DL II Adiabatic Humidification System Condair Instruction Manual

June 13, 2024
condair

DL II Adiabatic Humidification System Condair

DL-II-Adiabatic-Humidification-System-Condair

Product Information

  • Product Name: Adiabatic humidification system Condair DL II
  • Product Type: Humidification and Evaporative Cooling System
  • Model: Condair DL II
  • Manufacturer: Condair

Product Usage Instructions

First-time Commissioning:

  • Refer to the operation manual for detailed instructions on the first-time commissioning process.
  • Ensure that the installation date, commissioning date, site, model, and serial number are filled in.

Operation:

  • Refer to the operation manual for detailed instructions on operating the Condair DL II system.
  • Familiarize yourself with the display and operating elements of the system.
  • Take note of important operational considerations and safety precautions.
  • Learn how to perform remote operating and fault indication, as well as inspections during operation.
  • Understand the process of flushing the internal water system and washing over the ceramic plates.
  • Refer to the manual for instructions on system decommissioning.

Operating the Condair DL Control Software:

  • Refer to the operation manual for detailed instructions on operating the Condair DL control software.
  • Learn how to load and export error log files, start operating data recording, and view operating states.
  • Understand how to check the relays of the remote operating and fault indication board.
  • Explore various settings and features in the Features, Controls, and Network submenus.

Maintenance and Replacement of Components:

  • Take note of important maintenance considerations and hygiene guidelines according to VDI 6022.
  • Perform periodical checking and total system maintenance as recommended.
  • Follow instructions on cleaning and use of cleaning agents.
  • Learn how to remove and install components such as ceramic plates, spray nozzles, and nozzle support.

2603347-0 EN 2201

READ AND SAVE THESE INSTRUCTIONS

OPERATION MANUAL

Adiabatic humidification system Condair DL II
Humidification and Evaporative Cooling

Thank you for choosing Condair

Installation date (MM/DD/YYYY): Commissioning date (MM/DD/YYYY): Site: Model: Serial number: Fill in data at the commissioning!
Proprietary Notice This document and the information disclosed herein are proprietary data of Condair Group AG. Neither this document, nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorisation of Condair Group AG, except to the extent required for installation or maintenance of recipient’s equipment. Liability Notice Condair Group AG does not accept any liability due to incorrect installation or operation of the equipment or due to the use of parts/components/equipment that are not authorised by Condair Group AG. Copyright Notice © Condair Group AG, All rights reserved. Misapprehension and Technical modifications reserved.

Introduction

To the very beginning Notes on the operation manual
For your safety
Product Overview
Models overview Product designation / Which model do you have Basic design the humidification system Condair DL Functional description Hydraulic diagram System overview Condair DL Overview humidification unit Condair DL Overview control unit Condair DL Overview central unit Condair DL

Operation
First-time commissioning Display and operating elements Recommissioning after interruption of operation Notes on operation Important notes on operation Remote operating and fault indication Inspections during operation Flushing of the internal water system Wash over of the ceramic plates Decommissioning the system

Operating the Condair DL control software
Home screen Device and error status indication field Humidity control indication field Maintenance indication field Information functions in the “Help” Menu Acsessing the “Help” menu Query operating states in the “About” submenu Quick access to setting parameters in the “Quick Access” submenu Configuration Settings and features in the “General” submenu Accessing the “General” submenu Determine language and system of units in the “Region” submenu Date and time settings in the “Date & Time” submenu Read in parameter settings in the “Backup” submenu Activate/Deactivate password protection in the “Password Settings” submenu Set the brightness of the touchscreen and the LED in the “Brightness” submenu Settings and features in the “Maintenance” submenu Accessing the “Maintenance” submenu Reset functions in the “Reset” submenu Software update in the “Update” submenu View and export malfunctions and maintenance histories in the “Histories” submenu

5 5 5
7
9 9 9 10 11 13 14 15 16 17
18 18 19 20 21 21 21 21 22 23 24
25 25 26 27 27 28 28 29 30 31 31 31 31 32 32 33 33 34 34 34 35 35
Contents 3

5.3.2.5 Load and export the error log file in the “Error Analyzer” submenu

36

5.3.2.6 Start operating data recording in the “USB Data Logger” submenu

36

5.3.2.7 View operating states in the submenu “Diagnostics> Input Diagnostics”

37

5.3.2.8 Checking the relays of the remote operating and fault indication board in the

“RFI Diagnostics” submenu

38

5.3.3 Settings and features in the “Features”

38

5.3.3.1 Accessing the “Features” submenu

38

5.3.3.2 Set the power limitation in the “Operation” submenu

39

5.3.3.3 Set the flush timer in the “Flush Timer” submenu

39

5.3.3.4 Activate/deactivate the softstart function in the “Softstart” submenu

39

5.3.3.5 Activate/deactivate the ceramic wash over function in the “Ceramic Wash Over” submenu

40

5.3.4 Settings and features in the “Controls” submenu

41

5.3.4.1 Accessing the “Controls” submenu

41

5.3.4.2 Control settings in the “Signal Settings” submenu

42

5.3.5 Communication settings in the “Network” submenu

43

5.3.5.1 Accessing the “Network”submenu

43

5.3.5.2 Settings in the “IP Settings” submenu

44

5.3.5.3 Settings in the “IoT Settings” submenu

45

5.3.5.4 Settings in the “Modbus Settings” submenu

45

5.3.5.5 Settings in the “BACnet Settings” submenu

45

5.3.5.6 Settings in the “Remote Fault Indica …” submenu

46

6

Maintenance and Replacement of components

47

6.1

Important notes on maintenance

47

6.2

Hygiene and Maintenance according to VDI 6022 Page 1

48

6.2.1 Periodical checking

48

6.2.2 Total system maintenance

49

6.3

Notes on cleaning and cleaning agents

51

6.4

Removal and installation of components

52

6.4.1 Removal and installation of the ceramic plates

52

6.4.2 Removal and installation of the spray nozzles

54

6.4.3 Removal and installation of the nozzle support

55

6.5

Replacement of the silver cartridge “Hygiene Plus”

56

6.6

Replacement of the optional sterile filter and de-aeration of the filter housing

58

6.7

Resetting the maintenance counter

60

6.8

Performing a software update

61

7

Fault elimination

62

7.1

Important notes on fault elimination

62

7.2

Fault indication

63

7.3

Malfunction list

64

7.4

Malfunctions without indication

70

7.5

Saving fault and service histories to a USB stick

71

7.6

Resetting malfunction indication

72

7.7

Replacing the fuses and backup battery in the control unit

73

8

Taking out of service/Disposal

74

8.1

Taking out of service

74

8.2

Disposal/Recycling

74

9

Product specification

75

9.1

Technical data

75

9.2

Options

77

9.3

CE declaration of conformity

78

4 Contents

Introduction

To the very beginning
We thank you for having purchased the adiabatic air humidification system Condair DL. The humidification system Condair DL incorporates the latest technical advances and meets all recognized safety standards. Nevertheless, improper use of the humidification system Condair DL may result in danger to the user or third parties and/or impairment of material assets. To ensure a safe, proper, and economical operation of the humidification system Condair DL, please observe and comply with all information and safety instructions contained in the present documentation as well as in the separate documentations of the components installed in the humidification system. If you have questions after reading this documentation, please contact your Condair representative. They will be glad to assist you.
1.2 Notes on the operation manual
Limitation The subject of this operation manual is the humidification system Condair DL. The various options and accessories are only described insofar as this is necessary for proper operation of the equipment. Further information on options and accessories can be obtained in the respective instructions. This operation manual is restricted to the commissioning, operation, maintenance and troubleshooting of the humidification system Condair DL and is meant for well-trained personnel being sufficiently qualified for their respective work. This operation manual is supplemented by various separate items of documentation (operation manual, spare parts list, etc.), which are included in the delivery as well. Where necessary, appropriate crossreferences are made to these publications in the operation manual.
Introduction 5

Symbols used in this manual CAUTION!
The catchword “CAUTION” used in conjunction with the general caution symbol designates notes in this operation manual that, if neglected, may cause damage and/or malfunction of the unit or other material assets.
WARNING! The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this operation manual that, if neglected, may cause to injury to persons.
DANGER! The catchword “DANGER” used in conjunction with the general caution symbol designates safety and danger notes in this operation manual that, if neglected, may lead to severe injury or even death of persons.
Safekeeping Please safeguard this operation manual in a safe place, where they can be immediately accessed. If the equipment changes hands, the documentation must be passed on to the new operator. If the documentation gets mislaid, please contact your Condair representative. Language versions This operation manual is available in various languages. Please contact your Condair representative for information.
6 Introduction

For your safety
General Every person working with the humidification system Condair DL must have read and understood the installation manual and the operation manual of the Condair DL before carrying out any work. Knowing and understanding the contents of the installation manual and the operation manual is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly. All ideograms, signs and markings applied to the components of the humidification system Condair DL must be observed and kept in readable state.
Qualification of personnel All work described in this operation manual may only be carried out by specialist who are well-trained and adequately qualified and are authorized by the customer. For safety and warranty reasons any action beyond the scope of this manual must be carried out only by qualified personnel authorised by the manufacturer. It is assumed that all persons working with the humidification system Condair DL are familiar and comply with the appropriate regulations on work safety and the prevention of accidents. The humidification system Condair DL may not be used by persons (including children) with reduced physical, sensory or mental abilities or persons with lacking experience and/or knowledge, unless they are supervised by a person responsible for their safety or they received instructions on how to operate the system. Children must be supervised to make sure that they do not play with the humidification system Condair DL.
Intended use The humidification system Condair DL is intended exclusively for air humidification in AHU’s or air ducts within the specified operating conditions (see Section 9.1). Any other type of application, without the written consent of the manufacturer, is considered as not conforming with the intended purpose and may lead to the humidification system Condair DL becoming dangerous. Operation of the equipment in the intended manner requires that all the information contained in this operation manual are observed (in particular the safety instructions).
For your safety 7

Danger that may arise from the humidification system Condair DL DANGER! Risk of electric shock!
The control unit of the Condair DL and the pump motor inside the central unit (if applicable) are mains powered. Live parts may be exposed when the control unit and/or the central unit is/are open. Touching live parts may cause severe injury or danger to life. Prevention: Before carrying out any work on the components of the Condair DL take the system out of operation as described in Section 4.5 and secure the system against inadvertent power-up. Important: The frequency converter in the control unit of systems with booster pump contains capacitors. These can remain charged with a potentially deadly voltage for a certain period of time after the control unit has been disconnected from the power supply. Therefore, wait at least 10 minutes after disconnecting the power supply. Then make sure the appropriate contacts on the frequency converter and the terminals on the pump motor are free of voltage before starting any work on these components!
DANGER! Health risk because of inadequate hygiene! Inadequately operated and/or poorly maintained adiabatic humidification systems may endanger the health. When inadequately operated and/or poorly maintained micro-organisms (including the bacterium which causes Legionnaire’s disease) may grow in the water system and in the area of the humidification unit and may affect the air in the AHU/air duct. Prevention: The humidification system Condair DL must strictly be operated and maintained in accordance with this manual.
Behavior in case of danger If it is suspected that safe operation is no longer possible, then the humidification system Condair DL should immediately be shut down and secured against accidental power-up according to Section 4.5. This can be the case under the following circumstances: ­ if components of the humidification system Condair DL are not correctly positioned, locked or sealed ­ if the humidification system Condair DL is damaged ­ if the humidification system Condair DL is no longer operating correctly ­ if connections and/or piping are not sealed ­ if the electrical installations are damaged All persons working with the humidification system Condair DL must report any alterations to the system that may affect safety to the owner without delay.
Prohibited modifications to the unit No modifications must be undertaken on the humidification system Condair DL without the express written consent of the manufacturer. For the replacement of defective components use exclusively original accessories and spare parts available from your Condair representative.
8 For your safety

Product Overview

Models overview

The humidification system Condair DL is available in two base models (Type A: with booster pump, Type B: without booster pump) for different duct/AHU sizes.

Duct inside width “W” Duct inside height “H” Humidification capacity

[mm] [mm] [l/h]

** Larger systems on request

Condair DL .

Type A (with booster pump)

Type B (without booster pump)

450 … 8400 **

450 …4000 **

5 …1000 **

5 …1000 **

Both base models can be extended with different options in their functionality. Furthermore, there are different accessories available.

3.2 Product designation / Which model do you have
The product designation and the most important unit data are found on the rating plates fixed on the right side of the control unit and the central unit. Please refer to the Condair DL installation manual for detailed information regarding the type plate and the product key.

Product Overview 9

3.3 Basic design the humidification system Condair DL

1 2
3
U1
4 5

36

35

30

31

32

34

33

9 PS2

6 7 8
M1
10

29

29

18 19

17 20

PS4 12

Y1

Lf1

A3

Y4
21 22

11 15

23

23

Y3

24

13 14
PS5
16

Y10

Y9

Y8

Y7

Y6

Y5

(NO)

26

25

27

28

1 Control unit 2 Driver board 3 Control board with touch screen (Integrated Controller) 4 Frequency converter for booster pump (Type A) 5 Switch <Control unit On/Off> 6 Mains supply via electrical isolator 7 Voltage supply booster pump motor 8 Cable harnesses sensors and valves 9 Option sterile filter with pressure switch PS2 (Type A) or
without pressure switch PS2 (Type B) 10 Booster pump (Type A) 11 Inlet valve Y1 12 Pressure sensor inlet pressure PS4 13 Silver ionisation A3 14 Conductivity sensor Lf1 15 Air cleaning (option) 16 Pressure sensor nozzle pressure PS5 (on systems
Type B without optional sterile filter not present) 17 Central unit 18 Shut- off valve RO water supply (by others)

19 External water filter 5µm (recommended, option or by others) 20 External pipe flush (option) 21 Drain valve water supply pipe (by others) 22 Test valve, flame treatable (by others) 23 Funnel with trap (by others) 24 Shut-off valve pressured air supply (by others) 25 Valve manifold with spray nozzlesY5-Y9 and drain valveY10 26 Water jet pump (spray circuits drain) 27 Drain with trap (by others) 28 Drain pan or floor drain with trap (by others) 29 Duct/AHU drains with trap (by others) 30 Air filter min. ISO ePM1 60% (F7/EU7) (by others) 31 Spray nozzles 32 Post-evaporation elements (porous ceramics) 33 Humidity sensor (by others) 34 Temperature- and humidity sensor (by others) 35 External continuous controller (by others, e.g., Enthalpy
controller) 36 Air duct/AHU

Fig. 1: Basic design of the humidification system Condair DL

10 Product Overview

Functional description
From the reverse-osmosis system (RO system) the fully demineralized water (also called RO water or permeate) is fed via a shut-off valve (18, by others) and a external water filter 5 µm (19, recommended, option or by others) to the central unit (17). In the central unit the RO water is fed via the inlet valve Y1 (11), the conductivity sensor Lf1 (14), and the silver ionization (13) for disinfecting the water and the optional sterile filter (9) to the valve manifold (25) with the spray valves and the drain valve Y10. On systems type A the central unit is equipped with a booster pump (10) (controlled via the frequency converter) which increases the water pressure to the required operating pressure of approximately 7-7.5 bar (yield load) starting from a certain humidity demand. When a humidity demand is present the spray valves open depending on the demand: ­ one or two spray valves (with 2 spray circuits: Y5-Y6), ­ one, two or all three spray valves (with 3 spray circuits: Y5-Y7), ­ one, two or all four spray valves (with 3 spray circuits with double stage: Y5-Y7+Y9) or ­ one, two, three or all four spray valves (with 4 spray circuits: Y5-Y8) or ­ one, two, three or all five spray valves (with 4 spray circuits with double stage: Y5-Y8+Y9) or ­ one, two, three, four or all five spray valves (with 5 spray circuits: Y5-Y9). ­ one, two, three, four or all six spray valves (with 5 spray circuits with double stage: Y5-Y9 + Y9.1). The fully demineralized water is now fed to the respective spray nozzles (31) producing fine drops. The air passing by the nozzles absorbs the drop thus getting humidified. Drops not absorbed by the air is retained in the post- evaporation elements (32) thus humidifying the air passing through the postevaporation elements. Excess water flows down to the bottom of the post- evaporation unit and is led via the trap (29) and open funnel to the wastewater line of the building.
Control The system is controlled by an external controller (enthalpy controller recommended) or by the P/PI controller built into the control unit. On systems: ­ with 2 spray circuits a 3-step control is provided, ­ with 3 spray circuits (with or without double stage) a 7-step control is provided, ­ with 4 spray circuits (with or without double stage) a 15-step control is provided, ­ with 5 spray circuits (with or without double stage) a 31-step control is provided On systems type A the booster pump is switched on at a demand of approx. 60-70 % (switching point is dependent on the inlet pressure), and then the capacity is controlled continuously up to 100% via the pump speed.
Product Overview 11

Monitoring The inlet pressure and the nozzle pressure are monitored with the analogue pressure sensors “PS4” and “PS5”. On systems type B without booster pump and without optional sterile filter the nozzle pressure is equal to the inlet pressure, thus the pressure sensor “PS5” is not present. The pressure after the optional sterile filter is monitored with the pressure switch “PS2” on systems type A (with booster pump), and on systems type B (without booster pump) with the pressure sensor “PS5” since the pressure after the sterile filter is equal to the nozzle pressure. The conductivity of the fully demineralized water is continuously monitored. If the conductivity of the fully demineralized water exceeds the admissible range (max. 15 µS/cm), the drain valve Y10 on the valve manifold (25) opens and the water system is flushed until the conductivity meets the preset value. An error message is displayed or the system is stopped if the conductivity value does not reach the admissible range within a certain period (conductivity >100 µS/cm). Hygiene function/Flushing To prevent standing water, each spray circuit which is not active is emptied via the corresponding spray valve (the spray valves are connected to the drain in currentless status). After 1 hour without humidification, the flushing valve opens to empty the system. If the conductivity in the water supply line exceeds a preset value or if the humidification system has been without demand for more than 23 hours, the drain valve Y10 opens and the water supply line and the water lines in the central unit are flushed for a certain time with fresh RO water. During the flushing additionally residual water in the spray circuits is sucked out via the built-in water jet pump (26) and is led via the open funnel with trap (27) to the wastewater line of the building.
12 Product Overview

Hydraulic diagram

Option External pipe flush

Central unit

Ag Ionization

Conductivity

Inlet valve Y1

sensor Lf1

A3

Option sterile filter

PS4 Pressure sensor inlet pressure

PS2 Pressure switch

Option air cleaning
(compressed air 1-6 bar)

Pressure sensor
nozzle pressure PS5

Booster pump with frequency converter
(Type A)
M1

1

2

3

4

Y3 (NC)

1 Type A without optional sterile filter 2 Type A with optional sterile filter 3 Type B with optional sterile filter 4 Type B without optional sterile filter

Y8 and Y9 double stage

Y7 and Y9 double stage

Y9

Y8

Y7

Y6

Y5

Air duct
Flow restrictor Y10 (NO) (up to 210 kg/hr)

Valve manifold (spray valves Y5-Y9, drain valve Y10)
3 spray circuits: Y5, Y6 and Y7 (7-steps) 3 spray circuits double stage: Y5, Y6, Y7 and Y9 (7-steps) 4 spray circuits: Y5, Y6, Y7 and Y8 (15-steps) 4 spray circuits with double stage: Y5, Y6, Y7, Y8 and Y9 (15-steps)

Drain

Water jet pump

Fig. 2: Hydraulic diagram humidification system Condair DL (Figure shows 15 steps control)

Product Overview 13

3.6 System overview Condair DL

16
17
min. 3 m
1

2 15 14

3

4

5 6

7

8

13

12

10 11
9

1 Electrical isolator mains supply 2 Control unit 3 Central unit 4 Valve air cleaning (option) 5 Valve external pipe flush (option) – plug-in coupling
ø12 mm or 1/2″ male thread adapter (supplied) 6 Manometer (recommended, by others) 7 External water filter 5µm (recommended, option or by others) 8 Shut- off valve water supply (mandatory, by others) 9 Drain valve water supply line 10 Test valve, flame treatable (recommended, by others)
Fig. 3: System overview Condair DL

11 Open funnel with trap (by others) 12 Water drain connector – plug-in coupling ø10 mm
or 1/2″ male thread adapter (supplied) 13 Water supply connector – plug-in coupling ø12 mm
or 1/2″ male thread adapter (supplied) 14 Wall feed throughs spray circuits (ø8/10 mm) 15 Grid with nozzles 16 Post-evaporation unit 17 Humidity controller (e.g., enthalpy controller) or
humidity sensor (by others)

14 Product Overview

3.7 Overview humidification unit Condair DL

3

4

5
2 6
3
7 1

8

1 Support frame Nozzle unit 2 Spray nozzles 3 Lateral sealing plates 4 Upper sealing plates
Fig. 4: Overview Humidification unit Condair DL

5 Support frame post-evaporation unit 6 Ceramic plates 7 Rubber sealing duct floor 8 Wall feed throughs spray circuits

Product Overview 15

3.8 Overview control unit Condair DL
3 2

4 5 6
7 8 9 10

1 11 12
13 14

1 Frequency converter 2 Leak monitoring (option) 3 Remote operating and fault indication board 4 Driver board 5 Ag-Ionization board 6 Conductivity monitoring board 7 IoT Mobile Module (option) 8 BMS Gateway board (option LonWorks,
BTL certified BACnet IP or BACnet MS/TP)

9 Smartcard 10 Back-up battery (CR 2032, 3V) 11 RJ45 connector (ethernet interface) 12 USB connector 13 Terminals mains voltage supply 14 Snap ferrite mains voltage supply

Fig. 5: Overview control unit Condair DL (without internal cabling)

16 Product Overview

3.9 Overview central unit Condair DL

9

8

10

11

7 6 5 4 3
2 1
1 Water drain connector – plug-in coupling ø10 mm or 1/2″ male thread adapter (supplied)
2 Inlet valve 3 Water supply connector – plug-in coupling ø12 mm
or 1/2″ male thread adapter (supplied) 4 Connector spray circuit 1 (Y5) 5 Connector spray circuit 2 (Y6) 6 Connector spray circuit 3 (Y7+Y9) 7 Connector spray circuit 4 (Y8+Y9) 8 Silver ionisation cartridge 9 Booster pump (Type A only) 10 Sterile filter (option)
Fig. 6: Overview central unit Condair DL

12
13
14 15 16 17 18 19 20 21
11 Pressure switch PS2 (Type A with sterile filter only) 12 Check valve (Type A only) 13 Drain valve Y10 14 Pressure sensor PS5 15 Spray valve Y5 16 Spray valve Y6 17 Spray valve Y7 18 Spray valve Y8 19 Water jet pump 20 Pressure sensor PS4 21 Manometer inlet pressure

Product Overview 17

4 Operation
The humidification system Condair DL may be commissioned and operated only by persons familiar with the humidification system Condair DL and adequately qualified. It is the owner’s responsibility to verify proper qualification of the personnel.
4.1 First-time commissioning
The first-time commissioning must always be done by a service technician of your Condair representative or a well-trained and authorised person of the customer. Therefore, the current manual does not provide detailed information on this procedure. The following steps are carried out upon first-time commissioning in the specified order: · Inspecting the humidification unit, the control unit and the central unit for correct installation. · Inspecting the electrical installation · Inspecting the water installation · Flushing the water supply line and testing the water quality. · Checking direction of rotation of the booster pump and adjusting the speed of the booster pump. · Checking whether the spray circuits are connected to the corresponding nozzles and that all nozzles
are spraying correctly. · Configuring the control unit or the humidification system Condair DL, respectively. · Carrying out test runs. · Fill in the commissioning protocol.
18 Operation

4.2 Display and operating elements

Status LED ­ green: Condair DL is humidifying ­ green pulsing: No demand or humidification is
switched off ­ orange: Warning present or maintenance due ­ red: Error present
Touch screen

Humidifier

Electrical isolator Note: the electrical isolator is included in the delivery and must mandatory be installed in the mains supply line within 1 m to the control unit!

Fig. 7: Display and operating elements Condair DL

Switch <Control unit On/Off> (located on the right side of the control unit) Note: with this switch you can switch on and off the control unit. If the control unit is switched off all functions (including hygiene functions) of the humidification system Condair DL are deactivated (see DANGER note blow).

DANGER! Risk of electric shock!
There is still mains voltage inside the control unit even when you switch off the <Control unit On/ Off> switch. Therefore, the electrical isolator must be switched off before open the control unit.

Operation 19

4.3 Recommissioning after interruption of operation
The following description outlines the recommissioning procedure after an interruption of the operation (e.g., after servicing the system). It is assumed that first-time commissioning has been carried out properly by the service technician of your Condair representative. Proceed as follows to prepare the humidification system Condair DL for operation: 1. Examine the system components and installations for possible damage.
DANGER!
Damaged systems or systems with damaged components or installations may present danger to human life or cause severe damage to material assets. Damaged systems and/or systems with damaged or faulty installations must not be operated. 2. Make sure the ceramic plates are correctly located and properly sealed.
WARNING!
An unsealed post-evaporation unit may lead to severe damage of material assets. Put the system into operation only if the ceramic plates are correctly positioned and the post-evaporation unit correctly sealed. 3. Switch on the electrical isolator in the mains supply line (mains supply to control unit). 4. If closed, open shut-off valve in the water supply line. 5. Switch <Control unit On/Off> on the control unit to “On”, and activate control unit via the external enable switch if necessary. 6. If the humidification system Condair DL has been disconnected from the mains for more than 48 hours the message “Out of Commissioning” appears. If this is the case proceed as follows: · Switch off control unit via the <Control unit On/Off> switch. · Close shut-off valve in the water supply line. · Disconnect the water supply line from the connector on the central unit. · Lead the open end of the water supply line into open funnel of the waste water line of the build-
ing. · Open the shut-off valve in the water supply line and flush the supply line for at least 5 minutes.
Close shut-off valve in the water supply line again. Reconnect the water supply line to the connector on the central unit and open the shut-off valve. · Switch on control unit via the <Control unit On/Off> switch. Note: After switching on the control unit the “Out of Commissioning” message appears again. After 5 minutes, the Condair DL automatically flushes the water system and then goes into normal operating mode. The message is reset. 7. If the sterile filter has been replaced, deaerate the sterile filter as described in Section 6.6.
The humidification system Condair DL is now in normal operating mode and the home screen is shown in the display. Note: Further information on the operation of the Condair DL control software can be found in Section 5.
20 Operation

4.4 Notes on operation
4.4.1 Important notes on operation
­ For hygiene reasons the drain valve opens every 23 hours for aprrox. 300 seconds in standby mode in order to flush water supply line.
­ Humidification is activated if the humidification request is above approx. 14 % (with 3 spray circuits) or above approx. 7 % (with 4 spray circuits), respectively.

4.4.2 Remote operating and fault indication

Via the relays on the operating and fault indication board the following error and device status are indicated:

Activated remote indication relay “Error”
“Service”
“Running” “Unit on” “Furnace”

When?
An error is present, operation is stopped, or further operation is possible for a limited period of time only. One of the maintenance counters has elapsed. The corresponding maintenance must be performed. Demand present/humidification The humidification system is switched on and under voltage Not supported!

4.4.3 Inspections during operation
During operation the humidification system Condair DL must be inspected periodically. On this occasion check the following: · the water systems for any leak. · the components of the humidification system for correct installation and any damage. · the electric installation for any damage. · the display for whether a warning or error message is present.
If the inspection reveals any irregularities (e.g., leak, error indication) or any damaged components take the humidification system Condair DL out of operation as described in Section 4.5. Then, have the malfunction be corrected or the damaged component be replaced by a well-trained specialist or a service technician from your Condair representative.

Operation 21

4.4.4 Flushing of the internal water system

Note: if an error message is active flushing of the internal water system is not possible.

To perform a flushing of the internal water system, proceed as follows:

DL
1

Home

18:04 01.09.2021

18:04

DL

01.09.2021

2 Manual Functions

18:04

DL

01.09.2021

3 Manual Functions

Standby

Flushing

Flushing

Ceramic Wash Over
0%

Demand

1685 hr
Next Maintenance

Back

Continue

18:04

DL

01.09.2021

4

Flushing

In Progress

60 %

Cancel

1. Press on the button in the home screen (1).
2. The “Manual Functions” submenu (2) appears. Here, press on the button.
3. The flushing confirmation display appears. Here, press on the button to start the flushing of the water system. Note: A possible running humidification process is interrupted. If your system is equipped with the external pipe flush option, valve Y4 opens first, and the water supply line is flushed for a set period of time. Then, the inlet valve Y1 opens, and the internal water system of the central unit is flushed via the drain valve Y10 (normally open valve). If your system is equipped with the air cleaning option, finally valve Y3 opens and the spray circuits are blown out one after the other, assumed there is no humidity demand present and the safety loop and the external enable contact (if applicable) are closed.
4. The flushing progress display appears (4) and shows the current status of the flushing cycle. After flushing cycle has finished the home screen is shown again.
In order to stop the flushing cycle, press the button in the flushing progress window. The flushing cycle is stopped, and the home screen is shown again.

22 Operation

4.4.5 Wash over of the ceramic plates
The ceramic wash over function is only accessible if the ceramic wash over function has been activated in the control software (see Section 5.3.3.5).

CAUTION!

During the ceramic wash over the nozzles spray water onto the ceramic plates, similar to when 100% demand is present. In systems with a booster pump, this also switches on.
This process must be monitored by the operator since the humidity can significantly exceed the desired setpoint. Over-saturation of the ceramic plates is likely.
After the ceramic wash over is complete, any water behind the ceramic plates must be removed if it cannot drain from there.

Note: if an error message is active flushing of the ceramic plates is not possible.

To perform a flushing of the ceramic plates, proceed as follows:

DL
1

Home

18:04 01.09.2021

DL
2

18:04 01.09.2021
Manual Functions

18:04

DL

01.09.2021

3 Manual Functions

Standby

Flushing

Ceramic Wash Over

Ceramic Wash Over
0%

18:04

DL

01.09.2021

4 Ceramic Wash Over

In Progress

60 %

Demand
1685 hr
Next Maintenance

Back

Continue

Cancel

1. Press on the button in the home screen (1).
2. The “Manual Functions” submenu (2) appears. Here, press on the <Ceramic Wash Over> button.
3. The ceramic plate flushing confirmation display appears. Here, press on the button to start the flushing of the ceramic plate. Note: When the ceramic wash over is started, all spray valves open for the set spray time (see Section 5.3.3.5) and spray water onto the ceramic elements as with a 100% demand. In systems with a booster pump, the booster pump is also activated with the set pressure (see Section 5.3.3.5).
4. The flushing progress display appears (4) and shows the current status of the ceramic plate flushing cycle. After flushing cycle has finished the home screen is shown again.
In order to stop the ceramic plate flushing cycle, press the button in the flushing progress window. The flushing cycle is stopped, and the home screen is shown again.

Operation 23

4.5 Decommissioning the system
In order to take the humidification system Condair DL out of operation (e.g., to perform maintenance) perform the following steps: 1. Close the shut-off valve in the water supply line. 2. Switch off <Control unit On/Off> switch on the control unit, and if applicable deactivate control unit
via the external enable switch. 3. Disconnect then control unit from the mains supply: switch off electrical isolator in the mains
supply line and secure electrical isolator in the “Off” position against accidentally switching on. DANGER! Risk of electric shock!
The frequency converter in the control unit of systems with booster pump contains capacitors. These can remain charged with a potentially deadly voltage for a certain period of time after the control unit has been disconnected from the power supply. Therefore, wait at least 10 minutes after disconnecting the power supply. Then make sure the appropriate contacts on the frequency converter and the terminals on the pump motor are free of voltage before starting any work on these components! 4. Mind hygiene! Let the fan of the ventilation system run until the humidification unit is dry. 5. If work has to be carried out on the humidification unit switch off the AHU and secure the system against accidentally being switched on.
Important information on extended periods of non-use Important! For reasons of hygiene, we basically recommend that the control unit and the supplying reverse osmosis system should be left switched on. With the system switched on, the water circuit is flushed at regular intervals to eliminate standing water and reduce the risk of contamination in the supply lines. If the humidification system Condair DL is not be used for a longer period of time observe the following points: ­ Mind hygiene! Drain all water conduits.
Note: Regarding the emptying of the water supply line from the RO system please refer to the specifications of the manufacturer of the RO system. ­ Remove the sterile filter, drain the water in the filter housing, dry filter housing and install a new filter cartridge. ­ Drain the Ag ionisation cartridge. ­ For safety reasons the post-evaporation elements should remain in their working position, even if the humidifier is not used for an extended period. This prevents the water from being sprayed directly into the duct in case the humidifier is powered up inadvertently.
24 Operation

5 Operating the Condair DL control software

5.1 Home screen

After switching on the control unit and the automatic system test the control unit is in normal operating mode and the home screen is shown. Note: The appearance of the home screen depends on the current device and error status and the configuration of the humidity control of the system. It can deviate from the display shown below.

The home screen is structured as follows:

18:04

DL

01.09.2021

Home

Standby

Device and error status field (see Section 5.1.1)

0%
Demand
1685 hr
Next Maintenance

Humidity control indication field (see Section 5.1.2) Maintenance indication field (see Section 5.1.3)

Fig. 8: Home screen

button (accessing main menu) button (accessing Help) button (accessing list of active malfunctions) button> (accessing flushing functions) button (accessing home screen)

Operating the Condair DL control software 25

5.1.1 Device and error status indication field

If you press the device and error status field in the home screen, a window appears with further information on the device and error status.

DL

18:04

01.09.2021

DL

18:04 01.09.2021

­ Device Status: Shows the current device status.

Home
Standby
0%
Demand

Status
Device Status
Standby
Error Status
No Error
Max. Hum. Capacity
80 kg/hr

­ Error Status: Shows the current error status (“No Error”, “Warning” or “Error”).
­ Max. Hum. Capacity: Shows the maximum humidification output of the Condair DL in kg/hr.
­ Actual Hum. Capacity: Shows the current humidification output of the Condair DL in kg/hr.

1685 hr

Actual Hum. Capacity
0 kg/hr

Next Maintenance

Winterzeit

The following error status symbols may be shown:

Error status symbol

Description The Condair DL works perfectly.

A malfunction with the status “Warning” has occurred.

A malfunction with the status “Error” has occurred. Depending on the error, the operation of the Condair DL is stopped, or it continues to work to a limited extent.

The following device status indications may appear:

Device status Initializing Stopped
Flushing Standby
Humidifying Ready Air Pressure Cleaning Filling Conductivity Flush
Switched Off
Remote Off Temperature Flush
Ceramic Wash Over

Description
The control is initalising. The humidification system was stopped due to a malfunction that makes it impossible to continue operation. The water system is being flushed. No humidity demand for more than 60 minutes the humidification system is in standby mode. The water system is flushed automatically for 120 seconds before the next humidification takes place The humidification system is humidifying. The humidification system is flushed and ready to humidify immediately if a demand is present. The optional air cleaning is in progress. The humidification system is filling and deaerating after water shortage has occured. The conductivity of the supply water is beyond of the admissible range, the water system is flushed automatically for a certain period of time The humidification function is deactivated via the control software. The hygiene functions (regular flushing of the water system) remain still active. The humidification system was stopped via the external enable switch. The water temperature is too high or near the freezing point. The water system is flushed for a certain time. The optional ceramic wash over is carried out.

26 Operating the Condair DL control software

5.1.2 Humidity control indication field

If you press the humidity control indication field in the home screen, a window appears with further information on humidity control (control mode: “On / Off” or “Demand”) or the setpoint input (control mode: “RH P” or “RH PI), depending on the current control mode.

DL

18:04

01.09.2021

DL

18:04 01.09.2021

­ Source: Shows the source of the control signal

Home

Status

(“Analog”, “Modbus”, “BACnet” or “IoT”).

Standby
0%
Demand

Source
Analog
Control Mode
Demand
Signal Type Control
0-10V

­ Control Mode: Shows the current control mode (“On/Off”, “Demand”, “RH P” or “RH PI”).
­ Signal Type Control: Shows the control signal type used. Note: This setting only appears if the control mode is set to “Demand”.

1685 hr
Next Maintenance

Winterzeit

DL

18:04

01.09.2021

DL

18:04 01.09.2021

­ Setpoint: Setting of the desired humidity setpoint

Home

Setpoint

value in %rH.

Standby
0%
Humidity
1685 hr
Next Maintenance

41 %
Winterzeit

5.1.3 Maintenance indication field

If you press the Maintenance indication field in the home screen, a window appears with further information on maintenance.

18:04

DL

01.09.2021

Home

Standby
0%
Demand
1685 hr
Next Maintenance

18:04

DL

01.09.2021

Service

Next Maintenance
1685 hr

Next Disinfection
50 d

Remain. Ag-Ion Capacity
0.5 Ah

Operating Hours
315 hr

Winterzeit

­ Next Maintenance: Shows the remaining time in hours until the next system maintenance is due.
­ Next Disinfection: Shows the remaining time in days until the next disinfection is due. Note: Only appears if the setting “Disinfections Timer” has been activated in the engineering level of the control software.
­ Remain. Ag-Ion Capacity: Shows the remaining capacity of the silver cartridge in Ah until the next replacement is due.
­ Operating Hours: Shows the number of operating hours since initial commissioning.

Operating the Condair DL control software 27

5.2 Information functions in the “Help” Menu

5.2.1 Acsessing the “Help” menu

Press the button in the home screen. The help menu with the contact details appears.

18:04

DL

01.09.2021

DL

Home

Help

18:04 01.09.2021

Standby
0%
Demand

About
Quick Access
Contact Data Condair Group AG

1685 hr
Next Maintenance

info@condair.com www.condairgroup.com

28 Operating the Condair DL control software

5.2.2

Query operating states in the “About” submenu

18:04

DL

01.09.2021

About

Humidifier Model
DL

DL Type
Humidifier + FC

Software Version

Serial Number
1111111
Water Conductivity
0 µS
Water Conductivity
5 uS/cm
Water Temperature
10.0 °C
Remain. Ag-Ion Capacity
0.5 Ah
Ag-Ion Current
0.2 mA
Traget Ag-Ion Current
0.2 mA
Max. Hum. Capacity
155 kg/hr
Actual Hum. Capacity
7 kg/hr
PS2 Pressure Switch
On
PS4 Inlet Pressure
4.0 bar
PS5 Nozzle Pressure
4.0 bar
Y1 Inlet Valve
Open
Y2 Reserve
Closed
Y3 Air Cleaning
Closed
Y4 Ext. Pipe Flush
Closed
Y5 Spray Valve
Closed
Y6 Spray Valve
Closed
Y7 Spray Valve
Open
Continued on next page

­ Humidifier Model: Name of the humidifier model.
­ DL Type: Device type (“Humidifier”= Humidifier without booster pump, “Humidifier + FC”= Humidifier with booster pump, “Humidifier + FC – Off” (Humidifier with deactivated booster pump or frequency converter, respectively)).
­ Software Version: Actual software versions of the control board (“Device FW Version”, “FrameWork FW Version” and “Bootloader FW Version”) and driver boards (“Driver Board”, “Condu. Board”, “Ag-Ion Board” and “RFI Board”).
­ Serial Number: Serial number of the humidification system.
­ Water Conductivity: Actual conductivity of the supply water in µS/cm. Note: During the periodical system flushings or if the system is empty the conductivity is displayed temporarily with 0 µS/cm. Always wait, until the system is humidifying, before you read the conductivity value!
­ Water Temperature: Actual temperature of the supply water in °C. Note: this info field appears only if the “Water Temperature Monitoring” option is installed and activated in the engineering level of the control software.
­ Remain. Ag-Ion Capacity: Remaining capacity of the silver cartridge in Ah.
­ Ag-Ion Current: Actual current of the silver ionization in mA.
­ Target Ag-Ion Current: Calculated nominal current for silver ionization in mA.
­ Max. Capacity: Maximum humidification capacity in kg/hr.
­ Actual Hum. Capacity: Actual humidification capacity in kg/hr.
­ PS2 Pressure Switch: Actual status of the optional pressure switch PS2 when operating the humidification system Condair DL type A with sterile filter (On= pressure present, Off= no pressure present).
­ PS4 Inlet Pressure: Actual water inlet pressure in bar.
­ PS5 Nozzle Pressure: Actual atomization pressure of the water in bar (Type A with booster pump only).
­ Y1 Inlet Valve: Actual operating status of the inlet valve “Y1”.
­ Y2 Reserve: no function.
­ Y3 Air Cleaning: Actual operating status of the external valve “Y3” of the air cleaning option.
­ Y4 Ext. Pipe Flush: Actual operating status of the external valve “Y4” of the external pipe flush option.
­ Y5 Spray Valve: Actual operating status spray valve “Y5”.
­ Y6 Spray Valve: Actual operating status spray valve “Y6”.
­ Y7 Spray Valve: Actual operating status spray valve “Y7”.

Operating the Condair DL control software 29

Y8 Spray Valve
Closed
Y9 Spray Valve
Closed
Y10 Drain Valve
Closed
Y11 Aux. Outlet Valve
Closed

­ Y8 Spray Valve: Actual operating status spray valve “Y8”.
­ Y9 Spray Valve: Actual operating status spray valve “Y9”.
­ Y10 Drain Valve: Actual operating status drain valve (open when deenergized).
­ Y11 Aux. Outlet Valve: Actual operating status optional auxiliary outlet valve (open when de-energized). Note: this info field appears only if the optional auxiliary outlet valve is installed and activated in the engineering level of the control software.

5.2.3 Quick access to setting parameters in the “Quick Access” submenu

Press the button in the “Help” menu. Then enter the quick access number of the desired setting parameter. You will find this number in the top left corner in the setting window of the corresponding parameter. Confirm the entry and the setting dialog for the corresponding parameter appears. Note: If the parameter is password protected, after entering the quick access number, the password “8808” must first be entered before the setting dialog for the parameter appears.

Quick access number

18:04

18:04

12

18:04

DL

01.09.2021

DL

01.09.2021

DL

01.09.2021

Help

Quick Access

Language

About

12

English

Quick Access
Contact Data Condair Group AG
info@condair.com www.condairgroup.com

123 456 789
0
1001

German French Italian Spanish

30 Operating the Condair DL control software

5.3 Configuration

5.3.1 Settings and features in the “General” submenu

5.3.1.1 Accessing the “General” submenu

Access the “General” submenu as shown below.

18:04

18:04

DL

01.09.2021

DL

01.09.2021

Home

Password

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001
Password: “8808”

DL
Menu
General

18:04 01.09.2021

Maintenance

Features

Controls

Network

18:04

DL

01.09.2021

General

Region

Date & Time

Backup

Password Settings

Brightness

5.3.1.2 Determine language and system of units in the “Region” submenu

DL
Region
Language
English
Units
Metric

18:04 01.09.2021

­ Language: With this setting you determine the language.

Factory setting: Options:

depending on the country different languages

­ Units: With this setting you determine the desired unit system.

Factory setting: Options:

depending on the country Metric or Imperial

Operating the Condair DL control software 31

5.3.1.3 Date and time settings in the “Date & Time” submenu

Note: The date and time must be entered correctly, as these are used for the entries in the malfunctions and maintenance history list.

18:04

DL

01.09.2021

Date & Time

Date
01.09.2021

Time
08:51

Date Format
TT.MM.JJJJ

Clock Format
24H

Daylightsaving
Winterzeit

Daylightsaving
Wintertime

­ Date: With this setting you determine the current date in the set format (“MM/DD/YYYY” or “DD/MM/YYYY”). Factory setting: 01/01/2020

­ Time: With this setting you set the current hour of the day in the set time format (“12H” or “24H”).
Factory setting: 12:00

­ Date Format: With this setting you determine the desired date format.

Factory setting: Options:

DD/MM/YYYY DD/MM/YYYY or MM/DD/YYYY

­ Clock Format: With this setting you determine the desired time format.

Factory setting: Options:

24H
24H (24 hours, display 13:35) or 12H (12 hours, display: 01:35 PM)

­ Daylightsaving: With this setting you determine the daylight saving time summer time / winter time).

Factory setting: Options:

Wintertime Summertime or Wintertime

5.3.1.4 Read in parameter settings in the “Backup” submenu

18:04

DL

01.09.2021

Backup

Load Parameters from USB

­ Load Parameters from USB: With this function you can read in parameter settings that were previously saved on a FAT32 formatted USB stick. To do this, the USB stick with the parameter settings must be inserted into the USB interface on the control board. After pressing the selection field, a confirmation dialog appears in which you have to confirm the loading of the parameter settings again.

32 Operating the Condair DL control software

5.3.1.5 Activate/Deactivate password protection in the “Password Settings” submenu

18:04

DL

01.09.2021

Password Settings

Password Protection
On

­ Password Protection: With this function you can protect the access to

the main menu with the user password “8808” against unauthorized ac-

cess (“On”) or not (“Off”).

Factory setting: On

Options:

Off or On

5.3.1.6 Set the brightness of the touchscreen and the LED in the “Brightness” submenu

18:04

DL

01.09.2021

Brightness

Touchscreen
80 %

LED
25 %

­ Touchscreen: With this setting you determine the desired value for the display brightness. Factory setting: 80 % Settings range: 15 … 100 %
­ LED: With this setting you determine the desired value for the brightness of the status LED. Factory setting: 25 % Settings range: 25 … 100 %

Operating the Condair DL control software 33

5.3.2 Settings and features in the “Maintenance” submenu

5.3.2.1 Accessing the “Maintenance” submenu

Access the “Maintenance” submenu as shown below.

18:04

18:04

DL

01.09.2021

DL

01.09.2021

DL

Home

Password

Menu

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001

General Maintenance Features Controls Network

Password: “8808”

18:04 01.09.2021

18:04

DL

01.09.2021

Maintenance

Reset

Update

Histories

Error Analizer

USB Data Logger

5.3.2.2 Reset functions in the “Reset” submenu

DL
Reset
Ag-Ion Reset

18:04 01.09.2021

Error/Warning Reset

Settings Reset

­ Ag-Ion Reset: With this function you can reset the maintenance counter after replacing the silver cartridge. After pressing the selection field, a confirmation dialog appears in which you have to confirm the reset again
­ Error/Warning Reset: With this function you can reset pending errors/ warnings after eliminating the malfunction(s). After pressing the selection field, a confirmation dialog appears in which you have to confirm the reset again. The Condair DL then restarts.
­ Settings Reset: With this function you can reset the parameter setting values of the control software to the last saved values. After pressing the selection field, a confirmation dialog appears in which you have to confirm the reset again.

34 Operating the Condair DL control software

5.3.2.3 Software update in the “Update” submenu

18:04

DL

01.09.2021

Update

Update from USB

Update from Remote

­ Update from USB: With this function you can update the control software. The software is downloaded directly from the USB stick and then installed. Please note the information in Section 6.8.
­ Update from Remote: With this function you can update the control software. The software must already be downloaded before the update can be started. Please note the information in Section 6.8.

5.3.2.4 View and export malfunctions and maintenance histories in the “Histories” submenu

18:04

DL

01.09.2021

Histories

Error/Warning History

Service History
Export Error/Warning History
Export Service History

­ Error/Warning History: With this function you can view the error and warning history list.
­ Service History: With this function you can view the maintenance history list.
­ Export Error/Warning History: With this function you can save the error and warning history list on a USB stick. Note: Before you carry out this function, you must insert a FAT32 formatted USB stick into the USB interface on the control board.
­ Export Service History: With this function you can save the maintenance history list on a USB stick. Note: Before you carry out this function, you must insert a FAT32 formatted USB stick into the USB interface on the control board.

Operating the Condair DL control software 35

5.3.2.5 Load and export the error log file in the “Error Analyzer” submenu

18:04

DL

01.09.2021

Error Analyzer

Load Error Log Defintion

Export Log File

­ Load Error Log Definition (carried out ex works): With this function you can load an “Error Log Definition file” available from Condair on a USB stick for recording malfunctions. Once the “Error Log Definition file” has been loaded, an error log file is created as soon as an error occurs during operation. This file can then be saved on a USB stick using the “Export Log File” function. Note: Before you carry out this function, you must insert a USB stick with the “Error Log Definition” file into the USB interface on the control board.
­ Export Log File: With this function you can save an error log file created by the control on a USB stick and send it to Condair for further analysis. Note: Before you carry out this function, you must insert a FAT32 formatted USB stick into the USB interface on the control board.

5.3.2.6 Start operating data recording in the “USB Data Logger” submenu

18:04

DL

01.09.2021

USB Data Logger

Mode
On

Load USB Log Definition

­ Mode: With this function you can switch the operating data recording on

a USB stick on or off. A new csv file is created for each day and stored

on the USB stick.

Hinweis: Before you carry out this function, you must insert a FAT32 for-

matted USB stick into the USB interface on the control board.

Factory setting: Off

Options:

Off or On

­ Load USB Log Definition (carried out ex works): With this function you can load a “USB log Definition file” available from Condair on a USB stick. This file determines which parameters are recorded via the USB data logger as soon as data logging is started with the “Mode” parameter. Note: Before you carry out this function, you must insert a USB stick with the “USB log Definition file” into the USB interface on the control board.

36 Operating the Condair DL control software

5.3.2.7 View operating states in the submenu “Diagnostics> Input Diagnostics”

18:04

DL

01.09.2021

Input Diagnostics

Humidity Control
0.5 V

Safety Loop
Closed
Enable Humidification
Off

FC Error
Off

CS1 Contact
Off

CS1 Contact
Off
PS2 Pressure Switch
On
PS4 Inlet Pressure
4.0 bar
PS5 Nozzle Pressure
4.0 bar
Pump Current
0.0 A
Water Conductivity
5 µS/cm
Water Temperature
10.0 °C
Ag-Ion Current
0.2 mA
Disinfection Tank Level
Off
Leak Monitoring
Off
24V Ext. Supply
23.8 V
10V Ext. Supply
9.8 V
5V Per. Supply
4.9 V

­ Humidity Control: Shows the applied voltage signal at the input signal terminal “X16” between “HUM” and “GND”.
­ Safety Loop: Shows the current status of the safety loop. ­ Enable Humidification: Enable signal present at X16 or not (Remote
enable). ­ FC Error: Is “On” when FC is switched on and no error is present. Contact
drops out when the FC is switched off or there is an error at the FC. ­ CS1 Contact: Status of the input for flushings. ­ PS2 Pressure switch: Status of the pressure switch PS2 for sterile filter
(only for systems with a sterile filter and pump). ­ PS4 Inlet Pressure: Analog input of pressure sensor PS4 (inlet pressure). ­ PS5 Nozzle Pressure: Analog input of pressure sensor PS5 (nozzle
pressure). ­ Pump Current: Current power consumption of the pump motor. ­ Water Conductivity: Current conductivity of the inlet water in S/cm. ­ Water Temperature: Current temperature of the inlet water in °C. ­ Ag-Ion Current: Currently measured current of the silver ionization. ­ Disinfection Tank Level: Current level of the disinfection tank. ­ Leak Monitoring: Current status of the leak monitoring. ­ 24V Ext. Supply: Effective voltage of the 24 V DC supply. ­ 10V Ext. Supply: Effective voltage of the 10 V DC supply. ­ 5V Per. Supply: Effective voltage of the 5 V DC supply.

Operating the Condair DL control software 37

5.3.2.8 Checking the relays of the remote operating and fault indication board in the “RFI Diagnostics” submenu

Note: This submenu is only accessible if the remote operating and fault indication board has been installed and activated in the Engineering level of the control software.

18:04

DL

01.09.2021

RFI Diagnostics

Furnace
Off

Unit On
Off

­ Furnace: Activation and deactivation of the “Furnace” relay. ­ Unit On: Activation and deactivation of the “Unit On” relay. ­ Running: Activation and deactivation of the “Running” relay. ­ Service: Activation and deactivation of the “Service” relay. ­ Error: Activation and deactivation of the “Error” relay.

Running
Off

Service
Off

Error
Off

Error
Off

5.3.3 Settings and features in the “Features”

5.3.3.1 Accessing the “Features” submenu

Access the “Features” submenu as shown below.

18:04

18:04

DL

01.09.2021

DL

01.09.2021

DL

Home

Password

Menu

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001

General Maintenance Features Controls Network

Password: “8808”

18:04 01.09.2021

18:04

DL

01.09.2021

Features

Operation

Flush Timer

Softstart

Ceramic Wash Over

38 Operating the Condair DL control software

5.3.3.2 Set the power limitation in the “Operation” submenu

18:04

DL

01.09.2021

Operation

Capacity Limitation
100 %

­ Capacity Limitation: with this setting you determine the capacity limitation in relation to maximum capacity in %.

Factory setting: 100 %

Setting range:

20 … 100 %

5.3.3.3 Set the flush timer in the “Flush Timer” submenu

18:04

DL

01.09.2021

Flush Timer

Function
On

Start Time
00:00

­ Function: with this setting you can activate (“On”) or deactivate (“Off”) the timer-controlled flushing of the water system. Note: during the timer- controlled flushing of the water system, first the water supply line is flushed via the external pipe flush valve Y4, assumed your system is equipped with the external pipe flush option. Then, the inlet valve Y1 opens and the internal water system of the central unit is flushed via the drain valve Y10 (normally open valve). Finally, the air cleaning valve Y3 opens, and the spray circuits are blown out one after the other, assumed your system is equipped with the air cleaning option.
Factory setting: Off Optional settings: Off or On
­ Start Time: with this setting you determine the time of day, at which the timer-controlled flushing of the water system is to be carried out. Note: if at the point in time, on which the timer-controlled flushing is to be carried out, a humidification is in progress, the flushing is omitted.
Factory setting: 00:00 Optional settings: 00:00 to 23:59

5.3.3.4 Activate/deactivate the softstart function in the “Softstart” submenu

18:04

DL

01.09.2021

Softstart

Softstart
On

­ Softstart: With this setting you activate (“On”) or deactivate (“Off”) the softstart function. Note: The softstart function limits the amount of water sprayed by 50% for 10 minutes when the Condair DL starts humidifying again, provided the Condair DL has not humidified for more than 30 minutes (factory setting).
Factory setting: Off Optional settings: Off or On

Operating the Condair DL control software 39

5.3.3.5 Activate/deactivate the ceramic wash over function in the “Ceramic Wash Over” submenu

CAUTION!

During the ceramic wash over the nozzles spray water onto the ceramic plates, similar to when 100% demand is present. In systems with a booster pump, this also switches on.
This process must be monitored by the operator since the humidity can significantly exceed the desired setpoint. Over-saturation of the ceramic plates is likely.
After the ceramic wash over is complete, any water behind the ceramic plates must be removed if it cannot drain from there.

18:04

DL

01.09.2021

Ceramic Wash Over

Ceramic Wash Over
On

Spray Time
180 s

Pump Pressure
7.5 bar

­ Ceramic Wash Over: With this setting you activate (“On”) or deactivate (“Off”) the ceramic wash over function. Only when the ceramic wash over function has been activated, ceramic wash over can be started using the “Manual Functions” button and then the “Ceramic Wash Over” function.

Factory setting: Off Optional settings: Off or On

­ Spray Time: With this setting you determine the duration of the ceramic wah over in seconds.

Factory setting: Setting range:

180 s 1 … 900 s

­ Pump Pressure: With this setting you determine the pump pressure in bar with which the booster pump provides during ceramic flushing.

Factory setting: Setting range:

7.5 bar 4.0 … 9.0 bar

40 Operating the Condair DL control software

5.3.4 Settings and features in the “Controls” submenu

In the “Controls” submenu you determine the control settings for the humidification system Condair DL. The control settings available depend on the selected signal source and the control mode.

5.3.4.1 Accessing the “Controls” submenu

Access the “Controls” submenu as shown below.

18:04

DL

01.09.2021

Home

Standby
0%
Demand
1685 hr
Next Maintenance

18:04

DL

01.09.2021

Password


123 456 789
0
1001
Password: “8808”

DL
Menu
General

18:04 01.09.2021

Maintenance

Features

Controls

Network

18:04

DL

01.09.2021

Controls

Signal Settings

18:04

DL

01.09.2021

Signal Settings

Source
Analog

Control Mode
rF PI

Signal Type Control
0-10V

Setpoint
40 %

P-Band
15 %

Operating the Condair DL control software 41

5.3.4.2 Control settings in the “Signal Settings” submenu

18:04

DL

01.09.2021

Signal Settings

Source
Analog

Control Mode
rF PI

Signal Type Control
0-10V

Setpoint
40 %

P-Band
15 %

P-Band
15 %
I-Time
5 min
Lower Limit Hum.
3 %
Enable Contact
On

­ Source: With this setting you determine whether the control signal comes

from an analog source “Analog” (humidity sensor, demand signal from an

external humidity controller), a BMS (building management system) via

“Modbus”, “BACnet” or via “IoT”.

Factory setting: Analog

Options:

Analog (Analog sensor-/humidity signal)

Modbus (Signal via Modbus)

BACnet (Signal via BACnet)

IoT (Signal via IoT)

­ Control Mode: with this setting you determine the type of controller used with the humidification system Condair DL.

Factory setting: Options:

Demand
On/Off (external On/Off humidistat) Demand (external continuous controller) RH P (internal P controller) RH PI (internal PI controller)

­ Signal Type Control: with this setting you determine the control signal with which the humidification system is controlled. Note: this setting appears only if “Control Mode” is set to “Demand”, “RH P” or “RH PI”.

Factory setting: Options:

0-10 V 0-5 V, 1-5 V, 0-10 V, 2-10 V, 0-16 V, 3.2-16 V, 0-20 V, 4-20 V, 0-20mA, 4-20mA

­ Setpoint: with this setting you set the humidity setpoint for the internal P/ PI controller in % relative humidity. Note: this setting appears only if the “Control Mode” is set to “RH P” or “RH PI”.

Factory setting: Options:

40 %rh 5 … 95 %rh

­ P-Band: with this setting you set the proportional range for the internal P/ PI controller in % relative humidity. Note: this setting appears only if the “Control Mode” is set to “RH P” or “RH PI”.

Factory setting: Options:

15 %rh 6 … 65 %rh

­ I-Time: with this setting you set the integral time for the internal P/PI controller. Note: this setting appears only if the “Control Mode” is set to “RH PI”.

Factory setting: Options:

5 minutes 1 … 60 minutes

42 Operating the Condair DL control software

­ Lower Limit Hum.: With this setting you set the minimum signal value in % of the maximum signal value of the humidity sensor, if undershot a sensor interruption message (Error “E32”) is triggered. Note: this setting appears only if the “Control Mode” is set to “RH P” or “RH PI”.

Factory setting: Options:

3 % 0.0 … 10.0 %

­ Enable Contact: With this setting you determine whether the enable contact on the driver board is evaluated (“On”) or ignored (“Off”) by the control software.

Factory setting: Options:

On On or Off

5.3.5 Communication settings in the “Network” submenu

In the “Network” submenu you determine the parameters for digital communication protocols.

5.3.5.1 Accessing the “Network”submenu

Access the “Network” submenu as shown below.

18:04

18:04

DL

01.09.2021

DL

01.09.2021

Home

Password

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001
Password: “8808”

DL
Menu
Maintenance Features Controls Network

18:04 01.09.2021

18:04

DL

01.09.2021

Network

IP Settings

IoT Settings

Modbus Settings

BACnet Settings

Remote Fault Indication

Operating the Condair DL control software 43

5.3.5.2 Settings in the “IP Settings” submenu

The following network settings are used only for the communication via the integrated BACnet IP, Modbus TCP or IoT interface.

18:04

DL

01.09.2021

IP Settings

DHCP Mode
DHCP

IP Address
192.168.168.243

Subnet Mask
255.255.255.000

Default Gateway
000.000.000.000

Primary DNS
000.000.000.000

Primary DNS
000.000.000.000
Secondary DNS
000.000.000.000
MAC Address
FE:ED:AF:FE:BE:EF
Host Name
IC_1111111

­ DHCP Mode: with this setting you determine whether you want to assign the IP Address, the Subnet Mask, the Standard Gateway as well as the Primary and Secondary DNS address as fixed values or whether these should be dynamically assigned via a DHCP server. Note: If no address can be assigned via a DHCP server when “IP Type” is set to “DHCP”, an APIPA (Automatic Private IP Addressing) is automatically assigned. This is in the range from 169.254.1.0 to 169.254.254.255. The subnet mask is set to 255.255.0.0 and the standard gateway remains 0.0.0.0.

Factory setting: Options:

DHCP
DHCP (dynamic assignment) Fixed (fixed assignment)

­ IP Address: This field shows the actual IP address of Condair DL assigned manually or assigned by a DHCP server. If the parameter “IP Type” is set to “Fixed”, the IP address of Condair DL can be set via this field. If the parameter “IP type” is set to “DHCP”, the IP address of Condair DL is assigned by a DHCP server.

­ Subnet Mask: This field shows the actual subnet mask of the IP network assigned manually or assigned by a DHCP server. If the parameter “IP Type” is set to “Fixed”, the subnet mask can be set via this field. If the parameter “IP type” is set to “DHCP”, the subnet mask is assigned by a DHCP server.

­ Default Gateway: This field shows the actual IP address of the default gateway assigned manually or assigned by a DHCP server. If the parameter “IP Type” is set to “Fixed”, the IP address of the default gateway can be set via this field. If the parameter “IP type” is set to “DHCP”, the IP address of the default gateway is assigned by a DHCP server.

­ Primary DNS: This field shows the actual IP address of the primary domain name server (DNS) assigned manually or assigned by a DHCP server. If the parameter “IP Type” is set to “Fixed”, the IP address of the primary domain name server can be set via this field. If the parameter “IP type” is set to “DHCP”, the IP address of the primary domain name server is assigned by a DHCP server.

­ Secondary DNS: This field shows the actual IP address of the secondary domain name server (DNS) assigned manually or assigned by a DHCP server. If the parameter “IP Type” is set to “Fixed”, the IP address of the secondary domain name server can be set via this field. If the parameter “IP type” is set to “DHCP”, the IP address of the secondary domain name server is assigned by a DHCP server.

­ MAC Address: Factory set MAC Address (Media Access Control) of Condair DL. Not modifiable.

­ Host Name: Host Name of Condair DL automatically generated by the control. Format: “IC_”+”Serial number of Condair DL”. Not modifiable.

44 Operating the Condair DL control software

5.3.5.3 Settings in the “IoT Settings” submenu

The following settings are only required for communication via IoT.

18:04

DL

01.09.2021

IoT Settings

Cloud Connection
Off

­ Cloud connection: not yet available! ­ Channel: not yet available!

Channel
Ethernet

5.3.5.4 Settings in the “Modbus Settings” submenu

18:04

DL

01.09.2021

Modbus Settings

Modbus Protocol
Modbus/RTU

Modbus Address
10

Parity
Even

Baud Rate
19200

Register Sequence
MSR zuerst

­ Modbus Protocol: with this setting you can activate “Modbus/RTU” or

“Modbus/TCP” communication via a Modbus network or deactivate (“Off”)

Modbus communication.

Factory setting: Modbus/RTU

Options:

Off, Modbus/RTU or Modbus/TCP

Important: regarding the setting of the individual Modbus parameters as well as the wiring of the Condair DL for the Modbus communication, please observe the instructions in the separate Modbus addendum manual. This manual can be requested from your Condair representative.

5.3.5.5 Settings in the “BACnet Settings” submenu

18:04

DL

01.09.2021

BACnet Settings

BACnet Protocol
Off

­ BACnet Protocol: with this setting you can activate (“BACnet MS/TP” or

“BACnet/IP”) or deactivate (“Off”) the communication via the integrated

BACnet interfaces.

Factory setting: Off

Options:

Off (BACnet interface deactivated)

MS/TP Master (BACnet MS/TP Master via RS 485

interface)

MS/TP Slave (BACnet MS/TP Slave via RS 485

interface)

BACnet/IP (BACnet/IP via RJ45 interface)

Important: regarding the setting of the individual BACnet parameters as well as the wiring of the Condair DL for the BACnet IP or BACnet MS/TP communication, please observe the instructions in the separate BACnet addendum manual. This manual can be requested from your Condair representative.

Operating the Condair DL control software 45

5.3.5.6 Settings in the “Remote Fault Indica …” submenu

18:04

DL

01.09.2021

Remote Fault Indica…

Indication
Service

Safety Loop
Warning

Ag-Ion Exchange
Error

­ Indication: With this setting you determine whether maintenance mes-

sages (“Service”) only or all Warning messages (“Warning”) are outputted

via the service relay of the remote operating and fault indication board.

Factory setting: Service

Options:

Service or Warning

­ Safety Loop: With this setting you determine whether an Error (“On”) or

a Warning (“Off”) is triggered when the external safety loop is open.

Factory setting: Warning

Options:

Warning or Error

­ Ag-Ion Exchange: With this setting you determine whether an Error (“On”)

or a Warning (“Off”) is triggered when the capacity counter of the silver

ionization cartridge has elapsed.

Note: However, 7 days after the capacity counter of the silver ionization

cartridge has elapsed always an error message is triggered.

Factory setting: Error

Options:

Error or Warning

46 Operating the Condair DL control software

6 Maintenance and Replacement of components
6.1 Important notes on maintenance
Qualification of personnel All maintenance work must be carried out only by well qualified and trained personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel. General notes The instructions and details for maintenance work must be followed and upheld. Only carry out the maintenance work described in this documentation. The humidification system Condair DL must be maintained in the prescribed intervals, the cleaning work must be carried out correctly. Only use original spare parts from your Condair representative to replace defective parts or parts which have exceeded their lifetime.
Safety DANGER! Risk of electric shock!
Before carrying out any maintenance work take the humidification system Condair DL out of operation as described in Section 4.5 and secure the system against inadvertent power-up. In addition, take AHU out of operation as described in the operations instructions of the AHU and secure the AHU against inadvertent power-up.
CAUTION! The electronic components inside the control unit are very sensitive to electrostatic discharge. Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of the control unit, appropriate measures must be taken to protect the respective components against damage caused by electrostatic discharge (ESD protection).
DANGER! Health risk by inadequate maintenance! Inadequately operated and/or poorly maintained adiabatic humidification systems may endanger the health. When inadequately operated and/or poorly maintained micro-organisms (including the bacterium which causes Legionnaire’s disease) may grow in the water system and in the area of the humidification unit and may affect the air in the AHU/air duct. Prevention: The humidification system Condair DL must correctly be operated as described in Section 4, and must be correctly maintained and cleaned in the prescribed intervals as described in Section 6.
Maintenance and Replacement of components 47

6.2 Hygiene and Maintenance according to VDI 6022 Page 1

The humidification system Condair DL incorporates the very latest technology and has been designed to guarantee hygienically trouble-free operation when operating conditions are observed. The hygiene during operation was tested, proven and confirmed by the award of the SGS-Fresenius Hygiene Certificate following long-term tests at the Fresenius Institute.

To ensure operational safety and to guarantee hygiene in long-term operation, the maintenance concept for the Condair DL has been structured in two stages. This differentiates between periodical checking and the implementation of a total system maintenance of the Condair DL. In order to operate the system according to the regulations “optimised air humidification DGUV” the maintenance must be carried out in accordance with the information given in chapter Section 6, additionally an maintenance record must be provided.

Hygiene Service
For carrying out a total system maintenance your Condair representative offers maintenance contracts. The trained Condair service technicians have the necessary equipment and carry out the hygiene service following the most up to date factory approved procedures and guidelines. For this purpose, please contact your Condair representative.

Periodical checking

Periodical checking should be carried out monthly and include the following work:

Item Nozzle system
Post-evaporation unit
Central unit
Humidifier housing/ Drain pan

Work to be carried out
­ Check the spray pattern of the atomizing nozzles during operation (spray cone: 60° acceptable). Remove atomizing nozzles with uneven spray pattern and clean them (see total system maintenance).
­ Check hoses and connections for sealing, if necessary, replace defective components.
­ Check ceramic plates for damage. Damaged plates should be replaced (see full servicing guide). Note: A grey discolouration of the ceramic plates is normal. This is due to deposits from the silver ionisation.
­ Silver ionisation: see detailed information in Section 6.5. ­ Check hoses, connections, pressure sensors (PS4 and PS5), valves, etc.
in the central unit. Replace defective components where necessary. Important: replace pressure sensors (PS4 and PS5) every 3 years.
­ Check the drain pan and humidifier housing for soiling (Rust, slime, dust), clean if necessary (see total system service).
­ Check the drain pan behind the post evaporation unit for collection of residual water. If residual water is present, check the water drain and the post evaporation unit.

48 Maintenance and Replacement of components

6.2.2 Total system maintenance
The frequency of the implementation of a total system maintenance depends on the operating conditions. The state of the humidifier`s hygiene and its components mostly depends on the quality of the humidifier water, the performance (and the frequency of replacement) of the filter installed before the unit, the air velocity, the air temperature, and the microbiological and chemical composition of the inlet air. The basic rule is: when the “W28/E28 – Maintenance” message appears, or at least once a year, the implementation of a total system maintenance is obligatory.
Resetting the “W28/E28 – Maintenance” message
Upon completion of the total system maintenance the maintenance due message can be reset via the “Reset” submenu (see Section 6.7).

Item Nozzle system Post-evaporation unit
Central unit

Work to be carried out
­ Check the spray pattern of the atomizing nozzles during operation (spray cone: 60° acceptable). Remove spray nozzles with a poor spray pattern and clean them in an ultrasonic bath or with a household decalcifier.
­ Check hoses and connections for sealing, if necessary, replace defective components.
­ Check spray nozzles for secure seating. Slightly tighten loose nozzles by hand.
­ Clean supporting structure, nozzle grid(s) and tubing with a combined detergent and disinfectant (application in accordance with manufacturer data), finally rinse all components with hygienically pure water (RO water).
­ If the the post-evaporation unit is not accessible for cleaning from the air outlet side, the ceramic plates must be removed.
­ Check ceramic plates for damage. Damaged plates must be replaced. ­ Check ceramic plates for soiling. Dust deposits are to be rinsed off with water.
Ceramic plates, which cannot be cleaned any more, have to be replaced. Note: A grey discolouration of the ceramic plates is normal. This is due to deposits from the silver ionisation. If the ceramic plates show severe deposits of dust, the ventilation system air filter should be checked for cracks, cleanliness, and filter quality (ISO ePM1 60% (F7/EU7) or better). Clean soiled plates. ­ Clean supporting structure and sealing plates with a combined detergent
and disinfectant (application in accordance with manufacturer data), finally rinse all components with hygienically pure water (RO water). ­ Check the supporting structure, the ceramic plates, the sealing plates for
correct assembly and tight seating of screw connections. If necessary, install faulty components correctly and tighten loose screw connections.
­ Silver ionisation: observe notes in Section 6.5 . ­ Clean filter housing of the optional sterile filter and replace filter cartridge. ­ Check hoses, connections, pressure sensors (PS4 and PS5), valves, etc.
in the central unit. Replace defective components where necessary. Important: Replace pressure sensors (PS4 and PS5) every 3 years.

Maintenance and Replacement of components 49

Item Humidifier housing/ Drain pan
Components installed upstream in the water supply line
Electrical installation Humidifier water
System air

Work to be carried out
­ Check the drain pan behind the post evaporation unit for collection of residual water. In the event of a substantial amount of residual water, check the water drain and post evaporation unit. Please note: drops of water and small pools of water in the water tray behind the post-evaporation unit are as a rule caused by the system.
­ Clean the drain pan and humidifier housing (also clean behind the post evaporation unit) with a combined detergent and disinfectant. Finally rinse all components with hygienically pure water (RO water) and rub dry.
­ To ensure hygiene the components installed upstream in the water supply line (e.g., water filter, reverse-osmosis system, etc.) must be cleaned and maintained in accordance with the information of the manufacturer.
Important: The water filter in the water supply line (if applicable) must be replaced at least once a year. The water filter must be replaced immediately if the water supply has been contaminated by a malfunction.
­ Arrange for a qualified specialist to inspect connections and cables, fasten connecting terminals if required. Defective installations must be rectified only by a qualified specialist.
­ Determine the bacterial count at the water connection to the central unit. In the event of bacterial count concentrations above the limit of 100 cfu/ml, the water supply/water pipes must be subject to a microbiological inspection and appropriate action must be taken immediately (please contact your Condair representative). Bacterial count concentrations in the upper area of the permitted range may be an indication of the onset of bacterial problems in the water supply. The water supply and water pipes should also be subject to a microbiological inspection.
­ Determine the bacterial count in the supply air before the humidifier inlet. In the event of bacterial count concentrations above the limit of 1000 cfu/m3, the ventilation system must be subject to a microbiological inspection and appropriate action must be taken immediately to rectify the situation (please contact your Condair representative). Bacterial count concentrations in the upper area of the permitted range may be an indication of the onset of bacterial problems in the ventilation system. The ventilation system should also be subject to a microbiological inspection.
­ Determine the bacterial count in the air at the humidifier outlet to confirm the hygienic function of the humidifier.

50 Maintenance and Replacement of components

6.3 Notes on cleaning and cleaning agents
For the cleaning of the individual system components of the Condair DL use a household cleaning and disinfection agent. It is mandatory to observe and comply with the manufacturer’s information and instructions of the cleaning agents used. Observe in particular: all information relating to the protection of personnel, environmental protection, and restrictions regarding usage.
CAUTION! Do not use any solvents, aromatic hydrocarbons or halogenized hydrocarbons or other aggressive substances as they may cause damage to the components of the unit.
DANGER! Do not use no cleaning agents, which leave poisonous residues. These can get in contact with the ambient air during operation and endanger the health of persons. In any case the components have to be thoroughly rinsed with RO water after cleaning.
Maintenance and Replacement of components 51

6.4 Removal and installation of components 6.4.1 Removal and installation of the ceramic plates
WARNING! Risk of injury The ceramic plates of the post-evaporation unit are porous and have partial sharp edges. You may injure your hands on this sharp edges or may injure your eyes by splintering ceramic parts when handling the ceramic plates. Prevention: when handling the cermaic plates always wear protecting gloves and goggles. Removal of the ceramic plates
Start point of removal
Fig. 9: Removal of the ceramic plates Proceed as follows to remove the ceramic plates: 1. Remove upper sealing plates. 2. Start on top right and remove the ceramic plates from right to left.
Important: mark position of the ceramic plates for correct re-assembly. 3. Repeat step 2 for all ceramic plate rows.
52 Maintenance and Replacement of components

Installation of the ceramic plates
Start point of installation
Fig. 10: Installation of the ceramic plates Before installation, check all ceramic plates for possible damage. Damaged ceramic plates and ceramic angles must not be reinstalled. For installation of the ceramic plates proceed in the reverse order of removal (also see section “Install ceramic plates” in the installation manual). Important! Make sure to reinstall the ceramic plates in the appropriate locations and that the upper sealing plates on left and the right side are flush with the corresponding the lateral sealing plate.
Maintenance and Replacement of components 53

6.4.2 Removal and installation of the spray nozzles
A
C C
BA
Fig. 11: Removal and installation of the spray nozzles Removal of the spray nozzles 1. Loosen nozzle “A” by hand and remove it together with the O-ring”B”.
Note: prior to the removal note the position and the colour identification of the nozzle. 2. If necessary, disassemble the nozzle according to the illustration above. Installation of the spray nozzles 1. Before installation, check nozzle “A” and o-rings “B” and “C” for any damage. Damaged nozzles or
damaged o-rings must be replaced. 2. If necessary, assemble the nozzle according to the illustration above. 3. Before installation of the nozzle flush the corresponding spray circuit by activating the appropriate
spray valve via the “Output Diagnostics” submenu. 4. Screw in cleaned or new nozzle with O-ring into the nozzle support and tighten it by hand until it
comes to a stop (do not use tools). Note: make sure the nozzle is installed in the nozzle grid on the right place and with the correct orientation.
54 Maintenance and Replacement of components

6.4.3 Removal and installation of the nozzle support

DB

A

Fig. 12: Removal and installation of the nozzle support
Removal of the nozzle support 1. Remove nozzle”A” together with the O-ring “B” as described in Section 6.4.2. 2. Remove coloured ring “D” from the nozzle support. 3. Remove the hose(s) from the nozzle support (press the locking ring towards screw, then pull hose
off). 4. Remove connection nipple (press the locking ring towards screw, then pull off nipple). 5. Squeeze the catch locks of the nozzle support and remove the support.
Note: prior to the removal note the orientation of the nozzle support (straight, to the left, etc.).
Installation of the nozzle support 1. Before installation, check all parts (including O-rings) for any damage. Damaged parts must be
replaced. Important! Before installation, flush water conduits with RO water. 2. The installation follows the reverse order of the removal. ­ Make sure the nozzle support is installed in the nozzle grid on the right place and with the correct
orientation. ­ Following installation verify correct fastening of all hose connectors. Correctly mounted hoses
cannot be removed without pressing the locking ring.

Maintenance and Replacement of components 55

6.5 Replacement of the silver cartridge “Hygiene Plus”
If the silver cartridge is exhausted and needs to be replaced Error “55 – Ag- Ion Service” is shown. Via the “Service” relay and the “Error” relay on the remote operation and fault indication board, additionally a maintenance request and an error is issued. If the silver cartridge is not replaced and the counter is not reset within 7 days the humidification is stopped. Replacing the silver cartridge
F D E
H B
C G
A
E D
Fig. 13: Replacing the silver cartridge 1. Set the humidification system Condair DL out of operation as described in Section 4.5 and release
the pressure in the water system. 2. Unlock the front cover “A” of the central unit and remove the front cover. 3. Remove the two electrical connectors “B” from the connections “C” on the silver cartridge.
56 Maintenance and Replacement of components

4. CAUTION!
The silver cartridge is filled with water. Place an absorbent rag under the cartridge before loosening the connections and wipe away any splashed water afterwards. Loosen the hose connectors “D” at the entry and the exit, then remove both screw-in nipples “E”. 5.
CAUTION! The silver cartridge weighs approx. 3 kg. Undo the four screws “F” fastening the silver cartridge “G” to the holder “H”, then remove the cartridge. 6. Install the new silver cartridge in the reverse order. 7. Attach the front cover of the central unit “A” and lock it with the screw. Important: Exhausted silver cartridges must be sent to the local Condair representative for correct disposal.
Maintenance and Replacement of components 57

6.6 Replacement of the optional sterile filter and de-aeration of the filter housing
Replacing the sterile filter If error “E66” is shown or before each new humidification season the sterile filter must be replaced. Important: The sterile filter must be replaced immediately if the water supply has been contaminated due to a malfunction.
E
D
C
A B
Fig. 14: Replacing the sterile filter 1. Set the humidification system Condair DL out of operation as described in Section 4.5 and release
the pressure in the water system. 2. Unlock the front cover “A” of the central unit and remove the front cover. 3. Loosen and remove the filter housing “B”. Then, remove filter cartridge “C”. 4. Clean filter housing “B” and upper part of filter “D”. 5. Insert new filter cartridge “C” into the filter housing “B”.
Important! Use original filter cartridge from your Condair representative only. 6. Screw in filter housing “B” with new filter cartridge into upper part of filter “D” and tighten it.
58 Maintenance and Replacement of components

7. Vent the sterile filter: After replacement of the sterile filter cartridge or when the filter housing has been opened the sterile filter must be vented. Proceed as follow:
E
D
Fig. 15: Venting the sterile filter · Set the humidification system Condair DL into operation as described in Section 4.3.
Important: a minimum flow pressure of 3.0 bar must present in the water supply line. · Perform a manual flushing cycle (see Section 4.4.4). As soon as an acoustic noise is audible
from the water flow press the red venting knob “E” on top of the filter housing cover “D” (see Fig. 15) until water (without air) is pouring out. Note: If an error message is active the malfunction must be eliminated before a the flushing can be performed. · Check the filter housing for leaks. · If necessary, stop manual flushing cycle. 8. Attach the front cover of the central unit “A” and lock it with the screw.
Maintenance and Replacement of components 59

6.7

Resetting the maintenance counter

After completing the total system maintenance or after replacement of the silver cartridge, the corresponding maintenance indication or maintenance counter, respectively must be reset. Proceed as follows to reset the maintenance counter:

18:04

18:04

18:04

18:04

DL

01.09.2021

DL

01.09.2021

DL

01.09.2021

DL

01.09.2021

Home

Password

Menu

Maintenance

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001

General Maintenance Features Controls Network

Reset Update Histories Error Analyzer USB Data Logger

Passwort: “8808”

DL
Reset
Ag-Ion Reset

18:04 01.09.2021

Error/Warning Reset

18:04

DL

01.09.2021

Ag-Ion Reset

Do you really want to continue?

Factory Reset

Back

Continue

1. Select in the “Reset” submenu (Path: “Menu > Password: 8808 > Maintenance

Reset”). Then select the corresponding reset function (“Maintenance Reset” or “Ag-Ion Reset”). Note: The reset function “Maintenance Reset” only appears if the menu has been accessed with the engineering password.
2. The reset confirmation dialog appears:
· Press the button to reset the corresponding maintenance counter (“Maintenance Reset” or “Ag-Ion Reset”). The maintenance counter and the maintenance indication are reset.
· Press the button if the maintenance work has not been completed and you want to abort the reset procedure. The control unit returns to the “Reset” submenu.

60 Maintenance and Replacement of components

6.8 Performing a software update
To update the control software of the Condair DL or the firmware of one of its electronic boards, proceed as follows: 1. Set the <Control unit On/Off> switch on the right side of the control unit to the Off position, then
switch off the voltage supply to the control unit via the external electrical isolator and secure switch in the Off position to prevent it from inadvertent power up. 2. Unlock the front cover of the control unit and remove it. 3. Open control unit inner swing door. 4. Carefully insert FAT32 formatted USB stick containing the corresponding control software update into the USB port on the control board. Make sure that the maximum length of the USB stick does exceed 75 mm (3″). Note: In order to update the control software a USB stick with a valid software update (the update file must be on the highest level outside of any folder) must be connected to the USB port on the control board. Otherwise, an appropriate error message appears when starting the software update. 5. Close control unit inner swing door, then relocate the front cover of the control unit and lock it with the screw. 6. Remove the lock and tag from the external electrical isolator. Then, switch on external electrical isolator to restore power to the control unit. 7. Set the <Control unit On/Off> switch on the right side of the control unit to the On position. 8. When the home screen appears, select the

button, then enter the password (8808) to login. 9. Select the function “Software Update” (Path: “Menu > Password. 8808 > Maintenance > Update > Software Update”. See also Section 5.3.2.3. 10. The software update confirmation screen appears. Press the button. 11. An information window appears after a few minutes with information on the software update. Press the button to start the software update. The update starts. During the update, the display is inactive and the LED is flashing blue. If the update has completed the control unit returns to the home screen.
CAUTION!
Do not interrupt a software update once it has started. Wait until updating is completed. A corrupted control software can render the control unit unusable. Note: If software update is accidentally interrupted, the control unit will not operate, but the software update can be resumed by leaving the USB key inserted in the control board and power cycling the control unit. The integrated controller will detect the control software was not properly installed and restart the update. 12. Repeat steps 1 to 3, then carefully remove the USB stick. 13. Close control unit inner swing door, then relocate the front cover of the control unit and lock it with the screw. 14. Repeat Step 6 and 7 to power up the control unit.
Maintenance and Replacement of components 61

Fault elimination

Important notes on fault elimination
Qualification of personnel Repair work must be carried out only by qualified and well-trained professionals authorised by the owner. Repair work relating to the electrical installation must be carried out by an electrician or professionals authorised by the owner. General notes Repair work on the frequency converter and the booster pump must be carried only by your Condair representative. Only use original spare parts from your Condair representative to replace defective parts.
Safety DANGER! Risk of electric shock!
The control unit of the Condair DL and the pump motor inside the central unit (if applicable) are mains powered. Live parts may be exposed when the control unit and/or the central unit is/are open. Touching live parts may cause severe injury or danger to life. Prevention: Before carrying out any work on the components of the Condair DL take the system out of operation as described in Section 4.5 and secure the system against inadvertent power-up. Important: The frequency converter in the control unit of systems with booster pump contains capacitors. These can remain charged with a potentially deadly voltage for a certain period of time after the control unit has been disconnected from the power supply. Therefore, wait at least 10 minutes after disconnecting the power supply. Then make sure the appropriate contacts on the frequency converter and the terminals on the pump motor are free of voltage before starting any work on these components!
CAUTION! The electronic components inside the control unit are very sensitive to electrostatic discharge. Prevention: Before carrying out any repair work to the electrical or electronic equipment of the control unit, appropriate measures must be taken to protect the respective components against damage caused by electrostatic discharge (ESD protection).
62 Fault elimination

7.2 Fault indication
Malfunctions during operation detected by the control software are indicated by a corresponding Warning message (Status LED lights up yellow and the exclamation mark symbol is displayed in the device and error status field of the home screen) or Error message (Status LED lights up red and the cross symbol is displayed in the device and error status field of the home screen).

Warning
DL
Home

18:04 01.09.2021

Standby
0%
Demand
1685 hr
Next Maintenance
1

Temporary problems (e.g., water supply interrupted for a short time) or malfunctions which cannot cause damage to the system are indicated with a warning message, additionally the status LED lights up yellow. If the cause of the malfunction disappears of its own accord within a certain period
of time, the warning message will automatically switch off otherwise an
error message is triggered.
Note: Warnings can be indicated also via the service relay of the remote operating and fault indication. Therefore the warning indication via the service relay must be activated in the “Network” submenu of the control software (see Section 5.3.5.6).

Error
DL
Home

18:04 01.09.2021

Stopped

Malfunctions where further operation is not possible any longer or malfunctions which can damage the system are indicated with an error message, additionally the status LED lights up red. If such a malfunction occurs the operation of the system is limited only, or the system will be stopped automatically.

0%
Demand
1685 hr
Next Maintenance
1

Fault elimination 63

By pressing on the button in the home screen the error list shown with all active warning and error messages. By pressing on the corresponding Warning or Error entry additional information regarding the malfunction are displayed (see display on the far right).

18:04

DL

01.09.2021

Home

Stopped
0%
Demand
1685 hr
Next Maintenance
1

18:04

DL

01.09.2021

E59 Sensor Nozzle Pre…
0 01-09-2021 – 13:25
E48 Water Temperatu…
0 01-09-2021 – 13:11

1

18:04

DL

01.09.2021

E59 Sensor Nozzle Pressure
01.09.2021 – 13:25 0
Refer to the malfunction list in the operation manual for a description of the fault and remedial measures. No valid signal from nozzle/tank pressure sensor

7.3

Malfunction list

Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregard of planning guidelines. Therefore, a complete malfunction diagnosis always involves a thorough examination of the entire system (e.g., hose connections, humidity control system, etc.).
Note: Remedial measures highlighted in gray in the malfunction list may only be remedied by a Condair service technician or a service center authorized by Condair. If applicable, contact your Condair representative.

Code

Warning Error

W01

­­­

­­­

E10

­­­

E19

Message Smartcard Controller Reset
Freeze Protection

Information

Possible causes

Remedy

No communication with Smartcard.

No Smartcard installed.

Contact your Condair representative.

Smartcard not valid or defective.

The control unit (Integrated Controller) has been automatically restarted due to a software problem.

The control unit (Integrated Controller) has been automatically restarted due to a software problem

Contact your Condair representative if this problem regularly occurs.

Temperature of the supply water is near the freezing point. Temperature flushing has triggered. Note: The temperature flushing shall prevent the freezing of the hydraulic system by the movement of the water. Humidification is still possible.

Temperature of the supply water too low. Check water system. Insulate water pipes.

Ambient temperature in the area of the Place the central unit differently or

central unit too low.

protect it from the cold.

64 Fault elimination

Code

Warning Error

W20

E20

W22

E22

W28

E28

­­­

E32

W35

­­­

W44

E44

­­­

E48

Message Safety Loop
Water Missing!
Maintenance Demand Sensor Signal Timeout Water Temperature
Water Temperature Sensor

Information

Possible causes

Remedy

External safety loop is open, humidification is stopped! Note: as soon as the safety loop is closed again the humidification system Condair DL continues to work normally.

Ventilation interlock open.

Check/switch on fan of the AHU.

Air flow monitor has triggered.

Check fan/filter of the AHU.

High limit humidistat has triggered.

Wait, check/replace high limit humidistat.

Fuse “F2” on the driver board defec- Contact your Condair representative. tive.

Water inlet pressure too low or not present! Note: as soon as the water pressure rises again above the set minimum value the humidification system Condair DL to work normally.

Shut-off valve in the water supply line Open shut-off valve. closed.

Reverse osmosis system is regener- Wait or switch on reverse osmosis

ating or switched off.

system.

Inlet valve Y1 defective or clogged. Contact your Condair representative.

Pressure sensor PS4 defective.

The maintenance interval of the system maintenance has elapsed. If the system maintenance is not performed and the maintenance message is not reset within one week after the maintenance message has been triggered an error message is triggered!

System maintenance due.

Contact your Condair representative.

Demand signal invalid, humidification is stopped!

Humidity sensor or external controller Contact your Condair representative. not or not correctly connected.

Sensor/controller wrong configured.

Correctly configure sensor/controller via the configuration menu (see Section 5.3.4).

Sensor/controller defective.

Contact your Condair representative.

The network (Modbus, BACnet, LonWorks) has stopped sending humidity/ demand updates.

Signal cable from network not connected correctly or defective.

Contact your Condair representative.

Interfering signal present.

Address conflict with other units in the network.

Correctly set unit adresses.

Temperature of the supply water from the reverse osmosis system has exceeded the limit value. Humidification is still possible for the moment

Temperature of the supply water too Check water system. high.

Ambient temperature in the area of the Ventilate/cool the room. central unit too high.

Water temperature sensor defective. Contact your Condair representative.

Water temperature sensor not or not correctly connected.

Water temperature signal invalid.

Water temperature monitoring activated but water temperature sensor not or not correctly connected.

Contact your Condair representative.

Water temperature sensor defective. Contact your Condair representative.

Fault elimination 65

Code

Warning Error

W50

­­­

Message
Out of Commissioning

W51

­­­ Level Dis. Pump

­­­

E54 Leak Monitoring

W55

E55 Ag-Ion Service

­­­

E59 Sensor Nozzle

Pressure

­­­

E62 Nozzle Pressure

­­­

E63 Ag-Ion Broken

­­­

E64 Ag-Ion Shortcut

Information

Possible causes

Remedy

This message appears on commissioning if the system or the control unit, respectively was disconnected from the mains for more than 48 hours. The system remains blocked for 5 minutes, and then starts automatically with a flushing cycle.

The control unit was disconnected from the mains for more than 48 hours.

We recommend disconnecting the water supply line from the reverse osmosis system on the connection of the central unit and to flush the supply line for 5 minutes into a separate drain. Then, reconnect the water supply line.

Level of the disinfectant in the tank is too low. Humidification is further possible for limited period of time!

Disinfectant in the tank is used up. Refill disinfectant.

Level sensor is not or not correctly connected.

Contact your Condair representative.

Level sensor defective.

Leak monitoring has triggered, humidification is stopped!

Water supply line and/or spray circuit Check/seal water supply line, spray lines to the duct and/or water drain circuit lines and water drain line. line leaky.

Components (tubes, valves, sliver car- Contact your Condair representative. tridge, etc.) in the central unit leaky.

Fuse “F2” on the driver board defective.

Sliver cartridge is exhausted and must be replaced, humidification is further possible for limited period of time!

Sliver cartridge not replaced, or silver cartridge maintenance counter not reset after sliver cartridge has been replaced.

Replace sliver cartridge (see Section 6.5) and reset silver cartridge maintenance counter (see Section 6.7).

Invalid signal from nozzle pressure sensor PS5!

Pressure sensor PS5 not or not cor- Contact your Condair representative. rectly connected.

Pressure sensor PS5 wrong configured.

Pressure sensor PS5 defective.

Nozzle pressure too high!

Wrong type of nozzle installed.

Contact your Condair representative.

Nozzles clogged.

Replace sliver cartridge (see Section 6.5) and reset silver cartridge maintenance counter (see Section 6.7).

Max. nozzle pressure set too high. Contact your Condair representative.

Wrong order of spray circuits or spray valves.

Pressure relief valve on booster pump set too high.

No sufficient current can be built up in the sliver cartridge!

sliver cartridge exhausted or defective.

Replace sliver cartridge (see Section 6.5) and reset silver cartridge maintenance counter (see Section 6.7).

Electrical supply to sliver cartridge interrupted.

Contact your Condair representative.

Installed sliver cartridge too small.

Ag board defective.

Short circuit on sliver cartridge!

sliver cartridge has internal short circuit due to material defect or due to exhaustion.

Replace sliver cartridge (see Section 6.5) and reset silver cartridge maintenance counter (see Section 6.7).

66 Fault elimination

Code

Warning Error

­­­

E65

­­­

E66

W67

E67

­­­

E70

W71

E71

­­­

E72

­­­

E74

E80

W81

E81

Message Ag-Ion Test Sterile Filter
Air Missing
Water Conductivity Sensor Limite Permeate
Conductivity Permeate
Keep Alive USB Data Logger Disinfection

Information

Possible causes

Remedy

Daily silver ionization test failed.

The sliver cartridge cannot build up the required current because the end of lifespan of the cartridge is reached or a wrong cartridge type is installed.

Replace sliver cartridge (see Section 6.5) and reset silver cartridge maintenance counter (see Section 6.7).

Pressure after sterile filter too low.

Filter clogged.

Disinfect RO water supply line and replace sterile filter (see Section 6.6).

Water replenishment of the RO water Encrease diameter of the RO water

supply line too low.

supply line.

Pressure switch PS2 after sterile filter Contact your Condair representative. defective.

Pressure sensor PS5 defective.

Air pressure of the air cleaning option too low or no pressure present.

Pressure regulator wrongly adjusted. Correctly adjust pressure regulator (2…6 bar).

Shut-off valve in the compressed-air Open shut-off valve in the compressed-

supply line closed.

air supply line.

Air cleaning valve Y3 clogged or defective.

Contact your Condair representative.

Invalid signal from Conductivity sensor!

Conductivity sensor disconnected or Contact your Condair representative. connecting cable interrupted.

Conductivity monitoring wrong configured.

Conductivity board defective

Conductivity of the supply water from the reverse osmosis system has exceeded the upper limit value! Humidification still possible at the moment.

Reverse osmosis system defective or wrong configured or maintenance due.

Let have the reverse osmosis system be checked/repaired.

Conductivity sensor not correctly set. Contact your Condair representative.

