VEVOR Ref Center Tank Pump User Manual

June 14, 2024
VEVOR

Technical Support and E-Warranty Certificate https://www.vevor.com/support
Ref Center Tank Pump
USER MANUAL

VEVOR Ref Center Tank Pump

MODEL:RTP15WS115V/RTP24WS115V

We continue to be committed to provide you tools with competitive price.
“Save Half”, “Half Price” or any other similar expressions used by us only represents an
estimate of savings you might benefit from buying certain tools with us compared to the major
top brands and doses not necessarily mean to cover all categories of tools offered by us. You
are kindly reminded to verify carefully when you are placing an order with us if you are
actually saving half in comparison with the top major brands.

NEED HELP? CONTACT US!

Have product questions? Need technical support? Please feel free to contact us:

****CustomerService@vevor.com

This is the original instruction, please read all manual instructions carefully before operating. VEVOR reserves a clear interpretation of our user manual. The appearance of the product shall be subject to the product you received. Please forgive us that we won’t  inform you again if there are any technology or software updates on our product.

PACKAGE CONTENTS

Item Quantity
Ref Center Tank Pump 1
20 ft flexible Pipe 1
Instruction Manual 1

SPECIFICATIONS

Model RTP15WS115V RTP24WS115V
Voltage/Frequency AC115V/60Hz
Current 1A 2.5A
Power 1/50HP 1/30HP
Flow ≥65GPH ≥100GPH
Lift ≥15ft ≥24ft
Inlet Diameter 1.0in
Outlet Diameter 0.4in
Water tank volume 1/2 gallon

INTRODUCTION

Your Ref Center Tank Pump is designed as an automatic condensate removal pump for water dripping off an air conditioner evaporative coil. The pump is controlled by a float/switch mechanism which turns the pump on when approximately 2-1/4” of water  collects in the tank and automatically switches off when the tank drains to approximately 1-1/4”. The Ref center pump you have purchased is of the highest quality workmanship and material. It has been engineered to give you long and reliable service.
Refcenter pumps are carefully packaged, inspected, and tested to ensure safe operation and delivery. When you receive your pump, examine it carefully to determine that there are no broken or damaged parts that may have occurred during shipment. If damage  has occurred, make a notation and notify the firm that you purchased the pump from. They will assist you in replacement or repair if required.

READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THE REFCENTER PUMP. KNOW THE PUMP APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS. PROTECT YOURSELF AND OTHERS BY  OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! RETAIN INSTRUCTIONS FOR FUTURE REFERENCE. INSTALLATION AND CONNECTIONS ARE TO BE MADE BY A QUALIFIED PERSON.

SAFETY GUIDELINES

WARNING

DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE, ETC. DO NOT USE IT IN EXPLOSIVE ATMOSPHERES. THE PUMP SHOULD BE USED WITH LIOUIDS COMPATIBLE WITH PUMP  COMPONENT MATERIALS.
DO NOT HANDLE THE PUMP WITH WET HANDS OR WHEN STANDING ON A WET OR DAMP SURFACE OR IN WATER. THIS PUMP IS SUPPLIED WITH A GROUNDING CONDUCTOR AND/OR GROUNDING-TYPE ATTACHMENT PLUG. TO  REDUCE THE RISK OF ELECTRICAL SHOCK, BE CERTAIN THAT IT IS CONNECTED TO A PROPERLY GROUNDED GROUNDING-TYPE RECEPTACLE. IN ANY INSTALLATIONS WHERE PROPERTY DAMAGE AND/OR PERSONAL INJURY MIGHT RESULT FROM AN INOPERATIVE OF LEAKING PUMP DUE TO POWER OUTAGES, DISCHARGE LINE BLOCKAGE, OR ANY OTHER REASON, A BACKUP SYSTEM(S) AND/OR ALARM SHOULD BE USED.

SUPPORT PUMP AND PIPING WHEN ASSEMBLING AND WHEN INSTALLED. FAILURE TO DO SO MAY CAUSE PIPING TO BREAK, PUMP TO FAIL, MOTOR BEARING FAILURES, ETC.

INSTALLATION

  1. Before installing the pump, allow the air conditioner to cycle several times, collecting condensate in a separate container to help flush any residual oils that may remain in the system.

  2. Carefully unpack the pump. Remove the cardboard packing from the motor cover air slots. Carefully slide the packing away from the pump. This packing is used to prevent switch movement during shipment (Figure 1).

  3. Mounting the pump: the tank has two slots provided to mount the unit.
    The slots are located on the ends of the tank (Figure 5). The unit should be mounted either on the side of the air conditioner unit or a nearby wall. The pump must be level, and the inlet must be below the coil drain. Conduit fittings are not compatible with  the plastic pump housing.

  4. The pump should not be installed in a manner that will subject it tosplashing or spraying.

  5. This pump is not intended for use inside air plenums.

ELECTRICAL CONNECTIONS

WARNING

  1. Shut off the electrical power at fuse box before making any connections.
    All wiring must comply with local codes.

  2. Line voltage: Connect the power cord to the line voltage specified on the motor and nameplate. The power cord must be connected to a constant source of power (not a fan or other device that runs intermittently). If the power cord does not have a plug,  wiring is as follows: green (or green/yellow)-ground. Black (or brown)-line. White (or blue)-neutral.

