HAMPTON H27 LP Direct Vent Gas Fireplace Instruction Manual
- June 14, 2024
- HAMPTON
Table of Contents
H27U-NG/LP Direct Vent Gas FireplaceC
Owners &
Installation Manual
H27 LP Direct Vent Gas Fireplace
MODELS: H27U-NG Natural Gas H27U-LP Propane
www.hampton-fire.com
WARNING: If the information in these instructions are not followed
exactly, a fire or explosion may result causing property damage, personal
injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the
vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service
agency or the gassupplier.
FOR YOUR SAFETY
What to do if you smell gas:
- Do not try to light any appliance
- Do not touch any electrical switch:do not use any phone in your building.
- Immediately call your gas supplierfrom a neighbour’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gassupplier, call the fire department.
This appliance may only be installed in an aftermarket permanently located,
manufactured (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
Tested by:| Installer: Please complete the details on the back cover and leave
this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
---|---
HAMPTON®
Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Hampton®
Gas Stove by REGENCY FIREPLACE PRODUCTS. The H27U-NG/LP is a
hand crafted appliance designed to provide you with all the warmth and charm
of a wood fireplace at the flick of a switch.
The H27 was approved by Intertek for both safety and efficiency. As it also
bears Regency’s mark, providing you with economy, comfort, and security for
many trouble-free years to follow. Please take a moment to acquaint yourself
with these instructions and the many features of your Hampton ® Stove.
DANGER HOT GLASS WILL CAUSE BURNS
DO NOT TOUCH GLASS UNTIL COOLED
NEVER ALLOW CHILDREN TO TOUCH GLASS
A barrier designed to reduce the risk of burns from the hot viewing glass is
provided with this appliance and must be installed for the protection of
children and other at risk individuals.
CAUTION:
HOT WHILE IN OPERATION. DO NOT TOUCH.
SEVERE BURNS MAY RESULT. KEEP CHILDREN, CLOTHING, FURNITURE, GASOLINE, AND ANY
OTHER LIQUIDS WITH FLAMMABLE VAPOURS AWAY.
KEEP BURNER AND CONTROL COMPARTMENT CLEAN.
SEE INSTALLATION AND OPERATING INSTRUCTIONS ACCOMPANYING APPLIANCE.
“NATIONAL FIREPLACE INSTITUTE CERTIFIED
www.nficertified.erg
We recommend that our products be installed and serviced by professionals who
are certified in the U.S. by the National Fireplace Institute ” (NF1) or in
Canada by Wood Energy Technical Training (WETT).
safety label
This is a copy of the label that accompanies each Direct Vent Freestanding Gas
Stove. We have printed a copy of the contents here for your review.
NOTE: Hampton® units are constantly being improved. Check the label on
the unit and if there is a difference, the label on the unit is the correct
one.
Copy of Safety Label
DUPLICATE SERIAL NO.
561
Listed: VENTED GAS FIREPLACE HEATER
Ce rtified to : ANSI Z21.88-2019
DO NOT REMOVE THIS LABEL
561
Serial No.
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
Refer to Intertek’s Directory of Building Products for detailed information.
FACTORY EQUIPPED FOR NATURAL GAS Model:H27U-NG
Model: H27U-NG| Minimum supply pressure
Manifold pressure High
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude| 5″ WC/C.E. (1.25 kPa)
3.5″ WC/C.E. (0.87 kPa)
1.6″ WC/C.E. (0.40 kPa)
25,000 Btu/h (7.32 Kw/h)
18,000 Btu/h (5.28 Kw/h)
42 DMS (2.37mm)
0-4500 ft/pi (0-1372m)
---|---|---
FACTORY EQUIPPED FOR PROPANE GAS Model:H27U-LP
Model:
H27U-LP| Minimum supply pressure
Manifold pressure High
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude| 11″ WC/C.E. (2.74 kPa)
10″ WC/C.E. (2.49 kPa)
6.4″ WC/C.E. (1.59 kPa)
22,000 Btu/h (6.45 Kw/h)
17,500 Btu/h (5.13 Kw/h)
54 DMS (1.4mm)
0-4500 ft/pi (0-1372m)
---|---|---
Minimum Clearances to Combustibles
Minimum ceiling height from top of unit: 24″/610mm
A 6″/150mm
B 3″/75mm
C 2″ / 50mm
E 2″/50mm
Minimum clearance of Vent Terminal to Outside Corner & Inside Corner: with
AstroCap 6″/150mm with Dura-Vent Cap 12″/300mm
This appliance must be installed in accordance with local codes, if any; if
none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and
Propane Installation Code, CSA B149.1.
This appliance must be installed in accordance with the Standard CAN/CSA Z240
MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280, in the United States, or when such a
standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home
Installations Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational
Vehicles
This appliance is only for use with the type of gas indicated on the rating
plate and may be installed in an aftermarket, permanently located,
manufactured (mobile) home where not prohibited by local codes. See owner’s
manual for details. Optional Fan Kit (Part # 357-917)
This vented gas fireplace heater is not for use with air filters.
For use with glass doors certified with the appliance only.
For Use Only with Barrier (Part # 743-100) Follow installation instructions.
ELECTRICAL SUPPLY:115V_60HZ less than 2 AMP
VENTED GAS FIREPLACE HEATER – NOT FOR USE WITH SOLID FUELS. CATEGORY I.
FPI Fireplace Products International Ltd. Delta, BC, Canada
Made in Canada
920-417
Decal Location
Fold down access door, and then remove two screws as shown below
With the panel removed, the gas valve will be visible.
The rating plate will be attached to a black chain located under the IFC.
DO NOT REMOVE THE DECAL FROM THE UNIT.
Unit Dimensions with Vertical Venting
Unit Dimensions with Horizontal Venting
ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION
PURPOSES ONLY.
ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
owner’s information
Copy of the Lighting Plate Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life. Improper
installation, adjustment, alteration, service or maintenance can cause injury
or property damage. Refer to the owner’s information manual provided with this
appliance. For assistance or additional information consult a qualified
installer, service agency or gas supplier.
A)This appliance has a pilot that must be lighted by hand. When lighting the
pilot, follow these instructions exactly.
B) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
on the floor.
WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electric switch, do not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from a neighbours phone. Follow the gas
supplier’s instructions.
– If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, do not try to repair it;
call a qualified service technician. Force or attempted repair may result in a
fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and replace any
part of the control system and any gas control which has been underwater.
CAUTION: Hot while in operation. Do not touch. Severe burns may result.
Due to high surface temperatures keep children, clothing and furniture,
gasoline and other liquids having flammable vapors away. Keep burner and
control compartment clean. See installation and operating instructions
accompanying appliance.
LIGHTING INSTRUCTIONS
- STOP! Read the safety information above on this label.
- Push in gas control knob slightly and turn clockwise to “OFF”. Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do not force.
- Wait five (5) minutes to clear out any gas. If you then smell gas STOP! Follow step “B” in the Safety Information above on this label. If you don’t smell gas, go to the next step.
- Push in gas control knob slightly and turn counterclockwise to “PILOT” position.
- Push in control knob all the way and hold in until the pilot lights. Continue to hold the control knob in for about 20 seconds after the pilot lights. Release the knob.
- Push in gas control knob slightly and turn counterclockwise to “ON” position.
- Turn on the flame switch.
TO TURN OFF GAS TO APPLIANCE
- Turn off the flame switch.
- Push in the gas control knob slightly and turn clockwise to “OFF”. Do not force.
- Turn off all electric power to the appliance if service is to be performed.
You may shut off the pilot during prolonged non use periods to conserve fuel.
DO NOT REMOVE THIS INSTRUCTION PLATE
Installation
MA Code – CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in
every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above finished
grade in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
-
INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed. -
APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
-
SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
-
INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Gas Installation Checklist
REGENCY GAS INSTALLATION CHECKLIST
This general checklist does not contain all pertinent installation details or
specifics and does not supersede the guidelines in this manual. Your Regency
dealer/installer should use it in conjunction with manual instructions. Please
follow all local codes and jurisdictions in authority.
Customer:……………………
Install Address:…………………………
Serial No:……………
Model No:…………….
Date Installed:…………………..
Location of Fireplace:…………………..
Installer:……………….
Site Requirements | YES | NO |
---|
If applicable, are the insulation, vapour barrier, and drywall present if
installed on an outside wall or chase?| |
Does the area have a solid continuous base to support the unit?| |
Will the area accommodate the size of the applliance and all clearances?| |
Are the gas and electrical roughed into the area where the unit is being
installed?| |
In City & Grandview series cool wall applications, is the chase enclosure
sealed to prevent heat from escaping? All hot air from the unit must exit via
the mandatory ventilation openings.| |
In City & Grandview applications, Is the chase enclosure vented with the
mandatory heat ventilation openings? See manual for details.| |
If applicable, is the masonry/factory built freplace in its original condition
with no modifications?| |
If applicable, have the hearth requirements been met?| |
Unit Setup| YES| NO
If applicable, are the standoffs and top nailing flange extensions installed
and at the correct depth to accommodate finishing material? See manual for
details.| |
If applicable, is the fireplace level and secured, meeting framing clearances?
See manual for details.| |
If applicable, is the unit converted to top or rear vent per manual
instructions, and the insulation discarded?| |
Venting| YES| NO
Are the venting components approved for the unit installed?| |
Does the venting configuration comply with venting diagrams?| |
Is venting installed and secured, and are clearances for the vent pipe and
termination cap maintained?| |
If applicable, was a 1/4″ rise maintained for every foot of horizontal run?| |
Was the termination installed and sealed?| |
Is the direct vent termination at the highest point in the vent assembly?| |
If applicable, are both chimney liners continuous from flue collars to
termination?| |
Electrical and Wiring| YES| NO
Is the appliance connected to the household’s 110/120v per local codes? Check
local codes for receptacle placement.| |
Were the connections in the fireplace tested with a circuit tester?| |
Is the appliance properly grounded?| |
If applicable, is the supplied electrical/gang box affixed to the wall to
facilitate the mounting of the receiver/battery box ?| |
Gas| YES| NO
Does the supply pressure meet the requirements shown on the rating plate?| |
Was a conversion performed?| |
Was a leak check performed and manifold pressures verified?| |
Is the shut-off valve installed and easily accessible to the customer?| |
Finishing| YES| NO
---|---|---
If applicable, is only noncombustible material installed in the noncombustible
areas?| |
Do clearances meet installation and manual requirements?| |
Do the mantels and/or projections comply with the installation manual?| |
If applicable, was the solid fuel fireplace warning plate installed?| |
Appliance Media Setup| YES| NO
Do commands from the remote or wall switch light the pilot and main burner?| |
Are the burner media/log set, glass door, and screen installed per
instructions in the manual?| |
Was the air shutter on the proper setting after running the unit for 20
minutes?| |
If applicable, were the surround and trims installed according to the manual?|
|
Was the operation of the fan, lights (if installed), and flame modulation
checked?| |
Customer Tutorial and Presentation| YES| NO
Is the customer confident operating the new gas appliance and aware of all the
features on the remote?| |
Confirm that the rating and lighting plates are attached to the appliance. Do
not remove.| |
Was the customer informed of the location of the rating and lighting plates?|
|
Was accessing unit controls in a power outage explained to the customer?| |
Are the model and serial numbers and the date of installation of the unit
written in the manual and on the checklist?| |
Were the warranty and unit registration reviewed with the customer?| |
Comments:
Before You Start
Safe installation and operation of this appliance requires common sense,
however, we are required by the Canadian Safety Standards and ANSI Standards
to make you aware of the following:
**** INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON.
THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO
EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE
BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY
AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE
TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID
BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA
AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO
ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT
RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE,
INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER
AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE
APPLIANCE.
Important Message
SAVE THESE INSTRUCTIONS
The Direct Vent Freestanding Gas Stove must be installed in accordance with
these instructions.
Carefully read all the instructions in this manual first.
Consult the building authority having jurisdiction to determine the need for a
permit prior to starting the installation.
Note: Failure to follow the instructions could cause a malfunction of the
heater which could result in death, serious bodily injury, and/or property
damage. Failure to follow these instructions may also void your fire insurance
and/or warranty.
Note: These instructions take precedence over Simpson Dura-Vent
instructions.
Specifications
Fuels: H27U-NG is approved for use with naturalgas.
H27U-LP is approved for use with liquefiedpetroleum gases (propane).
Electrical: 120V A.C. system.
Optional Circulation Fan: Variable speed, 125CFM High/75CFM Low.
Log Sets: Ceramic fibre, 4 per set.
Vent System: Coaxial (6-5/8″ outer / 4″ inner liner) rigid flue and
termination cap.
Information for Mobile / Manufactured Homes After First Sale
This Hampton ® product has been tested and listed by Intertek Testing Services
as a Direct Vent Heater to the following standard: ANSI Z21.88. This Direct
Vent System Appliance must be installed in accordance with the manufacturer’s
installation instructions and the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety
Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA
501A, and with CAN/ CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer’s installation
instructions and local codes, if any. In the absence of local codes follow the
current National Fuel Gas Code, ANSI Z223.1 and the current National
Electrical Code ANSI/NFPA70 in the U.S.A., and the current CSA B149.1 Gas
Installation Code and the current Canadian ElectricalCode CSA C22.1 in Canada.
This Hampton® Mobile/Manufactured Home Listed appliance comes factory equipped
with a means to secure the unit.
This Hampton® Mobile/Manufactured Home listed appliance comes equipped with a
dedicated #8 ground lug to which an 18 gauge copper wire from the steel
chassis ground must be attached. This appliance may only be installed in an
aftermarket permanently located, manufactured (USA only) or mobile home, where
not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
-
Provide adequate clearances for servicing, proper operation and around the air openings into the combustion chamber.
-
The appliance must be installed on a flat, solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or it can be raised up on a platform to enhance its visual impact. The appliance may be installed on carpeting, tile, wood flooring or other combustible material, because the appliance’s base extends the full width and depth of the appliance. The Direct Vent Freestanding Gas Stove can be installed in a wide variety of ways and will fit nearly any room layout. It may be installed in a recessed
position, framed out into the room, or across a corner. -
The Direct Vent Freestanding Gas Stove is approved for alcove installations, which meet the clearances listed on in the “Clearance toCombustibles” section. This unit is approved for manufactured home installations, see the “Manufactured Mobile Home Additional Requirements” section and “Venting Arrangements” section for the required vent arrangements. If installed into a manufactured home the unit must be bolted down to the floor.
-
This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
-
This appliance is Listed for Alcove installations, maintain minimum Alcove clearances as follows, minimum width of 34-3/4″ (882mm), a maximum depth of 36″ (914mm), and minimum ceiling height of 51″ (1295mm) from floor to ceiling.
-
We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a qualified building inspector review your plans before installation.
General Safety Information
- The appliance installation must conform with local Canadian Electrical Code.
- The appliance when installed, must beelectrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.
- The appliance should be inspected for shipping damage before use and serviced annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material,etc. It is imperative that control compartments, and circulating air passageways of the appliancebe kept clean and free from excessive lint from carpeting.
- See general construction and assembly instructions. The appliance and vent should be enclosed when installed in or passing through a living area, where children may come in contact with it.
- This appliance must be connected to thespecified vent and termination cap to the outsideof the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per the instructions starting in the “Exterior Vent Terminal Locations” section.
- Inspect the venting system annually for blockageand any signs of deterioration.
- Venting terminals shall not be recessed into a wall or siding.
- Any safety glass removed for servicing must be replaced prior to operating the appliance.
- To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
Emissions from burning wood or gas could contain chemicals known to the State
of California to cause cancer, birth defects or other reproductive harm.
Installation Checklist
-
Locate your appliance. Refer to the following sections:
a. Clearances to Combustibles
b. Locating Your Gas Stove
c. For venting requirements, see “Venting
Introduction” to “Rigid Pipe Venting Systems” sections. -
Install Optional Fan. Refer to the “Optional Fan Installation” section.
-
Set vent restrictor. Refer to the “Vent Restrictor Position” section.
-
Install venting:
a. Check all venting requirements. See “Vent Restrictor Position” to Rigid Pipe Venting Systems” sections
b. Vertical Termination with Co-linear Flex System
c. DV Stove Horizontal Vent Kit
d. Minimum Horizontal Termination
e. Dura-Vent Termination Kit -
Make gas connections. Refer to the “Gas Connection” section.
Test the pilot. Must be as per diagram in the “Maintenance Instruction” section.
If converting to Propane, make changes prior.
Refer to the “Conversion from Natural Gas to Propane” section. -
Test Gas Pressure. Refer to the “Pressure Testing” section.
-
Install standard and optional features. Refer to the following sections where applicable:
a. Log Set Installation
b. LP Conversion Kit
c. Wall Thermostat
d. Remote Control
e. Fan Kit -
Final check. Refer to the “Final Check” section.
Before leaving this unit with the customer, the installer must ensure that the
appliance is firing correctly and operation fully explained to customer.
This includes:
- Clocking the appliance to ensure the correct firing rate (rate noted on label) after burning appliance for 15 minutes.
- If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning
that results in damage is not the responsibility of the manufacturer.
Clearances To Combustibles
The clearances listed are MINIMUM distances. Measure the clearance to both the
appliance and the chimney connector. The farthest distance is correct if the
two clearances do not coincide.
For example, if the appliance is set as indicated in one of the figures but
the connector is too close, move the stove until the correct clearance to the
connector is obtained.
This appliance may be installed only with the clearances as shown in the
situations pictured.
Do not combine clearances from one type of installation with another in order
to achieve closer clearances.
This unit can be installed on a solid combustible surface like a wood floor.
This unit can also be installed directly on carpeting or vinyl.
Use the minimum clearances shown in the diagrams below:
H27U-NG & H27U-LP Clearances
A Left Side Wall to Unit* 6″ / 150 mm
B Back Wall to Unit 3″ / 75 mm
C Vertical Vent Pipe to Back Wall 2″ / 50 mm
E Unit Corner to Wall 2″ / 50 mm
Unit Top to Alcove Ceiling 24″ / 610 mm
Minimum ceiling height is 24″ /610 mm from top of unit.
Locating Your Gas Stove
When selecting a location for your stove, ensurthat the clearances listed
above are met as welas ensuring that there is adequate accessibilitservicing
and proper operation. A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/Alcove
For Vent Termination requirements, see “Exterior Vent Terminal Locations”
section.
Manufactured Mobile Home
Additional Requirements
- Ensure that structural members are not cut or weakened during installation.
- Ensure proper grounding using the #8 ground lug provided.
- Appliance must be anchored to the floor with the supplied anchoring methods.
Combustion and Ventilation Air
The combustion air from this appliance is drawn from outside the building
through the outer flue.
Extra provision for combustion air inside the room is not required.
Optional Fan Installation
Fan Kit Contains:
Qty. Description
1 Fan Assembly c/w green wire attached
1 Thermodisc
1 Power Cord
2 2-1/4″ x 20 Hex Nut
1 Fan Speed Control
3 Clip Wire Holders
-
a) Remove the rear access panel on the back of the stove by removing the 2 screws under the rear panel. b) Lift off the 2 bolts at the top.
Take care not to cut wires when lowering the panel. -
Lift Rear Panel off the 2 top bolts
-
Remove the Top Control Panel Assembly by removing the three screws.
-
Remove the nylon hole plug from the control panel.
-
Install the fan speed controller onto the control panel and secure with nut and washer. Connect the red and black wires from the wire harness to speed controller.
NOTE: Speed control wires must be in the down position when control panel is in place. Fan Speed Controller -
Push black knob onto speed control.
-
Re-attach control panel with 3 screws, reversing step 3.
-
Place the blower close to the base of the unit and feed the 3 wires from the fan through theopening of the base of the unit.
-
Connect the ground (green) wire to the gound lug on either side of the unit.
-
Slide the thermodisc into the bracket on the left side of the rear firebox. Connect the black wire 811 (90 degrees) & red (straight,from speed controller) wires to the thermodisc.
-
Mount the blower assembly in position under the base of the stove and secure with the 2 supplied bolts (2-1/4″ #20 hex head).
-
Before re-attaching the rear access panel, connect live wire (black/ from fan) to black wire 704 (from speed controller). Use the clip wire holders to organize the wires.
-
Slide the Rear Access Panel back into position. Make sure the wires are not blocking the passage of the relief door. Secure with 2 screws.
Grounding lug in fan:
Grounding lug in fan: WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your
protection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the grounding prong from
this plug.
Venting Introduction
The Horizontal Termination Kit and other approved venting systems as per table
on next page, in combination with the Direct Vent Freestanding Gas Stoves,
H27U-NG, and H27U-LP, have been tested and listed as direct vent heater
systems by Warnock Hersey.
These units use the “balanced flue” technology Co-Axial system. The inner
liner vents products of combustion to the outside while the outer pipe draws
outside combustion air into the combustion chamber thereby eliminating the
need to use heated room air for combustion and losing warm room air up the
chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of
the building, and never be attached to a chimney serving a separate solid fuel
or gas burning appliance. Each direct vent gas appliance must use it’s own
separate vent system.
Common vent systems are prohibited.
IMPORTANT
Read all instructions carefully before starting the installation. Failure to
follow these instructions may create a fire or other safety hazard, and will
void the warranty. Be sure to check the venting and clearance to combustible
requirements. Consult your local building codes before beginning installation.
The location of the termination cap must conform to the requirements in the
“Exterior Vent Terminal Locations” section.
Installation Precautions
These venting systems are engineered products that have been designed and
tested for use with the H27U-NG, and H27U-LP. The warranty will be voided and
serious fire, health or other safety hazards may result from any of the
following actions:
- Installation of any damaged Direct Vent component
- Unauthorized modification of the Direct Vent System
- Installation of any component part not manufactured by approved venting systems as per table on next page or FPI Fireplace Products International Ltd.
- Installation other than as instructed by approved venting systems as per table on next page and FPI Fireplace Products International Ltd.
Warning: Always maintain required clearances (air spaces) to nearby
combustibles to prevent a fire hazard.
Do not fill air spaces with insulation.
Be sure to check the vent termination clearance requirements from decks,
windows, soffits, gas regulators, air supply inlets and public walkways as
specified in the “Exterior Vent Terminal Locations” section and in your local
building codes.
The gas appliance and vent system must be vented directly to the outside of
the building, and never be attached to a chimney serving a separate solid fuel
or gas-burning appliance. Each direct vent gas appliance must use it’s own
separate vent system. Common vent systems are prohibited.
Safety Precautions for the Installer
- Wear gloves and safety glasses for protection.
- Exercise extreme caution when using ladders or on roof tops.
- Be aware of electrical wiring locations in walls and ceilings.
Vent Restrictor Position
To set the Vent restriction as indicated in the diagrams in “Venting
Arrangements” section, simply loosen the screws and push the vent restrictor
plate to the correct position. Tighten the screws. Rotating 45 o Elbow
- Remove all 4 screws that securthe elbow to the unit using a 1/4″ magnetic nut driver.
- Rotate the elbow 180 o
- Secure the elbow by securing it with the 4 screws.
Exterior Vent Terminal Locations
| Minimum Clearance Requirements| Canada 1| USA 2
---|---|---|---
A| Clearance above grade, veranda, porch, deck, or balcony| 12″(30cm)|
12″(30cm)
B| Clearance to window or door that may be opened| 12″(30cm)| 9″ (23cm)
C| Clearance to permanently closed window| |
D| Vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 2 feet (61cm) from the center line of the
terminal (check with the local code)| 22″(56cm)| 22″(56cm)
E| Clearance to unventilated soffit| 12″(30cm)| 12″(30cm)
F| Clearance to outside corner: with AstroCap and Vent Riser
Termination Caps| 6″(15cm)| 6″(15cm)
Clearance to outside corner: with all other approved Termination Caps.|
12″(30cm)| 12″(30cm)
G| Clearance to inside corner: with AstroCap and Vent Riser
Termination Caps| 6″(15cm)| 6″(15cm)
Clearance to inside corner: with all other approved Termination Caps|
12″(30cm)| 12″(30cm)
H| Clearance to each side of center line extended above meter/regulator
assembly| 36″(90cm)a|
J| Clearance to service regulator vent outlet| 36″(90cm)|
K| Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance| 12″(30cm)| 9″ (23cm)
L| Clearance to a mechanical air supply inlet
3′ (91cm) above if within 10′ (3m) horizontally.| 72″(1.8m)| 36″(90cm)b
M| Clearance above paved sidewalk or a paved driveway located on public
property| 84″(2.1m)┼|
N| Clearance under veranda, porch, deck, or balcony| 12″(30cm)‡|
1 In accordance with current CSA B149.1, Natural Gas and Propane
Installation Code
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas
Code
┼ A vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a
minimum of two sides beneath the floor
*** a Clearance in accordance with local installation codes and the
requirements of the gas supplier
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator
assembly
b** 3 feet (91cm) above – if within 10 feet (3m) horizontally
4″ X 6-5/8″ RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe
components are available directly from Regency FPI.
Components from different Manufacturers may not be mixed. Not all rigid pipe
components are available directly from Regency.
