Danfoss Electric Floor Heating Cables Installation Guide

June 4, 2024
Danfoss

Danfoss Electric Floor Heating Cables Installation Guide

Introduction

In this installation manual, the phrase “heating cable” refers to heating cables in readymade lengths; heating cables on drums; heating cables on mesh; and preshaped taped heating cables. To get the full installation guide, warranty registration, product information, tips & tricks, addresses, etc. visit www.danfoss.com and www.gb.fhemanuals.danfoss.com.

Safety instructions

Heating cables must always be installed according to
local building regulations and wiring rules as well as the
guidelines in this installation manual.

  • De-energize all power circuits before installation and service.
  • Residual current device (RCD) protection is required. RCD trip rating is max. 30 mA.
  • The screen from each heating cable must be earthed inaccordance with local electricity regulations
  • Heating cables must be connected via a switch providing all pole disconnection.
  • The heating cable must be equipped with a correctly sized fuse or circuit breaker according to local regulations.
  • Never exceed the maximum heat density (W/m or W/m²) for the actual application.
  • Strongly recommended to use the heating cable together with an appropriate thermostat to secure against overheating.
  • Caution! Do not use M1 classified cables in areas subject to high mechanical loads or impact, such like outdoor applications, on steel reinforcing grids, in concrete with sharp stones, roof and gutters, etc. The presence of a heating cable must
  • be made evident by affixing caution signs in the fuse box and in the distribution board or markings at the power connection fittings and/or frequently along the circuit line where clearly visible (tracing).
  • be stated in any electrical documentation following the installation.

Installation guidelines

  • It is not recommended to install heating cables at temperatures below -5°C.
  • Heating cable bending diameter must be at least 6 times the cable diameter. Do not bend connections.
  • Free end from cold lead must be protected by installer to avoid water from coming in.

Mechanical class

  • M1 — For use in applications with low risk of mechanical damage according to IEC 60800:2009, e.g. installed on even surfaces and embedded in screeds with no sharp objects.
  • M2 — Can be used in applications with high risk of mechanical damage according to IEC 60800:2009.
  • C — High mechanical strength according to IEC 60800:1992.
  • MMM — Marking for high mechanical protection class according to NF C 32-330:2002

Warranty

A 20-year full service warranty is valid for:

  • heating cables incl. ECflex, ECsafe, ECsnow, ECasphalt, ECbasic, ECfreeze;
  • heating mats incl. ECsnow, ECasphalt, ECflex, ECsafe, ECinfracable.

Not only does this warranty include costs of reparation or replacement, but also installation and floor materials, such as damage to brickwork and tiles.

A 20-year product warranty is valid for:

  • heating cables incl. ECaqua.
    A 10-year product warranty is valid for:

  • Reflect insulation plates.
    A 5-year product warranty is valid for:

  • self-limiting cables incl. ECiceguard, ECpipeheat, SLPG, SLIG, EChotwatt

Should you, against all expectations, experience a problem with your Danfoss product, you will find that Danfoss offers Danfoss warranty valid from the date of purchase that was no later than 2 years from production date on the following conditions: During the warranty period Danfoss shall offer a new comparable product or repair the product if the product is found to be faulty by reason of defective design, materials or workmanship. The decision to either repair or replace will be solely at the discretion of Danfoss.

In addition to repair or replacement of the defective product Danfoss will also compensate installation costs and any damage to floor/surface materials (e.g. brickwork, tiles or roof surface) if the damage is caused by thedefective product or is an unavoidable result of repairing the defective product for all products with full-service warranty. Except for such costs and damage, Danfoss shall not be liable for any resulting losses or consequential or incidental damages including, but not limited to, damages to property or extra utility expenses. No extension of the warranty period following repairs undertaken is granted.

The warranty shall be valid only if the WARRANTY CERTIFICATE is completed correctly and in accordance with the instructions, the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided. Please note that the WARRANTY CERTIFICATE must be filled in, stamped and signed by the authorized installer performing the installation (Installation date must be indicated). After the installation is performed, store and keep the WARRANTY CERTIFICATE and purchase documents (invoice, receipt or similar) during the whole warranty period.

