous electrical voltage and uses the personal protective equipment required by national safety standards for all the operations indicated in this manual (see the examples listed in paragraph 2.3).

  • INDICATION

    • The safety manager is responsible for protection and company risks prevention according to what is indicated in European directives 2007/30/EC and 89/391/EEC regarding safety in the workplace.
    • The safety manager must ensure that all the people working on the equipment have received all the instructions concerning them in the manual, especially those contained in this chapter.
  • Operator
    The professional assigned to the equipment for normal use is called “Operator”.

    • This definition refers to people who know how to operate the equipment defined in the user manual and have the fol-lowing requisites:
    • technical education, which enables them to operate according to safety standards in relation to the dangers linked to the presence of electric current;
    • training on the use of personal protective equipment and basic first aid interventions.

The company safety manager, in choosing the person (operator) who uses the equipment, must consider

  • the person’s work fitness according to the laws in force;
  • the physical aspect (not disabled in any way);
  • the psychological aspect (mental stability, sense of responsibility);
  • the educational background, training and experience;
  • the knowledge of the standards, regulations and measures for accident prevention.
  • He shall also provide training in such a way as to provide thorough knowledge of the equipment and its component parts.

Some typical activities the operator is expected to carry out are:

  • the use of the equipment in its normal functioning state and the restore of the functioning after it shuts down;
  • the adoption of the necessary provisions for maintaining the quality performance of the UPS;
  • the cleaning the equipment;
  • cooperation with personnel responsible for ordinary maintenance activities (skilled technicians).

Personal Protective Equipment

DANGER

  • The UPS poses a considerable risk of electric shocks and a high short circuit current. During installation, use and maintenance operations, the equipment mentioned in this section must be used.
  • People responsible for operating this equipment and/or passing close to it must not wear garments with flowing sleeves, nor may laces, belts, bracelets or other metal pieces that might cause a danger.
  • The following list sum up the minimum Personal Protective Equipment to wear always.
  • Additional requirements may be needed according to national safety standards.legrand-LE13289AA-UPS-Keor-Compact-01 \(4\)

INDICATION
The skilled technician must work on electrical insulated carpet and he must not wear any kind of metal objects like watches, bracelets, etc.

Hazard signs in the workplace
The following signs must be exhibited at all points of access to the room where the equipment is installed:

  • Electric current
    This sign indicates the electrical live parts.

  • How to proceed in an emergency
    Do not use water to quench fires but just the extinguishers specially designed for putting out fires in electrical equipment.

  • No   smoking
    This sign This sign indicates that smoking is not allowed.

Signs on the equipment

  • Displayed on the UPS are explanatory plates that can vary depending on the country the equipment is intended for and constructional standards applied.
  • Make sure the instructions are adhered to. Removing these plates and working in a way that differs from what written there, is strictly prohibited.
  • The plates must always be clearly read, and they must be cleaned periodically.
  • If a plate deteriorates and/or it is no longer legible, even partially, the Manufacturer must be contacted for another one.

CAUTION
The plates must not be removed or covered. No other plates may be affixed to the equipment without the Manufacturer’s prior written authorisation

WARNING
Potential risks can be drastically reduced by wearing the Personal Protective Equipment listed in this chapter, which are indispensable. Always operate with due care around dangerous areas marked by the appropriate warning notices on the equipment.

General warnings

  • DANGER
    • The UPS works with dangerous voltages. Only skilled technicians qualified and authorized by LEGRAND must perform the installation and ordinary maintenance operations.
    • No part of the UPS can be repaired by the operator.
    • Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel.
  • DANGER
    • Before beginning any installation and/or maintenance operation, make sure that all the DC and AC power sources are disconnected.
    • The UPS and the external battery cabinet, if present, must be installed with an earth connection to avoid high leakage currents. First connect the earthing cable.
    • Check during each installation and/or maintenance operation the continuity of the earthing system.
  • DANGER
    • The UPS is powered by its own DC energy source (batteries). The output terminals may have a dangerous voltage even if the UPS is not connected to the AC power network.
    • Disconnect all batteries before performing any installation and/or maintenance operation
  • WARNING
    • A battery can present a risk of electrical shock and burns by high short-circuit circuit current.

Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. The following precautions should be observed when working on batteries:

  1. remove watches, rings or other metal objects.
  2. use tools with insulated handles.
  3. wear rubber gloves and boots.
  4. do not lay tools or metal parts on top of batteries.
  5. disconnect the charging source prior to connecting or disconnecting battery terminals.
  6. determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
  7. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
  8. never leave live cable terminals without an insulated protection.
  9. When replacing batteries, replace with the same type and number of batteries or battery packs. There is the risk of explosion if batteries are replaced by an incorrect type.

Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. The batteries installed inside the cabinet must be disposed of correctly. For the disposal requirements refer to local laws and relevant standards.

INDICATION
The UPS functions with TT, TN-C and TN-S systems. Input/Bypass and output neutral are not referenced to the same neutral potential.
For TN-C systems, it is necessary to bridge together the input, bypass and output neutral on the terminals during the installation.

CAUTION
Do not open the battery breakers while the UPS is powering the loads in battery mode.

WARNING
To reduce the risk of fire or electric shock, the UPS must work in closed, clean environments with controlled temperature and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must not be above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing.

CAUTION

  • Keor Compact 10 kVA is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
  • All the other models of Keor Compact are products for commercial and industrial application in the second environment – installation restrictions or additional measures may be needed to prevent disturbances.

CAUTION

  • The equipment must be maintained and used according to the instructions of this manual.
  • The departmental manager must instruct the operating and maintenance personnel on the safe use and maintenance of the equipment.
  • Only specifically trained, highly skilled personnel are allowed access to the equipment in order to perform maintenance. While the maintenance operation is being carried out, signs saying “Maintenance work in progress” must be affixed in the department in such a way that they can be easily seen from any access area.
  • Any intervention on the equipment must be done only after it has been disconnected from the power supply network by means of a switch disconnector and must be locked with an appropriate padlock.
  • The UPS must not be turned on if liquid is leaking from the batteries.
  • The equipment used for any maintenance operations (pliers, screwdrivers etc.) must be electrically insulated.
  • Depositing flammable material near the equipment is strictly forbidden. The equipment should always be locked, and only specifically trained personnel are allowed access to it.
  • Do not disable any safety, notification or warning device and do not ignore any alarm, warning message or notice, no matter whether they are generated automatically or represented by plates fixed to the equipment.
  • Do not run the equipment with fixed protections not installed (panels etc.).
  • In case of breaking, buckling or malfunctioning of the equipment or parts of it, repair or replace immediately.
  • For no reason can the structure of the equipment, the devices mounted on it, the operation sequence etc., be modified, manipulated or tampered with in any way, without prior consultation with the Manufacturer.
  • When replacing fuses, only use ones of the same type.
  • The replacement of the batteries is an operation intended to be carried out by a skilled technician.
  • Keep a register in which to enter the date, time, type, performer’s name and any other useful information about each and any routine and extraordinary maintenance operation.
  • Do not use oils or chemical products for cleaning because they could scratch, corrode or damage certain parts of the equipment.
  • The equipment and workplace must be kept completely clean.
  • Upon completion of the maintenance operations, before connecting the power supply, carefully check that no tools and/or material of any kind have been left next to the equipment.

How to proceed in an emergency
The following information are general.
For the specific interventions consult the regulations in force in the country where the equipment is installed.

  1. First-aid procedures
    When administering first aid, adhere to the company rules and the usual procedures.

  2. Fire procedures
    Do not use water to quench fires but just the extinguishers specially designed for putting out fires on electrical equipment.

Transportation and placement
Refer to the installation manual.

Installation

DANGER
All UPS installation operations must be carried out exclusively by a SKILLED TECHNICIAN (paragraph 2.2.1) and he will follow the instructions in the installation manual.

Rear View

  1. Communication Slot 1
  2. Communication Slot 2
  3. Dry Contacts
  4. External Battery Temperature Connector
  5. RS-232 Port for Setting Software
  6. Parallel Communication Ports (Option)
  7. Communication Selector for Service Only
  8. USB Port for Service Only
  9. Terminal Resistor Setting Switch for Parallel Communication
  10. Status LED Indictors
  11. EPO
  12. Backfeed Protection
  13. MBP Detector
  14. Manual Bypass Breaker
  15. Bypass Input Breaker
  16. Mains Input Breaker
  17. Battery Breaker
  18. AC Working Power
  19. Batt. Start
  20. Batt. Working Power
  21. Output Breaker
  22.  X10/X40: Mains/Bypass Input Connections Terminal (1N, 2N, 1L3, 2L3, 1L2, 2L2, 1L1, 2L1)
  23.  X50: Output Connection Terminals (3N, 3L3, 3L2, 3L1)
  24.  X20: External Battery Connection Terminals (B-, B_N, B+)

Operations

Switching on the UPSlegrand-LE13289AA-UPS-Keor-Compact-01
\(1\)

  • AC Power
    This is the auxiliary power switch needed to turn ON the UPS in normal mode. Do not turn OFF the switch while the UPS is working.