Description| Simpson Direct Vent Pro®| *Selkirk Direct Temp™*|
American Metal Products® Amerivent Direct| Metal-Fab™ Sure Seal|
Security Secure- Vent®| ICC Excel Direct| Olympia Ventis
DV*
---|---|---|---|---|---|---|---
6″ Pipe Length-Galvanized| 46DVA-06| 4DT-6| N/A| 4D6| SV4L6| TC-4DL6| VDV-0406
6″ Pipe Length-Black| 46DVA-06B| 4DT-6B| N/A| 4D6B| SV4LB6| TC-4DL6B|
VDVB-0406
7″ Pipe Length-Galvanized| N/A| N/A| 4D7| N/A| N/A| N/A| N/A
7″ Pipe Length-Black| N/A| N/A| 4D7B| N/A| N/A| N/A| N/A
9″ Pipe Length-Galvanized| 46DVA-09| 4DT-9| N/A| N/A| N/A| TC-4DL9| VDV-0409
9″ Pipe Length-Black| 46DVA-09B| 4DT-9B| N/A| N/A| N/A| TC-4DL9B| VDVB-0409
12″ Pipe Length-Galvanized| 46DVA-12| 4DT-12| 4D12| 4D12| SV4L12| TC-4DL1|
VDV-0412
12″ Pipe Length-Black| 46DVA-12B| 4DT-12B| 4D12B| 4D12B| SV4LB12| TC-4DL1B|
VDVB-0412
18″ Pipe Length-Galvanized| 46DVA-18| 4DT-18| 4D18| 4D18| SV4LA| TC-4DL18|
VDV-0418
18″ Pipe Length-Black| 46DVA-18B| 4DT-18B| 4D18B| 4D18B| SV4LA| TC-4DL18B|
VDVB-0418
24″ Pipe Length-Galvanized| 46DVA-24| 4DT-24| 4D24| 4D24| SV4L24| TC-4DL2|
VDV-0424
24″ Pipe Length-Black| 46DVA-24B| 4DT-24B| 4D24B| 4D24B| SV4LB24| TC-4DL2B|
VDVB-0424
36″ Pipe Length-Galvanized| 46DVA-36| 4DT-36| 4D36| 4D36| SV4L36| TC-4DL3|
VDV-0436
36″ Pipe Length-Black| 46DVA-36B| 4DT-36B| 4D36B| 4D36B| SV4LB36| TC-4DL3B|
VDVCB-0436
48″ Pipe Length-Galvanized| 46DVA-48| 4DT-48| 4D48| 4D48| SV4L48| TC-4DL4|
VDV-0448
48″ Pipe Length-Black| 46DVA-48B| 4DT-48B| 4D48B| 4D48B| SV4LB48| TC-4DL4B|
VDVB-0448
60″ Pipe Length-Galvanized| 46DVA-60| 4DT-60| N/A| N/A| N/A| N/A| N/A
60″ Pipe Length-Black| 46DVA-60B| 4DT-60B| N/A| N/A| N/A| N/A| N/A
Adjustable Length 3″-10″-Galvanized| N/A| N/A| N/A| 4DAL| N/A| TC-4DLT| N/A
---|---|---|---|---|---|---|---
Adjustable Length 3″-10″-Black| N/A| N/A| N/A| 4DALB| N/A| TC-4DLTB| N/A
Adjustable Length 7)-Galvanized| N/A| N/A| 4D7A| N/A| N/A| N/A| N/A
Adjustable Length 7″-Black| N/A| N/A| 4D7AB| N/A| N/A| N/A| N/A
Extension Pipe 8-1/2″-Galvanized| 46DVA-08A| N/A| N/A| N/A| N/A| N/A| N/A
Extension Pipe 8-1/2″-Black| 46DVA-08AB| N/A| N/A| N/A| N/A| N/A| N/A
Adjustable Length 12″-Galvanized| N/A| N/A| 4D12A| N/A| SV4LA12| TC-4dLSI| N/A
Adjustable Length 12″-Black| N/A| N/A| 4D12A| N/A| SV4LBA12| TC-4dLSIB| N/A
Extension Pipe 16″-Galvanized| 46DVA-16A| N/A| N/A| N/A| N/A| N/A| N/A
Extension Pipe 16″-Black| 46DVA-16AB| N/A| N/A| N/A| N/A| N/A| N/A
Ceiling Support| N/A| 4DT-CS| 4DSP| 4DFSP|
SV4SD| TM4-RDS| VDV-SCR04*
---|---|---|---|---|---|---|---
Cathedral Support Box| 46DVA-CS| 4DT-CSS| 4DRSB| 4DRS| SV4CSB| TM4-SDS| VDV-
CSS04
Wall Support/Band| 46DVA-WS| 4DT-WS/B| 4DWS| 4DWS| SV4BM| TM-SWS| VDV-WS04
Offset Support| 46DVA-ES| 4DT-OS| N/A| N/A| SV4SU| TM-SOS| N/A
Wall Thimble-Black| 46DVA-WT| 4DT-WT| 4DWT| 4DWT| SV4RSM| N/A| VDV-WPT04
Wall Thimble Cover/Ceiling Support| 46DVA-DC| N/A| N/A| N/A| SV4PF| N/A| N/A
Firestop Spacer| 46DVA-FS| 4DT-FS| 4DFSP| 4DFS| SV4BF| TM-4CS| VDV-FS04
Trim Plate-Black| N/A| 4DT-TP| 4DFPB| 4DcP| SV4LA| TM-4TP| VDV-WTC04
Description| Simpson Direct Vent Pro®| Selkirk Direct Temp™| American Metal
Products® Amerivent Direct| Metal-Fab™ Sure Seal| Security Secure- Vent®|
ICC Excel Direct| Olympia Ventis DV
---|---|---|---|---|---|---|---
Attic Insulation Shield 12″| 46DVA-IS| N/A| 4DAIS12| 4DIS| SV4RSA| N/A| VDV-
AIS04
Attic Insulation Shield – Cold Climates 36″| N/A| N/A| 4DAIS12| N/A| N/A| TM-
4AS| N/A
Basic Horizontal Termination Kit (A)| 46DVA-KHA| 4DT-HKA| 4DHTK2| 4DHTKA| SV-
SHK| TM4-HTK| VDV-KW04
---|---|---|---|---|---|---|---
Horizontal Termination Kit (B)| N/A| 4DT-HKB| 4DHTK1| 4DHTKB| SV-HK| TM4-HTK|
VDV-K04
Vertical Termination Kit| N/A| 4DT-VKC| 4DHTK| 4DHTK| SV-FK| N/A| N/A
High Wind Vertical Cap| 46DVA-VCH| N/A| N/A| N/A| N/A| TM-4VT| VDV-VCHW04
---|---|---|---|---|---|---|---
High Wind Horizontal Cap| N/A| N/A| N/A| N/A| N/A| TM-4DHT| N/A
Horizontal Square Termination Cap| 46DVA-HC| 4DT-HHC| 4DHC| 4DHT| SV4CHC-1|
TM-4HT| VDV-HC04
Vertical Termination Cap| 46DVA-VC| 4DT-HVC| 4DVC| 4DVT| SV4CGV-1| N/A| N/A
Storm Collar| 46DVA-SC| 4DT-SC| 4DSC| 4DSC| SV4FC| TM-SC| VDV-SC04
Flashing – Flat Roof| 46DVA-FF| N/A| N/A| N/A| N/A| N/A| N/A
---|---|---|---|---|---|---|---
Adjustable Flashing 0/12-6/12| 46DVA-F6| 4DT-ST14| 4D12S| 4DF| SV4STC14| TF-
4FA| VDV-F0406
Adjustable Flashing 6/12-12/12| 46DVA-F12| 4DT-ST36| 4D36S| 4DF-12| SV4STC36|
TF-4FB| VDV-SSO
Vinyl Siding Standoff| 46DVA-VSS| 4DT-VS| N/A| 4DVS| SV4VS| TM-VSS| N/A
---|---|---|---|---|---|---|---
Vinyl Siding Shield Plate| N/A| 4DT-VSP| N/A| N/A| SV4VS| N/A| N/A
Snorkel Termination 14”| 46DVA-SNK14| N/A| N/A| N/A| N/A| TM-4ST14| N/A
---|---|---|---|---|---|---|---
Snorkel Termination 36”| N/A| N/A| N/A| N/A| N/A| TM-4ST36| N/A
Wall Firestop| 46DVA-WFS| N/A| N/A| N/A| N/A| TM-4TR| VDV-FS04
---|---|---|---|---|---|---|---
- Not available from Regency
***Olympia Ventis DV application for the following units only when using 4″ x 6-5/8″ vent system: B36XTE, B36XTCE, all City Series 40 models, CV72E/CB72E (power-vented models only), G600C, G600C-1, G600EC, G800C, G800C-1, G800EC, P36, P36E, and RC500E.
FPI
946-506/P| Vent Guard (Optional) for AstroCap| 946-205| Vinyl Siding Shield
for Riser Vent Terminal
**510-994| Rigid Pipe Adaptor (Must use with all rigid piping)| 946-208/P|
Vent Guard (Optional) for Riser Vent Terminal
640-530/P| Riser Vent Terminal| 946-523/P| AstroCap Horizontal Cap
| | 946-206| Vinyl Siding Standoff for AstroCap
The rigid pipe adaptor is not required on the C34, C34E, U39, U39E, H15,
H27, H35 & RC500E.
Note:** When using Metal-Fab Sure Seal Rigid Piping please note that the
Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor
(510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.|
|
---|---|---
Pipe Length (L)| 4″ x 6-5/8″ Venting| | For specific instructions on venting
components – visit the manufacturers website listed below.
Run (X)| Rise (Y)
0″ (0mm)| 4-7/8″ (124mm)| 13-7/8″ (340mm)| Simpson Direct Vent Pro:
www.duravent.com
6″ (152mm)| 8″ (203mm)| 16-1/2″ (419mm)| Selkirk Direct-Temp:
www.selkirkcorp.com
9″ (229mm)| 10-1/8″ (257mm)| 18-5/8″ (473mm)| American Metal Products:
www.americanmetalproducts.com
12″ (305mm)| 12-1/4″ (311mm)| 20-3/4″ (527mm)| Metal-Fab Sure Seal:
www.mtlfab.com
24″ (610mm)| 20-5/8″ (524mm)| 29-1/8″ (740mm)| Security Secure Vent:
www.securitychimneys.com
36″ (914mm)| 29″ (737mm)| 37-1/2″ (953mm)| Industrial Chimney Company: www
.icc-rsf.com
48″ (1219mm)| 37-7/16″ (951 mm)| 45-15/16″ (1167mm)| Olympia Ventis DV:
www.olympiachimney.com
Note: Horizontal runs of vent must be level, or have a 1/4” rise for
every 1 foot of run towards the termination.
Never allow the vent to run downward – this could cause high temperatures and
may present a possible fire hazard.
Rigid Pipe Venting Systems
Horizontal or Vertical Terminations
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all
systems. This product has been evaluated by Intertek for using a Rigid Pipe
Adaptor in conjunction with Duravent Direct-Vent Pro, Selkirk DirectTemp,
Ameri Vent Direct, ICC Excel venting and Security Secure Vent systems. Use of
these systems with the Rigid Pipe adaptor is deemed acceptable and does not
affect the Intertek WHI listing of components.
When using Rigid Vent other than Simpson Dura-Vent, 3 screws must be used to
secure rigid pipe to adaptor.
The FPI AstroCap TM and FPI Riser Vent terminal are certified for
installations using FPI venting systems as well as Simpson Dura-Vent ® Direct
Vent, American Metal Products Ameri Vent Direct Vent, Security Secure Vent ® ,
Selkirk Direct-Temp and ICC Excel. AstroCap TM is a proprietary trademark of
FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent Pro are
registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
Venting Arrangements
Horizontal Terminations for All Venting Systems
The shaded areas in the diagram below showall allowable combinations of
vertical runs with horizontal terminations. Maximum one 90 O elbow (two 45 o
elbows equal one 90 o elbow).
Propane and Natural Gas: Residential, Manufactured and Mobile Homes
Installations
May be installed in Manufactured (Mobile) Homes after first sale.
Vertical Terminations Systems for Residential Manufactured and Mobile Homes
The shaded area in the diagram below shows all allowable combinations of
straight vertical and offset to vertical runs with vertical terminations.
Maximum two 45 o elbows.
If the vent is ENCLOSED in a chase (min. size 9″ x 9″) maintain a 1-1/4″
clearance to combustibles.
May be installed in Manufactured (Mobile) Homes after first sale.
Offset to Vertical Terminations
Venting Arrangements – Horizontal Terminations Using Dura-Vent Venting Sand/or
Riser Vent Termination
The two diagrams show all allowable combinations of straight horizontal
termination with one 45 o elbow off the unit with Snorkels or FPI Riser Vent.
Restrictor position “A”. Horizontal Venting with Two (2) 90 o Elbows
One 90 o elbow = Two 45 o elbows.
Option| V| H + H1| With these options, maxi- mum total pipe
length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet
total horizontal.
Please note minimum 1 foot between 90 o elbows is
required.
---|---|---|---
A)| 2′| Min.| 4′| Max.
B)| 3′| Min.| 5′| Max.
C)| 4′| Min.| 6′| Max.
