Century C12-100XLi Lithium Pro Battery User Manual
- June 14, 2024
- CENTURY
Table of Contents
LITHIUM PROPRO
C12-100XLi
C12-100XSLi
C12-200XLi
USER MANUAL
C12-100XLi Lithium Pro Battery
General Information
Century Lithium Pro batteries are designed to provide long lasting power in
recreational deep cycle applications.
To ensure proper safe use, optimum performance, durability, and reliability of
your Century Lithium Pro battery, please read through this user manual
carefully and completely before use.
A technical data sheet and a material safety data sheet (SDS) are also
available as additional information on the Century Batteries website.
Australia: centurybatteries.com.au/lithium
New Zealand:
centurybatteries.co.nz/lithium
If you have any questions concerning safety precautions, installing, or using
the battery please contact Century Yuasa Batteries. AU 1300 361 161 or NZ
0800 93 93 93
Disclaimer: All rights reserved. Information contained in this user manual is
subject to change without notice or obligation.
Any information provided in or omitted from this user manual in any
circumstances resulting in incidental or consequential damages or injuries is
the responsibility of the consumer and does not constitute additional
liability of Century Yuasa Batteries Pty Ltd.
Introduction
1.1 Product Description
The Century Lithium Pro is a 12.8V lithium-ion battery incorporating Lithium
Iron Phosphate (LFP or LiFePO4) technology and is designed for recreational
cyclic applications. It contains 4 or 8 cells connected in series and in a
parallel where applicable, equipped with an internal battery management
system (BMS) to monitor each single prismatic cell for correct operation of
the battery, as well as the loads and charge source that are connected to the
battery.
This LFP battery is suitable for replacement of deep cycle lead acid
batteries, used in RV, camper trailer, caravan, 4WD (AUX/boot), marine, and
mobility applications. This LFP battery should not be used in any applications
other than those described in this user manual. It is important to read and
follow the information provided before installation, operation, and
maintenance of this battery.
MODEL| Voltage (V)| CAPACITY (Ah)| STANDARD
CHARGE
CURRENT (A)| MAX CHARGE
CURRENT (A)| STANDARD
DISCHARGE
CURRENT (A)| MAX DISCHARGE
CURRENT (A)| DIMENSIONS LWH (MM)| TERMINAL| WEIGHT (Kg)
---|---|---|---|---|---|---|---|---|---
C12-100XLi| 12| 100| 50| 100| 50| 100| 3071 72*217| M8| 13.5
C12-100XSL1| 12| 100| 50| 100| 60| 100| 5081 10’236| M8| 13.6
C12-200XLi| 12| 200| 50| 150| 100| 180″| 4831 70’241| M8| 24.5
^Continuous discharge at maximum current at high temperature will result in reduced run time and potentially BMS cut-off for temperature protection.
Components & Construction
(Example of C12-100XLi shown)
-
Handle
-
Positive terminal, M8 nut insert
-
Negative terminal, M8 nut insert
-
Top cover: Flame Retardant ABS/PC
-
Positive connecting copper bar
-
Epoxy board Insulator
-
Negative connecting copper bar
– Module to BMS -
Connecting aluminium bars
– Prismatic cells -
Battery module hold-down bracket
-
Electrical insulating sheet
-
Prismatic cells
-
Epoxy board insulator
-
BMS
-
Battery case: Flame Retardant ABS/PC
-
Negative connecting copper bar
1.2 Terminology
BMS | Battery Management System |
---|---|
DOD | Depth of Discharge |
OCV | Open Circuit Voltage |
SOC | State of Charge (%) |
°C | Degree Celsius in temperature |
V | Volt |
A | Ampere |
Ah | Capacity in Ampere-hour |
M8 | 8mm nut insert terminal |
Series Connection | Batteries connected to increase voltage by connecting |
positive terminal of one battery to negative terminal of the next battery
Parallel Connection| Batteries connected to increase overall capacity by
connecting positive terminal of one battery to positive terminal of the next
battery
Safety
Warning! Risk of fire, explosion, or burn.