  • Batt. Start
    This button is needed only for the cold start-up (see paragraph 5.2.2).

  • Batt. Power
    This switch is needed only for the cold start-up (see paragraph 5.2.2).

Normal mode

  1. In the rear of UPS, turn ON the AC Power switch.
  2. Close the UPS Mains Input and Bypass Input Switches.legrand-LE13289AA-UPS-Keor-Compact-01 \(2\)
  3. Check that the parameters in the configuration setting of the UPS correspond to the UPS installation (see paragraph 5.4.3)
  4. Select on the LCD panel.
  5. Return to the Mimic Display and wait for the start of the rectifier.legrand-LE13289AA-UPS-Keor-Compact-01 \(3\)
  6. Close the battery breakers only after the rectifier has been turned on.legrand-LE13289AA-UPS-Keor-Compact-01 \(4\)
  7. The inverter will be started and supply output voltage.legrand-LE13289AA-UPS-Keor-Compact-01 \(5\)
  8. Close the UPS Output Switch to supply the power to the load.legrand-LE13289AA-UPS-Keor-Compact-01 \(6\)

Cold start

  1. Close the battery breakers.
  2. Turn ON the Batt. Power switch in the rear of UPS.
  3. In the rear of UPS, push and hold down the button “Batt. Start” at least for seven seconds.
  4. Select on the LCD panel.

If you want switch to normal mode operation, apply the procedure of the previous paragraph.
Once the UPS is working in normal mode, turn OFF the Batt. Power switch in the rear of the UPS.

Start-up in Eco mode
This mode effectively improves the overall efficiency. Grid power is routed through the Static Switch to the load. At the same time, grid power continues to charge the battery in DC/DC mode through the rectifier. The Inverter is also kept ready to switch power supply modes at any time.
Select on the LCD panel.

Start-up in Converter mode
Converter mode allows the user to provide a power supply with constant voltage and constant frequency based on their power requirements. The frequency can be set to 50Hz or 60Hz. The voltage options are 380/220V, 400/230V and 415/240V. These can be fine-tuned by ±8V.
Select on the LCD panel.

Switch to bypass
During the normal mode operation of the UPS, select

on the LCD panel. The inverter will be shutdown and the bypass line will supply power to the load.

Front Panel
The UPS is equipped with an LCD touch screen which provides a simple and intuitive user interface. The touch screen is organized with a home page, through which it is possible to access all the main sections, and with a mimic diagram which shows the energy flow and the main input/output operating parameters.

Touch screen sections
The bottom part of the touch screen contains tap-sensible areas which lead to different sections of the UPS monitoring interface.legrand-LE13289AA-UPS-
Keor-Compact-01 \(7\)

  • [A] Display the current time and the status of the UPS
  • [B] Indicate Single or Parallel system, and select the desired UPS unit to check the information
    • Single unit
    • Parallel system
  • [C] Shows the alarm messages
    • The green icon indicates that no alarm is present
    • The red icon indicates the presence of alarms
  • [D] Shows the UPS status
  • [E] Enters the Sub-Menu, if available in that specific page
  • [F] Opens the Menu page (Home)

Menu pages
The Menu page can be opened by tapping the icon .
The pages can be changed by sliding on the screen until the required section is shown. The sections available are:

  • Mimic Display;
  • Command;
  • Monitor;
  • Configuration;
  • Management;
  • Setting;
  • Event Log;
  • Permission Setting.

Each menu also contains sub-sections, which can be accessed by pressing the icon

When entering the Command menu, the following page is shown:legrand-
LE13289AA-UPS-Keor-Compact-01 \(14\)

  • By pressing the icon , the sub-sections can be shown or hidden. legrand-LE13289AA-UPS-Keor-Compact-01 \(16\)
  • Some function pages will also show command buttons.

legrand-LE13289AA-UPS-Keor-Compact-01 \(10\)

The structure of the menu and sub-menu is shown in the following table.

