prolink SFC Series Super Fast Charging Line Interactive User Guide
- June 15, 2024
- PROLiNK
Table of Contents
- Important Safety Warning
- Package Contents
- Overview
- Installation & Initial Startup
- Software Download & Installation
- Storage and Maintenance
- Storage and Maintenance
- Troubleshooting
- Specifications
- WARRANTY TERMS
- Worldwide Customer Care Centers
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
prolink SFC Series Super Fast Charging Line Interactive
Important Safety Warning
CAUTION
- To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (See the specifications for the acceptable temperature and humidity range.)
- To reduce the risk of overheating the UPS, DO NOT cover the UPS’ cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
- DO NOT attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
- DO NOT plug the UPS input into its own output.
- DO NOT allow liquids or any foreign object to enter the UPS. DO NOT place beverages or any other liquid-containing vessels on or near the unit.
- In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.
- DO NOT attach a power strip or surge suppressor to the UPS.
- Attention hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary.
- Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
- When replacing the batteries, use the same number and type of batteries.
- Internal battery voltage is 12VDC. Sealed, lead-acid, 6-cell battery.
- DO NOT dispose of batteries in a fire. The battery may explode. DO NOT open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.
- Unplug the UPS prior to cleaning and DO NOT use liquid or spray detergent.
- A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed before replacing batteries:
- Remove watches, rings, or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting batteries terminal.
WARNING
- DO NOT modify the UPS input cable.
- Consult your dealer if the UPS input cable connector does not match the utility receptacle.
- The UPS must be grounded while in use. Operate the UPS only from a properly grounded AC outlet (2 wire plus ground).
- Turn off the UPS before unplugging it from the AC outlet.
Package Contents
Note:
- The illustrations in this document may appear different from your model.
- If any of above item is not packed in your package when open, please consult your seller immediately.
Overview
INSPIRE 703SFC
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- Power AC Input
- Backup Outlets
INSPIRE 853SFCU
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- USB Port
- Power AC Input
- RJ11 Ports (In & Out)
- Backup Outlets
INSPIRE 1203SFCU
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- Power AC Input
- USB Port
- RJ45 Ports (In & Out)
- Backup Outlets
INSPIRE 1253SFCU
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- Power AC Input
- USB Port
- RJ45 Ports (In & Out)
- Backup Outlets
INSPIRE 1503SFCU
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- Fan
- Power AC Input
- USB Port
- RJ45 Ports (In & Out)
- Backup Outlets
INSPIRE 2003SFCU
Legend
- Power Switch
- Fault Indicator: Red LED Lighting
- Battery Mode Indicator: Yellow LED Flashing
- AC Mode Indicator: Green LED Lighting
- Fan
- Power AC Input
- USB Port
- RJ45 Ports (In & Out)
- Backup Outlets
INSPIRE 3003SFCU
Legend
- AC Mode: Indicating load level Battery Mode: Indicating battery capacity
- Fault Indicator: Red LED Lighting
- AC Mode Indicator: Green LED Lighting Battary Mode Indicator: Green LED Flasing
- Power switch
- Modem/Phone/ Network surge protection
- Circuit breaker
- AC input
- USB port
- Backup Outlets
Installation & Initial Startup
Note
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
Connect to Utility and Charging
Connect the AC Input Cord from the wall outlet to the UPS. For the best result, suggest to charge the battery at least 6 hours before initial use. The unit charges its battery while connecting to the utility.
Placement & Storage Conditions
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Please place the UPS away from other units at least 20cm to avoid interference. DO NOT operate the UPS where the temperature and humidity is outside the specific limits. (Please check the specs for the limitations).
Connect the Loads
Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the power switch of UPS unit, and then devices connected to the UPS will be protected by UPS unit.
CAUTION
NEVER connect a laser printer or scanner to the UPS unit. This may cause the damage of the unit.
Data Line Surge Protection (Only for the model with RJ11/RJ45)
Connect a single network/telephone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet with another network/telephone/fax line cable.
Connect Communication Cable (Only for the model with USB port)
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
Turn On/Off the Unit
Turn on the UPS unit by pressing the power switch. Turn off the UPS unit by pressing again the power switch.
Software Download & Installation
Note
Only for model with USB port.
Please follow steps below to download and install monitoring software:
- Go to the website http://www.power-software-download.com
- Click ViewPower software icon and then choose your required OS to download the software.
- Follow the on-screen instruction to install the software.
- When your computer restarts, the monitoring software will appear as orange plug icon located in the system tray, near the clock.
- For UPS with HID-compliant USB Port (optional), you may safely shutdown the UPS during power failure simply by connecting to a computer with pre-installed Windows/ Linux/ Mac OS through the USB port even without monitoring software.
Storage and Maintenance
Storage
Before storing, charge the UPS at least 6~8 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
STORAGE
TEMPERATURE
| RECHARGE FREQUENCY| CHARGING DURATION
---|---|---
-25°C – 40°C| Every 3 months| 1-2 hours
40°C – 40°C| Every 2 months| 1-2 hours
The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS
system are still connected to the battery packs which are potentially
dangerous.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Batteries may cause electric shock and have a high short-circuit current.
Please remove all wristwatches, rings and other metal personal objects before
maintenance or repair, and only use tools with insulated grips and handles for
maintaining or repairing.
Storage and Maintenance
When replace the batteries, install the same number and same type of
batteries.
Do not attempt to dispose of batteries by burning them. This could cause
battery explosion. The batteries must be rightly deposed according to local
regulation.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
Do not disassemble the UPS system.
Troubleshooting
Use the table below to solve minor problems.
PROBLEM | POSSIBLE CAUSE | SOLUTIONS |
---|---|---|
No LED display on the front panel | Low battery | Charge the UPS at least 6 |
hours
Battery fault| Replace the battery with the same type of battery
The UPS is not turned on| Press the power switch again to turn on the UPS
Alarm continuously sounds when the main is normal| The UPS is overload| Remove
some loads first. Before reconnecting equipment, please verify that the load
matches the UPS capability specified in the specs.
When power fails, back-up time is shortening| The UPS is overload| Remove some
critical load
Battery voltage is too low| Charge the UPS at least 6 hours
Battery defect. It might be due to high temperature operation environment or
improper operation to battery| Replace the battery with the same type of
battery
The main is normal but LED is flashing| Power cord is loose| Reconnect the
power cord properly
Specifications
MODEL | INSPIRE 703SFC | INSPIRE 853SFCU |
---|---|---|
Capacity | 650 VA | 850 VA |
INPUT
Voltage Range| 140 – 300VAC ±5% for 230VAC mode
140 – 290VAC ±5% for 220VAC mode
---|---
Frequency| 50Hz/60Hz (Auto-sensing)
Phase| Single + GND
OUTPUT
Voltage Range | 220VAC/230VAC + 12%-14% |
---|---|
Battery Mode | 220VAC/230VAC ±10% |
Frequency | 50Hz ± 1% (Battery Mode); 60Hz ± 1% (Battery Mode) |
Waveform | Simulated Sine Wave (Battery Mode), Sine Wave (AC Mode) |
Transfer Time | 2ms typical |
BATTERY
Type & Number | 12 V/ 7 AH x 1 | 12 V/ 9 AH x 1 |
---|---|---|
Backup Time | 8 – 30 mins depending on the load | |
Charging Time | 2 – 4 hours recover to 90% capacity |
PROTECTION/MONITORING
Short Circuit Protection | Yes (Line Mode and Battery Mode) |
---|---|
Surge Protection | Yes |
Alarm | Audible & Visual |
UPS Protection | Load Auto Sensing and Abnormal Protection |
Overload Protection | Line Mode – 100 – 120% 5mins change to fault mode |
120% change to fault mode immediately Battery Mode – 100 – 120% 5 secs shutdown
120% shutdown immediately
Intelligent Battery| Prevent overcharging of battery
Management| Protect battery and prolong battery life
Data Line Surge Protection| –| RJ11
SOFTWARE MONITORING
USB Connector #1 | AC Fault, Battery Low, Shutdown UPS |
---|---|
Software #1 | Support Windows® 7/ 8/ 10, Linux and Mac |
GENERAL
Noise Level | < 40dB |
---|---|
Temperature | 0˚C – 40˚C |
Humidity | 0 – 90% |
Built in AVR | TRUE Full AVR (3steps) |
Dimension D x W x H | 279 x 101 x 142mm |
Weight (kg) | 4.2 |
MODEL | INSPIRE 1203SFCU |
--- | --- |
Capacity | 1200 VA |
INPUT
Voltage Range| 140 – 300VAC ±5% for 230VAC mode