The Danfoss warranty shall not cover any damage caused by incorrect conditions of use, incorrect installation or if installation has been carried out by non- authorized electricians. All work will be invoiced in full if Danfoss is required to inspect or repair faults that have arisen as a result of any of the above. The Danfoss warranty shall not extend to products which have not been paid in full. Danfoss will, at all times, provide a rapid and effective response to all complaints and inquiries from our customers. All claims exceeding the above conditions are explicitly excluded from the Danfoss warranty.

For full warranty text please use QR cod

WARRANTY CERTIFICATE

The Danfoss warranty is granted to:

The insulation resistance shall be measured by means of a DC voltage of at least 1000 V for one minute. The measured value shall be no less than 50 MΩ.

  • Address
  • Stamp
  • Purchase date
  • Serial number of the product
  • Product
  • Art. No
  • Installation Date & Signature
  • Cable resistance [Ω]
  • Insulation [MΩ]
  • Connection Date & Signature
  • Cable resistance [Ω]
  • Insulation [MΩ]

Application overview

Cable type Mechanical class Applications
Pipe tracing  inside Pipe tracing – outside Joist floor
plates Concrete >3 cm Seed beds
Cold stores Ground melting Roof and gutter

low temp
ECflex 10T| M2|  | x| x| x| x| x|  |  | x|  |  |  |
ECflex 18T, ECflex 20T| M2|  | x|  |  | x| x|  |  | x|  |  |  |
ECflex 50T, ECflex 75T, ECflex 100T| M2|  |  |  |  | x|  |  |  | x|  |  |  |
ECfreeze 7,5T| M2|  | x|  |  | x|  |  |  | x|  |  |  |
ECsafe 20T| M2|  | x|  |  | x| x|  | x| x| x| x|  |
ECsafe 100T| M2|  |  |  |  | x|  |  |  |  |  |  |  |
ECsnow 20T| M2|  | x|  |  | x| x|  | x|  | x| x|  | x
ECsnow 30T| M2|  |  |  |  |  |  |  | x|  | x| x|  | x
ECsnow 300T| M2|  |  |  |  |  |  |  |  |  | x|  |  | x
ECinfracable 75T, ECinfracable 100T| M2|  |  |  |  | x|  |  |  |  |  |  |  |
ECbasic 20S| C|  | x|  |  | x| x|  |  | x| x|  |  |
ECasphalt 30T| M2|  |  |  |  |  |  |  |  |  |  |  | x| x
ECasphalt 300T| M2|  |  |  |  |  |  |  |  |  |  |  | x| x
ECaqua 9T 2) 3)| M1| x|  |  |  |  |  |  |  |  |  |  |  |
ECpipeheat 10 V2 1) 4)| M2|  | x|  |  |  |  |  |  |  |  |  |  |
SLPG 1), EChotwatt 1)| M2|  | x|  |  |  |  |  |  |  |  |  |  |
ECiceguard, SLIG 1)| M2|  | x|  |  |  |  |  |  |  |  | x|  |

  1. Heating cables/mats can be customized for the specific project, depending on voltage, required output, length of heating cable and length of cold leads.
    Note: It is the full responsibility of the installer/designer to use proper cold lead dimensioned for the purpose and assembly sets that establish sufficient mechanical strength, flammability resistance and water tightness – and to design the heating unit with correct output for the specific application to avoid overheating of the cable or building materials. 2) The heating cable shall only be installed in concrete or used while fully covered with non-flamable material e.g. soil or similar.

  2. The cable are approved for use in contact with drinking water or water for human consumption – comply to Danish GDV (Godkendt til drikkevand) demands.

  3. The cable are not approved for installation inside the water pipe and for use in contact with drinking water or water for human consumption, waste water, etc.!

Regarding other types of applications please contact your local Danfoss sales company.
More information about applications can be found at www.danfoss.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Danfoss User Manuals

Related Manuals