Menu Sub-menu Functions
Mimic Display Display the UPS status, alarms, operating mode and

measurements. See paragraph 5.3.4.
Command 1| Operation|

  • Normal mode
  • ECO mode
  • Converter mode
  • Shutdown
  • Load on bypass
  • Cold start precharge ready

Buzzer & Alarm|

  • Enable/disable buzzer
  • Clear latched alarms and silence buzzer

Other|

  • Force Charger ON
  • Recover backfeed protection signal
  • Clear UPS Maintenance Alarm

Battery Test|

  • Battery Test
  • Turn OFF the Battery Test

Monitor

| Identification| Display UPS information
Real Time Information| Display real time measurements of input, output, bypass and battery
Maintenance Code| Display the maintenance code for technician to check the status of the UPS
Version| Display the control MCU software and firmware version
Configuration| Alarm| Set alarm latch function

  • General alarm
  • Mains alarm
  • Bypass alarm
  • Over temperature
  • Battery low
  • Inverter overload
  • Bypass overload
  • EPO activated

Mains| Select the measurements on mimic display
Bypass
Output

(1) This function menu is only shown after login, refer to Permission setting

Menu Sub-menu Functions

Management

| Schedule| Display the schedule
Schedule setting 1| Define the schedule for the ECO mode operation
Battery test schedule 1| Define the schedule for the battery test
Setting| Language| Select the display language
Update Prog.| Upgrade the software of LCD touch display
General| Set the turn off time of LCD backlight
Date and Time| Set date and time
Peripherals 1| Set communication card
Parameters 1| Set the UPS parameters
Event log| –| Display the event log list of UPS.
Permission setting| Login / Logout| Login with the password. 2
Password Modification 1| Change the user password.

  1. This function menu is only shown after login, refer to Permission setting
  2. Default password is 1234

Parameters section
The Parameters page is a sub-section of the Setting menu.
Locate the Setting icon on the home page and tap on it to open the relevant section; the following page will appear.legrand-LE13289AA-UPS-Keor-
Compact-01 \(17\)

  • Tap the arrow to scroll the sub-sections and select Parameters.
  • In the following page enter the password and press Enter to enable the modification of the UPS parameters. The parameters cannot be modified in normal operation mode but only when the UPS is in bypass mode.
Parameters Content Range Default
Battery Independent/Common Ind. / Common Common
Total cell number 180 ÷ 240 1 240
Capacity 1 ÷ 1000 9
Voltage temperature/compensation Yes / No No
Detect the batt. connecting Yes / No Yes
Charger current 0.0 ÷ 1.0 0.1
CV Charger voltage [V/cell] 2 ÷ 2.55 2.3
FV Charger voltage [V/cell] 2 ÷ 2.55 2.25
Low battery voltage [V/cell] 1.85 ÷ 1.883 1.85
Weak battery voltage [V/cell] 1.6 ÷ 1.8 1.67
Battery test 2 minutes Yes / No Yes

Output

| Output voltage| 220 – 230 – 240| 230
Output frequency| 50 – 60| 50
Fine adjustment voltage| -8 ÷ 8| 0
Transformer| Input transformer| No / Mains & Bypass| No
Input transformer ratio 2| 0.00 ÷ 10| 0
Output transformer| No / Yes| No
Output transformer ratio 2| 0.00 ÷ 10| 0
Other| Unit number| 1 ÷ 6| 1
Number of units in parallel system| 1 ÷ 6| 1
Set EPO logic| NO/NC| NO

  1. The Range setting for 10kVA is 156 ~ 240 and 15-20kVA is 192 ~ 240.
  2. Transformer ratios can be calculated as following:
  3. Input transformer ratio = Vp_in/Vs_in; Output transformer ratio = Vs_out/Vp_outlegrand-LE13289AA-UPS-Keor-Compact-01 \(18\)

Mimic display
The mimic display shows the energy flow and gives immediate information about the UPS status.legrand-LE13289AA-UPS-Keor-Compact-01
\(19\)

  • [A] Rectifier

  • [B] Static switch

  • [C] Inverter
    legrand-LE13289AA-UPS-Keor-Compact-01 \(11\)

  • [D] Displays the bypass input measurements

  • [E] Displays the mains input measurements

  • [F] Displays the UPS output measurements

    • Any abnormal measurement will have a red background
    • Tap on the desired section to change the measure parameters. Press for 3 seconds to check the real time information.
  • [G] Displays the battery status.

