Xpelair DX100 100mm Simply Silent Extractor Fan Instruction Manual
- June 13, 2024
- Xpelair
Table of Contents
- DX100 100mm Simply Silent Extractor Fan
- Xpelair Simply Silent™
- Installation
- I calling mounting the fan, you will also need:
- If window mounting the fan, you will also need:
- Installing the isolating switch and cables.
- For Australia Only -DX100TR / DX100TS
- Preparing the Fan for installation.
- Mark the position of the back-plate
- Mount the back-plate.
- Fan Settings
- Using the fan
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DX100 100mm Simply Silent Extractor Fan
Xpelair Simply Silent™
DX100
Installation and Maintenance Instructions
DX100R (93005AW)
DX100S (93025AW)
DX100TR (93006AW)
DX100TS (93026AW)
DX100PR (93007AW)
DX100PS (93027AW)
DX100HTR (93008AW)
DX100HTS (93028AW)
DX100HPTR (93009AW)
DX100HPTS (93029AW)
DX100PIRR (93010AW)
DX100PIRS (93030AW)
This appliance is intended for
connection to fixed wiring. Check
that the electrical rating shown on
each fan matches the mains Supply.
THE APPLIANCE IS DOUBLE INSULATED
AND DOES NOT REQUIRE AN EARTH
CONNECTION. Al installations must be Supervised
by qualified electrician. Installations and wing
must conform to current IEE Regulations (UK), local
or appropriate regulations (other Countries).
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and maintenance of the appliance shall not be made by children.
All Xpelair Simply Silent™ DX100 AC fans have the following features:
+ Two speed extraction
(Selectable at installation)
DX100R/DX100S – Operate the fan using an
on/off switch (not supplied).
DX100TR/DX100TS” – Buti timer operates fan
fora preset delay rom 30 Seconds to 30 minutes.
DX100PR/DX100PS – Operate the fan using an
integral pull-cord.
DX1SOHTS/DXISOHTR – Operates when triggered
automatically by the integral humidity sensor, or by:
using an external on/off Switch (not supplied).
In automatic mode: the bultin mer automatically
operates the fan for a pre-set delay time from 30
seconds to 30 minutes once humidity drops below
the pre-set Relative Humidity (RH) value.
External operation: When switched off using the
external on/off switch the fan Continues to run for
the preset delay from 30 seconds to 30 minutes.
DX100HPTR/DX100HPTS” – Operates when
triggered automatically by the integral humidity
sensor, by using an external logoff Switch (not
supplied), or by using th integral pull cord Switch.
In automatic made: The but in timer automatically
operates the fan for the pre-set delay time from 30
Seconds t0 30 minutes once humidity crops below
the pre-set Relative Humidity (RH) value.
External operation: When switched off using
either the external ono switch or the integral
pull cord switch the fan continues to run for the.
pre-set delay from 30 seconds to 30 minutes.
DX100PIRR/DX100PIRS” – An integral body
movement sensor operates the fan as long
a5 movement is detected. The buit-n timer
automatically Operates the fan for a pre-set delay of
1020 minutes.
- Factory settings: Timer 15 minutes, RH 75%
Where to locate the fan.
-
Locate it as high as possible.
-
At least 110mm from the edges of
the mounting surface to the centre of the hole. -
As far away as possible from and opposite to
the main source of air replacement to ensure
airflow across the room (eg. opposite the -
If installed in a kitchen
fans must not be mounted
immediately above a cooker
hob, or eye level grill. -
Installing in a room containing a fuel burning
device which has a non-balanced flue, itis the
Installers responsibility to ensure that there
Is enough replacement air to prevent fumes.
being drawn down the flue when the fan is
‘operating up to maximum extract. Refer to
Building Regulations for specific requirements. -
Exhaust air must not be discharged into
a flue used for exhausting of fumes from
appliances supplied with energy other than
electric. Requirements of all authorities
concerned must be observed for exhaust air
discharge and intake flow rates. -
Not suitable for use in possible chemical
corrosive atmospheres.
Installation
What the installer will need.
- 3mm electrician’s screwdriver and No.1 or 2 Pozidrive Screwdrivers.
If wall mounting the fan, you will also need:
- A 100mm diameter prepared hole.
- An appropriate external Wall Grille and
100mm wall sleeve duct (supplied). Cut
ducting to correct length f required. The
wall tube supplied is telescopic and can be
extended to 300mm maximum.
I calling mounting the fan, you will also need:
-
A 100mm diameter prepared hole.
-
A 100mm diameter prepared hole for the.
external grille, ideally positioned to allow
condensation to run away from the first bend
in the duct towards the external grille. -
Appropriate ancillaries for termination. These
items are available from Xpelair:
-
3m fiexible ducting Ref: 89663AA. If the
duct passes through a cold space use
insulated duct ref. B9B47AA. -
Sofft Grille Ref: 89742AW
If window mounting the fan, you will also need:
- SSWIN – Simply Sent Window Kit
Ref: 9200688
Installing the isolating switch and cables.
means for disconnection in al pokes
must be incorporated in the fixed wiring
in accordance with wiring regulations
-
If metal switch boxes are used, earthing
regulations must be followed. -
The cross-sectional area of the Supply cord
used should be ranged from 1-1.5me. -
DX100R/ DX100S / DX100PR / DX100PS /
DX100PIRR / DX100PIRS – 2 core, -
DX100TR / DX100TS / DX100HTR” /
DX100HTR” / DX{00HPTR” / DX100HPTS” —
3 core. * If wiring to remote switch.
-
Check that the electrical rating shown inside
he back-plate matches your mains supply. -
heck there are no buried pipes or Cables
e.g electricity, gas, water behind the switch
location n the wall or above the ceiling). If in
doubt, seek professional advice. -
Isolate the mains Supply.
-
Lay in the cable rom the isolating switch
10 the fan location via the on/off switch (If required) -
Lay in the cable from the isolating switch to
the point of connection {0 the mains supply.
Warning: Do not make any connections to the electrical supply at this stage.
6. Install the isolating switch and on/off switch (if required).
7. Make all connections within the isolating
switch and the on/off switch (f required).
Wet Rooms: On/Off switch must
be situated so that it cannot be
touched by persons making use of
the bath or shower.
For Australia Only – DX100R / DX100S
7 DX100PR / DX100PS / DX100PIRR /
DX100PIRS Connection to the supply can be
made by a flexible 2-core cable complete with
3 pin plug for insertion into an approved 10A
GPO or directly wired through an approved 10A
wall mounted surface switch with at least 3mm
clearance between contacts.
For Australia Only -DX100TR / DX100TS
7 DX100HTR / DX100HTS / DX100HPTR /
DX100HPTS
These models are permanently
connected to the supply and operation is
controlled by a remote switch. They should
be directly wired to the supply through an
approved 10A wall mounted surface switch
with at least 3mm clearance between contacts.
Preparing the Fan for installation.
1. Remove the front cover by depressing the
latch on the underside of the cover and
pulling off the front cover from the bottom
(See Figure C).If working above ground floor
level, safety precautions must be
observed.
Mark the position of the back-plate
2. Hold the back-plate so that the level line
marked on it is orientated horizontally.
3. Carefully insert the fan tube into the wall duct.
4. Mark on the wall the positions of the fixing
holes in the back-plate.
5. Remove the back plate from the ducting.
6. Drill screw holes in these positions if necessary,
and fit wall plugs and screws as required.
If installing in a ceiling, appropriate
termination ancillaries are required.
& Follow instructions provided.
Mount the back-plate.
7. Push the ribbed gasket onto the duct
section of the back plate (see Figure D).
8. Push the larger diameter piece of the telescopic
wall tube onto the ribbed gasket. Cut the tube:
to the required size first if necessary.
9. Feed the mains cable through the cable
entry hole in the back plate to the terminals.
10. Insert the fan tube into the wall duct/ceiling
as before.
11. Fasten the back-plate to the wall/ceiling
using appropriate fasteners supplied. See
figure A.
12.If using screws, do not over tighten.
Mount the back draft shutter
13.Peel the backing from the foam strip
supplied and attach it around the outside lip
on the backdraft shutter.
14. Go outside. Holding open the top and bottom
vanes insert the lip into the wall duct.
15. Making sure that the back draft shutter is.
level, mark the positions of the two fixing
holes in the top right hand and bottom left
hand corners.
16. Remove the back draft shutters from the wall duct.
17. Drill screw holes in marked positions and fit
the remaining wall plugs.
18. Holding open the top and bottom vanes,
refit the back draft shutter and fasten
it to the wall using the screws. Do not
overtighten screws.
19. Make sure that the vanes open and shut fully.
Wire the electrical connections.
20. Make sure the mains supply is isolated.
Switch off the mains electrical supply and
remove fuses.
21. Feed the cable to the terminal block. Wire
the fan as shown in Figure H using the
diagram appropriate to the fan model.
22. Connect the cable from the isolating switch
to the electrical supply wiring.
Fan Settings
SPEED SETTING
The fans are factory set to low speed, but have
two speed settings for different applications.
Select either high or low speed by connecting
the jumper between the centre and high or low
speed pin on the jumper (see Figure G).
DX100TR / DX100TS / DX100PIRR / DX100PIRS only.
- To adjust the over-run period tun the control
(T) clockwise to increase and anti-clockwise
to decrease – see Figure F.
DX100HTR / DX100HTS / DX100HPTR / DX100HPTS only – see figures F and G.
-
The pre-set humidity operation is factory set
at approximately 75% Relative Humidity (RH),
but can be adjusted between 65% and 85%
RH by control H. -
The over-run timer is factory set at 15 minutes.
but can be adjusted from 30 seconds to 30
minutes by control T. -
Tum the controls clockwise to increase RH or
time and anti-clockwise to decrease.
Using the fan
DX100R / DX100S Only
- Operate the fan using the on/off switch (not
supplied). Repeat to switch off.
DX100TR/ DX100TS Only
- Operate the fan using an on/off switch (not
supplied). Note ~ the fan may take up to 10
seconds to tum on once the switch has been
operated. When the switch is turned off,
the fan continues to operate for the set time
delay. To adjust the over-run period, turn the
control “T” clockwise to increase and anti-
clockwise to decrease — see Figure F.
DX100PR / DX100PS Only
- Operate the fan by pulling and releasing the
cord. Repeat to switch off.
DX100HTR / DX100HTS Only.
-
Automatic mode – The fan automatically
adjusts to slow changes in natural humidity
levels without operating the fan. If the
humidity levels increase at a rate slower
than 5% RH in 5 minutes, up to the pre-set
humidity level, the fan will not be triggered
by humidity. This is to prevent nuisance
triggering of the fan. If humidity levels
increase quicker than 5% RH in 5 minutes
the fan will operate. When relative humidity
drops the fan continues to operate for the.
adjustable time delay. -
External operation – Use the external on/off
Switch. When the fan is switched off, the fan
continues to operate for the adjustable time
delay then goes into automatic mode.
DX100HPTR / DX100HPTS Only.
-
Automatic mode – The fan automatically
adjusts {0 Siow changes in natural humidity
levels without operating the fan. the humidity
levels increase at a rate Slower than 5% RH
in 5 minutes, up to the pre-set humidity level,
the fan will not be triggered by humidity. This
is to prevent nuisance triggering of the fan. ff
humidity levels increase quicker than 5% RH
in 5 minutes the fan will operate. When relative.
humidity drops the fan continues to operate for
the adjustable time delay. -
External operation – Use the external on/off
switch. When the fan is switched off, the fan
continues to operate for the adjustable time
delay then goes into automatic mode. -
Pull Cord operation ~ Use the integral pull
cord switch. When the fan is switched of, the:
fan continues to operate for the adjustable:
time delay then goes into automatic mode.
DX100PIRR / DX100PIRS Only.
- The sensor detects movement in the room
‘and activates the fan. When movement is
‘sensed, the fan will run or a pre-set over run
period and any further movement sensed
will re-start the sequence. This ensures.
that the room is only ventilated during and
immediately after use. When the fan it fast
installed it will un for the time set by the
‘overrun timer. After this time, f no movement
is sensed the fan will go into stand-by mode.
All Fans
Rei he front cover by hooking in the top first,
and then Swing the Cover down to Clip into place.
Cleaning (Recommended on mar)
-
Before cleaning, isolate the fan completely
from the mains Supply. -
Remove the front cover by depressing the
latch on the underside of the cover and
puling off the front cover from the bottom. -
To clean the front cover, either wipe it with
a damp, lint free cloth or wash it with warm
soapy water. Thoroughly dry the front cover
and ref, -
Do not immerse the fan in water or other
liquids to clean any other parts of the fan. -
Do not use strong detergents, solvents or
chemical cleaners -
Allow fan to dry thoroughly before use.
-
Apart from cleaning, no other maintenance is
required.
Disposal
This product should not be disposed
of with household waste.
Please recycle where facilities exist.
Check with your local authority for
recycling advice.
Guarantee
UK only
We, Glen Dimplex Heating & Ventilation provide a
guarantee against faulty parts and manufacture
for a period of 2 years from the date of
purchase. In the unlikely event of a product
breakdown during the guarantee period the
product should be returned to the place of
purchase or to Glen Dimplex Heating & Ventilation.
Exclusions
-
This guarantee does not cover compensation
for the loss of the product or consequential loss of any kind. -
Damage or defects to the product arising
from incorrect installation or lack of
maintenance. -
Transportation costs.
This guarantee does not affect your statutory rights
Technical advice and service
Customers outside UK –
see international below.
United Kingdom
Xpolair have a comprehensive range of services including:
-
Free technical advice help-desk from
Engineers on all aspects of ventilation -
Free design service, quotations and site
surveys. -
Service and maintenance contracts to suit all
requirements.
Glen Dimplex UK Ltd,
Millbrook House, Grange Drive, Hedge End,
Southampton, S030 20F
customer services @glendimplex com
+44 (0) 344.879.3583
Ireland
Glen Dimplex Europe Limited,
Airport Road, Cloghran,
Co. Dublin, K&7 VEOS
seviceireland@glendimplex.com
+353 (0)1 8523400
International.
-
Guarantee: Contact your local distributor or
Xpelair direct for detail. -
Technical Advice and Service: Contact your
local Xpelai distributor.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>