Failure to install or use according to the instructions in this manual may
result in early battery failure or cause risk of electrical or fire damage to
the battery and surrounding property and may cause personal injuries.
The Century Lithium Pro LFP battery is designed with an integrated BMS to prevent internal damage to the battery under various conditions. When this occurs in connected equipment, power can be abruptly interrupted to the system which may cause undesirable consequence. The system installer must understand the automatic safety shutdown functions of the BMS and shall assume all responsibility and liability for any damages if these functions are not properly applied.
Do’s
- The battery must be kept in the original packaging until use.
- Wear personal protective equipment (eye protection and gloves) before handling.
- Keep sparks and open flames away from the battery.
- Use insulated tools when working on or with the battery.
- Secure connections with correct torque setting.
- Only connect the charger in line with recommended settings. Always disconnect the charger when working on batteries.
- Charge the battery before installing.
- Remove charger immediately and contact the dealer if any abnormal smell or noise while on charge or when a discharge is detected.
Don’t s
- Do not drop, impact, or puncture the battery. The battery must be protected from mechanical impacts.
- Do not store the battery below 30% SOC.
- Do not use for cranking/starting applications.
- Do not install under the bonnet or engine compartment.
- Do not use the battery outside the specified temperature range.
- Do not expose to direct sunlight for extended period. During storage, the battery must be protected from direct sunlight.
- Do not submerse in water or expose to rain for any extended periods. The battery should be stored in a cool and dry environment.
- Do not install near heat source or flammable materials.
- Do not disassemble or modify the outer casing of the battery.
- Do not dispose of in fire, household waste or landfill
- Do not connect LFP batteries from different manufacturers, different brands, capacity, size, or type in series or parallel.
- Over-voltage charging, incorrect wiring, reverse polarity connection or short circuits of the terminals may damage the battery.
Handling and Installation
-
Before connecting the battery, check that the battery voltage is ≥13.3V. Recharge as required.
-
Ensure that the cable connecting the battery terminals is correctly sized and in length.
-
Ensure that the bolts on the terminals are firmly fastened to the recommended torque of 10~12Nm to avoid loosening during operation.
-
Ensure the maximum output voltage of any charging device connected to the battery does not exceed 14.6V before connecting. Recommended charging voltage is 14.4V
-
Side mounting with terminals on the upper side is acceptable but not recommended. Where feasible, always install upright to optimise the performance under a dynamic condition such as vibration.
-
Fully charge each battery before use and if connecting them in series or parallel.
-
When connecting in parallel, ensure the capacity and voltage between each battery is consistent.
Any variance should be below 100mV. -
Do not connect different batches, types, old or new batteries in series or parallel.
-
To optimise batteries with balanced cells, it is advisable not to mix batteries from a different batch and group for parallel connection. Each battery is labelled with a production batch code and serial number.
Some may be followed by a group code. The last 3 numeric numbers are designated as the group code such as 001, 002… For example, LA120221J270443-001: LA120221J27 is the batch code; 0443 is the serial number and 001 is the group code. For batteries in parallel connection, check that the batch code and group code are the same. -
The battery can be connected in series up to 4 batteries, or in parallel up to 2 batteries. For example, four 12V100Ah batteries connected in series can create a 48V100Ah battery bank; and two batteries connected in parallel can create a 12V200Ah battery bank.
-
The total maximum configuration in a string of series and/or parallel (i.e., 4S2P) is 8 batteries (refer to the individual product spec sheets).
-
Due to small variations in new LFP battery capacity, LFP batteries may be slightly unbalanced when unpacked for multiple connection in parallel. BMS interruption of charging is likely to occur during the initial charging which is considered normal. If the charger trips out, reset the charger until charging continues normally. For best result, each battery should be charged individually before being connected in series or parallel. Contact Century Yuasa Batteries for any further assistance.
Operation Use
Caution: Improper use will cause irreversible damage to the battery and could cause battery swelling and smoke in extreme cases.