    • Press for 3 seconds to check the real time information.legrand-LE13289AA-UPS-Keor-Compact-01 \(12\)
  • [H] Silences the buzzer

    • Tap on it to silence the alarm.
    • Press for 3 seconds to enable/disable the buzzer.
  • [I] Displays the UPS internal temperature

    • Press for 3 seconds to check the real time information.
  • [J] Overload counter

Maintenance

DANGER
INSTALLATION and ORDINARY MAINTENANCE operations must be carried out only by SKILLED TECHNICIANS (paragraph 2.2.1).
EXTRAORDINARY MAINTENANCE operations must be carried out only by LEGRAND TECHNICAL SUPPORT SERVICE. LEGRAND declines all liability for any injury or damage caused by activities carried out differently from the instructions written in this manual.

Preventive maintenance
The UPS does not contain parts for preventative maintenance by the operator.

The operator must regularly perform:

  • a general external cleaning;
  • a check to verify there is no alarm indication on the display;
  • a check to verify the correct functioning of the ventilating fans.

Periodical checks

  • The correct functioning of the UPS must be guaranteed by periodical maintenance inspections.
  • These are essential to safeguard the reliability of the equipment.
  • These inspections should also be made to determine if components, wiring, and connections exhibit evidence of overheating.

WARNING
The periodical checks involve operations inside the UPS in presence of dangerous voltages. Only maintenance personnel trained by LEGRAND are authorized to intervene.

Warehousing

DANGER
All storage operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1)

DANGER
A SKILLED TECHNICIAN must check that there is no voltage present before disconnecting the cables. All the battery isolator switches on the UPS and on the external battery cabinets must be open.

UPS
The UPS must be stored in an environment with a room temperature between -20°C (-4°F) and +50°C (+122°F) and humidity less than 90% (not condensing).

Batteries
It is possible to store batteries without recharging them in the following conditions:

  • up to 6 months if the temperature is between +20°C (+68°F) and +30°C (+86°F);
  • up to 3 months if the temperature is between +30°C (+86°F) and +40°C (+104°F);
  • up to 2 months if the temperature is over +40°C (+104°F).

CAUTION
Batteries must never be stored if partially or totally discharged.
LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries.

Dismantling

DANGER
Dismantling and disposal operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1). The instructions in this chapter are to be considered indicative: in every country there are different regulations regarding the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere to the standards in force in the country where the equipment is used.
Do not throw any component of the equipment in the ordinary rubbish.

Battery disposal
Batteries must be disposed of in a site intended for the recovery of toxic waste. Disposal in the traditional rubbish is not allowed.
Apply to the competent agencies in your countries for the proper procedure.

WARNING

  • A battery may constitute a risk of electric shock and high short-circuit current.
  • When working on batteries, the prescriptions indicated in chapter 2 must be adhered to.

UPS dismantling

  • The dismantling of the UPS must occur after the dismantling of the various parts it consists of.
  • For the dismantling operations, it is necessary to wear the Personal Protective Equipment mentioned in paragraph 2.3. Sub-divide the components separating the metal from the plastic, from the copper and so on according to the type of selective waste disposal in the country where the equipment is dismantled.
  • If the dismantled components must be stored before their disposal, be careful to keep them in a safe place protected from atmospheric agents to avoid soil and groundwater contamination.

Electronic component dismantling
For the disposal of electronic waste, it is necessary to refer to the relevant standards.

This symbol indicates that in order to prevent any negative effects on the environment and on people, this product should be disposed of separately from other household waste, by taking it to authorized collection Centres, in accordance with the EU countries local waste disposal legislations. Disposing of the product without following local regulations may be punished by law. It is recommended to check that this equipment subject to WEEE legislations in the country where it is used.

