City650 Line Interactive UPS
User Manual
AcerAltos City650 UPS User Manual
Line-interactive UPS
IMPORTANT SAFETY INSTRUCTIONS
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all
instructions carefully during installation and operation of the unit. Read
this manual thoroughly before attempting to unpack, install, or operate your
UPS.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area free of conductive
contaminants. (See the specifications for the acceptable temperature and
humidity range.)
CAUTION! To reduce the risk of overheating the UPS, do not cover the UPS’
cooling vents and avoid exposing the unit to direct sunlight or installing the
unit near heat emitting appliances such as space heaters or furnaces.
CAUTION! Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
CAUTION! Do not plug the UPS input into its own output.
CAUTION! Do not allow liquids or any foreign object to enter the UPS. Do
not place beverages or any other liquid-containing vessels on or near the
unit.
CAUTION! In the event of an emergency, press the OFF button and
disconnect the power cord from the AC power supply to properly disable the
UPS.
CAUTION! Do not attach a power strip or surge suppressor to the UPS.
CAUTION! Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
CAUTION! Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required precautions. Keep
unauthorized personnel away from batteries.
CAUTION! The battery supply should be therefore disconnected in the plus
and minus pole at the quick connectors of the battery when maintenance or
service work inside the UPS is necessary.
CAUTION! Internal battery voltage is 12Vdc. Sealed, lead-acid, 6-cell
battery.
CAUTION! When replacing the batteries, use the same number and type of
batteries.
CAUTION! Do not dispose of batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes.
INSTALLING YOUR UPS SYSTEM
UNPACKING
The box should contain the following: (1) UPS Unit x1; (2) USB Cable x 1
(Except City650); (3) User Manual 1; (4) Warranty Card 1
OVERVIEW
The UPS provides automatic voltage regulation for inconsistent utility power,
and provides battery backup during power outages, and ensures consistent power
to your computer system.
HARDWARE INSTALLATION GUIDE
- Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is recommended to ensure that the battery’s maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
- With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz drive, Tape drive), etc. into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the battery power supplied outlets. The power demands of these devices will overload and possibly damage the unit.
- Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc. Avoid using extension cords.
- Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will “beep”.
- If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker / fuse is normal and then turns the UPS on.
- To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
- To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure battery life.
BASIC OPERATION
Front panel
-
Power Switch
Press the switch for 2 seconds to turn the UPS ON or OFF.
Mute setting: The audible alarm can be turned OFF or ON by quickly pressing the power button twice. The default setting is for the Alarm On.
-
Line Mode LED The green LED will light when utility power is normal.
-
Battery Mode LED The yellow LED will light when input power is abnormal and the unit will work in battery mode.
-
Fault LED The red LED will light when fault or over load occurs.
Rear panel
-
USB COMM. Port
This port allows connection and communication from the USB port on the computer to the UPS unit. -
RJ45/11 Communication Protection Ports
Communication protection ports will protect any standard modem, fax, telephone line, or network cable
-
Input Circuit Breaker
The circuit breaker provides optimal overload protection. -
Input power cord
Connect to utility power. -
Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection.
They ensure power is provided to connected equipment over a period of time during a power failure.
TECHNICAL SPECIFICATIONS
Model | City650 | City850 | City1200 | City1500 | City2000 |
---|---|---|---|---|---|
Capacity(VA/W) | 650/360 | 850/480 | 1200/720 | 1500/900 | 2000/1200 |
1QT?113 | l40-300Vac |
Voltage Range
Nominal Frequency| 50/60Hz
Output|
On Battery Output Voltage| Simulated Sine Wave at 230Vac +/-10%
On Battery Output Frequency| 50/60Hz +/-1%
Overload Protection| Breaker / Fuse
Physical| | 148 X 178 X 298
Dimensions (W x H x D)(mm)| 96 x 138 x 286
Battery|
Sealed Maintenance Free Lead Acid Battery| I 2V xl| 12V x2
Typical Recharge Time| 8 Hours
Management I|
Auto-Charger| Yes
Auto-Restart| Yes
USB PORT| NA| Yes
Warning Diagnostics|
| | | | |
Indicators| Line Mode. Battery Mode. Fault
---|---
Audible Alarms| On Battery. Low Battery. Overload. Fault
Communication|
Power Master Software| Windowsill/ Windows8/ Windows // Windows Server 2012 RI
Windows
Server2008 R2.
Linux & Mac
Environmental r| W
Operating Temperature| OQC to 40’C
Operating Relative Humidity| 0 to 90%
DEFINITIONS FOR LED & ALARM
UPS Stator | LED Stags r | Ain |
---|---|---|
UPS is Nonnal | Green LED is always On | No Beep sound |
Battery Mode (No AC) | Yellow LED is blinking every 30 seconds | Beep sound |
every 30 seconds
Low Battery| Yellow LED is blinking every 2 seconds| Beep sound every 2
seconds
Overload| Red LED is blinking every 0.5 seconds| Beep sound every 0.5 seconds
UPS is shut down| All LEDs are Off| No Beep sound
UPS is malfunction| Red LED is always On| Constant Long Beep Sound
TROUBLE SHOOTING
Problem | Possible Cause | Sebes |
---|---|---|
The UPS does not perform expected runtime. | Batteries are not fully charged. |
Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out.| Contact Technical Support.
The UPS will not turn on.| The on/off switch is designed to prevent damage by
rapidly turning it off and on.| Turn the UPS off. Wait 10 seconds and then
turn the UPS on.
The unit is not connected to an AC outlet.| The unit must be connected to a
230Vac 50/60Hz outlet.
The battery is worn out.| Contact Technical Support.
Mechanical problem.| Contact Technical Support.
provide power to equipment| Outlets do not Circuit breaker is tripped due to
overload| Turn the UPS off and unplug at least one piece connected equipment.
Unplug the power breaker knob. of the UPS then press the circuit
Batteries are discharged| Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or spike.| Contact Technical Support.
SOFTWARE DOWNLOAD
Power Master Management software provides a user-friendly interface for your
power systems. The graphic user interface is intuitive and displays essential
power information at a glance. Please follow procedure below to install the
software.
Installation procedure:
- Download Power Master from the website: http://www.powermonitor.software/#PowerMasterSoftware
- Double-click the file and follow the installation steps.
When your computer restarts, the Power Master software will appear as a blue
icon located in the system tray.
In a continuing effort to improve
the quality of our products, information in this document is subject to change
without notice. Please refer Altos support website (www.altoscomputing.com)
for latest information. Responsible Party: Altos Computing Incorporated
Address: 6F, No.88, Section 1, Xintai 5th Road, New Taipei City 221, Taiwan
(R.O.C.)
© 2020. All rights reserved.
Altos, AcerAltos and the Altos logo are registered trademarks of Altos
Computing, Inc.
Other trademarks, registered trademarks and/or service marks, indicated or
otherwise the properties of their respective owners.
About Altos
Altos Computing Inc. (abbr. Altos) is established in 2017 and it is a
subsidiary of Acer Inc. The business model of Altos is to provide the best
streamlined and cost-effective integrated solutions thru in-house R&D working
with ODM/IHV/ISV on servers, workstations, thin client, network, storage and
UPS. In the era of demanding speed, Altos provides leading solution included,
but not limited to High Performance Computing, Virtual Desktop Infrastructure,
Cloud Infrastructure and Software Defined Storage, etc. Altos provides
solutions and services to government, academia, cloud service providers,
datacenter operators and enterprises.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>