4.1 Operating Conditions
The Century LFP battery is in sleep mode when not in use to reduce self-
discharge. It will go into sleep mode after 24 hours when the charge or
discharge current is below 1A.
A charge or discharge will activate the battery from this sleep mode:
- Charge activation – Connect a charger with 1.2V above the battery voltage
- Discharge activation – Connect a load (<5kΩ)
The following operating ambient temperatures and humidity must be followed (refer to the individual product spec sheets in case of exceptions):
- Charging at between 0°C~45°C
- Discharging at between -20°C~55°C
- Ambient humidity: ≤85%
Reduce current when charging battery at temperatures <10°C and >35°C
4.2 Bluetooth Connection
The Century Lithium Pro battery has an integrated wireless Bluetooth
monitoring function.
The Century Lithium Pro Bluetooth App is available for iOS and Android
portable smart devices and can be downloaded from Apple App Store or Google
Play Store
Through the Century Lithium Pro Bluetooth monitoring system, the following information can be read or monitored:
- Battery Capacity
- Battery Voltage
- Individual Cell Voltage
- Battery State of Health
- Battery Cycle
- Battery Event Information
- Battery State of Charge (SOC)
- Battery Current
- Battery Status
- Battery Temperature
- Battery Alarm
4.2.1 Installation and Pairing App on iOS or Android.
Download the App ‘Century Lithium Pro’.
Ensure Bluetooth is enabled on the smart device before pairing. Ensure the
battery is in ‘WAKE-UP’ mode before pairing. Activate the Bluetooth connection
by charging or discharging the battery.
There are two options for pairing or connecting, by scanning the Bluetooth QR
code and by the unique ID both of which are located on the top of each
battery.
a. Search the battery from the listed battery Bluetooth ID(s) on the smart device, then toggle it ON:
b. Scan the QR code on the battery and the battery Bluetooth ID will appear:
The Bluetooth Monitoring System provides point to point connection. Only one
battery can be connected to one device at a time. If more than one battery is
configured in series or in parallel, each battery can be checked in turn, one
by one, on the same smart device. Simply follow the pairing/connection
process for each individual battery.
After being connected, the battery can be renamed from its ID code by the user
on the smart device.
All connected batteries will appear on the first screen when accessing the App
next time.
4.2.2 Using the App.
a. After connecting, touch the paired battery name and it will bring up the
‘Basic Info’ screen. This screen shows the SOC in percentage; battery voltage;
battery capacity; battery status (standby, charge, or discharge); and battery
state of health (good, or service – if below 80% initial capacity)
b. Swiping across from the Basic Info screen will show the ‘Details Info’
screen.
This screen shows battery voltage, battery current, estimated run time,
individual cell voltage, battery temperature and battery cycle count.
c. Touching “ ” icon on the ‘Basic Info’ screen will bring up the ‘Alarm’ screen.
This screen displays the BMS protection function.
Automatic Safety Shutoff and Restart
C12-100XLi
BMS Function | Automatic Shutoff | Recovery and Automatic Restart |
---|---|---|
Over Charge Voltage | Cell ≥3.7V or Battery ≥14.8V; 3S max | Cell ≤3.45V or |
Battery ≤13.8V
Over Discharge Voltage| Cell ≤2.5V or Battery ≤10.0V; 3S max| Cell ≥2.8V or
Battery ≥11.2V
Over Charge Current| 105A for 3S or 138A for 500mS or
284-345A for 17mS| After 13S, up to 3 consecutive times.
Except at >284A, no auto recovery
Over Discharge Current| 350A for 3S or 560-650A for 8mS| After 13S, up to 3
consecutive times.