Technical data

Main features

| 3 111 00
3 111 01
Keor Compact 10| 3 111 02
3 111 03
Keor Compact 15| 3 111 04
3 111 05
Keor Compact 20
---|---|---|---
Nominal Power (kVA)| 10| 15| 20
Active Power (kW)| 9| 13,5| 18
Technology| online, double conversion VFI-SS-111 (EN62040-3)
IN/OUT configuration| Three-phase / Three-phase
Dual Input| available
Architecture| Stand-alone or Distributed Parallel up to 6 units
Wave form during operation in normal/ battery mode| Pure sine wave
Bypass| Automatic (static and electromechanical) Manual (for maintenance)

Input electrical characteristics

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Maximum input current (A)| 17.4| 25.6| 34.4
Input voltage (V)| 400 ± 20% at full load 400 – 40% ~ -20% at half load (3F+N+PE)
Input frequency (Hz)| 40 ~ 70
Input Power Factor| > 0.99
Total harmonic distortion of the input current| THDi < 3% (at full load)
Compatibility with Diesel Generators| available

Output electrical characteristics

| 3 111 00
3 111 01 Keor Compact 10| 3 111 02
3 111 03
Keor Compact 15| 3 111 04
3 111 05 Keor Compact 20
---|---|---|---
Maximum output current (A)| 15.2| 22.8| 30.4
Output voltage (V)| 380/400/415 ± 1% (with static load) (3F+N+PE)
Output frequency (Hz)| 50 / 60
Range of the output frequency| ± 0.01 % (free running)
Power Factor| 0.9
Crest factor admitted on the output current| 3:1
Total harmonic distortion of the output voltage| THDv < 2% (at full linear load) THDv < 5% (at full non-linear load)
Efficiency in Normal Mode
(AC/AC online)| Up to 95%
Efficiency in Eco Mode| Up to 98.5%
Overload capacity| 110% for 60 minutes
125% for 10 minutes
150% for 1minutes
<105% overload continuously without alarm

= 105% <110% continuously with alarm

Bypass electrical characteristics

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Bypass voltage (V)| 380/400/415 ± 10% (adjustable ± 5% ~ ± 15%) (3F+N+PE)
Bypass frequency (Hz)| 50 / 60
Range of the bypass frequency| ± 1 / ± 3 (selectable)

Batteries and Battery Charger Characteristics

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Battery type| VRLA 12V
Number of internal batteries installed| 30 – 9Ah (3 111 01)| 36 – 9Ah (3 111 03)| 40 – 9Ah (3 111 05)
Cold start| available
Charging current (A)| 3.5 at 100% load
7.0 at 80% load 10 at 60% load| 5 at 100% load
10 at 80% load
15 at 60% load
| 7 at 100% load
14 at 80% load
21 at 60% load

(*) enabling by SW

Features

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Display| 4.3″ Colorful LCD Touch Screen
Communication ports| RS232 port dry contacts 2 Communication Slots for SNMP Card (optional) RS-485 MODBUS Card (optional) Programmable Dry Contact Card (optional)
Protections| Backfeed protection embedded Emergency Power Off (EPO) Electronic against overloads, short-circuit and excessive battery discharge

Mechanical characteristics

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Dimensions W x D x H (mm)| 260 x 850 x 890
Color| RAL9017 (Black-cabinet) RAL9003 (White-control panel)
Ventilation| Forced with FANs from front to rear
Transport Packaging| Carton Box on Pallet
Net weight with batteries

(kg)

| 149| 166| 176
Net weight without batteries () (kg)| 74 ()| * 76 ()| ** 76 (*)

Environmental conditions

| 3 111 00| 3 111 02| 3 111 04
---|---|---|---
3 111 01| 3 111 03| 3 111 05
Keor Compact 10| Keor Compact 15| Keor Compact 20
Operating temperature (°C)| 0 ÷ +40
(+20 ÷ +25 recommended for longer battery life)
Relative humidity during operation| 20% ÷ 95% non-condensing
Storage temperature (°C)| -20 ÷ +70 (excluding batteries)
Noise level at 1 meter (dBA)| < 52
Ingress Protection Marking| IP 20
Operating height| up to 1000 meters above sea level without derating (power derate -1% every additional 100 meters)
Heat dissipation with full load and battery in recharge (W)| 600| 900| 1300

LEGRAND

  • Pro and Consumer Service BP 30076 – 87002 LIMOGES CEDEX FRANCE www.legrand.com
  • Legrand reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals