COMMSCOPE PPL-2U-HD-FX Propel Fixed Panel User Manual
- June 13, 2024
- CommScope
Table of Contents
- PPL-2U-HD-FX Propel Fixed Panel
- Product Information
- Propel Fixed Panel Configurations Covered by This User
- Available Connection Components
- 1. Unpacking and Mounting the Propel Fixed Panel
- 2. Installing Connection Components
- 3. Routing and Securing Cables and Patch Cords
- 4. Obtaining Technical Assistance
PPL-2U-HD-FX Propel Fixed Panel
Product Information
The CommScope Propel Fixed Panel is a modular fiber connection
platform that allows for the installation of Propel modules, splice
cassettes, and adapter packs of different sizes. It is designed to
be mounted on a rack and provides flexibility in positioning the
connection components.
This user manual provides instructions on how to unpack the
panel, mount it on a rack, and install various connection
components. It also includes information on routing and securing
cables and patch cords, as well as obtaining technical assistance
if needed.
Propel Fixed Panel Configurations Covered by This User
Manual
The user manual covers the following configurations of the
Propel Fixed Panel:
Material ID (MID) | Catalog # | Density |
---|---|---|
760253796 | PPL-1U-HD-FX | 48 duplex LC, 48 MPO, 192 SN |
760253797 | PPL-2U-HD-FX | 96 duplex LC, 96 MPO, 384 SN |
760253798 | PPL-4U-HD-FX | 192 duplex LC, 192 MPO, 768 SN |
760254865 | PPL-1U-HD-FX-OPEN | 48 duplex LC, 48 MPO, 192 SN |
760254908 | PPL-2U-HD-FX-OPEN | 96 duplex LC, 96 MPO, 384 SN |
Available Connection Components
The Propel Fixed Panel is compatible with various connection
components. The following MPO modules and adapter packs are
available:
Modules & Adapter Packs| Material ID (MID)| Catalog Number| Fiber Type| Fiber
Count
---|---|---|---|---
MPO8 Modules with MPO/UPC| 760252332| PPL-DM-8U-8LC-OM4-BEU| OM4| 8
MPO8 Modules with MPO/APC in multimode| 760252335| PPL-DM-8AU-8LC-OM4-BEU|
OM4| 8
Product Usage Instructions
1. Unpacking and Mounting the Propel Fixed Panel
Follow these steps to unpack and mount the Propel Fixed Panel on
a rack:
-
Ensure you have the necessary mounting hardware.
-
Remove the Propel Fixed Panel from its packaging.
-
Choose the appropriate rack size and mounting hardware based on
your requirements. -
Refer to section 5.1 of the user manual for instructions on
determining rack size and mounting hardware. -
If you are using a rack size other than 19 inches, follow the
instructions in section 5.2 to install kits for alternative rack
sizes. -
If you need to mount the bracket in the 9-inch offset position
(rear of rack mounting), refer to section 5.3.4 for
instructions. -
For panel recess options, if you are using a Fixed Open Panel,
refer to section 5.4 for instructions.
2. Installing Connection Components
Follow these steps to install connection components in the
Propel Fixed Panel:
-
Select the appropriate Propel modules, splice cassettes, and
adapter packs based on your requirements. -
Refer to the available connection components listed in Table 2
of the user manual. -
Install the selected components in any available position
within the panel.
3. Routing and Securing Cables and Patch Cords
Follow these steps to route and secure cables and patch
cords:
-
Ensure you have the necessary cables and patch cords.
-
Route the cables and patch cords through the designated cable
management features of the Propel Fixed Panel. -
Secure the cables and patch cords using appropriate cable ties
or other fastening methods.
4. Obtaining Technical Assistance
If you require technical assistance with the Propel Fixed Panel,
refer to the user manual for contact information and instructions
on how to obtain support.
TC-96342-IP Rev B, August 2023 commscope.com
User Manual
PropelTM Fixed and Fixed Open Panels
28033-A
Propel Fixed and Fixed Open Panel 2RU Shown (Left), 2RU-OPEN Shown (Right)
Content
Page
1 INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 3 1.1 Propel Fixed Panel Configurations Covered by
This User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 3 1.2 Available Connection Components . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 3 1.3 Important Safety Cautions . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 5 1.4 Precautions. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.5 Related
Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 6
2 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 7 2.1 General Description . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 7 2.2 Main Product Features . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.3 Specifications and
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.4 Blades . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 12 2.5 QR Codes . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 13 2.5.1 Product QR Codes on Panel . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 14 2.5.2 Component QR Codes. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . 15
3 UNPACKING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 16 4 OVERVIEW OF INSTALLATION . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 18 5 INSTALLING THE PANEL . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 Determining Rack Size and Mounting Hardware . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 5.2
Installing Kits for Alternative Rack Sizes (Not 19-Inch) . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.2.1 23-Inch Rack (584mm) Mount Kit . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 5.2.2 ETSI
Rack Mount Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 5.3 Panel
Recess Options, Fixed Panel . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.3.1 Mounting Bracket Position on Panel as Shipped . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 20 5.3.2 Mounting
Bracket in 3.5-Inch Offset Position (Front of Rack Mounting) . . . . . . . . .
. . . . . . . . . . . . 20 5.3.3 Mounting Bracket in 6-Inch Offset Position
(Front of Rack Mounting) . . . . . . . . . . . . . . . . . . . . . . 20
Continued
Electronic Only Document (EOD)
© 2023 CommScope, Inc.
TC-96342-IP
Content
Page
5.3.4 Mounting Bracket in 9-Inch Offset Position (Rear of Rack Mounting) . . .
. . . . . . . . . . . . . . . . . . . . 21 5.4 Panel Recess Options, Fixed
Open Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 21
5.4.1 Mounting Bracket Position on Panel as Shipped . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5.4.2 Mounting
Bracket in 3.5-Inch Offset Position (Front of Rack Mounting) . . . . . . . . .
. . . . . . . . . . . . 22 5.4.3 Mounting Bracket in 6-Inch Offset Position
(Front of Rack Mounting) . . . . . . . . . . . . . . . . . . . . . . . 22
5.4.4 Mounting Bracket in 9-Inch Offset Position (Rear of Rack Mounting) . . .
. . . . . . . . . . . . . . . . . . . . 23 5.5 Mounting the Panel on the Rack
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 23 5.6 Installing Connection
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 25 5.7 Installing Cables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.7.1 Installing Cables in a Propel Fixed Panel. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 5.7.2
Installing Cables in a Propel Fixed Open Panel . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 28 5.8 Installing Patch
Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6
OPERATIONAL DETAILS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . 30 6.1 Front Door . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 30 6.1.1 Opening the Front Door . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 30 6.1.2 Closing the Front Door . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . 30 6.2 Rear Cover (Propel Fixed Panel) .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . 31 6.2.1 Removing the Rear
Cover on the 1RU and 2RU Panel (Propel Fixed Panel) . . . . . . . . . . . . .
. . . . . 31 6.2.2 Re-installing the Rear Cover on the 1RU and 2RU Panel
(Propel Fixed Panel) . . . . . . . . . . . . . . . . 31 6.2.3 Opening the Rear
Cover on the 4RU Panel (Propel Fixed Panel) . . . . . . . . . . . . . . . . .
. . . . . . . . . . 31 6.2.4 Closing the Rear Cover on the 4RU panel (Propel
Fixed Panel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 6.3
Connection Components . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 32 6.3.1 Placement of Connection Components on a Blade . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 6.3.2 Installing
a Connection Component . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 33 6.3.3 Removing a Connection
Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 33 6.4 Cables and Rear Cable Management Clips
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 34 6.4.1 Installing a Cable on a Propel Fixed
Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 34 6.4.2 Installing a Cable on a Propel Fixed Open Panel . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.4.3 Routing Cables from the Panel on the Frame . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 6.5 Patch Cords. .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 41 7 CONTACT INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 42
Page 2 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
1 INTRODUCTION
The CommScope Propel Fixed Panel, available in the configurations listed in
Table 1, is a modular fiber connection platform that allows Propel modules,
splice cassettes, and adapter packs of different sizes to be installed in any
position in the panel where space is available.
This user manual describes the Propel Fixed Panel and tells how to unpack the
panel, mount it on a rack, and install connection components including Propel
modules, splice cassettes, and adapter packs. In addition, this manual tells
how to route and secure cables and patch cords, and how to obtain technical
assistance if needed.
1.1 Propel Fixed Panel Configurations Covered by This User Manual
Table 1 lists the Propel Fixed Panel configurations covered in this user manual.
Table 1. Propel Fixed Panel Configurations
Material ID (MID) 760253796 760253797 760253798 760254865 760254908
Catalog # PPL-1U-HD-FX PPL-2U-HD-FX PPL-4U-HD-FX PPL-1U-HD-FX-OPEN PPL-2U-HD- FX-OPEN
Density 48 duplex LC, 48 MPO, 192 SN 96 duplex LC, 96 MPO, 384 SN 192 duplex LC, 192 MPO, 768 SN 48 duplex LC, 48 MPO, 192 SN 96 duplex LC, 96 MPO, 384 SN
1.2 Available Connection Components
For a listing of the available Propel connection components, including MPO
modules and adapter packs, see Table 2. Splice cassettes are not available at
this time.
Table 2. Available MPO Modules and Adapter Packs
Modules & Adapter Packs
Material ID (MID)
MPO8 Modules with MPO/UPC
12 per 1RU
760252332 760252333
760252334
4 per 1RU
760252337 760252338
760252339
MPO8 Modules with MPO/APC in multimode
12 per 1RU
760252335
760252336
8-fiber Adapter Packs
Catalog Number
PPL-DM-8U-8LC-OM4-BEU PPL-DM-8U-8LC-OM5-BEU PPL-DM-8AU-8LC-SM-BEU PPL-DM-8U-
24LC-OM4-BEU PPL-DM-8U-24LC-OM5-BEU PPL-DM-8AU-24LC-SM-BEU
PPL-DM-8AU-8LC-OM4-BEU PPL-DM-8AU-8LC-OM5-BEU
Fiber Type
OM4 OM5 OS2 OM4 OM5 OS2
OM4 OM5
Fiber Count
8 8 8 24 24 24
8 8
Page 3 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Table 2. Available MPO Modules and Adapter Packs, continued
Modules & Adapter Packs
12 per 1RU
MPO12 Modules 8 per 1RU
4 per 1RU 12-fiber Adapter Packs
8 per 1RU
MPO16 Modules 6 per 1RU 16-fiber Adapter Packs
6 per 1RU
12 per 1RU 8 per 1RU 4 per 1RU MPO24 Modules 4 per 1RU 24-fiber Adapter Packs
4 per 1RU
Material ID (MID) 760252359 760252360 760252361 760252371
Catalog Number PPL-AP-8-LC-SM PPL-AP-8-LC-OM4 PPL-AP-8-LC-OM5 PPL-AP-4-MPO- ALL-B
760252343 760252344 760252345 760252346 760252347 760252348
PPL-DM-12U-12LC-OM4-BEU PPL-DM-12U-12LC-OM5-BEU PPL-DM-12AU-12LC-SM-BEU PPL- DM-12U-24LC-OM4-BEU PPL-DM-12U-24LC-OM5-BEU PPL-DM-12AU-24LC-SM-BEU
760252362 760252363 760252364 760252372
PPL-AP-12-LC-SM PPL-AP-12-LC-OM4 PPL-AP-12-LC-OM5 PPL-AP-6-MPO-ALL-B
760252352 760252353 760252354
PPL-DM-16AU-16LC-SM-BEU PPL-DM-16AU-16LC-OM4-BEU PPL-DM-16AU-16LC-OM5-BEU
760252365 760252366 760252367 760252804 760252806 760252805 760252803
PPL-AP-16-LC-SM PPL-AP-16-LC-OM4 PPL-AP-16-LC-OM5 PPL-AP-8-MPO16-ALL-B PPL- AP-4-MPO16-ALL-B PPL-AP-6-MPO16-ALL-B PPL-AP-12-MPO16-ALL-B
760252356 760252357
PPL-DM-24U-24LC-OM4-BEU PPL-DM-24U-24LC-OM5-BEU
760252368 760252369 760252370 760252374
PPL-AP-24-LC-SM PPL-AP-24-LC-OM4 PPL-AP-24-LC-OM5 PPL-AP-12-MPO-ALL-B
Fiber Type OS2 OM5 OS2 All
Fiber Count 8 8 8 32
OM4
12
OM5
12
OS2
12
OM4
24
OM5
24
OS2
24
OS2
12
OM4
12
OM5
12
All
72
OS2
16
OM4
16
OM5
16
OS2
16
OM4
16
OM5
16
All
128
All
64
All
96
All
96
OM4
24
OM5
24
OS2
24
OM4
24
OM5
24
All
288
Page 4 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Table 2. Available MPO Modules and Adapter Packs, continued
Modules & Adapter Packs
S/N Modules 12 per 1RU 8 per 1RU 12 per 1RU S/N Adapter Packs 12 per 1RU 8 per
1RU 6 per 1RU 4 per 1RU
Material ID (MID) Catalog Number
760252342 760252349 760252355
PPL-DM-8AU-8SN-SM-BEU PPL-DM-12AU-12SN-SM-BEU PPL-DM-16AU-8SN-SM-BEU
760252375 760252376 760252377 760252378
PPL-AP-8-SN-SM PPL-AP-12-SN-SM PPL-AP-16-SN-SM PPL-AP-24-SN-SM
Fiber Type Fiber Count
OS2
16
OS2
24
OS2
16
OS2
16
OS2
24
OS2
32
OS2
48
1.3 Important Safety Cautions
When installing or operating the panel, observe these safety cautions:
· To reduce the risk of fire, electric shock, and injury to persons, read,
understand, and adhere to the following instructions as well as any warnings
marked on the product.
· This product has a remote risk of electric shock. Never install the product
in wet conditions or during lightning storms. Never touch uninsulated
communication wires or terminals.
· Wearing safety glasses during installation of this panel is recommended.
Although standard safety glasses provide no protection from potential optical
radiation, they offer protection from accidental airborne hardware and
cleaning solvents.
· Disconnected optical components may emit invisible optical radiation that
can damage your eyes. Never look directly into an optical component that may
have a laser coupled to it. Serious and permanent retinal damage is possible.
If accidental exposure to laser radiation is suspected, consult a physician
for an eye examination.
1.4 Precautions
When installing or operating the panel, observe the following precautions:
· Fiber optic trunk cable and jumper performance is sensitive to bending,
pulling, and crushing. Minimum bend radius must be maintained during
installation per the manufacturer’s specification. Appropriate pulling grips
must be used during installation, and pulling forces shall not exceed
manufacturer’s recommendations.
· All wiring that connects to this equipment must meet applicable local and
national building codes and network wiring standards for communication cable.
· IMPORTANT: Dust covers are installed in the ports to protect the fibers
connected to the back of the ports. Do not remove a dust cover from a port
until you connect a patch cord to that port. If you remove a patch cord later,
replace the dust cover in the port.
· Prior to installation, clean the trunk cable and jumper connectors per the
manufacturer’s recommendations.
Page 5 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
· Isopropyl alcohol is flammable, and can cause eye irritation on contact. If
eye contact occurs, flush with water for at least 15 minutes. In case of
ingestion, consult a physician. Use only in well ventilated areas.
· Care should be taken not to compromise the stability of the rack by
installation of this equipment.
1.5 Related Publications
The related publications listed are available by contacting the CommScope Support Center at https://www.commscope.com/SupportCenter
Publication Title Propel Fixed Panel Quick Start Propel Fixed Open Panel Quick Start
Publication Number
TC-96341-IP TC-96355-IP
Page 6 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
2 PRODUCT DESCRIPTION
2.1 General Description
The Propel Fixed Panel is a 19-inch rack-mount fiber optic connector panel intended for indoor use. Rack adapter kits are available that enable the panel to be mounted in a 23-inch or ETSI rack. The standard panel is available in one, two, or four rack unit sizes (abbreviated as 1RU, 2RU, or 4RU), while a reduced-depth, open version of the panel is available in one or two rack unit sizes (1RU or 2RU). Figure 1 shows the five Fixed panels.
Note:
The open panel is officially called “Propel Fixed Open Panel” to distinguish it from the standard version. The term “Propel Fixed Panel” is often used to refer to the fixed and fixed open panels collectively.
The Propel Fixed Panel contains two fixed position “blades” per RU, installed in the factory. Each blade supports multiple sizes of connection components including MPO modules, adapter packs, and splice cassettes. Connection components are installed by positioning them in any available location on the blade and sliding them in until they click into position.
PROPEL FIXED PANEL
PROPEL FIXED OPEN
PANEL
Figure 1. Propel Fixed Panel and Propel Fixed Open Panel
28034-A
Precise positioning on the blade is enforced by rails that the connection components slide onto when installed. The rails direct the components into 12 equal-sized lanes, labeled A to L. Each lane accommodates 4 fibers or the connector equivalent. For example, an MPO module with 4 front duplex LC ports and a rear MPO 8 connector occupies two lanes. Propel connection components are available in 4 sizes accommodating 8, 12, 16, or 24 fibers. The largest size component occupies 6 lanes, which is half of the blade. The Propel Fixed Panel capacity per blade is 48 fibers
Page 7 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
(24 duplex LC ports). Capacity per RU is 96 fibers (48 duplex LC ports). If SN
connection components are used, the fiber capacity of the panel doubles in
comparison to LC, because a single SN connector has 4 fibers, while LC has 2.
2.2 Main Product Features
Figure 2 shows a front view of a 2RU Propel Fixed Panel with front door
removed. The main features are:
· Rear Cover–can be removed providing top access to rear of the panel. · Cable
Entry Area–is the portal through which cables are routed into the rear of the
panel. · Mounting Brackets (one on each side)–provide for mounting the panel
in a frame or
cabinet. The panel is shipped with 19-inch mounting brackets. Kits are
available for mounting in a 23-inch or ETSI rack or cabinet. · Blade–supports
the slide-in connection components and holds them in position. · Integral
Patch Cord Entry Managers–are used to manage patch cords.
REAR COVER
INTEGRAL PATCH CORD MANAGER
BLADE
CABLE ENTRY AREA
MOUNTING BRACKET
28063-A
Figure 2. Propel Fixed Panel Front View (2RU Shown)
Figure 3 shows rear views of a 2RU Propel Fixed Panel with rear cover present
and removed. The main features visible from this view include the following.
· Rear Cover–can be removed providing top access to the panel.
· Cable Entry Area–is the portal through which cables are routed into the rear
of the panel.
· Cable Management Bracket–holds the rear cable management clips. Each clip
holds one cable tied to it with hook-and-loop straps.
· Cable Routing Platform–is a surface across which cables are routed from
connection components out of the panel.
Page 8 © 2023 CommScope. All Rights Reserved.
REAR COVER
TC-96342-IP
CABLE ENTRY AREA
CABLE ROUTING PLATFORM
CABLE MANAGEMENT
BRACKET
Figure 3. Propel Fixed Panel (2RU Shown)
28064-A
Figure 4 shows the rear of the 2RU Propel Fixed Open Panel. The main features
visible from this view include the following.
· Patch Cord Entry Area–is the portal through which cables are routed into the
front of the panel.
· Cable Management Strip–supports cables routed from connection components and
provides tie-down locations via cable management slots.
· Cable Management Slots–allow hook-and-loop straps or cable ties to secure
rear cables to cable management strip.
Page 9 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
CABLE
CABLE
MANAGEMENT MANAGEMENT
STRIP
SLOTS
28065-A
PATCH CORD ENTRY AREA
Figure 4. Rear View of Propel Fixed Open Panel (2RU Shown)
2.3 Specifications and Dimensions
Table 3 lists dimensions for the Propel Fixed and Fixed Open Panels. Figure 5 shows dimensions for the Propel Fixed Panels. Figure 6 shows dimensions for the Propel Fixed Open Panels.
Table 3. Propel Fixed and Fixed Open Panel Specifications
Parameter Height
Width
Depth
Weight (Panel Only) Weight (Packaged)
PPL-1U-HD-FX 1.72 in (4.36 cm) 19.0 in. (48.26 cm) 18.55 in. (47.11 cm) 8.65 lbs. (5.92 kg) 13.20 lbs. (5.99 kg)
PPL-2U-HD-FX 3.47 in. (8.81 cm) 19.0 in. (48.26 cm) 18.55 in. (47.11 cm) 12.15
lbs. (5.51 kg)
17.05 lbs. (7.73 kg)
PPL-4U-HD-FX 6.97 in (17.70 cm) 19.0 in. (48.26 cm) 18.55 in. (47.11 cm) 22.15 lbs. (10.05 kg) 28.10 lbs. (12.75 kg.
PPL-1U-HD-FX-OPEN 1.72 in (4.36 cm) 19.0 in. (48.26 cm) 11.51 in. (29.24 cm) 6.05 lbs. (2.74 kg) 9.20 lbs. (4.17 kg)
PPL-2U-HD-FX-OPEN 3.47 in. (8.81 cm) 19.0 in. (48.26 cm) 11.51 in. (29.24 cm) 8.80 lbs. (3.99 kg) 12.15 lbs. (5.51 kg)
Page 10 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
15.11 IN. (38.37 CM)
TOP VIEW 17.20 IN. (43.68 CM)
19.00 IN. (48.25 CM) 18.31 IN. (46.51 CM)
1RU PANEL (FRONT VIEW)
2RU PANEL (FRONT VIEW)
3.06 IN. (7.77 CM)
1.72 IN. (4.36 CM)
3.47 IN. (8.81 CM)
27504-A
18.55 IN. (47.11 CM) 1RU PANEL (SIDE VIEW) 2RU PANEL (SIDE VIEW)
6.96 IN. (17.68 CM)
4RU PANEL (FRONT VIEW)
4RU PANEL (SIDE VIEW)
Figure 5. Propel Fixed Panel Dimensions
Page 11 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
17.42 IN. (44.25 CM)
8.45 IN. (21.47 CM)
3.06 IN. (7.78 CM)
1RU PANEL (TOP VIEW)
19.00 IN. (48.25 CM) 18.31 IN. (46.51 CM)
1.74 IN. (4.42 CM)
QR CODE (ENLARGED)
11.51 IN. (29.24 CM)
1RU PANEL (FRONT VIEW)
3.46 IN. (8.79 CM)
1RU PANEL (SIDE VIEW)
2RU PANEL (FRONT VIEW)
28067-A
2RU PANEL (SIDE VIEW)
Figure 6. Propel Fixed Open Panel Dimensions
2.4 Blades
Propel blades have rails that guide Propel connection components into lanes.
Each blade has 12 lanes labeled A to L. Table 4 lists the available Propel
Panel Fixed and Fixed Open configurations.
Table 4. Available Modules and Adapter Packs
Fixed Panel Catalog # PPL-1U-HD-FX/ PPL-1U-HD-FX-OPEN PPL-2U-HD-FX/ PPL-2U-HD-
FX-OPEN PPL-4U-HD-FX
Each blade has 12 lanes
8-fiber modules/ adapter packs
up to 6 per blade/ 12 per panel
up to 6 per blade/ 24 per panel
up to 6 per blade/ 48 per panel
12-fiber modules/ adapter packs
up to 4 per blade/ 8 per panel
up to 4 per blade/ 16 per panel
up to 4 per blade/ 32 per panel
16-fiber modules/ adapter packs
up to 3 per blade/ 6 per panel
up to 3 per blade/ 12 per panel
up to 3 per blade/ 24 per panel
Requires 2 lanes Requires 3 lanes Requires 4 lanes
24-fiber modules/ adapter packs up to 2 per blade/ 4 per panel up to 2 per
blade/ 8 per panel up to 2 per blade/ 16 per pane
Requires 6 lanes
Page 12 © 2023 CommScope. All Rights Reserved.
TC-96342-IP Figure 7 shows a fully occupied blade. The components shown are 3
of the available 4 sizes. The largest component, which occupies half of the
blade, is not shown. As shown in Figure 8, Propel components can be installed
from the front or rear of a blade.
Figure 7. Fully Loaded Blade
Figure 8. Connection Components Can Be Installed from Front or Rear 2.5 QR
Codes Propel products are labeled with QR codes providing different types of
information of interest to the user. Included are the QR code types described
below.