Except at >560A, no auto recovery
High Temperature on Charge| Above 50ºC| Below 45ºC
High Temperature on Discharge| Above 65ºC| Below 55ºC
Low Temperature on Charge| Below 0ºC| Above 5ºC
Low Temperature on Discharge| Below -20ºC| Above -15ºC
Short Circuit| Above 1200A, 400 µS| No automatic recovery
Over Charge Voltage| Cell ≥3.7V or Battery ≥14.8V; 1S max| Cell ≤3.45V or
Battery ≤13.8V
Over Discharge Voltage| Cell ≤2.5V or Battery ≤10.0V; 1S max| Cell ≥2.8V or
Battery ≥11.2V
Over Charge Current| 105A for 3S or 138A for 500mS| After 10S, up to 3
consecutive times
Over Discharge Current| 110A for 13S or 350A for 3S| After 10S, up to 3
consecutive times
High Temperature on Charge| Above 50ºC| Below 45ºC
High Temperature on Discharge| Above 65ºC| Below 55ºC
Low Temperature on Charge| Below 0ºC| Above 5ºC
Low Temperature on Discharge| Below -20ºC| Above -15ºC
Short Circuit| Above 600A, 200 µS| No automatic recovery
C12-200XLi
BMS Function | Automatic Shutoff | Recovery and Automatic Restart |
---|---|---|
Over Charge Voltage | Cell ≥3.7V or Battery ≥14.8V; 3S max | Cell ≤3.45V or |
Battery ≤13.8V
Over Discharge Voltage| Cell ≤2.5V or Battery ≤10.0V; 3S max| Cell ≥2.8V or
Battery ≥11.2V
Over Charge Current| 170A for 3S or 284-345A for 17mS| After 13S, up to 3
consecutive times.
At >284A, no auto recovery
Over Discharge Current| 350A for 3S or Above 600A for 8mS| After 13S, up to 3
consecutive times.
Except at >600A, no auto recovery
High Temperature on Charge| Above 60ºC| Below 50ºC
High Temperature on Discharge| Above 65ºC| Below 55ºC
Low Temperature on Charge| Below 0ºC| Above 5ºC
Low Temperature on Discharge| Below -20ºC| Above -15ºC
Short Circuit| Above 1200A, 400 µS| No automatic recovery
d. Touching the “ ” icon on any of the screen will bring up the ‘Menu’ screen.
Notification preferences can be set up on the smart device. CYB contact details, App information and user manual can be located in this area.
4.3 Charging
-
The battery must be fully charged before first use.
-
Ensure charging voltage does not exceed 14.6V. 14.4V is recommended (refer to product spec sheets in case of exception).
-
Ensure the charging current does not exceed the maximum charging current as indicated in the specification sheet. Any inrush current may activate the short circuit protection function and charging may stop.
-
Ensure charging is carried out at an ambient temperature within the recommended range of 0°C~45°C (refer to product spec sheets in case of exception).
-
Below 0°C or above 45°C may cause irreversible damage (i.e., permanent loss of capacity) to the battery or even a safety risk.
-
DO NOT charge the battery for more than 24 hours. Disconnect the LFP battery from the charger when the charger is no longer in use.
-
DO NOT use a lead-acid battery charger if it has ‘Equalisation’ and ‘De-sulphation’ mode or function.
-
DO NOT leave a lead-acid battery ‘smart’ charger connected to float charge the LFP battery. This type of charger will NOT maintain a proper voltage algorithm and can cause damage to LFP battery.
-
Batteries connected in series do not need to be disassembled for individual recharging. However, each individual battery should be fully charged before being connected in series or parallel. Even after the charger is disconnected, the battery may not be ready until the cells are balanced. After charger has been disconnected allow 30 minutes rest time for the battery cells to balance.
-
If charging batteries in series, ensure the charging voltage is less than 14.6V times the series number.
For example, to charge 2 LFP batteries in series, the charging voltage should be less than 29.2V and the charging current should be as recommended in the specification sheet. -
DO NOT connect more than 2 LFP batteries in parallel. The voltage difference between the 2 LFP batteries must be below 100mV after being fully recharged and before the batteries are connected. The maximum charging current should be the same as single battery connection.
-
Some constant voltage chargers that require the detection of battery terminal voltage to start charging may fail to activate the LFP battery from its state of under-voltage protection (Sleep Mode). The low impedance of LFP cells may result in an inrush of current interrupting the charge. If the charger trips out, reset the charger until charging continues normally.
