Xpelair DX100 100mm Simply Silent Extractor Fan Instruction Manual

June 13, 2024
Xpelair

DX100 100mm Simply Silent Extractor Fan

Xpelair Simply Silent™

DX100

Installation and Maintenance Instructions

DX100R (93005AW)
DX100S (93025AW)
DX100TR (93006AW)
DX100TS (93026AW)
DX100PR (93007AW)
DX100PS (93027AW)
DX100HTR (93008AW)
DX100HTS (93028AW)

DX100HPTR (93009AW)
DX100HPTS (93029AW)
DX100PIRR (93010AW)
DX100PIRS (93030AW)

This appliance is intended for

connection to fixed wiring. Check

that the electrical rating shown on

each fan matches the mains Supply.

THE APPLIANCE IS DOUBLE INSULATED
AND DOES NOT REQUIRE AN EARTH
CONNECTION. Al installations must be Supervised
by qualified electrician. Installations and wing
must conform to current IEE Regulations (UK), local
or appropriate regulations (other Countries).

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and maintenance of the appliance shall not be made by children.

All Xpelair Simply Silent™ DX100 AC fans have the following features:
+ Two speed extraction
(Selectable at installation)

DX100R/DX100S – Operate the fan using an
on/off switch (not supplied).
DX100TR/DX100TS” – Buti timer operates fan
fora preset delay rom 30 Seconds to 30 minutes.
DX100PR/DX100PS – Operate the fan using an
integral pull-cord.
DX1SOHTS/DXISOHTR – Operates when triggered
automatically by the integral humidity sensor, or by:
using an external on/off Switch (not supplied).

In automatic mode: the bultin mer automatically
operates the fan for a pre-set delay time from 30
seconds to 30 minutes once humidity drops below
the pre-set Relative Humidity (RH) value.

External operation: When switched off using the
external on/off switch the fan Continues to run for
the preset delay from 30 seconds to 30 minutes.
DX100HPTR/DX100HPTS” – Operates when
triggered automatically by the integral humidity
sensor, by using an external logoff Switch (not
supplied), or by using th integral pull cord Switch.
In automatic made: The but in timer automatically
operates the fan for the pre-set delay time from 30
Seconds t0 30 minutes once humidity crops below
the pre-set Relative Humidity (RH) value.
External operation: When switched off using
either the external ono switch or the integral
pull cord switch the fan continues to run for the.
pre-set delay from 30 seconds to 30 minutes.
DX100PIRR/DX100PIRS” – An integral body
movement sensor operates the fan as long
a5 movement is detected. The buit-n timer
automatically Operates the fan for a pre-set delay of
1020 minutes.

  • Factory settings: Timer 15 minutes, RH 75%

Where to locate the fan.

  • Locate it as high as possible.

  • At least 110mm from the edges of
    the mounting surface to the centre of the hole.

  • As far away as possible from and opposite to
    the main source of air replacement to ensure
    airflow across the room (eg. opposite the

  • If installed in a kitchen
    fans must not be mounted
    immediately above a cooker
    hob, or eye level grill.

  • Installing in a room containing a fuel burning
    device which has a non-balanced flue, itis the
    Installers responsibility to ensure that there
    Is enough replacement air to prevent fumes.
    being drawn down the flue when the fan is
    ‘operating up to maximum extract. Refer to
    Building Regulations for specific requirements.

  • Exhaust air must not be discharged into
    a flue used for exhausting of fumes from
    appliances supplied with energy other than
    electric. Requirements of all authorities
    concerned must be observed for exhaust air
    discharge and intake flow rates.

  • Not suitable for use in possible chemical
    corrosive atmospheres.

Installation

What the installer will need.

  • 3mm electrician’s screwdriver and No.1 or 2 Pozidrive Screwdrivers.

wiring parts

wiring setting

If wall mounting the fan, you will also need:

  • A 100mm diameter prepared hole.
  • An appropriate external Wall Grille and
    100mm wall sleeve duct (supplied). Cut
    ducting to correct length f required. The
    wall tube supplied is telescopic and can be
    extended to 300mm maximum.

I calling mounting the fan, you will also need:

  • A 100mm diameter prepared hole.

  • A 100mm diameter prepared hole for the.
    external grille, ideally positioned to allow
    condensation to run away from the first bend
    in the duct towards the external grille.

  • Appropriate ancillaries for termination. These
    items are available from Xpelair:

  1. 3m fiexible ducting Ref: 89663AA. If the
    duct passes through a cold space use
    insulated duct ref. B9B47AA.

  2. Sofft Grille Ref: 89742AW

If window mounting the fan, you will also need:

  • SSWIN – Simply Sent Window Kit
    Ref: 9200688

Installing the isolating switch and cables.

means for disconnection in al pokes
must be incorporated in the fixed wiring
in accordance with wiring regulations

  • If metal switch boxes are used, earthing
    regulations must be followed.