D)| 5′| Min.| 7′| Max.
E)| 6′| Min.| 8′ Max.
| |
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the “Vent Restrictor
Position” section.
Horizontal Venting with Two (2) 90 o Elbows
One 90 o elbow = Two 45 o elbows.
Option| H| V| H + H1| With these options, max. total pipe
length is 30 feet with min. of 8 feet total vertical and max. 8 feet total
horizontal.
Please note min. 1 foot between 90 o elbows is required.
---|---|---|---|---
A)| 1′ Max.| 1′ Min.| 3′ Max.
B)| 2′ Max.| 2′ Min.| 5′ Max.
C)| 3′ Max.| 4′ Min.| 6′ Max.
D)| 4′ Max.| 6′ Min.| 7′ Max.
E)| 5′ Max.| 8′ Min.| 8′ Max.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the “Vent Restrictor
Position” section.
Vertical Venting with Two (2) 90 o Elbows
One 90 o elbow = Two 45 o elbows.
Option| V| H| V + V1| With these options, max. total pipe
length is 30 feet with min. of 6 feet total vertical and max. 8 feet total
horizontal.
Please note min. 1 foot between 90 o elbows is required.
---|---|---|---|---
A)| 1′ Min.| 4′ Max.| 2′ Min.
B)| 2′ Min.| 5′ Max.| 3′ Min.
C)| 3′ Min.| 6′ Max.| 4′ Min.
D)| 4′ Min.| 7′ Max.| 5′ Min.
E)| 5′ Min.| 8′ Max.| 6′ Min.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the “Vent Restrictor
Position” section.
Vertical Venting with Two (2) 90 o Elbows
One 90 o elbow = Two 45 o elbows.
Option| H + H1| V| With these options, max. total pipe length
is 30 feet with min. of 6 feet total vertical and max. 6 feet total
horizontal.
Please note min. 1 foot between 90 o elbows is
required.
---|---|---|---
A)| 2′ Max.| 2′ Min.
B)| 3′ Max.| 3′ Min.
C)| 4′ Max.| 4′ Min.
D)| 5′ Max.| 5′ Min.
E)| 6′ Max.| 6′ Min.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the “Vent Restrictor
Position” section.
Vertical Termination with Co-linear Flex System
THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE
SOLID FUEL BURNING APPLIANCE.
This appliance is designed to be attached to two 3″ (76mm) co-linear aluminium
flex running the full length of the chimney. See the Venting Arrangements
chart below for minimum and maximum flue lengths. See chart below for minimum
distances from roof. Periodically check that the vent is unrestricted.
Vertical Terminations with Co-linear Flex System for Residential &
Manufactured Homes into Masonry Fireplaces
The shaded area in the diagram shows the allowable vertical terminations.
Note: Must remove 4 screws from stove collar and rotate 130 to have collar
facing straight back. Secure into place with 4 screws.
Straight Vertical Terminations
Masonry chimneys may take various contours which the flexible liner will
accommodate. However, keep the flexible liner as straight as possible, avoid
unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the
termination cap.
Required Parts:
Part # | Description |
---|---|
946-529 | Co-linear DV Vertical Termination Cap |
948-305 | 3″ Flex – 35 ft. |
946-563 | Co-Axial to Co-Linear Adapter Kit which contains the following: Co- |
linear Flex Adapter (270-585) Outer Pipe (946-257) Inner Pipe Adapter (946-219)
Alternate Approved Caps:
Part # | Description |
---|---|
46DVA-HC | Vertical Termination Cap OR |
46DVA-VCH | High Wind Cap |
46DVA-GK | 3″ Co-linear Adaptor with flashing |
DV Stove Horizontal Vent Kit
DV 2 ft. Stove Vent Kit (Part # 946-116) and DV 4 ft. Stove Vent Kit (946-216)
includes all the parts needed to install the H27U-NG Direct Vent unit with
minimum horizontal and vertical vent dimensions. For installations that
require longer vertical and/or horizontal vents use the Dura-Vent system as
shown in the “Dura-Vent Termination Kit” and “Dura-Vent Venting Components”
sections.
Qty. | Description |
---|---|
1) 1 | Rigid Pipe Section (Kit # 946-116: 2 ft. (1.2m) length,Kit # 946-216: 4 |
ft. (1.2m) length), 6-1/2″ (165mm) inside diameter
2) 1| Flex Liner, compressed aluminium 2 ply liner, 4″ (102mm) inside diameter
3) 4| spring spacers
4) 1| 90 deg. Elbow
5) 1| Adjustable pipe section 13-1/2″ to 24″ (343mm x 610mm), 2 pcs.
6) 1| Thimble Cover
7) 1| Wall Thimble (2 pcs.)
8) 1| Adapter
9) 1| AstroCap Termination Cap
10) 2| Trim Collars
11) 1| Tube of Mill-Pac, high temperature sealant
12) 12| Screws, #8 x 1/2″ Self tapping, Stainless Steel
13) 14| Screws, #8 x 1/2″ Self tapping, Black
14) 4| Screws #8 x 1-1/2″ Drill Point, Black
15) 4| Screws #8 x 1-1/2″ Drill Point, Stainless Steel
16) 8| Wood screws #8 x 1″
Note:
a) Liner sections should be continuous without any joints or seams.
b) This is an approved system, therefore components in this system must not be
substituted for any other manufacturer’s products.
DV Stove Horizontal Vent Kit (#946-116 & #946-216) Installation
Review the following sequence of instructions which are typical of most
installations. The sequence may vary depending on wall thickness. See the
“Exterior
Vent Terminal Locations” section for vent location and clearance dimensions,
and “Vent Restrictor Position” section to set the Vent Restrictor to the
correct position.
-
Set the unit in its desired location. Check to determine if wall studs will be in the way of the venting system, adjust location until all clearances are met and there are no obstructions.
Nbote: A 1-1/2″(38mm) clearance around the outer pipe must be maintained except that only a 1″ (25mm) clearance is needed at the termination end.
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area. -
Assemble a trial fit to determine the vertical centerline for the vent termination.
a) Cut a 9-1/2″ x 9-1/2″ (241mm x 241 mm) square hole on both the interior and exterior wall. The larger diameter end of the adjustable pipe goes to the vent terminal.
d) Install the 90 o elbow onto the adjustable pipe to determine the vertical centerline.
Note: if the centerline cannot be met, the adjustable sections will have to be cut.
e) Cut the 4 ft. section of rigid pipe to length.
Attach the 45 o elbow to the rigid pipe, and ensure that the pipe length when cut (with the 45 o elbow) will seat onto both the starter collar and the 90 o elbow. Crimped section of rigid pipe seats into the 90 o elbow. Only cut the uncrimped side of pipe.
Dismantle all pipe sections including vent terminal. 3) -
Attach the 4″ dia. flex liner to the vent terminal ensuring that the flex overlaps the collar of the vent terminal by a minimum of 1-3/8″(35mm).
Use Mill-Pac to seal and secure with 3 of the #8 x 1/2″ screws (stainless steel). -
Attach the adjustable pipe section to the vent terminal using Mill-Pac and/or high temperature silicone and attach with 3 of the #8 x 1/2″ screws (stainless steel).
NOTE: For best results and optimumperformance with each approveventing system, it is highlyrecommended to apply “Mill-Pac”sealant (supplied) to every inner pipe connection. Failure to do so may resulin drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
Note: The pipe seam should be facing down.
Note: To make the installation moraesthetically pleasing, we recommendframing out a square that the cap can be mounted on.
Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. For vinyl siding standoffinstallation refer to the Dura-VentTermination instructions. -
Slide the partially connected pipe and vent terminal assembly through the wall thimbles (from the exterior into the interior) and secure the cap to the exterior wall with 4 of the supplied screws (#8 x 1-1/2″ drill point, stainless steel).
Note: pilot holes will need to be drilled through the wall thimble on all 4 corners.
Note: The four screws provided for the vent cap should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings. -
A bead of non-hardening mastic should be run around both the termination and vinyl siding standoff to prevent water from entering and to make a tight seal between the cap and the standoff.
-
Stretch the 4″ dia. flex liner out fully and get a trial fit of the liner onto the 4″ dia. starter collar.
-
Cut the 4″ dia. flex liner to the desired size. Hint: leave an extra 12″ to 16″ of length, this will make the final assembly easier to work with. Fourrures en bois
-
Secure the 4″ dia. flex liner to the 4″ adapter with Mill-Pac and 3 of the #8 x 1/2″ screws (stainless steel).
-
Slide the decorative Thimble Cover over the pipe sections and secure with 4 screws (#8 x 1-1/2″ drill point, black) to the wall.
-
Slide the 90 o elbow (crimp end up), the 45 o elbow and the 4 ft. pipe section (crimp end up) over the 4″ dia. flex liner.
-
Install the spring spacers onto the pipe sections.
-
Secure the 4″ dia. flex liner with adapter onto the stove collar. Put a bead of Mill-Pac around the appliance adapter and secure with 3 screws (#8 x 1/2, stainless steel).
-
Attach the 45 o elbow onto the starter collar by sealing with Mill-Pac and/or high temperature silicone and securing with 3 of the #8 x 1/2″ (black) screws.
-
Attach the pipe section to the 45 o elbow by sealing with Mill-Pac and/or high temperature silicone and securing with 3 of the #8 x 1/2″ screws (black). Pipe seams should be facing the wall.
-
Attach the 90 o elbow onto the pipe section by sealing with Mill-Pac and/or high temperature silicone and securing with 3 of the #8 x 1/2″ screws (black).
-
Slide the adjustable pipe section onto the 90 o elbow. Slide the trim collar over the adjustable pipe sections to cover the joint of the telescopic section.) The flex may have to be compressed back in order for the adjustable pipe to properly mate to the elbow. Seal with Mill-Pac and/or high temperature silicone and secure with 3 of the #8 x 1/2″ screws (black). Pipe seams facing down.
-
Install the trim collar over the starter collar and secure with a #8 x 1/2″ screw (black).
If the pipe needs to be touched up, use only Stove Brite High Temperature Metallic Black Stove Paint. see also c34020a.eps
Residential and Manufactured Homes / Mobile Homes Minimum Horizontal
Termination Installations
Planning Your Venting Installation See the “Exterior Vent Terminal
Locations” section for requirements. The gas stove is approved for a minimum
horizontal termination with the FPI Riser Vent Kit. See the diagram for
minimum and maximum pipe lengths.
When planning your installation, it will be necessary to select the proper
length of vent pipe for your particular requirements. Determine the minimum
clearance to combustibles from the rear of the unit to the wall.
It is also important to note the wall thickness. Before cutting the vent hole
through the wall ensure that ALL vent and termination clearances (see the
“Exterior Vent Terminal locations” section) will be met.
*If this is an outside corner, the minimum distance between the vent and the outside corner is 6″ (15cm). See “F” on the diagram in the “Exterior Vent Terminal Locations” section. NOTE: Ensure compliance with the outside vent terminal location before cutting hole as both dimensions must be met.
You will require the following components with your new Hampton® Rear Vent
Direct Vent Freestanding Gas Stove. Please review your product to make sure
you have everything you need. In the event that you are missing any part,
contact your dealer. Decorative brass or chrome trim kits are available from
Simpson Dura-Vent for their wall thimbles, as well as a square wall thimble
cover. Note: These are the minimum piecesrequired. Other parts may
berequired for your particularinstallation.
Minimum components for a Horizontal Installation:
946-544 | Horizontal | Termination Kit which includes: |
---|---|---|
1 | 6-5/8″ Dia. x 18″ Black Pipe | |
1 | 4″ Dia. x 18″ Aluminum Vent | |
1 | Wall Penetration Heat Shield (Wall Thimble) (2 pcs) | |
1 640-530/P | Riser Vent Terminal | |
1 | Decorative Wall Trim (Black) | |
1 948-128 | Tube Mill-Pac Screws |
Optional Components:
946-204 | 45º Elbow – 6-5/8″ Black pipe and 4″ Aluminum Vent |
---|---|
946-205 | Vinyl Siding Shield for Riser Vent Terminal |
946-208/P | Vent Guard |
Planning Your Dura-Vent Installation
There are two basic types of Dura-Vent Direct Vent System installations:
horizontal termination and vertical termination. Confirm the maximum
horizontal run and maximum vertical rise from the diagrams in the “Venting
Arrangement” section.
When planning your installation, it will be necessary to select the proper
length of vent pipe for your particular requirements. For horizontal
installations, determine the minimum clearance from the rear of the unit to
the wall. It is also important to note the wall thickness. (The wall thimble
is suitable for 2 x 4 or 2 x 6 wall construction.) Select the amount of
vertical rise desired for “vertical-to-horizontal” type installations.
Warning: Always maintain required clearances (air spaces) to nearby
combustibles to prevent a fire hazard. Do not fill air spaces with insulation.