-
Constant current constant voltage charging (CCCV) is recommended for LFP batteries. Refer to diagram below for illustration:
4.4. Discharging
- Do not exceed the maximum discharge current as specified in the data sheet.
- Avoid discharging the LFP battery at its maximum current (1C) several times in succession, as this may cause the BMS to cut out.
- For 100Ah LFP battery, the maximum continuous load should not exceed 1100W. A maximum 1000W inverter can be connected to avoid damaging the battery including the BMS and the cells. Likewise, for 200Ah LFP battery, an inverter not exceeding 2000W is recommended.
- If connecting two 100Ah LFP batteries in parallel, a maximum 2000W inverter can also be recommended.
Continuous discharge at maximum current at high temperature will result in reduced run time and potentially BMS cut-off for temperature protection.
Troubleshooting
NO. | SIGN | POSSIBLE CAUSES | CORRECTIVE ACTIONS |
---|---|---|---|
1 | Battery working time is too short | The charging voltage is lower than | |
14.4V, and the battery charging capacity is less than the rated Ampere-Hour |
Use the standard charge voltage
The load is too high, and the battery ends discharging prematurely| Reduce
load wattage
The cell over-voltage protection has been triggered continuously| Reduce the
charge voltage (eg. 14.2V)
The ambient temperature is too high or too low, and the battery cannot be
fully charged or discharged (capacity drop at low temperature range)| Keep
working at normal ambient temperature
In parallel string, one for the two batteries is in sleep mode due to over-
current protection| Remove connection and wake up the battery then ensure both
batteries are at similar SOC before reconnection
In series string, the SOC of batteries is out of balance| Disconnect the
batteries and recharge then individually to similar SOC before reconnection
The battery life is naturally attenuated, the capacity is reduced, and the
working time is short| Replace the battery
2| BMS keeps cutting off during discharge| Discharge current is too high,
trigger overcurrent protection| Reduce discharge current
Voltage is too low, trigger low voltage protection| Recharge the battery
In parallel string, one of the two batteries is in sleep mode due to over
current protection| Remove connection and wake up the battery then ensure both
batteries are at similar SOC before reconnection
Inrush current has triggered over current protection| Reduce load current
3
|
BMS keeps cutting off during charge
| Charge current is too high, trigger overcurrent protection| Reduce charge
current
Voltage is too high, trigger high voltage protection| Disconnect charging
voltage (eg. 14.2V)
4| Bluetooth not detected by the App| Battery under sleep mode| Activate the
battery
Mobile is more than 10m away from the battery| Move the mobile closer to the
battery
Mobile device cannot detect the battery| Close the App and reopen it
Battery is already connected to a different device| Close Bluetooth connection
from the other device
App failed to display correct battery information| Update App to the latest
version
5| Battery gets too hot| Frequent overload use/high current draw| Use
according to battery specifications
Working with the maximum continuous charge and discharge current for a long
time, the heat dissipation environment is poor, resulting in heat
accumulation| Ensure a good heat dissipation environment
6| Battery no voltage reading| The battery is over-discharged below 10V and is
lower than the working voltage of the BMS, the BMS cannot work normally|
Recharge the battery in time and confirm that the battery can be switched on
normally. If the battery cannot be turned on again, replace the battery
BMS power supply line is damaged, BMS cannot work normally| Replace the
battery
Internal power cord disconnected| Replace the battery
BMS failed| Replace the battery
7| Sleep mode cannot be deactivated| The activation voltage is 1.2V lower than
the battery voltage| Ensure that the charging activation voltage is 1.2V
higher than the battery voltage
The current of load is too small| Disconnect the load and reconnect the load
to ensure that load resistance <5kΩ
In parallel string, one battery is in sleep mode due to over-discharge sleep
protection| Disconnect the battery and ensure both batteries are at similar
SOC before reconnecting
8| Battery external damage – terminal, cover, casing| Improper operation such
as drop, impact, etc.| Replace the battery
9| Battery exploded| High voltage due to improper charging causes BMS to fail,
and the battery is not protected| Replace the battery
Instant violent collisions, squeezing, puncture, rupture etc. making the
battery unable to release energy
10| BMS keeps cutting off when batteries connected in series or parallel| One
battery triggers over-voltage, under-voltage and over-current protection,
etc.| Check the load and charger situation. Ensure the system works within the
specification. Also refer to all the above relevant information
Care & Maintenance
6.1 Maintenance Inspection
- Examine the external condition of the battery. The top of battery and terminal connections should be clean, dry, and free of corrosion.