  • The cross-sectional area of the Supply cord
    used should be ranged from 1-1.5me.

  • DX100R/ DX100S / DX100PR / DX100PS /
    DX100PIRR / DX100PIRS – 2 core,

  • DX100TR / DX100TS / DX100HTR” /
    DX100HTR” / DX{00HPTR” / DX100HPTS” —
    3 core. * If wiring to remote switch.

  1. Check that the electrical rating shown inside
    he back-plate matches your mains supply.

  2. heck there are no buried pipes or Cables
    e.g electricity, gas, water behind the switch
    location n the wall or above the ceiling). If in
    doubt, seek professional advice.

  3. Isolate the mains Supply.

  4. Lay in the cable rom the isolating switch
    10 the fan location via the on/off switch (If required)

  5. Lay in the cable from the isolating switch to
    the point of connection {0 the mains supply.

Warning: Do not make any connections to the electrical supply at this stage.

6. Install the isolating switch and on/off switch (if required).

7. Make all connections within the isolating
switch and the on/off switch (f required).

Wet Rooms: On/Off switch must
be situated so that it cannot be
touched by persons making use of
the bath or shower.

For Australia Only – DX100R / DX100S
7 DX100PR / DX100PS / DX100PIRR /
DX100PIRS Connection to the supply can be
made by a flexible 2-core cable complete with
3 pin plug for insertion into an approved 10A
GPO or directly wired through an approved 10A
wall mounted surface switch with at least 3mm
clearance between contacts.

For Australia Only -DX100TR / DX100TS

7 DX100HTR / DX100HTS / DX100HPTR /
DX100HPTS

These models are permanently
connected to the supply and operation is
controlled by a remote switch. They should
be directly wired to the supply through an
approved 10A wall mounted surface switch
with at least 3mm clearance between contacts.

Preparing the Fan for installation.

1. Remove the front cover by depressing the
latch on the underside of the cover and
pulling off the front cover from the bottom
(See Figure C).If working above ground floor
level, safety precautions must be
observed.

Mark the position of the back-plate

2. Hold the back-plate so that the level line
marked on it is orientated horizontally.

3. Carefully insert the fan tube into the wall duct.

4. Mark on the wall the positions of the fixing
holes in the back-plate.

5. Remove the back plate from the ducting.

6. Drill screw holes in these positions if necessary,
and fit wall plugs and screws as required.

If installing in a ceiling, appropriate
termination ancillaries are required.
& Follow instructions provided.

Mount the back-plate.

7. Push the ribbed gasket onto the duct
section of the back plate (see Figure D).

8. Push the larger diameter piece of the telescopic
wall tube onto the ribbed gasket. Cut the tube:
to the required size first if necessary.

9. Feed the mains cable through the cable
entry hole in the back plate to the terminals.

10. Insert the fan tube into the wall duct/ceiling
as before.
11. Fasten the back-plate to the wall/ceiling
using appropriate fasteners supplied. See
figure A.

12.If using screws, do not over tighten.
Mount the back draft shutter

13.Peel the backing from the foam strip
supplied and attach it around the outside lip
on the backdraft shutter.

14. Go outside. Holding open the top and bottom
vanes insert the lip into the wall duct.

15. Making sure that the back draft shutter is.
level, mark the positions of the two fixing
holes in the top right hand and bottom left
hand corners.

16. Remove the back draft shutters from the wall duct.

17. Drill screw holes in marked positions and fit
the remaining wall plugs.

18. Holding open the top and bottom vanes,
refit the back draft shutter and fasten
it to the wall using the screws. Do not
overtighten screws.

19. Make sure that the vanes open and shut fully.
Wire the electrical connections.

20. Make sure the mains supply is isolated.
Switch off the mains electrical supply and
remove fuses.

21. Feed the cable to the terminal block. Wire
the fan as shown in Figure H using the
diagram appropriate to the fan model.

22. Connect the cable from the isolating switch
to the electrical supply wiring.

Fan Settings

SPEED SETTING
The fans are factory set to low speed, but have
two speed settings for different applications.
Select either high or low speed by connecting
the jumper between the centre and high or low
speed pin on the jumper (see Figure G).

DX100TR / DX100TS / DX100PIRR / DX100PIRS only.

  • To adjust the over-run period tun the control
    (T) clockwise to increase and anti-clockwise
    to decrease – see Figure F.

DX100HTR / DX100HTS / DX100HPTR / DX100HPTS only – see figures F and G.

  • The pre-set humidity operation is factory set
    at approximately 75% Relative Humidity (RH),
    but can be adjusted between 65% and 85%
    RH by control H.

  • The over-run timer is factory set at 15 minutes.
    but can be adjusted from 30 seconds to 30
    minutes by control T.

  • Tum the controls clockwise to increase RH or
    time and anti-clockwise to decrease.