140 – 290VAC ±5% for 220VAC mode
---|---
Frequency| 50Hz/60Hz (Auto-sensing)
Phase| Single + GND
OUTPUT
Voltage Range | 220VAC/230VAC + 12%-14% | 230VAC + 12%-14% |
---|---|---|
Battery Mode | 220VAC/230VAC ±10% | 230VAC ±10% |
Frequency | 50Hz ± 1% (Battery Mode); 60Hz ± 1% (Battery Mode) | |
Waveform | Simulated Sine Wave (Battery Mode), Sine Wave (AC Mode) | |
Transfer Time | 2ms typical |
BATTERY
Type & Number | 12 V/ 7 AH x 2 |
---|---|
Backup Time | 8 – 30 mins depending on the load |
Charging Time | 2 – 4 hours recover to 90% capacity |
PROTECTION/MONITORING
Short Circuit Protection | Yes (Line Mode and Battery Mode) |
---|---|
Surge Protection | Yes |
Alarm | Audible & Visual |
UPS Protection | Load Auto Sensing and Abnormal Protection |
Overload Protection | Line Mode – 100 – 120% 5mins change to fault mode |
120% change to fault mode immediately Battery Mode – 100 – 120% 5 secs shutdown
120% shutdown immediately
Intelligent Battery| Prevent overcharging of battery
Management| Protect battery and prolong battery life
Data Line Surge Protection| RJ45
SOFTWARE MONITORING
USB Connector | AC Fault, Battery Low, Shutdown UPS |
---|---|
Software | Support Windows® 7/ 8/ 10, Linux and Mac |
GENERAL
Noise Level | < 40dB |
---|---|
Temperature | 0˚C – 40˚C |
Humidity | 0 – 90% |
Built in AVR | TRUE Full AVR (3steps) |
Dimension D x W x H | 320 x 130 x 182mm |
Weight (kg) | 8.2 |
MODEL | INSPIRE 1503SFCU |
3003SFCU
---|---|---|---
Capacity**| 1500 VA| 2000 VA| 3000 VA
INPUT
Voltage Range| 140 – 300VAC ±5% for 230VAC mode 140 – 290VAC ±5% for
220VAC mode| 162 – 300VAC ±5% for 220/230/240VAC mode
---|---|---
Frequency| 50Hz/60Hz (Auto-sensing)| 60Hz/50Hz (Auto-sensing)
Phase| Single + GND| Single + GND
OUTPUT
Voltage Range | 220VAC/230VAC + 12%-14% | 220VAC/230/240VAC ±15% |
---|---|---|
Battery Mode | 220VAC/230VAC ±10% | 220VAC/230/240VAC ±10% |
Frequency | 50Hz ± 1% (Battery Mode); 60Hz ± 1% (Battery Mode) | |
Waveform | Simulated Sine Wave (Battery Mode), Sine Wave (AC Mode) | |
Transfer Time | 2ms typical | 2 – 6ms typical |
BATTERY
Type & Number | 12 V/ 9 AH x 2 |
---|---|
Backup Time | Up to 40 mins depending on the load |
Charging Time | 2 – 4 hours recover to 90% capacity |
to 90% capacity
PROTECTION/MONITORING
Short Circuit Protection | Yes (Line Mode and Battery Mode) |
---|---|
Surge Protection | Yes |
Alarm | Audible & Visual |
UPS Protection | Load Auto Sensing and Abnormal Protection |
Overload Protection | Line Mode – 100 – 120% 5mins change to fault mode |
120% change to fault mode immediately Battery Mode – 100 – 120% 5 secs shutdown
120% shutdown immediately
Intelligent Battery| Prevent overcharging of battery
Management| Protect battery and prolong battery life
Data Line Surge Protection| RJ45
SOFTWARE MONITORING
USB Connector | AC Fault, Battery Low, Shutdown UPS |
---|---|
Software | Support Windows® 7/ 8/ 10, Linux and Mac |
GENERAL
Noise Level | < 40dB | < 45dB |
---|---|---|
Temperature | 0˚C – 40˚C | |
Humidity | 0 – 90% | |
Built in AVR | TRUE Full AVR (3steps) | |
Dimension D x W x H | 320 x 130 x 182 | 397 x 146 x 205 |
Weight (kg) | 10.4 | 10.6 |
WARRANTY TERMS
We thank you for your trust in choosing this product us and as a Distributor in Indonesia, we provide a service guarantee Repair and Replacement of UPS Parts and Batteries with the following provisions:
- Improvement hope is given for 24 (twenty four) months starting from the date of purchase against the following damages replacement of spare parts, except batteries, only 12 (twelve) months.
- Shipping costs and damage that may occur during transit is the responsibility of the owner of the goods.
- Warranty is VOID or VOID:
- The item has been unsealed or repaired by the owner / third party.
- The goods are damaged due to transportation, falls or errors caused by the user.
- The item was damaged due to fire, lightning strike or disaster natural.