Page 13 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
2.5.1 Product QR Codes on Panel
Each panel is affixed with a QR code that goes to the Propel Panels product
page in the CommScope electronic catalog. The product page has documentation,
including specifications, the quick start guide, and electronic only user
manuals, for all types of Propel panels. Other customer aides such as videos
when available are also placed on the product page for viewing online or
downloading by the customer
Figure 9 shows the front QR code location on the Propel Fixed and Fixed Open
Panel. Figure 10 shows the rear QR code locations in the Propel Fixed and
Fixed Open Panel.
FRONT QR CODE LOCATION ON PROPEL PANEL FRONT DOOR
28096-A
Figure 9. Front QR Code Location, Propel Fixed and Fixed Open Panel
Page 14 © 2023 CommScope. All Rights Reserved.
REAR QR CODE LOCATION PROPEL FIXED PANEL
TC-96342-IP
REAR QR CODE LOCATION PROPEL FIXED OPEN PANEL
28096-A
Figure 10. Rear QR Code Location, Propel Fixed and Fixed Open Panel 2.5.2
Component QR Codes Each Propel connection component (module, adapter pack, or
splice cassette) has a label specific to that particular item. The label is
sized to the width of the component and has information such as the item
serial number (for a module only) and test results. See Figure 11.
Page 15 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
ITEM SPECIFIC QR CODE ITEM SERIAL NUMBER
MANUFACTURER COUNTRY AND DATE
CATALOG NUMBER PORT NUMBERS
27523-A
Figure 11. Example of Propel Connection Component Labeling
3 UNPACKING AND INSPECTION
Use the following procedure to unpack and inspect the product. Verify parts against Table 5 below.
Table 5. Propel Fixed Panel Parts List
Description Propel Fixed Panel Quick Start (TC-96341-IP or TC-96355-IP) Propel
Fixed Panel (1RU, 2RU, 4RU, 1RU-OPEN, or 2RU-OPEN) Panel fastener pack
Quantity 1 1 1 per panel
1. Inspect the exterior of the shipping container(s) for evidence of rough
handling that may have damaged the components in the container.
2. Unpack each container while carefully checking the contents for damage.
3. If damage is found or parts are missing, contact the CommScope Support
Center using the URL: http://www.commscope.com/SupportCenter
4. Save any damaged cartons for inspection by the carrier.
For an exploded view of product packaging, refer to Figure 12 for the Propel
Fixed Panel and to Figure 13 for the Propel Fixed Open Panel.
Page 16 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
NOTE: ON 4RU PANEL, REMOVE AND DISCARD (2) TRANSIT SCREWS FROM REAR DOOR
(IDENTIFIED WITH YELLOW LABELS).
28074-A
Figure 12. Unpacking a Propel Fixed Panel
Page 17 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
28069A
Figure 13. Unpacking a Propel Fixed Open Panel 4 OVERVIEW OF INSTALLATION
Installing the panel and accessories involves the following procedures:
· Determining rack size and mounting hardware (covered in Section 5.1 on Page
19). · Installing kits for alternative rack sizes (not 19-inch) (Section 5.2
on Page 19). · Selecting panel recess options for a fixed panel (Section 5.3
on Page 19). · Selecting panel recess options for a fixed open panel (Section
5.4 on Page 21). · Mounting the panel on a rack (Section 5.5 on Page 23). ·
Installing connection components (Section 5.6 on Page 25). · Installing cables
(Section 5.7 on Page 27). · Installing patch cords (Section 5.8 on Page 29).
The installation procedures listed above describe the sequential steps for a
typical installation in a way that facilitates going quickly and efficiently
through the installation. For operational details for covers, doors,
connection components, cables, cable management clips, and patch cords, refer
to
Page 18 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Section 6 on Page 30. Refer to these sub-sections during installation if any
problem arises in moving through the installation procedures.
5 INSTALLING THE PANEL 5.1 Determining Rack Size and Mounting Hardware The
Propel Fixed Panel is shipped with mounting brackets suitable for mounting on
a 19-inch equipment rack or cabinet.
Accessory kits are available for mounting on a 23-inch or ETSI rack. Whatever
the type of rack being used, four recess options are available for positioning
the mounting brackets.
The mounting brackets shown in illustrations are those used for 19-inch rack
mounting. Refer to the following sections for more information.
5.2 Installing Kits for Alternative Rack Sizes (Not 19-Inch)
5.2.1 23-Inch Rack (584mm) Mount Kit To mount the panel on a 23-inch (584mm)
rack, use the G2-23BRKT accessory kit (one kit per RU, available separately)
and install two conversion brackets to the pre-installed mounting brackets,
using the four #10-32 x 3/8-inch conversion screws included in the accessory
kit.
Use one conversion bracket and two screws per side. Mount the panel to rack
using four #12-24 x 1/2-inch screws (provided as part of basic panel).
5.2.2 ETSI Rack Mount Kit To mount the panel on an ETSI rack, use the
G2-23BRKT accessory kit (available separately) and install one conversion
bracket to either of the pre-installed mounting brackets, using two of four
10-32 x 3/8-inch conversion screws included in accessory kit.
The panel will not be centered when mounted in rack.
Mount the panel to rack using four M6 x 12mm screws (provided as part of basic
panel).
5.3 Panel Recess Options, Fixed Panel The Propel Fixed Panel is shipped with
the mounting brackets in a 3-inch offset position for front of rack mounting.
The mounting brackets can be relocated to 3.5-inch or 6-inch offset positions
for front of rack mounting, or to a 9-inch offset position for rear of rack
mounting. Note: The mounting brackets are stamped with the letter “1” at key
locations to assist in
orienting the mounting brackets in the following procedures.
Page 19 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
5.3.1 Mounting Bracket Position on Panel as Shipped Figure 14 shows the
mounting bracket position when shipped. Note: The holes used for this mounting
location are stamped with a “1” on the physical bracket
and are also shown in these illustrations.
3.0 IN. (7.62 CM)
28076-A
Figure 14. Rack Mounting Position for 3.0-Inch Recess (Shipped Panel)
5.3.2 Mounting Bracket in 3.5-Inch Offset Position (Front of Rack Mounting)
Figure 15 shows the mounting bracket in the 3.5-inch offset position for front
of rack mounting. To mount a mounting bracket at this position, remove screws
from holes marked “1” and remount the mounting bracket using the unmarked
holes shown in Figure 15.