  3. Safety switch: The safety overflow switch should be connected to a class II low-voltage circuit. To control a thermostatic circuit, the COM and NO connections from the safety switch are to be wired in series with the low-voltage thermostat circuit to shut  down the heating/AC circuit. The COM and NC switch contacts may be used to actuate a low-voltage alarm circuit (connected in series) if the heating/cooling system cannot be disrupted. The safety switch comes from the factory with leads connected to the  COM and NO switch terminals. Typical hook-up of “NC” circuits would be (Figures 2 & 3),

VEVOR Ref Center Tank Pump - terminals

VEVOR Ref Center Tank Pump - terminals 2

PIPING

  1. Run flexible tubing or pipe from the evaporator drain into one of the three pump inlets. Be sure inlet piping is sloped downward to allow gravity flow (Figure 4). Extend the inlet piping into the tank from 1 to 3 inches to ensure that it will not interfere with  proper float operation. Be sure that the inlet piping is cut at an angle where it enters the tank.
  2. The outlet piping should be flexible tubing secured with a hose Clamp (not provided) or pipe (3/8 inch ID. maximum to prevent excessive flow back to the unit). From the condensate unit, extend the discharge piping straight up as high as necessary. Do not  extend this line above the head/GPH of the particular model being installed. From this high point, slope the discharge line down slightly to a point above the drain area, then turn down and extend to a point below or approximately level with the bottom of the condensate unit. This will give a siphoning effect which will improve the efficiency of the condensate unit and will, in most cases, eliminate the need for a check valve (Figure 5). If it is not possible to slope the discharge line down, make an inverted “U”  trap directly above the pump at the highest point.

SERVICE INSTRUCTIONS

WARNING

  1. Make certain that the unit is disconnected from the power source before attempting to service or remove any component!
  2. Be sure the floats move freely. Clean as necessary (Figure 6).
  3. Clean the tank with warm water and mild soap.
  4. Check the inlet and outlet piping. Clean as necessary. Be sure there are no kinks in the line that would inhibit flow.

VEVOR Ref Center Tank Pump - outlet piping

TESTING

  1. Turn on the power.
  2. Remove the motor/tank cover assembly and hold level.
  3. Test the motor switch by raising the motor switch float with a finger (Figure 6). The motor should turn on just before the float contacts cover.
  4. Test the safety switch by raising the safety switch float with a finger. The safety switch should activate before the float contacts cover.
  5. Replace the motor/tank cover assembly on the tank.
    This pump is suitable for gas furnace condensate applications. Caution must be taken to ensure the acidity of condensate does not increase below the average pH of 3.4 (to prevent localized pocket of acid that acts like a battery causing pitting) by routinely  cleaning or flushing the tank with fresh water.

LIMITED WARRANTY

Your product is guaranteed to be in perfect condition when it leaves our factory. It is warranted against defective materials and workmanship for a period of 12 months from the date of purchase by the user.
Any product that should fail for either of the above two reasons and is still within the warranty period will be repaired or replaced at the option of the Ref center. All defective products returned under warranty will be fully inspected to determine the cause of  failure before the warranty is approved.
DISCLAIMER: THE FOREGOING WARRANTY IS AN EXCLUSIVE WARRANTY IN LIEU OF ANY OTHER EXPRESS WARRANTIES. ANY IMPLIED WARRANTIES (INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF  MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE) TO THE EXTENT EITHER APPLIES TO A PUMP SHALL BE LIMITED IN DURATION TO THE PERIODS OF THE EXPRESS WARRANTIES GIVEN ABOVE.

Warranty will be VOID if any of the following conditions are found:

  1. Sealed motor housing opened.
  2. Product connected to a voltage other than indicated on the nameplate.
  3. Cord cut off to a length of fewer than three feet.
  4. Pump allowed to operate dry (fluid supply cut off).
  5. Pump used to circulate anything other than water.
  6. Product abuse by Customers.

Any oral statements about the product made by the seller, the manufacturer, the representatives, or any other parties, do not constitute warranties, shall not be relied upon by the user, and are not part of the Contract for sale. The seller’s and manufacturer’s only  obligation, and the buyer’s only remedy, shall be the replacement and/or repair by the manufacturer of the product as described above. NEITHER SELLER NOR THE MANUFACTURER SHALL BE LIABLE FOR ANY INJURY, LOSS, OR DAMAGE, DIRECT,  INCIDENTAL, OR CONSEQUENTIAL (INCLUDING, BUT NOT LIMITED TO, INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR LOST PROFITS, LOST SALES, INJURY TO PERSON OR PROPERTY, OR ANY OTHER INCIDENTAL OR  ONSEQUENTIAL LOSS), ARISING OUT OF THE USE OR THE INABILITY TO USE THE PRODUCT AND THE USER AGREES THAT NO OTHER REMEDY SHALL BE AVAILABLE TO IT. Before using, the user shall determine the suitability of the product for the intended use,  and the user assumes all risk and liability whatsoever in connection therewith.
Some states and Countries do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal  rights, and you may also have other rights which vary from state to state and country to country.

*There are any minor changes to the numbers included in the user manual without prior notice.

Manufacturer: CHINAFORE CO., LTD.
Address:No. 499, Hongcan Road, HongkenNongchang Economic
Development Zone, Xiaoshan District, HANGZHOU
Made In China