- Check battery cables and connections are firmly secure.
- Check the battery state of charge (SOC) regularly. When not in use the Century Lithium Pro battery will partially self-discharge.
- Depending on the charging profile used, overtime the series and parallel configured batteries may not be equally charged. To fully balance batteries in either of these configurations, maintenance charge each battery individually at periodic intervals.
6.2 Cleaning
- Before cleaning, disconnect the battery from the charging source and the load.
- The surface of LFP battery can be cleaned with a soft, dry cloth made of non-electroconductive material.
- Keep the area around batteries clean, dry, and away from any flammable materials.
Storage
-
Disconnect the battery from all electrical loads and from the charger to eliminate potential parasitic loads that may discharge the battery.
-
Cover the LFP battery terminals with suitable non-electroconductive material (e.g. insulating tape or plastic caps).
-
Observe the minimum and maximum storage temperatures.
-
Store in a cool, dry place. There is no specific ventilation requirements for Century Lithium Pro batteries, however sufficient airflow should be ensured to prevent excessive heat build-up.
-
Keep area free from flammable materials.
-
Keep out of reach of children and animals.
-
Do not store in direct sunlight.
-
The battery should be stored at a state of charge of between 40% ~60% of its nominal capacity.
Storing a deep discharged battery can result in permanent damage and reduced run time. -
Allowing the battery to self-discharge to a severely low state of charge may result in the battery not being able to be recovered.
-
Check battery every 6 months, or more frequently in ambient temperatures exceeding 35°C, to determine if charging is required.
Transportation
- Century Lithium Pro batteries are packed by the manufacturer to comply with all applicable national transportation regulations.
- If the battery is not installed, it must be transported in the original packaging or equivalent material.
- It is recommended that the battery should be below 60% SOC during transportation.
- Follow all applicable national transport regulations before transporting the Century Lithium Pro batteries.
- Transporting a used, damaged or defective LFP battery may be subject to restrictions. Use a qualified shipping agent properly certified for hazardous material shipment.
- The transport of a LFP battery is subject to the hazard classification UN3480, Class 9.
The following identification label must be attached to the package:
Disposal & Recycling
-
Lithium batteries must not be disposed of with household or landfill waste and in line with relevant national and or local government regulations.
-
Lithium batteries can be recycled but should not be mixed with lead acid batteries.
It is important to prevent lithium-ion batteries being mixed with lead acid and or other battery types at any stage of the recycling process. -
Refer to relevant sections of this manual, if any batteries are collected, stored and transported for recycling.
-
It is advisable to fully discharge used lithium-ion batteries prior to recycling.
-
Tape or insulate the terminals of the battery with non-conductive material to prevent short circuits.
-
In the case of a damaged battery, it must also be packaged according with the local transportation and environmental protection regulations.
-
Century Lithium Pro LFP battery can be returned to CYB or a qualified disposal facility for recycling.
Further Information
If you have any questions concerning safety precautions, installing, or using a Century Lithium Pro battery please contact Century Yuasa Batteries.
Century Yuasa Batteries Pty Ltd,
37-65 Cobalt Street, Carole Park QLD 4300
Ph: 1300 361 161 | cyb.com.au | ABN 66 009 685 232
Century Yuasa Batteries (NZ) Ltd,
259 Church Street, Onehunga, Auckland 1643
Ph: 0800 93 93 93 | cyb.co.nz | NZBN 94 290 3937 7319
NOTES___.
For more information visit
centurybatteries.com.au or call 1300 362 287
centurybatteries.co.nz or call 0800 93 93 93
CB113-3136d