- The serial number has been changed or removed and does not match item to be repaired.
- The Guarantee Card does not have the seller’s signature or stamp.
- The Warranty Card does not match the actual item or There are scribbles and deletions on the Warranty Card.
- Show this Guarantee card when the goods are to be serviced.
- For information regarding storage and maintenance, please see instructions in the manual.
Register online for your product guarantee at www.prolink2u.com
*Shipping costs are borne by the buyer
LIST OF AFTER SALES SERVICES:
- PT. INTIDATA NUSANTARA PROLINK | JL. WEST CIDENG NO. 79, CENTRAL JAKARTA 10150 | Tel: 021-34831777
- AT COMPUTER | SULTAN ADAM COMPANY SHOP PERMAI, NO. 13 BANJARMASIN | Tel: 0511-7404486
- PT. GREATER EAST PROSHOP | JL. RAYA MANYAR 69E SURABAYA RT.004 RW.010, MENUR PUMPUNGAN SUKOLILO SURABAYA JAVA EAST 60286 | Tel: 031-59173511
- PT. ANDARU PRIMA HARSA | JL BRIGJEN KATAMSO NO 75-77 RT 044 RW 013, PRAWIRODIRJAN GONDOMANAN YOGYAKARTA 55655 | Tel: 0274-420277
- DELTACOM | JL. GREAT MOSQUE NO.90K MAKASSAR | Tel: 0411-442806
- PT. ARTHANAYA TECHNOLOGY | JL TEUKU UMAR NO 200 AGUNG RAYA SHOPPING COMPLEX NO 12, DAUH PURI KAUH – WEST DENPASAR- DENPASAR-BALI 80113 | Tel: 0361-2096382
- METRO COMPUTER | JL. ELEPHANT MADA NO.87 | Tel: 0561-741610
- PT. DWIWIRA PUTRADYNAMICS | JL. LOYAL BUDDHIST NO. 107A, NEW WEEK | Tel: 0761-36486
- PT. SQUARE GORONTALO | JL. S. PARMAN NO.38 BIAWAO, SOUTH CITY CITY GORONTALO | Tel: 082188007111
- PT. CORE SANHO MAIN TECHNOLOGY | JL. WHEELING NO. 48 MEDAN | Tel: 061-7330800
Stick it stamps here.
Dear.
Customer Service
PT. INTIDATA NUSANTARA PROLINK
JI. West Cideng No. 79
Central Jakarta 10150 – Indonesia
Worldwide Customer Care Centers
NDONESIA Office
PT PROLINK INTIDATA NUSANTARA
Walk-In : Jl. Cideng Barat No. 79, Jakarta Pusat 10150, Indonesia.
Telephone : +62 21 3483 1777
Sale Enquiries : sales.id@prolink2u.com
Technical Support :
support.id@prolink2u.com
MALAYSIA Office
FIDA SYSTEMS (M) SDN BHD
Walk-In : 29 Jalan USJ 1/31, 47600 Subang Jaya, Selangor Darul Ehsan,
Malaysia.
Telephone : +60 3 8024 9151
Sale Enquiries : sales.my@prolink2u.com
Technical Support :
support.my@prolink2u.com
SINGAPORE Office
FIDA INTERNATIONAL (S) PTE LTD
Walk-In : Block 16 Kallang Place #06-02, Kallang Basin Industrial Estate,
Singapore 339156.
Telephone : +65 6357 0668
Sale Enquiries : sales@prolink2u.com
Technical Support : support@prolink2u.com
Technical Support Hotline
INDONESIA : +62 21 3483 1717
MALAYSIA : +60 3 8023 9151
SINGAPORE : +65 6357 0666
Note: Closed on Saturdays, Sundays and local/regional Public Holidays.
Register online for your Product Warranty at www.prolink2u.com
Prolink is a registered trademark of Fida International (S) Pte Ltd. Other brands and product names are trademarks or registered trademarks of their respective holders. Product images are purely for illustrative purposes and may defer from the actual product. Specifications are subjected to changes without prior notice. Copyright © 2023 Fida International (S) Pte Ltd.
Kartu Garansi harus diisi lengkap, kirimkan paling lambat 14 hari setelah Tgl. Pembelian
Tanda pendaftaran No:
Alamat Pengiriman PT. PROLINK INTIDATA NUSANTARA
Address JI. Cideng Barat No. 79 Jakarta Pusat 10150 – Indonesia
Telp. : (62-21) 34831777
Fax : (62-21) 34830788
Email : support.id@prolink2u.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>