The minimum clearance requirements between the outer wall of the vent pipe and
nearby combustible surfaces is 1-1/2″, except when passing through a wall,
ceiling, or at the termination where the use of a firestop or wall thimble
reduces the required clearance to 1″.
Be sure to check the vent termination clearance requirements from decks,
windows, soffits, gas regulators, air supply inlets and public walkways as
specified in the “Exterior Vent Terminal Locations” section and in your local
building codes.
To determine the length of vent pipe required for vertical installations,
measure the distance from the unit flue outlet to the ceiling, the ceiling
thickness, the vertical rise in an attic or second storey, and allow for
sufficient vertical height above the roof line.
For multi-storey applications, fire stops are required at each floor level. If
an offset is needed, additional pipe, elbows and supports will be required.
Do not exceed the maximum number of elbows. One 90º for horizontal
terminations and two 45º for vertical termination.
The FPI AstroCap™ is certified for installations using FPI venting systems as
well as Simpson Dura-Vent® and Direct Vent Pro.
The FPI AstroCap™ is the proprietary trademark of FPI Fireplace Products
International Ltd.
Dura-Vent® and Direct Vent Pro are registered and/or proprietary trademarks of
Simpson Dura-Vent Co. Inc.
You will require the following components with your new Direct Vent
Freestanding Gas Stove. Please review your product to make sure you have
everything you need. In the event that you are missing any part, contact your
dealer.
Note: These are the minimum pieces required. Other parts may be required
for your particular installation. See above for a list of vent parts.
If installing termination on a siding covered wall, a vinyl siding standoff or
furring strips can be used in order to ensure that the termination is not
recessed into siding.
The vinyl siding standoff is required for walls with vinyl siding.
Minimum components for a Dura-Vent Horizontal Installation:
A) Dura-Vent Horizontal Termination Kit
B) Wall Thimble (required for combustible walls)
Minimum components for a Dura-Vent Vertical Termination:
D) Dura-Vent Vertical Termination Kit. See above for pipe lengths.
Horizontal Terminations
-
Set the unit in its desired location. Check to determine if wall studs are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit.
-
Assemble the desired combination of pipe and elbow to the appliance adapter with pipe seams oriented down. Offset the pipe seams as double seams in one place will cause the outer pipe to take an oval shape. Kit comes complete with 18″ of straight vent – 6-5/8″ dia. black outer pipe and 4″ dia. inner vent.
-
With the pipe attached to the stove, slide the stove into its correct location, and mark the wall for a 9-1/2″ (inside dimensions) round hole. The center of the round hole should line up with the centerline of the horizontal pipe, as shown in diagram 1. Cut and frame the 9-1/2 round hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a 7″ diameter hole is acceptable. a) The horizontal run of vent should have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the ventto run downward. This could cause high temperatures and may present the possibilityof a fire.
b) The location of the horizontal venttermination on an exterior wall must meet allocal and national building codes, and must not be blocked or obstructed. Refer to the “Exterior Vent Terminal Locations” section.
c) Snorkel Terminations: For installations requiring a vertical rise on the exterior of the building, 14-inch and 36-inch tall Snorkel Terminations as shown in Diagram 2 are available, as welas the standard Riser Vent. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.
*Diagram 2a: As specified in CSA B149.1 Installation Code. Local codes or regulations may require different clearances. NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.
Below Grade Snorkel Installation
If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Installation instructions for details.. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure. -
Install wall penetration heat shield in the center of the 9-1/2″ round hole and attach with wood screws. The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings. Diagram 3.
-
If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. Diagram 3.
-
Take the Riser Vent terminal and separate the Backing Plate from the Riser Vent Front by removing 8 screws as shown in diagram 4.
-
Install the Backing Plate into the wall penetration heat shield and attach using 4 screws. Dia. 4.
-
Connect all pipe sections to unit and install into wall:
a) Measure pipe length required and cut to length. Hint: use the cut end of the 6-5/8″ dia. outer pipe at the vent terminal end.
b) Push the pipe sections completely together, the minimum pipe overlap is 1-1/4″. Secure all outer pipe joints by using at least two screws. Locate the screws at the bottom of the pipe so that the screw heads are hidden on the final installation.
NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional. c) Before connecting the vent pipe to the vent termination, slide the black decorative wall thimble cover over the vent pipe, then slide the Wall Penetration Heat Shield (Part # 946-202) over the vent pipe. Dia. 3.
d) Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the riser vent terminal assembly. It is important thatthe vent pipe extends into the Riser Vent BackingPlate a sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the Riser Vent Backing Plate into the outer wall of the vent pipe. Use two aluminum screws provided to connect the strips to the pipe section. Bend any remaining portion of the sheet metal strip back towards the vent cap and cut off any excess, it will be concealed by the decorative wall thimble cover. See diagram 5. -
Slide the decorative wall thimble up to the wall surface being careful not to scratch the paint. See diagram 5.
-
Back outside: Apply sealant to the 4″ inner flue and slide the Riser Vent Front into the Backing Plate and fasten with 8 screws.
IMPORTANT:
When connecting the pipe to the Riser Vent, apply Mill-Pac to the inner pipe on the Riser Vent Terminal, around the bead. Ensure that the vent pipe is pushed past the bead for a secure fit. -
Seal around the outer edge of the Riser Vent Backing Plate.
Vertical Terminations
-
Maintain the 1-1/2″ clearances, except when passing through a wall, ceiling, or at the termination where the use of a firestop or wall thimble reduces the required clearance to 1″. Do not pack air spaces with insulation. Check the “Venting Arrangement” section for the maximum vertical rise of the venting system and the maximum horizontal offset limitations.
-
Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system. You may wish to relocate the appliance or to offset, as shown in diagram 8 to avoid cutting load bearing members.
-
To install the Round Support Box/Wall Thimble in a flat ceiling, cut a 10 inch square hole in the ceiling centred on the hole drilled in Step 2. Frame the hole as shown in diagram 9.
-
Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance adapter up though the Round Support Box.
Insure that all pipes and elbow connections are in the fully twist-locked position and sealed. NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional. -
Cut a hole in the roof centred on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/4″. Slip the flashing under the shingles (shingles should overlap half the flashing) as per diagram 10. Diagram 10: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed. This allows for small adjustments.
-
Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation.
Wall straps are available for this purpose. See diagram 5.
Galvanized pipe and elbows may be utilized in the attic as well as above the roofline.
The galvanized finish is desirable above the roofline due to its higher corrosion resistance.
Continue to add pipe sections through the flashing until the height of the vent cap meets the minimum height requirements specified in diagram 11 or local codes. Note that for steep roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.Roof Pitch| Minimum Vent Height
---|---
Feet| Meters
over 7/12 to 8/12| 2| 0.61
over 8/12 to 9/12| 2| 0.61
over 9/12 to 10/12| 2| 0.61
over 10/12 to 11/12| 2.5| 0.76
over 11/12 to 12/12| 3.25| 0.99
over 12/12 to 14/12| 4| 1.22
over 14/12 to 16/12| 5| 1.52
over 16/12 to 18/12| 6| 1.83
over 18/12 to 20/12| 7| 2.13
over 20/12 to 21/12| 8| 2.44 -
Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic.
-
Install the vertical termination cap by twist locking it.
Notes:
a) For multistorey vertical installations, a Ceiling Fire stop is required at the second floor, and any subsequent floor. Diagram 12. The opening should be framed to 10 ” x 10″ inside dimensions, in the same manner as shown in diagram -
b) Any occupied areas above the first floor, including closets and storage spaces, through which the vertical vent passes, must be enclosed.
Offset Chart
GS 6″(152mm) Nominal Diameter ID
Offset| Pipe Length (L)| Height
inches| mm| inches1mm| | inches| mm
4’/,| 121| 0| 0| 131/4| 337
9| 229| 6| 152| 171/2| 445
111/4| 286| 9| 229| 19 1/2| 495
13 1/4| 337| 12| 305| 21 3/4| 552
21 3/4| 552| 24| 610| 30 1/4| 768
30 1/4| 768| 36| 914| 39| 991
38| 965| 48| 1219| 47| 1194
Converting Class-A Metal Chimney to Direct Vent System
Approved for US Installations Only.
The use of an existing chimney as an air intake is not covered under the ANSI
Z21.88 2.33 test methods and the resulting ITS/ WHI product certification. The
code Authority Having Jurisdiction must be consulted prior to proceeding with
this installation method.
Prior to installation and connection of the vent system to a Class A chimney,
the chimney must be inspected and thoroughly cleaned by a qualified service
person, such as a certified chimney sweep or home inspection service.
The direct vent system must not be connected to a damaged Class A chimney.
For Class A chimneys cleanout doors and caps or plugs for cleanout tee
fittings and ash dumps shall be secured in place and sealed before installing
a Direct Vent system within the chimney.
If the appliance shuts off during operation, contact a qualified service
person to determine if a negative pressure and/or leaky chimney condition
exists. Do not operate the appliance until the problem is corrected.
Important : If converting this appliance to a Class A Metal Chimney, the
IPI/CPI switch on the hand held remote control/ transmitter must be turned to
CPI (Continuous Pilot Ignition) at all times.
This will avoid nuisance pilot outages during operation of this appliance. See
Remote manual for setup of this IPI/ CPI switch.
-
Remove the existing chimney cap.
-
Measure the distance from the top end of the chimney to the bottom of the ceiling support box, add 3″ (76mm) to this measurement, and cut a section of the 4″ flex pipe to that length (the flex should already be extended to its nominal length).
-
Connect the end of the flex pipe section to the underside of the Top Adaptor using 3 sheet metal screws. Diagram 2.
-
Pass the flex pipe down through the center of the chimney system, and center the adaptor on the top of the chimney pipe. Drill four 1/8″ diameter holes through the adaptor and into the chimney top. Insure that you are in fact, drilling into the metal on the chimney. Twistlock the Termination Cap onto the Adaptor. (Diagrams 3 and 4).
-
Pull the flex pipe down through the ceiling support box, until it protrudes approximately 3″ (76mm). Connect the flex pipe to the Retro Connector by slipping it into the 4-3/4″ diameter sleeve on the top side of the Connector.
Use 3 sheet metal screws to assemble these two parts. -
Push the flex pipe back up into the ceiling support box, center the Retro Connector, and attach it to the support box, or decorative sleeve for double wall solid packed pipe, with the sheet metal screws (supplied). The holes in the Retro Connector are pre-punched. Diagram 5.
-
The connection between the appliance and the Retro Connector may be completed with sections of black direct vent pipe, together with an adjustable length.
-
Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic.
-
Install the vertical termination cap by twist locking it.
Notes:
a) For multistorey vertical installations, a Ceiling Fire stop is required at the secondfloor, and any subsequent floor. Diagram12. The opening should be framed to 10 ” x 10″ inside dimensions, in the same manner as shown in diagram -
b) Any occupied areas above the first floor, including closets and storage spaces, through which the vertical vent passes, must be enclosed. Slope| X
---|---
0/12 – 2/12| 4″
2/12 – 7/12| 5-1/2″
7/12 – 12/12| 6-3/4″
12/12 – 24/12| 7-1/2″
24/12+| 12-1/2″
Cathedral Ceilings
Round Support (RDS) & Square Support (SQS)
If your home has a cathedral ceiling (no attic space between the ceiling and the roof), install the chimney and support as follows.
-
Situate the chimney in a convenient location as near as possible to the appliance outlet.
Cut and frame a hole in the roof for the support. The sides of this hole must be vertical with 1 1/4″ clearance. -
Place the support in the opening. Lower it to the correct height as determined by the table and diagram below.
Using a level, make sure the support is vertical. If the support extends above the roof, cut it flush with the top of the roof.
Nail the support to the frame opening using (8) 3″ spiral nails or #8 x 1-1/2″ screws.
Note : If you are using a 6″ square support you may find it difficult to screw it in place because it is fairly small inside.
Simpson Dura-Vent has provided angle brackets with this support which can be screwed to the outside of the support box and nailed to surrounding framing as required. Use a minimum of four #8 x 1/2″ screws per bracket. In some cases these brackets may need to be trimmed (e.g.: to fit under a flashing). Place the Finish Collar around the support and fasten it to the ceiling using the screws provided. -
Use appropriate roof flashing. Place the flashing under the upper shingles and on top of the lower shingles approximately half of the flashing should be under the shingles.
-
Assemble the desired lengths of Black Pipe and Elbows necessary to reach from the appliance adapter up through the support box and flashing to proper height as per Dia. 12, local codes or in the “Venting Arrangement” section.
Ensure that all pipe and elbow connections are in their fully twist lock position. -
Ensure vent is vertical and secure flashing to the roof with roofing nails. Slide the storm collar over the pipe section and seal with a mastic.
-
Twist lock the vent cap on to the last section.
Support Extensions – Round (RDSE) or Square (SQSE)
Steep pitched cathedral ceilings may require the use of a support extension.