3.5 IN. (8.89 CM)
28077-A
Figure 15. Rack Mounting Position for 3.5-Inch Recess
5.3.3 Mounting Bracket in 6-Inch Offset Position (Front of Rack Mounting)
Figure 16 shows the mounting bracket in the 6-inch offset position for front
of rack mounting. To mount a mounting bracket at this position, remove screws
from holes marked “1” and rotate the bracket 180 degrees. Reinstall 4 screws
in holes marked “1”.
Page 20 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.0 IN. (15.24 CM)
28078-A
Figure 16. Rack Mounting Position for 6-Inch Recess
5.3.4 Mounting Bracket in 9-Inch Offset Position (Rear of Rack Mounting)
Figure 17 shows the mounting bracket at the 9-inch offset position for rear of
rack mounting. To mount a mounting bracket at this position, remove the 4
screws from holes marked “1”, rotate the bracket 180 degrees, reposition the
bracket at the rearward position, and reinstall 4 screws in the holes marked
“1”.
9.0 IN. (22.86 CM)
28079-A
Figure 17. Rack Mounting Position for 9-Inch Recess
5.4 Panel Recess Options, Fixed Open Panel
The Propel Fixed Open Panel is shipped with the mounting brackets in a 3-inch
offset position for front of rack mounting.
The mounting brackets can be relocated to 3.5-inch or 6-inch offset positions
for front of rack mounting, or to a 9-inch offset position for rear of rack
mounting.
Note: The mounting brackets are stamped with the letter “1” at key locations
to assist in orienting the mounting brackets in the following procedures.
5.4.1 Mounting Bracket Position on Panel as Shipped
Figure 18 shows the mounting bracket position when shipped.
Note: The holes used for this mounting location are stamped with a “1” on the
physical bracket and are also shown in these illustrations.
Page 21 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
3.0 IN. (7.62 CM)
28070-A
Figure 18. Rack Mounting Position for 3.0-Inch Recess (Shipped Panel)
5.4.2 Mounting Bracket in 3.5-Inch Offset Position (Front of Rack Mounting)
Figure 19 shows the mounting bracket in the 3.5-inch offset position for front
of rack mounting. To mount a mounting bracket at this position, remove screws
from holes marked “1” and remount the mounting bracket using the unmarked
holes shown in Figure 19.
3.5 IN. (8.89 CM)
28071-A
Figure 19. Rack Mounting Position for 3.5-Inch Recess
5.4.3 Mounting Bracket in 6-Inch Offset Position (Front of Rack Mounting)
Figure 20 shows the mounting bracket in the 6-inch offset position for front
of rack mounting. To mount a mounting bracket at this position, remove the
screws from the holes marked “1” and rotate the bracket 180 degrees. Reinstall
4 screws in holes marked “1”.
Page 22 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.0 IN. (15.24 CM)
28072-A
Figure 20. Rack Mounting Position for 6-Inch Recess
5.4.4 Mounting Bracket in 9-Inch Offset Position (Rear of Rack Mounting)
Figure 21 shows the mounting bracket at the 9-inch offset position for rear of
rack mounting. To mount a mounting bracket at this position, remove the 4
screws from holes marked “1”, rotate the bracket 180 degrees, reposition the
bracket at the rearward position, and reinstall 4 screws in the holes marked
“1”.
28073-A
9.0 IN. (22.86 CM)
Figure 21. Rack Mounting Position for 9-Inch Recess
5.5 Mounting the Panel on the Rack
Note:
The panel is shipped with mounting brackets suitable for mounting on a 19-inch equipment rack or cabinet. If mounting on a 23-inch or ETSI equipment rack or cabinet, install the mounting kit per Section 5.2 on Page 19, then return to this procedure.
Page 23 © 2023 CommScope. All Rights Reserved.
TC-96342-IP To install the panel on the rack, use the following procedure,
referring to Figure 22 for the Propel Fixed Panel and to Figure 23 for the
Propel Fixed Open Panel. The steps shown are numbered corresponding to
numbered steps below.
1. Install the bottom two screws at the desired panel location. 2. Set the
panel into position on the screws just installed. 3. Secure the panel to the
rack by installing the remaining two mounting screws. 4. If required, connect
panel to earth ground per local practice.
32
3 1
28076-A
Figure 22. Mounting the Propel Fixed Panel (2RU Panel Shown)
Page 24 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
32
3 1
28081-A
Figure 23. Mounting the Propel Fixed Open Panel (2RU-OPEN Panel Shown) 5.6
Installing Connection Components Connection components include modules,
adapter packs, and splice cassettes. Precise positioning on the blade is
enforced by rails that the connection components slide onto when installed.
The rails direct the components into 12 equal-sized lanes, labeled A to L.
Connection components are available in 4 sizes occupying 2, 3, 4, or 6 lanes.
Use the following procedure, referring to Figure 24.
1. Open the front cover of the panel.
Page 25 © 2023 CommScope. All Rights Reserved.
TC-96342-IP 2. Determine where the connection component will be installed. It
can be installed anywhere there is enough space for it. 3. Determine whether
the component will be installed from the front or rear, as shown in Figure 24.
Either option is possible, though connection components with pre-attached or
spliced in cables are more easily installed from the rear. NOTE: FIXED TOP
REMOVED.
28084-A
Figure 24. Connection Components Can be Installed from Front or Rear
Page 26 © 2023 CommScope. All Rights Reserved.
4. Position the component on the rails as indicated in Figure 25.
NOTE:
Align grooves on bottom of connection component with rails on blade. Slide in
on rails.
TC-96342-IP
RAIL
GROOVE
28083-A
Figure 25. Positioning Connection Component on Rails 5. Slide in the
connection component until it clicks into place. 5.7 Installing Cables Cables
are installed on the rear of the Propel Fixed Panel or Propel Fixed Open Panel
to transition from the rear of the connection components to other equipment.
If the connection component is a module or adapter pack, the cable needs to be
terminated with the appropriate connectors. If the connection component is a
splice cassette, the cable must have a pigtail termination for splicing to the
fibers within the splice cassette.
Page 27 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Procedures follow below for the Propel Fixed Panel (Section 5.7.1) and the
Propel Fixed Open Panel (Section 5.7.2).
5.7.1 Installing Cables in a Propel Fixed Panel
On a Propel Fixed Panel, once connected or spliced, the cables are routed from
the connection components across the cable management platform to the cable
management bracket where the individual cables are secured using cable
management clips. From the cable management bracket, the cables are routed to
the far end equipment. Use the following procedure.
1. Route the cable in an arc to the cable management bracket. Avoid kinking
the cable or bending it beyond the minimum bend radius as specified by the
cable manufacturer.
2. At the point where the cable passes over the cable management bracket,
install a cable management clip. For detailed instructions, refer to Section
6.4.1 on Page 34.
Note: Further instructions for the cable management clip are provided with
each Propel cable assembly.
3. Insert the cable management clip into the cable management bracket, as
also instructed in Section 6.4.1 on Page 34.
4. Route the cables out of the panel, through the vertical cable guide of the
frame structure, and to the far end equipment.
5.7.2 Installing Cables in a Propel Fixed Open Panel
On a Propel Fixed Open Panel, once connected or spliced, the cables are routed
from the connection components across the cable management strip, where they
can be secured to the cable management slots with hook-and-loop straps, cable
ties, or other means of cable fastening. From the cable management strip, the
cables are routed to the far end equipment.
Use the following procedure. 1. Route the cable to the desired slots of the
cable management strip. Avoid kinking the cable or bending it beyond the
minimum bend radius as specified by the cable manufacturer. 2. Secure the
cable to the cable management strip using the cable management slots and the
preferred means of cable fastening (hook-and-loop strap, cable tie, etc). For
detailed instructions, refer to Section 6.4.2 on Page 38. 3. Route the cables
out of the panel, through the vertical cable guide of the frame structure, and
to the far end equipment. Optionally, the cables can be secured to the frame
structure. Refer to Section 6.4.3 on Page 38.
Page 28 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
5.8 Installing Patch Cords Patch cords are installed on the front of the
Propel Fixed Panel or Propel Fixed Open Panel to connect the front of the
connection components to other equipment at the same site. Patch cords are
grouped and secured by routing them through the nearest patch cord manager at
the front of the panel. To install patch cords, adhere to the following
procedure.
1. Connect the patch cords to the desired ports. 2. Route the patch cords
neatly to both sides of the blade as shown in Figure 26. The number
of patch cords routed to each side does not matter so long as the patch cords
are neatly arranged.
Figure 26. Patch Cords Fanned to Both Sides of a 4RU Fixed Panel 3. Route the
opposite patch cord ends to the desired equipment location.
Page 29 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6 OPERATIONAL DETAILS This section contains operational details that can be
accessed separately outside of the installation procedures. Electronically,
the most direct way to access these operational details is through the table
of contents for this user manual on page 1. 6.1 Front Door The front door is
present in both the Propel Fixed Panel and the Propel Fixed Open Panel. The
front door can be opened and closed as described in the following sub-
sections. 6.1.1 Opening the Front Door To open the front door of the Propel
Fixed Panel, adhere to the following procedure. 1. Grasp the top corners of
the door with thumb and forefingers as shown in Figure 27. Look for
the tabs on the upper corners of the door. 2. Swing open the top of the door
as shown in Figure 27.
27546-A
Figure 27. Swinging Down the Front Door of the Propel Fixed Panel 6.1.2
Closing the Front Door To close the front door of the Propel Fixed Panel,
swing the door upward until it clicks into place.
Page 30 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.2 Rear Cover (Propel Fixed Panel) The Propel Fixed Panel has a rear cover
that can be removed as described in the following subsections.
6.2.1 Removing the Rear Cover on the 1RU and 2RU Panel (Propel Fixed Panel)
Note: Rear cover operation on the 4RU panel is different than on the 1RU and
2RU panels. To remove the rear cover of the Propel Fixed Panel, loosen the two
captive screens on the bottom corners of the cover, and lift off the cover.
CAPTIVE SCREWS (2x)
Figure 28. Loosening the Captive Screws
27553-A
6.2.2 Re-installing the Rear Cover on the 1RU and 2RU Panel (Propel Fixed
Panel)
To re-install the rear cover on a 1RU or 2RU panel, place it into position and
secure it with the two captive screws.
6.2.3 Opening the Rear Cover on the 4RU Panel (Propel Fixed Panel)
To open the rear cover of the 4RU panel, loosen the two captive screws to
release the door and swing it down on its hinges.
6.2.4 Closing the Rear Cover on the 4RU panel (Propel Fixed Panel)
To close the rear cover of the 4RU panel, swing the door up into its closed
position. Secure it with its two captive screws.
Page 31 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.3 Connection Components 6.3.1 Placement of Connection Components on a Blade
When installing a connection component, take care to align the grooves on the
bottom of the component with the rails on the blade, as shown in Figure 29.
NOTE:
Align grooves on bottom of connection component with rails on blade. Slide in
on rails.
RAIL
GROOVE
28083-A
Figure 29. Positioning Connection Component on Rails
Page 32 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.3.2 Installing a Connection Component To install a connection component,
position it on the blade rails wherever there is space for it. Slide the
component in until it clicks into place. Refer to Figure 30
Figure 30. Installing a Connection Component
6.3.3 Removing a Connection Component
Danger!
Disconnected optical components may emit invisible optical radiation that can damage your eyes. Never look directly into an optical component that may have a laser coupled to it. Serious and permanent retinal damage is possible. If accidental exposure to laser radiation is suspected, consult a physician for an eye examination.
To remove a connection component, disconnect it by pulling on the light gray handle, and slide it off the blade, heeding the Danger warning above.
Page 33 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.4 Cables and Rear Cable Management Clips 6.4.1 Installing a Cable on a
Propel Fixed Panel To attach a cable management clip on a cable, perform the
following steps: 1. Obtain two hook-and-loop straps and a cable management
clip (provided with each Propel
cable assembly). Refer to Figure 31.
