amazon commercial B084QYK57Y 2 LED Adjustable Heads Emergency Light Exit Sign Instruction Manual

June 14, 2024
amazon commercial

amazon commercial B084QYK57Y 2 LED Adjustable Heads Emergency Light Exit

Sign

IMPORTANT SAFEGUARDS

When using electrical appliances, basic safety precautions should always be followed including the following:

READ AND FOLLOW ALL INSTRUCTIONS

  • Do not use outdoors.

  • Do not let power supply cords touch hot surfaces.

  • Do not mount near gas or electric heaters.

  • Use caution when servicing or replacing batteries. Battery acid can cause skin burns to skin and/or severe eye irritation. If battery acid is exposed to skin or eyes, flush acid with fresh water and contact a physician immediately.

  • Equipment should be mounted in locations and at heights where it cannot easily be subjected to tampering by unauthorized personnel.

  • The use of accessories or other equipment not recommended by the manufacturer may cause an unsafe condition.

  • Do not use this equipment for other than intended use.
    CAUTION Risk of electric shock!

  • To prevent risk of electric shock, turn off the power at the main circuit breaker box before installation.

  • This product must be installed in accordance with the applicable installation codes by a person familiar with the construction and operation of the product and the hazards involved. Consult a qualified electrician to ensure correct branch circuit conductor.

  • This product is rated 120/277 VAC and must be connected to a suitable power source.

  • The product employs non-replaceable LED light sources.

  • All servicing should be performed by qualified personnel only.

  • Flexible conduit only.

SAVE THESE INSTRUCTIONS

PARTS

Intended Use

Risk of electric shock!

  • DO NOT USE WHERE DIRECTLY EXPOSED TO WATER.
  • This product is intended for emergency lighting applications such as stairways and hallways. During an electrical power failure, the sign automatically lights up for a minimum of 90 minutes.
  • This product is intended for commercial and residential use.
  • This product is intended to be used in dry and damp indoor areas only.
  • No liability will be accepted for damages resulting from improper use or non­ compliance with these instructions.
  • Maximum mounting height: 13.8 ft (4.1 m)

Before First Use
DANGER Risk of suffocation!

  • Keep any packaging materials away from children – these materials are a potential source of danger, e. g. suffocation.
  • Check the product for transport damages.
  • Remove all the packing materials.

Installation

DANGER Risk of electric shock!

  • To prevent risk of electric shock, turn off the power at the main circuit breaker box before installation.
  • Unused wires must be capped using the supplied wire connectors (G).

WARNING Risk of falling!

  • Take special precautions when working on heights, for example, while using a ladder. Use the right type of ladder and ensure it is structurally sound. Use the ladder in accordance with the manufacturer’s instructions.
  1. Push into the holes of the housing (C) to release the front panel (A).
  2. Connect the battery cable.
    NOTICE This product is supplied with a battery for use when mains power is not available. Refer to chapter “Specifications” for the battery replacement date.

Wall mounting

  1. Drill through the knockouts on the mounting plate (B) for wires and screws, then feed the wires through the center hole.
  2. Use twist-on wire connectors (G) to join the wires to the electrical box. Refer to chapter “Wiring” for more details.
  3. Screw the mounting plate (B) to the electrical box using screws (J) making sure no wires are pinched.
  4. Clip on the front plate (A). Turn on power from the mains then press the TEST button (K). The emergency sign should dim, and the AC ON indicator goes off.
  5. Insert direction arrow(s) (F) into the front and/or back plate (A) to hide the incorrect exit direction.
    NOTICE in case there is only 1 exit direction, disconnect the unused light head’s wire. The opposite light head can be also removed by twisting it and then pulling out. After removing the light head, cover the hole with a knockout (H).

Ceiling mounting
NOTICE If you require EXIT signs on both sides of the housing, remove the mounting plate (B) and replace with the spare front plate (A).

  1. Using a screwdriver, remove the top knockout (H) from the housing (C), then feed the wires through the hole, mounting bracket (D) and crossbar (E).
  2. Use twist-on wire connectors (G) to join the wires to the electrical box. Refer to chapter “Wiring” for more details.
  3. Screw the crossbar (E) to the electrical box using screws (I) making sure no wires are pinched, then screw the mounting bracket (D) to the crossbar (E) using screws (J).
  4. Align the clips on the mounting bracket (D) to the housing (C) and twist the housing to secure.
  5. Clip on the front plate (A). Turn on the main power source then press the TEST button (K). The emergency sign should dim, and the AC ON indicator goes off.
  6. Insert direction arrow(s) (F) into the front and/or back plate (A) to hide the incorrect exit direction.
    NOTICE In case there is only 1 exit direction, disconnect the unused light head’s wire. The opposite light head can be also removed by twisting it and then pulling out. After removing the light head, cover the hole with a knockout (H).

Wiring

WARNING Risk of electric shock!

  • To prevent risk of electric shock, turn off the power at the main circuit breaker box before installation.
  • Connect the black (live) and white (neutral) wires to the building utility for 120VAC.
  • Connect the orange (live) and white (neutral) wires to the building utility for 277VAC.
  • Cap off the unused wire with a wire connector (G).

Cleaning & Maintenance

Maintenance

  • Battery replacement
    This product is fitted with a Nickel-Cadmium battery which needs to be replaced as specified in the chapter “Specifications”.

  • Product testing

    • In accordance with NFPA 101, this product must be tested monthly for a minimum of 30 seconds and annually for 90 minutes.
    • To test, press the TEST button. The emergency sign should dim, and the AC ON indicator should go off.

Cleaning
WARNING Risk of electric shock!

  • To prevent electric shock, turn off the power at the main circuit breaker box before cleaning.
  • To clean the product, wipe with a soft, slightly moist cloth.
  • Never use corrosive detergents, wire brushes, abrasive scourers, or metal or sharp utensils to clean the product.

Specifications

  • Model number: CR-7082RX-1, CR-7082RX-2, CR-7082RX-4
  • Rated voltage: 120/277 VAC 60 Hz
  • Power input: 1.2W
  • Current consumption: 100 mA
  • Battery type: 3.6 V 1000 mAh, AA Nickel-Cadmium
  • Battery replacement date: 7/12/2027
  • Operating conditions: 32 °F to 1 04 °F (0 °C to 40 °C)
  • Net weight: approx. 2.57 lbs (1. 17 kg)
  • Dimensions (N x H x D): approx. 25.2 x 8.27 x 4.53″ (64.0 x 21.0 x 11.5 cm)

Feedback and Help