L2003790-A DucoBox Energy Comfort Plus
Product Information
Specifications
- Model: L2003790-A
- Date: 05.06.2023
Product Usage Instructions
Calibration of the Desired Flow Rate
Before mounting and connecting the flow regulator, it is necessary to calibrate the desired flow rate.
Procedure:
- Slide the control module gently up or down until the mark on the control module on the left or right corresponds to the desired flow rate.
- Retighten the adjustment screw on the control module.
Mounting and Connection
The flow regulator is simply inserted into a vertical or horizontal duct (e.g.
DucoFlex). For a horizontal duct, the indication BAS/ DOWN at the front of the
flow regulator must be respected.
A lip seal ensures good airtightness.
If the flow regulator is placed near a vent, the minimum distance between the
vent and the flow regulator should be at least the diameter of the flow
regulator for an extract diffuser and at least three times the diameter of the
flow regulator for a supply vent.
IMPORTANT: DO NOT TOUCH THE MOVING CONTROL VALVE DURING ASSEMBLY!
When mounting, respect the direction of the air flow indicated on the flow
regulator.
FAQ
-
Q: Who should perform the installation, connection, maintenance, and repairs?
A: Installation, connection, maintenance, and repairs should be done by a recognized installer. -
Q: Can the electronic components of this product come into contact with water?
A: No, you should avoid contact with water as the electronic components may be live.
CALIBRATION OF THE DESIRED FLOW RATE
Before mounting and connecting the flow regulator, it is necessary to calibrate the desired flow rate.
Procedure
- Loosen the adjustment screw on the control module ¼ turn using a #10 torx screwdriver.
- Now gently slide the control module up or down until the mark on the control module on the left or right corresponds to the desired flow rate.
- Retighten the adjustment screw on the control module.
Example of setting the flow rate to 50 m³/h : the marking is on the left at the level of the number “50”.
MOUNTING AND CONNECTION
- The flow regulator is simply inserted into a vertical or horizontal duct (e.g. DucoFlex).
- For a horizontal duct, the indication “BAS/ DOWN” at the front of the flow regulator must be respected.
- A lip seal ensures good airtightness. If the flow regulator is placed near a vent, the minimum distance between the vent and the flow regulator should be at least the diameter of the flow regulator for an extract diffuser and at least three times the diameter of the flow regulator for a supply vent
DO NOT TOUCH THE MOVING CONTROL VALVE DURING ASSEMBLY!
When mounting, respect the direction of the air flow indicated on the flow
regulator!
Position of flow regulator at extraction (D = diameter)
Position of flow regulator at supply (D = diameter
Translation of the original instructions
See www.duco.eu for information regarding warranty,
maintenance, technical data, etc. Installation, connection, maintenance and
repairs should be done by a recognised installer. The electronic components of
this product may be live. Avoid contact with water.
Vero DUCO – Handelsstraat 19 – 8630 Veurne – Belgium tel +32 58 33 00 33 –
info@duco.eu – www.duco.eu