This piece fits down inside the support and can be adjusted to increase the
support’s length by up to 22″.
The extension is attached to the support using the eight metal screws
provided. Be sure there is at least a 2 inch overlap where the extension joins
the support.
High Elevation
This unit is approved in Canada for altitude to 4500 ft. (CSA 2.17). For
Natural Gas installations above 4500 ft. follow current CSA-B149.1.
Gas Connection
The gas connection is a 3/8″ NPT 90 o elbow. The gas line can be rigid pipe or
to make installation easier, use a listed flexible connector and/or copper
tubing if allowed by local codes.
Since some municipalities have additional local codes it is always best to
consult with your local authorities and the CSA B149.1 installation codes.
For USA installations follow local codes and/or the current National Fuel Gas
Code, ANSI Z223.1.
When using copper or flex connectors use only approved fittings. Always
provide a union so that gas lines can be easily disconnected for burner and/or
valve servicing. Flare nuts for copper lines and flex connectors are usually
considered to meet this requirement.
IMPORTANT : ALWAYS CHECK FOR GAS LEAKS WITH A SOAP AND WATER SOLUTION OR GAS LEAK DETECTOR. DO NOT USE OPEN FLAME FOR LEAK TESTING.
Note: Prior to any pressure testing of the gas supply piping system that exceeds test pressures of 1/2 psig, this appliance must be disconnected from the piping system. If test pressures equal to or less than 1/2 psig are used then this appliance must be isolated from the piping system by closing its individual manual shut-off valve during the testing.
SYSTEM DATA – H27U-NG/LP
For 0 to 4500 feet altitude Burner Inlet Orifice Sizes:
Natu al Gas Propane Burner #42 #54
Max. Input Rating
– Natural Gas
– Propane
Min. Input Rating
– Natural Gas
– Propane| 25,000 Btu/h
23,000 Btu/h
12,500 Btu/h
11,500 Btu/h
Supply Pressure
Natural Gas
Propane| min. 5.0″ w.c.
min. 12.0″ w.c.
Manifold Pressure
Natural Gas
Propane| 3.8″ +/- 0.2″ w.c.
11″ +/- 0.2″ w.c.
Aeration Adjustment
The burner aeration is factory set but may need adjusting due to either the
local gas supply, air supply or altitude.
Natural Gas | 3/16″ (4.76 mm) |
---|---|
Propane | 1/4″ (6.4 mm) |
The aeration adjustment rod is located on the right lower side of the unit. Remove the small access panel by removing 1 screw to access Aeration Adjustment Rod – see below.
Push up to close or pull down to open.
Caution : Carbon will be produced if the air shutter is closed too much.
Note : Any damage due to carboning resulting from improperly setting the
aeration controls is NOT covered under warranty.
Note : Aeration Adjustment should only be performed by an authorized
Hampton ® Installer at the time of installation or service.
Gas Pipe Pressure Testing
The appliance must be isolated from the gas supply piping system by closing
its individual manual shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control,
and should be checked at the pressure test point.
Note : To properly check gas pressure, both inlet and manifold pressures
should be checked using the valve pressure ports on the valve.
- Make sure the valve is in the “OFF” position.
- Loosen the “IN” and/or “OUT” pressure tap(s), turning counterclockwise with a 1/8″ wide flat screwdriver.
- Attach manometer to “IN” and/or “OUT” pressure tap(s) using a 5/16″ ID hose.
- Light the pilot and turn the valve to “ON” position. Read manometer.
- The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.
- When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8″ flat screwdriver.
Note : Screw should be snug, but do not over tighten
Valve Description
- Gas on/off knob
- Manual high/low adjustment
- Pilot Adjustment
- Thermocouple Connection
- Main Operator
- Outlet Pressure Tap (Manifold Pressure)
- Inlet Pressure Tap (Supply Pressure)
- Pilot Outlet
- Main Gas Outlet
- Flange Securing Screw Holes
- Alternative TC Connection Point
- Thermoelectric Unit
- Additional Valve Mounting Hole
Conversion Kit #358-969 from NG to LP
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Each Kit contains one LPG Conversion Kit.
LPG Conversion Kit Contains:
Qty. | Part # | Description |
---|---|---|
1 | 904-163 | Burner Orifice #54 |
1 | 918-590 | Decal “Converted to LPG” |
1 | 908-528 | Red “LPG” label |
1 | 904-529 | 5/32″ Allen Key |
1 | 910-037 | LPG Injector (Pilot Orifice) |
1 | 920-490 | Instruction Sheet |
Installation of the LPG Conversion Kit:
-
Shut off the gas supply.
-
a) Lift off the Cast Top and Cast Front, remove the glass front (refer to Glass Replacement section in the 1127 manual) and carefully remove the logs and lava rock (refer to Log Installation section in manual).
b) Remove burnerby removing the2screws on each side and then lifting the burner tray out. Note : Use a magnetic type screwdriver if possible. -
Pull off the pilot cap to expose the pilot orifice.
-
Unscrew the pilot orifice with the Allen key and replace with the LPG pilot orifice in the kit and replace pilot cap.
-
Remove burner orifice with a /2″ wrench and discard. Use another wrench to hold on to the elbow behind the orifice.
-
Reinstall new burner orifice LPG stamped #54 and tighten.
-
Turn control knob to the “OFF” position.
-
Remove the Hi/Low extension knob by pulling it towards you. This will expose the black protection cap. Remove the black protection cap by hand from the high-low knob (Fig.1).
-
Insert a 5/32” or 4mm Allen wrench into the hexagonal key-way of the screw (Fig. 2), rotate it counter-clockwise until it is free and extract it.
-
Check that the screw is clean and if necessary remove dirt.
-
Flip the screw (Fig. 3).
-
Using the Allen wrench as shown in Fig.4, rotate the screw clockwise until snug, do not overtighten. WARNING! Do not overtighten the screw. Recommended to grip the wrench by the short side.
-
Verify that if the cawerson s from NG to LPG. the screed must be re-assemtied wth the red oinig visible (Fig. 5).
-
RetaiScenbe the axed protection cap (Flet Fig.6 WARNING! Also check that the pilot and main burner injectors are appropriate or the gas type.
-
Reverse step 2.
-
Attach the label This unit has been converted to LPG’ near or on lop of the sepal ; decal.
-
Replace yellow ‘NG’ label with red ‘LPG’ label.
-
Check for gas leaks
-
Check in and oufel pressures.
-
heck operation of flame control.
-
Check tar proper flame appearance and Sim on logs.
-
Adjust aeranon settings: 1/f lfirrsvi) for LP.
NOTE : In higher elevations. at shutter setings may have to be opened more 1:1 compensate.
Log Set Installation
Read the instructions below carefully and refer to the diagrams. If the logs
are broken do not use the unit until they are replaced. Broken logs can
interfere with the pilot operation.
The gas log kit (Part #350-930) contains the following:
a) Rear Log
b) Left Side Front Log
c) Right Side Front Log
d) Center Front Log
e) Embers
f) Platinum Embers
902-156
946-669 (supplied with packaged manual)
-
Shut off the gas supply.
-
Lift off the Cast Top, remove Cast Front – then remove the Glass Door (see manual pg. 41).
-
Carefully remove the logs from the box and unwrap them.
The logs are fragile, handle with care – do not force into position. -
Place the rear log on the 2 rear log locating pins on the rear of the burner with the fl at side to the back. The Front Right Log front edges should be placed parallel against the front edge of the burner. NOTE : This is a rear view.
-
Take the embers and place on the burner in the space between the 2 front logs. Do not put embers on the burner in the area between the front logs and the rear log. See photo below.
Separate platinum e mbers and place at t he front o f the burner in and around where the embers are placed. Avoid stacking platinum embers. -
Place the center cross log D so it rests in the notch located on the top of the rear log – position as shown below. Logs must be oriented as shown below.
-
Test fi re to ensure proper light off (make sure fl ame fl ows smoothly from one end of burner to the other). If there is any fl ame hesitation, check that area for any blockage of the burner ports.
-
Re-install the Glass door and Cast Front and Cast Top.
Optional Remote Control/Wall Thermostat
Part #910-407 Basic Wall Thermostat
Part #910-404/P Programmable Wall Thermostat
Part #910-399 Remote Control
A wall thermostat may be installed if desired. Connect the wires as per the
wiring diagrams. Note that the wires are connected to the “TH” on the gas
valve.
Use table below to determine the maximum wire length:
Note: Preferable if the thermostat is installed on an interior wall.
Hampton ® offers an optional programmable thermostat but any 250-750 millivolt
rated non-anticipator type thermostat that is CSA, ULC or UL approved may be
used.
CAUTION Do not connect the millivolt wall thermostat wires to the 120V wires.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System) Wire Size| Max. Length
---|---
14 GA.| 50 Ft.
16 GA.| 32 Ft.
18 GA.| 20 Ft.
20 GA.| 12 Ft.
22 GA.| 9 Ft.
Final Check
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly. This includes:
-
Clocking the appliance to ensure the correct firing rate (rate noted on label) at 15 minutes.
-
If required, adjusting the primary air to ensure that the flame does not carbon.
First allow the unit to burn for 15 min. to stabilize. -
Check for proper draft.
CAUTION
Any alteration to the product that causes sooting or carboning that results in
damage to the exterior facia is not the responsibility of the manufacturer.
Wiring Diagrams
If any of the original wires as supplied with the appliance must be replaced, it must be replaced with CSA type SEW (200 C) or its equivalent.
This heater does not require a 120V A.C. supply for operation. In case of a
power failure, the burner switch and the optional remote control/ thermostat
will continue to operate. However, a 120V A.C. power supply is needed for the
fan/ blower operation.
Caution: Ensure that the wires do not touch any hot surfaces and are away from
sharp edges.
CAUTION: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
WARNING : Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Operation
Final Check
Before leaving this unit with the customer, the installer must ensure that the
appliance is firing correctly. This includes:
- Clocking the appliance to ensure the correct firing rate (rate noted on label) at 15 minutes.
- If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15 min. to stabilize.
- Check for proper draft.
CAUTION
Any alteration to the product that causes sooting or carboning that results in
damage to the exterior facia is not the responsibility of the manufacturer.
Operating Instructions
- Read and understand these instructions before operating this appliance.
- Check to see that all wiring is correct and enclosed to prevent possible shock.
- Check to ensure there are no gas leaks.
- Make sure the glass in the door frame is properly positioned. Never operate the appliance with the glass removed. Never strike the glass or slam the door shut.
- Verify that the venting and cap are unobstructed.
- Verify log placement. If the pilot cannot be seen when lighting the unit, the logs are incorrectly positioned.
- The unit should never be turned off, and on again without a minimum of a 60 second wait.
Lighting Procedure
IMPORTANT
To ignite or reignite the pilot, the door to the firebox must be opened.
Only when the pilot holds without pressure to the control knob should the door
to the firebox beclosed. The unit must never be operated with the glass or
door open.
NOTE : For all propane units and unitsequipped with electric spark boxes,
see “Copyof Lighting Plate Instructions” section formore details.
IMPORTANT : Gas on/off knob cannot beturned from “PILOT” to “OFF” unless
it is partially depressed.
-
Turn stove OFF using the Burner “ON/OFF” switch remote or thermostat.
-
Turn gas control knob so indicator points to “OFF” position and allow 5 minutes for any gas in the combustion chamber to escape.
-
Turn gas control knob counterclockwise so indicator points to the “PILOT” position. Depress the gas control knob fully until the pilot lights.
After approximately one minute, release the gas control knob. The pilot flame should continue to burn. If the pilot does not remain lit, repeat operation allowing a longer period before releasing gas control knob. -
When the pilot stays lit, turn the gas knob further counterclockwise to the “ON” position.
-
Use the ON/OFF switch, thermostat or remote control to turn on the unit.
-
Rotate the flame height regulator to adjust the flame height higher or lower.
Shutdown Procedure
- Turn the main gas control clockwise to the “OFF” position to turn off the pilot (push knob in slightly).
- Turn off all electric power to appliance if service is to be performed.
First Fire
The FIRST FIRE in your stove is part of the paint curing process. To ensure
that the paint is properly cured, it is recommended that you burn your
fireplace for at least four (4) hours the first time you use it with the fan
on. When first operated, the unit will release an odour caused by the curing
of the paint and the burning off of any oils remaining from manufacturing.
Smoke detectors in the house may go off at this time. Open a few windows to
ventilate the room for a couple of hours. The glass may require cleaning.
DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT!
Note : When the glass is cold and the appliance is lit, it may cause
condensation and fog the glass. This condensation is normal and will disappear
in a few minutes as the glass heats up.
DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.
During the first few fires, a white film may develop on the glass front as
part of the curing process. The glass should be cleaned or the film will bake
on and become very difficult to remove. Use a non-abrasive cleaner and NEVER
clean the glass while it is hot.
