maintronic CI4 AC Casambi Input Controller 4CH Installation Guide
- June 4, 2024
- maintronic
Table of Contents
CI4 AC
Casambi Input Controller 4C
installation guide
Important: Notice all safety instructions and related documents for Installation and operation. Names, brand marks, products or companies can be claimed. All rights are on their respective owners.
Valid from Version
Type:| Item No.| Hard-| I Firmware
CI4 AC| 11.| H 1
Document: 10805_IN_de-en_CI4AC_20211221
Fig. 1 – Icons functions
|
Fig. 2 – Housing dimensions and installation
---|---
Fig. 3 – Block diagram
L | Spannung 230V AC | 1 | Tasteingang 1 |
---|---|---|---|
N | Neutralleiter | 2 | Tasteingang 2 |
N | Neutralleiter / COM | 3 | Tasteingang 3 |
4 | Tasteingang 4 | ||
0,5…1,5mm² starr | single wire | ||
--- | --- | ||
0,5…1,5mm² flexibel | fine wire | ||
0,5…0,75mm² flexibel mit Aderendhülse | fine wire with ferrule |
Fig. 4 – Screenshot „Add to my network“
| Controls an element Light – meeting room| >
---|---|---
| Cycle Scenes Up -stop -down -stop| >
| Control Scene Main light 50%| >
| Controls a luminaire CRD400| >
Controls what happens when a push button is used.
Use toggle|
---|---
Tapping the button will switch the configured target between OFF and ON (100% or last dim level)
INFORMATION|
---|---
Name| CI4 AC
Fig. 5 – Screenshot „Configure switches (pushbuttons)“
Functions and features
See figure 1 – Icons functions
Product | Item No. | Features | Construction design |
---|---|---|---|
CI4 AC | 10.805 | 4CH pushbutton inputs | Installation housing mini (INS |
Intended use
PushButton interface with 4 inputs for PushButtons connected to mains voltage potential to control 4 Casambi functions.
- Only approved for dry indoor use
- Mini installation housing for dry interiors for installation or mounting in walls, ceilings or other cavities
- Operation is only allowed on 1 phase
http://qr.maintronic.de/10805en
| Further information and applicable documents
http://qr.maintronic.de/10273de
---|---
Installation
See figure 2 – Housing dimensions and connections
NOTE – Even if the device has tiny dimensions, a deep installation box
(>60 mm) is highly recommended. Depending on which push-button is used, up to
30 mm of the available space must be deducted.
Connections – mains powered
See figure 3 – Block diagram
DANGER – All wiring and pushbuttons must be insulated for maximum supply
voltage. Ensure the appropriate contact protection after installation. All
pushbuttons of the well-known switch manufacturers are suitable. DO NOT
connect mains (L) to COM/1/2/3/4. Ignoring leads to the destruction of the
device.
L | Input Voltage 230V AC | 1 | PushButton input 1 |
---|---|---|---|
N | Neutral conductor | 2 | PushButton input 2 |
N | Neutral conductor / COM | 3 | PushButton input 3 |
4 | PushButton input 4 |
Initial operation
5.1 Add to a Casambi network
See figure 4 – Screenshot „Add to my network“ First you need to add the device
to a Casambi network. Therefore the following steps are required:
- Open the Casambi app and select a network
- Click on devices nearby
- Add found CI4 AC to a network
5.2 PushButton configuration in Casambi
See figure 5 – Screenshot „Configure switches (pushbuttons)“ As soon as the
device is added into a Casambi network, the buttons can be configured with
functions. Therefore the following steps are required:
- Open Casambi App and click on „… More“
- Open item „Switches“
- Select CI4 AC
- Now you can link the buttons with functions
© 2021 – maintronic® GmbH reserve the right to make technical changes and product improvement without prior notice. Mistakes and typing errors are reserved. All rights reserved. MTC intronic GmbH Carl-Zeiss-Str. 10-14D-97424 Schweinfurt/Germany
Tel: +49 (0)9721-7766-0
www.maintronic.de
support@maintronic.de
References
- Casambi LED-/Retrofit-Dimmer INS
- Casambi input controller
- MTC maintronic GmbH - Business Solutions - Gebäudeautomation - Pro Audio - MTC maintronic GmbH
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>