Using the fan

DX100R / DX100S Only

  • Operate the fan using the on/off switch (not
    supplied). Repeat to switch off.

DX100TR/ DX100TS Only

  • Operate the fan using an on/off switch (not
    supplied). Note ~ the fan may take up to 10
    seconds to tum on once the switch has been
    operated. When the switch is turned off,
    the fan continues to operate for the set time
    delay. To adjust the over-run period, turn the
    control “T” clockwise to increase and anti-
    clockwise to decrease — see Figure F.

DX100PR / DX100PS Only

  • Operate the fan by pulling and releasing the
    cord. Repeat to switch off.

DX100HTR / DX100HTS Only.

  • Automatic mode – The fan automatically
    adjusts to slow changes in natural humidity
    levels without operating the fan. If the
    humidity levels increase at a rate slower
    than 5% RH in 5 minutes, up to the pre-set
    humidity level, the fan will not be triggered
    by humidity. This is to prevent nuisance
    triggering of the fan. If humidity levels
    increase quicker than 5% RH in 5 minutes
    the fan will operate. When relative humidity
    drops the fan continues to operate for the.
    adjustable time delay.

  • External operation – Use the external on/off
    Switch. When the fan is switched off, the fan
    continues to operate for the adjustable time
    delay then goes into automatic mode.

DX100HPTR / DX100HPTS Only.

  • Automatic mode – The fan automatically
    adjusts {0 Siow changes in natural humidity
    levels without operating the fan. the humidity
    levels increase at a rate Slower than 5% RH
    in 5 minutes, up to the pre-set humidity level,
    the fan will not be triggered by humidity. This
    is to prevent nuisance triggering of the fan. ff
    humidity levels increase quicker than 5% RH
    in 5 minutes the fan will operate. When relative.
    humidity drops the fan continues to operate for
    the adjustable time delay.

  • External operation – Use the external on/off
    switch. When the fan is switched off, the fan
    continues to operate for the adjustable time
    delay then goes into automatic mode.

  • Pull Cord operation ~ Use the integral pull
    cord switch. When the fan is switched of, the:
    fan continues to operate for the adjustable:
    time delay then goes into automatic mode.

DX100PIRR / DX100PIRS Only.

  • The sensor detects movement in the room
    ‘and activates the fan. When movement is
    ‘sensed, the fan will run or a pre-set over run
    period and any further movement sensed
    will re-start the sequence. This ensures.
    that the room is only ventilated during and
    immediately after use. When the fan it fast
    installed it will un for the time set by the
    ‘overrun timer. After this time, f no movement
    is sensed the fan will go into stand-by mode.

All Fans

Rei he front cover by hooking in the top first,
and then Swing the Cover down to Clip into place.

Cleaning (Recommended on mar)

  1. Before cleaning, isolate the fan completely
    from the mains Supply.

  2. Remove the front cover by depressing the
    latch on the underside of the cover and
    puling off the front cover from the bottom.

  3. To clean the front cover, either wipe it with
    a damp, lint free cloth or wash it with warm
    soapy water. Thoroughly dry the front cover
    and ref,

  4. Do not immerse the fan in water or other
    liquids to clean any other parts of the fan.

  5. Do not use strong detergents, solvents or
    chemical cleaners

  6. Allow fan to dry thoroughly before use.

  7. Apart from cleaning, no other maintenance is
    required.

Disposal

This product should not be disposed
of with household waste.

Please recycle where facilities exist.

Check with your local authority for
recycling advice.

Guarantee

UK only

We, Glen Dimplex Heating & Ventilation provide a
guarantee against faulty parts and manufacture
for a period of 2 years from the date of
purchase. In the unlikely event of a product
breakdown during the guarantee period the
product should be returned to the place of
purchase or to Glen Dimplex Heating & Ventilation.

Exclusions

  • This guarantee does not cover compensation
    for the loss of the product or consequential loss of any kind.

  • Damage or defects to the product arising
    from incorrect installation or lack of
    maintenance.

  • Transportation costs.

This guarantee does not affect your statutory rights

Technical advice and service

Customers outside UK –
see international below.

United Kingdom

Xpolair have a comprehensive range of services including:

  • Free technical advice help-desk from
    Engineers on all aspects of ventilation

  • Free design service, quotations and site
    surveys.

  • Service and maintenance contracts to suit all
    requirements.

Glen Dimplex UK Ltd,
Millbrook House, Grange Drive, Hedge End,
Southampton, S030 20F

customer services @glendimplex com

+44 (0) 344.879.3583

www.xpelair.co.uk

Ireland

Glen Dimplex Europe Limited,
Airport Road, Cloghran,

Co. Dublin, K&7 VEOS
[email protected]
+353 (0)1 8523400

International.

  • Guarantee: Contact your local distributor or
    Xpelair direct for detail.

  • Technical Advice and Service: Contact your
    local Xpelai distributor.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Xpelair User Manuals

Related Manuals