Copy of the Lighting Plate Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING : If you do not follow these instructions exactly, a fire or
explosion may result causing property damage,personal injury or loss of life.
Improper installation, adjustment, alteration, service or maintenance can
cause injury orproperty damage. Refer to the owner’s information manual
provided with this appliance. For assistance or additionalinformation consult
a qualified installer, service agency or gas supplier.
A)This appliance has a pilot that must be lighted by hand. When lighting the
pilot, follow these instructions exactly.
B) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch, do not use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C) Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control which has been underwater.
CAUTION : Hot while in operation. Do not touch. Severe burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having flammable vapors away. Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
LIGHTING INSTRUCTIONS
-
STOP! Read the safety information above on this label.
-
Push in gas control knob slightly and turn clockwise to “OFF”. Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. Do not force.
-
Wait five (5) minutes to clear out any gas. If you then smell gas STOP! Follow step “B” in the Safety Information above on this label. If you don’t smell gas, go to the next step.
-
Push in gas control knob slightly and turn counterclockwise to “PILOT” position.
-
Push in control knob all the way and hold in until the pilot lights. Continue to hold the control knob in for about 20 seconds after the pilot lights.
Release the knob. -
Push in gas control knob slightly and turn counterclockwise to “ON” position.
-
Turn on the flame switch.
TO TURN OFF GAS TO APPLIANCE
- Turn off the flame switch.
- Push in the gas control knob slightly and turn clockwise to “OFF”. Do not force.
- Turn off all electric power to the appliance if service is to be performed.
You may shut off the pilot during prolonged non use periods to conserve fuel.
DO NOT REMOVE THIS INSTRUCTION PLATE
Maintenance
Normal Operating Sounds of Gas Appliances
It is possible that you will hear some sounds from your gas appliance. This is
perfectly normal due to the fact that there are various gauges and types of
steel used within your appliance. Listed below are some examples. All are
normal operating sounds and should not be considered as defects in your
appliance.
Blower: Hampton ® gas appliances use high tech blowers to push heated air
farther into the room. It is not unusual for the fan to make a “whirring”
sound when ON. This sound will increase or decrease in volume depending on the
speed setting of your fan speed control.
Burner Tray:
The burner tray is positioned directly under the burner tube(s) and logs and
is made of a different gauge material from the rest of the firebox and body.
Therefore, the varying thicknesses of steel will expand and contract at
slightly different rates which can cause “ticking” and “cracking” sounds. You
should also be aware that as there are temperature changes within the unit
these sounds will likely re-occur. Again, this is normal for steel fireboxes.
Blower Thermodisc:
When this thermally activated switch turns ON it will create a small
“clicking” sound. This is the switch contacts closing and is normal.
Pilot Flame:
While the pilot flame is on it can make a very slight “whisper” sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a dull clicking sound may be
audible, this is normal operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will expand and contract at different
rates resulting in some “cracking” and “ticking” sounds will be heard
throughout the cycling process.
Maintenance Instructions
-
Always turn off the valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year.
When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged. -
Clean glass (never when unit is hot), appliance, and door with a damp cloth. Never use an abrasive cleaner.
-
The heater is finished in a porcelain finish or with a heat resistant paint and should only be refinished with heat resistant paint (not with wall paint).
Never use an abrasive cleaner on the porcelain finish as it may scratch the surface. -
Make a periodic check of burner for proper position and condition. Visually check the flame of the burner periodically, making sure the flames are steady; not lifting or floating.
If there is a problem, call a qualified service person. -
Caution: Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation. -
The appliance and venting system must be inspected before use, and at least annually, by a qualified field service person, to ensure that the flow of combustion and ventilation air is not obstructed.
During the annual service call, the burner should be removed from the burner tray and cleaned. Replace the embers but do not block the pilot. -
Keep the area near the appliance clear and free from combustible materials, gasoline, and other flammable vapours and liquids.”
WARNING : CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEENUNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICETECHNICIAN TO INSPECT THE APPLIANCE AND TO REPLACEANY PART OF CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.
CAUTION : ANY SAFETY SCREEN OR GUARD REMOVED FOR SERVICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE. -
Each time the appliance is lit, it may cause condensation and fog the glass. This condensation and fog is normal and will disappear in a few minutes as the glass heats up.
Never operate the appliance without the glass properly secured in place. 9) Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile and 1 around the thermocouple, and 1 flowing across the rear of the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pattern, contact your Hampton ® dealer for further instructions. Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear of the burner or thermopile. Top View of pilot flame
General Vent Maintenance
Conduct an inspection of the venting system semiannually.
Recommended areas to inspect as follows:
- Check the Venting System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.
- Remove the Cap, and shine a flashlight down the Vent. Remove any bird nests, or other foreign material.
- Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fittings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
- Inspect joints, to verify that no pipe sections or fittings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers’ tape for rigidity.
- Verify proper operation after servicing.
Log Replacement
The unit should never be used with broken logs. Turn off the gas valve and
allow the unit to cool before opening door to carefully remove the logs. The
pilot light generates enough heat to burn someone. If for any reason a log
should need replacement, you must use the proper replacement log. The position
of these logs must be as shown in the diagram under Log Installation.
Note: Improper positioning of logs may create carbon build-up and will alter
the unit’s performance which is not covered under warranty.
Glass Gasket
If the glass gasket requires replacement, use Part # 846-687.
Glass Replacement
Your stove is supplied with high temperature, 5 mm Neoceram ceramic glass
that will withstand the highest heat that your unit will produce. In the event
that you break your glass by impact, purchase your replacement door from an
authorized Hampton® dealer only, and follow our step-by-step instructions for
replacement.
-
Lift off the Cast Top.
-
Open front access panel and remove 2 – 7/16″ bolts from locations shown below.
-
Lift the Glass Front Assembly up.
-
a) Remove the glass and replace with the new glass.
b) Remove logs and replace the newer logs. -
Reinstall the door and Cast Front and Top.
-
Remove the 2 – 7/16″ bolts which secure the top of the cast front on both the left and right side as shown.
-
Lift off Cast Front – place on a soft surface.
-
On top of firebox – undo 2 latches.
Replacement Part #940-427/P Glass
WARNING: Do not operate appliance with glass panel removed, cracked or broken.
Replacement of the glass should be done by a licensed or qualified service
person.
Note: Wearing gloves will protect your hands while handling glass.
Fan Maintenance
If your fan requires maintenance or replacement, access to the fan is through
the rear access panel on the back of the unit. NOTE: the unit MUST NOT be
operated without the fan access panel securely in place and correctly sealed.
IMPORTANT : These fans collect a lot of dust from within your home.
Ensure you maintain these fan motors on a regular basis by vacuuming out the
fan squirrel cages, around the motor, and around the grills on the back of the
stove.
To Remove Fan:
WARNING: Electrical Grounding Instructions This appliance is equipped with a
three pronged (grounding) plug for your protection against shock hazard and
should be plugged directly into a properly grounded three-prong receptacle. Do
not cut or remove the grounding prong from this plug.
IMPORTANT
Disconnect power supply before servicing
-
Unplug or disconnect power source to stove.
-
Remove the rear access panel on the back of the stove by removing the 2 screws under the rear panel, then lift off the 2 screws at the top.
Take care not to cut wires when lowering the panel. -
Unclip the black and white wires from the fan motor.
-
Remove the 2 bolts holding the fan to the rear base. Disconnect the green ground wire from the right side of the fan as soon as you can reach it. Replacing the Fan:
Reverse the above steps (1 – 4). Make sure the fan wires and the ground wire are reattached.
Removing Valve
If your valve requires maintenance or replacement, use the following instructions:
Note : Always close off the gas supply before removing the valve.
-
If optional fan is installed, disconnect power source to stove.
-
Remove access panel.
-
Disconnect gas line to stove.
-
Disconnect 3/8″ NPT pipe from 90 o elbow on valve or flex connector.
-
Disconnect the two (2) switch wires from valve.
-
Disconnect piezo wire.
-
Lift off the Cast Top and remove the Cast Front and glass door (refer to pg. 41).
-
Carefully remove the logs and embers.
-
Remove burner by removing the 2 screws on each side and then lifting the burner tray out.
Note : Use a magnetic type screwdriver if possible. -
Remove all 6 screws holding the burner tray assembly in place.
-
Carefully lift the burner tray assembly out.
-
To remove the valve, remove the 4 screws (2 per bracket) that hold the valve to the valve bracket assembly.
-
To replace the burner tray assembly, simply reverse these instructions.
To remove valve from valve assembly, continue. -
Remove two (2) thermopile wires.
-
Remove thermocouple with a 9 mm (metric) wrench.
-
Remove pilot nut with an 11 mm wrench.
-
Remove valve to orifice nut with a 13/16″ wrench.
-
Remove inlet pipe with pipe wrench. Note orientation of 90 o elbow.
-
Remove two (2) phillips head M5 screws on each side of the valve.
-
Remove valve and remove gas out 90 o brass fitting. Note orientation of fitting.
Installing Valve Assembly
- To install a new valve assembly, reverse instructions for removing valve. See assembly steps 1-12.
- Check for leaks and manifold pressure. See Gas Pressure Test instructions.
- To reinstall valve, reverse instructions for removing valve assembly, steps 13-19.
Gas Maintenance – Recommended Annual Routine
In order for your Regency appliance to continue to provide comfort to your
home periodic maintenance must be performed to ensure it is operating at peak
efficiency. The items in the list should be checked by a licensed gas service
technician during the annual service check.
Your unit may require more frequent maintenance checks if you notice any
changes in how it operates. Operational changes to look for can include, but
are not limited to, extended start up time, increased fan noise,
residue/carbon build up, white build up on the glass/firebox, increased
operating noise etc. Should any of these or other conditions arise,
discontinue use and schedule a service check with your local licensed gas
technician. The list below shows items your licensed service technician will
need to check and service at least annually.
Clean
- Glass
- Interior bricks / panels
- Burner ports & burner air shutter
- Fan blades
- Log set
- Pilot orifices
- Pilot hood (change as needed)
- Flame sensor (electronic ignition models)
- Flame electrode
- Burner orifice
- Thermocouple (millivolt models)
- Thermopile (millivolt models)
Gas Leak Tests
- Check main gas line connection to valve
- Check shut off valve connections
- Check connection at gas valve outlet
- Check connection at main burner orifice
- Check pilot fuel line at valve and at pilot assembly
Inspect
- Pilot assembly
- Burner
- Pressure relief gaskets/doors
- Flue connector gasket if present
- Door seal
- Firebox
- Venting
- Batteries (remote handheld, remote receiver,
- DC sparker, change as needed)
- Burner media (change as needed)
- Air shutter setting
- Wiring
Check
- Voltage on thermocouple/thermopile (millivolt models)
- Ohms reading on flame sense (electronic ignition models)
- Inlet/outlet fuel pressures as per rating plate
- Voltage/ohms readings on gas valve
- Ohms reading to on/off switch circuit (Milivolt models)
Parts list
Main Assembly
| Part #| Description
---|---|---
1)| 357-201| Casting – Top
3)| 357-211| Casting – Front
4)| 357-241| Casting – Side Right
4)| 357-231| Casting – Side Left
5)| 357-251*| Casting – Leg (each)
9)| 260350| Gasket for Rear Relief Plate
10)| 290-015
350-524
350-002| Rear Relief Plate
Front Door Assembly
Door Support
19)| 350-006
846-687| Door Frame
1/4″ x 5/16″ Tadpole w/ Adhesive
Glass Gasket (6′) (41225)
23)| 940-327/P| Replacement Glass
24)| 350-007| Glass Bracket
30)| 948-219| HamptoW Logo
38)| | Firebox
43)| 948-255
918-812| Latch c/w Hook Manual
Baffle Restrictor Assembly
44)| 350-005| Restrictor
45)| 350-004| Baffle Plate for Firebox
48)| 350-022| Casting Mount Bracket
49)| | Fan Air Divider
---|---|---
50)| W260260| Top Relief Frame Gasket
51)| 942-117| Top Relief Frame
52)| W260280| Top Relief Plate Gasket
53)| 1/0-0661-| lop Relief Plate
54)| 904-012| Capscrew 1/4 x 1-3/4 NC (Each’,
55)| | Side Shield
57)| W260108| Gasket for Inner Flue
58)| W842051| Gasket for Flue Adaptor
59)| 945 F| Dtira-Vent Collar
79)| | Stove Base
114)| | Wire Tie
115)|
910-704| Wire Tie Mount
Wire Harness – Fan End
134)| 358-011| Rear Panel
135)| 358-009| Rear Control Panel
136)| 910-246| Burner ON/OFF Switch
137)|
920-443
350-917| Hole Plug 0.375
Decal Rear Control Panel Fan ON/OFF Switch
Fan Assembly Complete -120 ‘s (Option)
144)| 910-157/P| Fan Motor 120 V
145)| 910-233| Fan Thermodisc Auto On/Off
146)| 910-794| Power Cord (120 V)
148)| 910-330
357-007| Fan Speed Control (120 V) Mesh Glass Guard
149)| 904-568| Knob – Fan Speed Control
150)| 358-010| Heat Shield
---|---|---
151)| 384-018F| Fan Guard Grill (Each)
152)| 350-026| Valve Access Door
153)| 357-022| Cast Mount Bracket (Each)
*Note: Not available as a replacement part.