TIE WRAP (2x) (OPTIONAL)
HOOK-ANDLOOP STRAP (2X)
CABLE MANAGEMENT
CLIP
HEAT-SHRINK (AT CABLE BREAKOUT IF ANY)
28094-A
Figure 31. Cable Ties (Optional), Hook-and-Loop Straps, Cable Management Clip,
and Cable
2. Lay out the cable in a gentle arcing route to the cable management
bracket. Mark the cable at the point where it will enter the cable management
bracket. If the cable has multiple sub-units, break out the cable per local
practice at the mark just made on the cable.
3. Wrap the cable at the breakout location in heat-shrink or, if no breakout
is present, at the mark made on the cable in the previous step
Page 34 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
4. Secure the cable jacket to the clip with the hook-and-loop straps or cable ties as follows (refer to Figure 32):
a. Attach the cable or cables to the snap-in mounting clip with the included hook-and-loop straps or with any style of cable tie you prefer.
Note:
The snap-in cable mounting clip can accommodate single or multiple cables in a variety of cable sizes. For more instructions and an illustration, refer to the installation drawing that came with the cable assembly.
b. After securing the hook-and-loop straps or cable ties to the cable, use a side cutter or scissors to remove excess material.
Note:
Ensure that the cable breakout is not retained by the hook-and-loop strap or cable tie, referring to the guidelines provided in Figure 32 and in the installation drawing provided with the cable assembly.
ATTACH CABLE OR CABLES TO SNAP-IN MOUNTING CLIP WITH INCLUDED
HOOK-AND-LOOP STRAP OR WITH ANY STYLE OF CABLE TIE YOU PREFER
HEAT-SHRINK
AFTER SECURING HOOK-AND-LOOP STRAP OR CABLE TIE (NOT INCLUDED)
USE SIDE CUTTER OR SCISSORS TO REMOVE EXCESS MAERIAL
HEAT-SHRINK END
FOR REFERENCE ONLY: SLOT IN MOUNTING CLIP CAN ALSO BE USED TO ATTACH CABLES
WITH
PANDUIT HLT OR COMMSCOPE HOOK-AND-LOOP CABLE TIES (1375254-2)
27610-A
ALIGN THE BACK OF THE SNAP-IN CABLE MOUNTING CLIP TO THE BACK OF THE HEAT
SHRINK ON CABLE JACKET.
THIS WILL GIVE YOU THE CORRECT 22″ BREAKOUT LENGTH FOR THE CHASSIS
MOUNTING SLOT FOR ADDING OPTIONAL EXTRA CABLE TIES (NOT INCLUDED)
Figure 32. Cable Management Clip Detailed View
Page 35 © 2023 CommScope. All Rights Reserved.
TC-96342-IP 5. Insert the lead bottom feature of the clip into the selected
slot, and slide it in to the final position, as shown in Figure 33 and Figure
34. Start at forward most position and install additional cables working
toward back of panel. Figure 35 shows a fully-installed cable assembly routed
in a slack loop on the cable management platform, with connections made to the
rear module ports.
Note: Detailed instructions for the cable management clip are provided with
each Propel cable assembly.
CABLE MANAGEMENT
BRACKET 28085-A
Figure 33. Inserting and Sliding in a Cable and Clip Assembly
Page 36 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
CABLE MANAGEMENT
BRACKET 28086-A
Figure 34. Final Position of Cable and Clip Assembly in Cable Management
Bracket
Figure 35. Fully-Installed Cable Assembly with Slack Loop, Propel Fixed Panel
Page 37 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.4.2 Installing a Cable on a Propel Fixed Open Panel To install a cable in
the Propel Fixed Open Panel, perform the following steps:
1. Connect cable to the selected rear port of the Propel connection component
being used. Take care to prevent the trunk cable and any cable subunits from
exceeding their manufacturer specified minimum bend radii.
2. Route the cable out the back of the panel and align it with the vertically
or horizontally oriented slots in the cable management strip.
3. Use hook-and-loop straps or cable ties to secure the cable to the cable
management strip. Refer to Figure 36. Optionally, refer to Figure 37 for an
example of using the cable management strip to facilitate and secure slack
loops.
Figure 36. Securing Cables on a Fixed Open Panel 6.4.3 Routing Cables from the
Panel on the Frame Route all cables neatly from the cable management strip
into the vertical cable management of the supporting infrastructure. Cable
mounting bracket accessories can be added to facilitate cable routing outside
of the panel. Generic brackets for rack and cabinet applications are outlined
in Table 6. Figure 38 shows an example of a Fixed Open Panel used with EHD-RMB
cable mounting brackets in a rack mounting application.
Page 38 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Figure 37. Securing Cables with Slack Loops on a Fixed Open Panel
Material ID (MID) EHD-CMB
Table 6. Cable Mounting Bracket Accessories
Catalog # EHD-CMB
Description
Cabinet mount accessory bracket for attaching cables or breakout kits 5.5″
long
Product Image
EHD-RMB
EHD-RMB
Rack mount accessory bracket for attaching cables or breakout kits 5.5″ long
Page 39 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
Material ID (MID) 760239859
Table 6. Cable Mounting Bracket Accessories
Catalog # UMB-RMB-LG
Description
Extended rack mount accessory bracket for attaching cables or breakout kits
11.3″ long
Product Image
760239861
UMB-CMB-LG
Extended cabinet mount accessory bracket for attaching cables or breakout kits 11.3″ long
Figure 38. Typical Use of Cable Mounting Brackets (EHD-RMB Shown)
Page 40 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
6.5 Patch Cords To install a patch cord, connect the connector to the selected
front port of the connection module. Route patch cords neatly through patch
cord managers as needed. Figure 39 shows how to feed patch cords into and out
of the integral patch cord managers.
Figure 39. Feeding Patch Cords through Front Cable Managers Refer to Figure 26
on Page 29 for a fully-patched Propel Fixed Panel example.
Page 41 © 2023 CommScope. All Rights Reserved.
TC-96342-IP
7 CONTACT INFORMATION · To find out more about CommScope® products, visit us
on the web at
www.commscope.com · For technical assistance, customer service, or to report
any missing/damaged parts, visit
us at http://www.commscope.com/SupportCenter
Page 42 © 2023 CommScope. All Rights Reserved.
References
- CommScope | now meets next
- CommScope | now meets next
- CommScope | now meets next
- Support options from CommScope
- Product Patent
- Support Center | CommScope
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>