**Last digit of part number indicates colour:
1=Charcoal Grey, 5=Timberline,
Diagram – next page.
Main Assembly
Burner & Log Assembly
| Part #| Description
---|---|---
60)| 358-574/P| Valve Assembly S.I.T. – Natural Gas
358-576/P| Valve Assembly S.I.T. – LP
910-568| SIT Valve NG/LP 820 SIT High/Low 0.820.852
904-430| #42 Orifice – NG
904-163| #54 Orifice – LP
936-170| Orifice Gasket
66)| 910-038/P| Pilot Assy-S.I.T.-3 flame-NG
910-039/P| Pilot Assy-S.I.T.-3 flame-LP
67)| | Pilot Holder
68)| W840470| Pilot Assembly Gasket
69)| | Valve Shield
70)| | Valve Bracket
75)| 350-930| Log Set
76)| 358-008| Front Control Panel
920-447| Front Control Panel Decal
77)| 910-373| Extension Knob ON/OFF/Pilot
78)| 910-372| Extension Knob Hi/Low
79)| 910-341| Thermopile
910-386| Thermocouple
910-030| Spark Electrode
910-096| 3 Way Pilot Hood
910-432| Pilot Tube With Nuts
910-073| DC Spark Box
910-074| DC Spark Box Wires
932-009| Tubing SS Flexible 3/8 x 9 inch Long
910-036| Pilot Orifice NG
910-037| Pilot Orifice LP
80)| 350-530| Burner Assembly – Natural Gas
82)| 350-020| Log Tray Rear
86)| 432-513| Air Shutter Gear Assembly – Female
87)| 904-565| Hex Key 3/16″
88)| 350-019| Burner Box Gasket
90)| | Burner Box
Notes
Warranty
Limited Lifetime Warranty
FPI Fireplace Products International Ltd. (for Canadian customers) and
Fireplace Products U.S., Inc. (for U.S.
customers) (collectively referred to herein as “FPI”) extends this Limited
Lifetime Warranty to the original purchaser of this appliance provided the
product remains in the original place of installation. The items covered by
this limited warranty and the period of such coverage is set forth in the
table below.
Some conditions apply (see below).
The policy is not transferable, amendable or negotiable under any
circumstances.
Indoor Gas Products
Warranty Coverage
Parts and Labor| Part Lifetime| 5 years| 2 years| 1 year| Supplier Warranty|
Labor Coverage
(Years)
---|---|---|---|---|---|---
Firebox and Heat Exchanger| | | | | | 3
Steel Burner Tube| | | | | | 3
Glass Thermal breakage only| | | | | | 3
All Surrounds/Inlays Finishes| | | | | | 3
Brick Panels/Log sets/CeramicBurners| | | | | | 3
All Castings| | | | | | 3
Valve assembly and all gas control
components, (Pilot assembly,
flame sensors, Spark Electrode,
Pilot Tubing, Orifices,
Thermocouple, Thermopile)| | | | | | 2
All Other Electrical
components,(Ignition Control
Boards, Wiring, Switches, Blowers,Blower Control Module, Battery
Pack, Remote Control Systems)| | | | | | 2
Enamel Panels| | | | | | 1
Venting/Venting Components| | | | | | 1
All Stainless steel surrounds| | | | | | 1
All Firebox Media (Crystals,
Firebeads, Volcanic,
Ceramic & Spa Stones)| | | | | | 1
All hardware| | | | | | 1
Mesh/Glass Safety Barriers| | | | | | 1
Accent Light Bulbs| | | | | | 1
Glass (Crazing)| | | | | | 1
Conditions:
Warranty protects against defect in manufacture or FPI factory assembled
components only, unless herein specified otherwise.
Any part(s) found to be defective during the warranty period as outlined above
will be repaired or replaced at FPI’s option through an accredited
distributor, dealer or pre-approved and assigned agent provided that the
defective part is returned to the distributor, dealer or agent for inspection
if requested by FPI. Alternatively, FPI may at its own discretion fully
discharge all of its obligations under the warranty by refunding the verified
purchase price of the product to the original purchaser. The purchase price
must be confirmed by the original Bill of Sale.
The authorized selling dealer, or an alternative authorized FPI dealer if pre-
approved by FPI, is responsible for all in-field diagnosis and service work
related to all warranty claims. FPI is not responsible for results or costs of
workmanship of unauthorized FPI dealers or agents in the negligence of their
service work.
At all times FPI reserves the right to inspect reported complaints on location
in the field claimed to be defective prior to processing or authorizing of any
claim. Failure to allow this upon request will void the warranty.
All warranty claims must be submitted by the dealer servicing the claim,
including a copy of the Bill of Sale (proof of purchase by you). All claims
must be complete and provide full details as requested by FPI to receive
consideration for evaluation. Incomplete claims may be rejected.
Unit must be installed according to all manufacturers’ instructions as per the
manual.
All Local and National required codes must be met.
The installer is responsible to ensure the unit is operating as designed at
the time of installation.
The original purchaser is responsible for annual maintenance of the unit, as
outlined in the owner’s manual. As outlined below, the warranty may be voided
due to problems caused by lack of maintenance.
Repair/replacement parts purchased by the consumer from FPI after the original
coverage has expired on the unit will carry a 90 day warranty, valid with a
receipt only. Any item shown to be defective will be repaired or replaced at
our discretion. No labor coverage is included with these parts
Exclusions:
This Limited Lifetime Warranty does not extend to paint, rust or corrosion of
any kind due to a lack of maintenance or improper venting, combustion air
provision, corrosive chemicals (i.e. chlorine, salt, air, etc.), door or glass
gasketing.
Malfunction, damage or performance based issues as a result of environmental
conditions, location, chemical damages, downdrafts, installation error,
installation by an unqualified installer, incorrect chimney components
(including but not limited to cap size or type), operator error, abuse,
misuse, use of improper fuels , lack of regular maintenance and upkeep, acts
of God, weather related problems from hurricanes, tornados, earthquakes,
floods, lightning strikes/bolts or acts of terrorism or war, which result in
malfunction of the appliance are not covered under the terms of this Limited
Lifetime Warranty.
FPI has no obligation to enhance or modify any unit once manufactured (i.e. as
products evolve, field modifications or upgrades will not be performed on
existing appliances).
This warranty does not cover dealer travel costs for diagnostic or service
work. All labor rates paid to authorized dealers are subsidized, pre-
determined rates. Dealers may charge homeowner for travel and additional time
beyond their subsidy.
Any unit showing signs of neglect or misuse will not be covered under the
terms of this warranty policy and may void this warranty. This includes units
with rusted or corroded fireboxes which have not been reported as rusted or
corroded within three (3) months of installation/purchase.
Units which show evidence of being operated while damaged, or with problems
known to the purchaser and causing further damages will void this warranty.
Units where the serial no. has been altered, deleted, removed or made
illegible will void this warranty.
Minor movement, expansion and contraction of the steel is normal and is not
covered under the terms of this warranty.
FPI is not liable for the removal or replacement of facings or finishing in
order to repair or replace any appliance in the field.
Freight damages for products or parts are not covered under the terms of the
warranty.
Products made or provided by other manufacturers and used in conjunction with
the FPI appliance without prior authorization from FPI may void this warranty.
Limitations of Liability:
The original purchaser’s exclusive remedy under this warranty, and FPI’s sole
obligation under this warranty, express or implied, in contract or in tort,
shall be limited to replacement, repair, or refund, as outlined above. IN NO
EVENT WILL FPI BE LIABLE UNDER THIS WARRANTY FOR ANY INCIDENTAL OR
CONSEQUENTIAL COMMERCIAL DAMAGES OR DAMAGES TO PROPERTY. TO THE EXTENT
PERMITTED BY APPLICABLE LAW, FPI MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO
DURATION OF THE EXPRESSED WARRANTY SPECIFIED ABOVE. IF IMPLIED WARRANTIES
CANNOT BE DISCLAIMED, THEN SUCH WARRANTIES ARE LIMITED IN DURATION TO THE
DURATION OF THIS WARRANTY.
Some U.S. states do not allow limitations on how long an implied warranty
lasts, or allow exclusion or limitation of incidental or consequential
damages, so the above limitations or exclusions may not apply to you.
Customers located outside the U.S. should consult their local, provincial or
national legal codes for additional terms which may be applicable to this
warranty.
How to Obtain Warranty Service:
Customers should contact the authorized selling dealer to obtain warranty
service. In the event the authorized selling dealer is unable to provide
warranty service, please contact FPI by mail at the address listed below.
Please include a brief description of the problem and your address, email and
telephone contact information. A representative will contact you to make
arrangements for an inspection and/or warranty service.
Canadian Warrantor:
FPI Fireplace Products International Ltd.
6988 Venture St.
Delta, British Columbia
Canada, V4G 1H4| U.S. Warrantor:
Fireplace Products U.S., Inc.
PO Box 2189 PMB 125
Blaine, WA
United States, 98231
---|---
Or contact the Regency Customer Care Centre at 1-800-442-7432 (phone) / 604-946-4349 (fax)
Product Registration and Customer Support:
Thank you for choosing a Regency Fireplace. Regency strives to be a world
leader in the design, manufacture, and marketing of hearth products. To
provide the best support for your product, we request that you complete a
product registration form at http://www.regency-fire.com/Customer-Care
/Warranty-Registration.aspx within ninety (90) days of purchase.
Product Registration and Customer Support:
Thank you for choosing a Regency Fireplace. Regency strives to be a world
leader in the design, manufacture, and marketing of hearth products. To
provide the best support for your product, we request that you complete a
product registration form found on our Web Site under Customer Care within
ninety (90) days of purchase.
For purchases made in CANADA or the UNITED STATES: http://www.regency-
fire.com/Customer-Care/Warranty-Registration.aspx
For purchases made in AUSTRALIA: http://www.regency-fire.com.au/Customer-Care
/Warranty-Registration.aspx
You may also complete the warranty registration form below to register your
Regency Fireplace Product and mail and/or fax it back to us, and we will
register the warranty for you. It is important you provide us with all the
information below in order for us to serve you better.
Warranty Registration Form (or Register online immediately at the above Web
Site):
Warranty Details
Serial Number (required):|
Purchase Date (required) (mm/dd/yyyy):|
Product Details
Product Model (required):|
Dealer Details
Dealer Name (required):|
Dealer Address:|
Dealer Phone #:|
Installer:|
Date Installed (mm/dd/yyyy):|
Your Contact Details (required)
Name:|
Address:|
Phone:|
Email:|
For purchases made in CANADA:
FPI Fireplace Products
International Ltd.
6988 Venture St.
Delta, British Columbia
Canada, V4G 1H4
Phone: 604-946-5155
Fax: 1-866-393-2806| For purchases
made in the UNITED STATES:
Fireplace Products US, Inc.
PO Box 2189 PMB 125
Blaine, WA
United States, 98231
Phone: 604-946-5155
Fax: 1-866-393-2806| For purchases
made in AUSTRALIA:
Fireplace Products Australia Pty Ltd
99 Colemans Road
Dandenong South, Vic. 3175
Australia
Phone: +61 3 9799 7277
Fax: +61 3 9799 7822
---|---|---
For fireplace care and tips and answers to most common questions please visit
our Customer Care section on our Web Site.
Please feel free to contact your selling dealer if you have any questions
about your Regency product.
Hampton® H27U-NG/H27U-LP Direct Vent Freestanding Gas Stove
warranty
…………………….
Installer: Please complete the following information
Dealer Name & Address:
Installer: ____
Phone #: ____
Date Installed:
Serial #: ____
Hampton® and AstroCap™ are trademarks of FPI Fireplace Products International
Ltd.
© Copyright 2023, FPI Fireplace Products International Ltd. All rights
reserved.
Printed in Canada
Documents / Resources
|
HAMPTON H27 LP Direct Vent Gas
Fireplace
[pdf] Instruction Manual
H27 LP Direct Vent Gas Fireplace, H27, LP Direct Vent Gas Fireplace, Vent Gas
Fireplace, Gas Fireplace, Fireplace
---|---
References
- Duravent
- Cast Iron Stoves & Cast Iron Fireplace Inserts | Regency
- ICC-RSF
- Metal-Fab Residential Commercial Venting Products
- Olympia Chimney – Distributed through Copperfield
- Warranty Registration | Register Your Unit Today | Regency
- Warranty Registration | Register Your Unit Today | Regency
- Selkirk
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>