Conductivity of the supply water from the reverse osmosis system has exceeded the max. limit value! Humidification is stopped!

Reverse osmosis system wrong configured.

Let have the reverse osmosis system be setup correctly.

Permeate membrane of the reverse osmosis system defective or maintenance due.

Let have the reverse osmosis system be checked/maintained/repaired.

Conductivity board wrong configured Contact your Condair representative. or defective.

Conductivity sensor soiled or defective (short circuit).

Communication between control board and driver board interrupted.

Driver board not connected.

Contact your Condair representative.

Wrong driver board installed.

Driver board defective.

USB data logger fault.

USB data logger not connected or defective.

Check/replace USB data logger.

Day counter for the disinfection has expired.

Disinfection due.

Contact your Condair representative.

Fault elimination 67

Code

Warning Error

W82

E82

­­­

E84

­­­

E85

­­­

E86

­­­

E87

­­­

E88

­­­

E89

­­­

E91

­­­

E93

­­­

E94

­­­

E96

Message Driver Missing Driver Defective Driver ID Wrong Driver Incompatible Local 24VSupply Local 5V Supply Local Reference Supply Pressure Instable
FC Error
FC Current
Peripheral 5V Supply

Information

Possible causes

Remedy

Communication with driver board interrupted.

RS485 Bus to driver board interrupted. Contact your Condair representative.

Unknown fault on driver board

Driver board defective.

Contact your Condair representative.

Driver board ID wrong.

Wrong driver board connected or SAB Contact your Condair representative. address wrong.

Wrong version of driver board.

Wrong version of driver board.

Contact your Condair representative.

Local 24V voltage on driver board out of valid range!

Short circuit on supply module or supply Contact your Condair representative. module defective.

Local 5V voltage on driver board out of valid range!

Short circuit on supply module or supply Contact your Condair representative. module defective.

Local reference voltage out of valid range!

DC supply faulty or supply line inter- Contact your Condair representative. rupted.

Water inlet pressure unstable!

Shut-off valve in the water supply line Check/completely open shut-off

not fully open.

valve.

Pressure of the reverse osmosis system too low.

Let have the reverse osmosis system be checked/maintained/repaired.

Cross section of the supply line too small.

Install water supply line with lager cross section (min. ø10/12 mm).

Sterile filter clogged.

Clean sterile filter housing and replace filter cartridge (see Section 6.6).

Monitoring of the frequency converter has triggered.

Frequency converter overloaded, too hot, or over current monitoring has triggered. Error code can be checked on frequency converter.

Contact your Condair representative.

Fuse “F1” on the driver board defective.

Pressure relief valve on booster pump set too high.

Current of the frequency converter is too high!

Booster pump or pump motor blocked.

Contact your Condair representative.

Frequency converter or control wrong configured.

Spray circuit valves clogged or defective.

Nozzles or spray circuit lines clogged.

Check/clean/replace Nozzles or spray circuit lines.

Pressure relief valve on booster pump set too high.

Contact your Condair representative.

Peripheral 5V supply out of valid range.

5V supply interrupted.

Contact your Condair representative.

Fuse “F2” on the driver board defective.

Overload on external connection.

Overload due to defective pressure sensor.

68 Fault elimination

Code

Warning Error

­­­

E97

­­­

E98

­­­

E100

­­­

E103

to

E107

­­­

E110

­­­

E111

­­­

E113

­­­

E118

­­­

E153

W157

­­­

W158

­­­

­­­

E162

Message External 24V Supply
External 10V Supply
Y1 Yx (e.g., Y5) Y10 Y4 Y3 Water Temperature
Y11 Software download from USB failed Software download from Cloud failed Software update failed

Information

Possible causes

Remedy

External 24 V supply faulty. Voltage too high or too low.

Fuse “F2” on the driver board defec- Contact your Condair representative. tive.

Short circuit on external connection.

Overload on external connection.

External 10 V supply faulty. Voltage too high or too low.

Fuse “F2″ on the driver board defec- Contact your Condair representative. tive.

Short circuit on external connection.

Overload on external connection.

Fault on Inlet valve Y1.

Inlet valve not connected or coil defective.

Contact your Condair representative.

Fault on corresponding spray valve (Y5 to Y9).

Spray valve not connected or coil de- Contact your Condair representative. fective.

Fault on drain valve Y10.

Drain valve not connected or coil de- Contact your Condair representative. fective

Fault on external optional water supply flushing valve Y4.

Water supply flushing valve not con- Contact your Condair representative. nected or coil defective

Fault on optional air cleaing valve Y3.

Air cleaing valve not connected or coil Contact your Condair representative. defective

Temperature of the supply water from the reverse osmosis system has exceeded the max. limit value. Humidification is stopped.

Ambient temperature in the area of the Ventilate/cool the room. central unit too high.

Supply water temperature too high. Check water system.

Water temperature sensor defective. Contact your Condair representative.

Water temperature sensor not or not correctly connected.

Fault on optional auxiliary outlet valve Y11.

Auxiliary outlet valve not connected or coil defective.

Contact your Condair representative.

Software download from USB failed.

Connection aborted during software download from USB stick or faulty update file.

Contact your Condair representative.

Software download from Cloud failed.

Connection aborted during software Contact your Condair representative. download from Cloud or faulty update file.

Software update failed.

Integrated controller switched off during update process or invalid software version downloaded.

Contact your Condair representative.

Fault elimination 69

7.4

Malfunctions without indication
The following table presents malfunctions that do not trigger a fault message, together with indications on their cause and notes on how to eliminate the sources of trouble

Failure

Cause

Remedy

Residual water in the section of Sealing elements improperly installed or de- Mount sealing elements correctly or

the duct outside the drain pan. fective

replace, as required (see Condair DL instal-

lation manual).

Ceramic plates improperly installed or ceramic Correctly install or replace ceramic plates (see

plates broken.

Condair DL installation manual).

Air velocity in the duct is too high (systems Reduce air velocity in the duct, if possible, or

without droplet separator >2.5 m/s, systems install droplet separator (consult your Condair

with droplet separator >4 m/s).

representative).

Condair DL humidifies permanently.

Nominal value of humidity is set too high.

Set humidity setpoint value correctly (siehe Section 5.3.4.2).

Ambient humidity very low.

Wait.

The internal controller is activated although Deactivate the internal controller (siehe Sec-

an external controller is connected.

tion 5.3.4.2).

Spray valves open and close Unstable control signal. continually.

Check controller settings and adjust controller, as required (siehe Section 5.3.4.2).

Maximum humidification capacity is not reached

Capacity limitation active.

Deactivate capacity limitation (set to: 100%). See Section 5.3.3.2.

Nozzles clogged.

Clean or replace nozzles (see Section 6.4.2).

Softstart function in progress.

Wait until set time has elapsed and the softstart function is terminated.

System incorrectly dimensioned (insufficient Contact your Condair representative. capacity).

Booster pump defective (insufficient permeate pressure)

Pressure relief valve of booster pump not adjusted correctly.

Booster pump starts too late Capacity limitation activated. or not at all

Deactivate capacity limitation (set to: 100%). See Section 5.3.3.2.

Booster pump not activated.

Contact your Condair representative.

Softstart function in progress.

Wait until set time has elapsed and the softstart function is terminated.

Spray valve Y5 (spray circuit 1) and/or spray valve Y6 (spray circuit 2) and/or spray valve Y7 (spray circuit 3) do not open

Spray valve Y5 and/or spray valve Y6 and/or spray valve Y7 defective.
Capacity limitation active.

Replace spray valves (see Section 6.4.2).
Deactivate capacity limitation (set to: 100%). See Section 5.3.3.2.

Spray valve Y8 (spray circuit 4) and/or Y9 (spray circuit 5) do not open even with 100% humidity demand.

Spray valve Y8 and/or spray valve Y9 defective or not activated in the control system.
Wrong stage control (7-steps instead of 15-steps)

Contact your Condair representative.

The humidifier is automatically Silver ionisation defective or exhausted. Ca- Replace silver cartridge (see Section 6.5) and

powered down after about one pacity counter run-out.

reset the capacity counter (see Section 6.7).

week of operation.

70 Fault elimination

7.5 Saving fault and service histories to a USB stick
The fault and service histories of the Condair DL can be saved to a USB stick for logging and further analysis. For this purpose, proceed as follows: 1. Set the <Control unit On/Off> switch on the right side of the control unit to the Off position, then
switch off the voltage supply to the control unit via the external electrical isolator and secure switch in the Off position to prevent it from inadvertent power up. 2. Unlock the front cover of the control unit and remove it. 3. Open control unit inner swing door. 4. Carefully insert FAT32 formatted USB stick into the USB port on the control board. Make sure that the maximum length of the USB stick does exceed 75 mm (3”). 5. Close control unit inner swing door, then relocate the front cover of the control unit and lock it with the screw. 6. Remove the lock and tag from the external electrical isolator. Then, switch on external electrical isolator switch to restore power to the control unit. 7. Set the <Control unit On/Off> switch on the right side of the control unit to the On position. 8. When the home screen appears: · Select “Menu > Password: 8808 > Maintenance > Histories > Export Error/Warning History”.
The last 80 events are then downloaded to the USB stick as separate .csv file (Automatically generated file name: “ExceptionHistory<Serial#>

7.6

Resetting malfunction indication

To reset the malfunction indication, proceed as follows:

18:04

18:04

DL

01.09.2021

DL

01.09.2021

DL

Home

Password

Menu

Standby
0%
Demand
1685 hr
Next Maintenance


123 456 789
0
1001

General Maintenance Features Controls Network

Passwort: “8808”

18:04 01.09.2021

18:04

DL

01.09.2021

Maintenance

Reset

Update

Histories

Error Analyzer

USB Data Logger

DL
Reset
Ag-Ion Reset

18:04 01.09.2021

Error/Warning Reset

18:04

DL

01.09.2021

Error/Warning Reset

Do you really want to continue?

Factory Reset

Back

Continue

1. Select in the “Error/Warning Reset” function (Path: “Menu > Password: 8808

Maintenance > Reset > Error/Warning Reset”).
2. The reset confirmation dialog appears: · Press the button to reset the malfunction indication(s). · Press the button to abort the reset procedure. The control unit returns to the “Reset” submenu.
If the malfunction indication cannot be reset via the control software (e.g., the display hangs), proceed as follows to reset the malfunction indication(s):

  1. Disconnect the control unit from the mains via the <Control unit On/Off> switch (located on the
    right side of the control unit). 2. Wait approx. 10 seconds, then reconnect the control unit to the mains by switching the <Control
    unit On/Off> switch again.
    Note: If the cause of the malfuntion(s) has/have not been eliminated, the malfunction indication(s) reappear(s) after a short while.

72 Fault elimination

7.7 Replacing the fuses and backup battery in the control unit
The fuses of the control unit must be replaced by authorized personnel only (e.g. electrician). Replace fuses of the control unit only with fuses matching the specifications below with the appropriate nominal current capacity. Never use refurbished fuses. Do not bridge the fuse holder.
To replace the fuses or the backup battery, proceed as follows: 1. Disconnect control unit from the mains by switching off the electrical isolator and secure electrical
isolator in “Off” position against inadvertent switching on. 2. Undo the screw of the front cover of the control unit, then remove the front cover. 3. Open control unit inner swing door. 4. Replace desired fuse or the backup battery.
DANGER!
It is mandatory that the contact protection for fuse “F1” be reinstalled after the fuse has been replaced. 5. Close control unit inner swing door, then relocate the front cover of the control unit and lock it with
the screw. 6. Reconnect control to the mains by switching on the electrical isolator.
Backup battery 3V (CR 2032)

F1= 6,3 A, slow acting Contact protection

F2= 630 mA, slow acting

Fig. 16: Fuse and battery replacement

Fault elimination 73

8 Taking out of service/Disposal
8.1 Taking out of service
If the humidification system Condair DL must be replaced or if the humidification system is not needed any more, proceed as follows: 1. Take the humidification system Condair DL out of operation as described in Section 4.5. 2. Have the system components unmounted by a qualified service technician.
8.2 Disposal/Recycling
Components not used any more must not be disposed of in the domestic waste. Please dispose of the individual components in accordance with local regulations at the authorised collecting point. If you have any questions, please contact the responsible authority or your local Condair representative. Thank you for your contribution to environmental protection.
74 Taking out of service/Disposal

9 Product specification

9.1

Technical data

Dimensions/Weight Installation length in AHU/duct (Min-Max) Width AHU/duct (Min-Max) Height AHU/duct (Min-Max) Dimensions central unit HxWxD Weight central unit Dimensions control unit HxWxD Weight control unit Wet weight post-evaporation unit Dry weight post-evaporation unit Hydraulic Humidification capacity Nozzle pressure Nozzle sizes Spray circuit valves Flushing water consumption
Electric Supply voltage/current control unit Control booster pump motor Power consumption control unit (including solonoid valves)
Motor rating booster pump
Voltage solenoid valves (Y1-Y10) Frequency converter Control signals
Control accuracy 4) Number of steps (humidity control)
Sound level Sound level Hygiene Silver ionisation cartridge “Hygiene Plus”

Type A (with booster pump)

Condair DL

Type B (without booster pump)

600 – 900 mm 1)

450 – 8400 mm 2)

450 – 4000 mm 2)

800 x 529 x 285 mm

approx. 54 kg

approx. 35 kg

485 x 344 x 217 mm

approx. 15 kg

approx. 55 kg/m2 humidifier area

approx. 40 kg/m2 humidifier area

5 … 1000 l/hr 3)

5 … 1000 l/hr 3)

3 … 7 bar

8 (1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5 and 5.0 l/hr at 4 bar)

3/2 way NO (normally open)

<210 kg/hr nozzle capacity: 2.2 – 2.5 l/min at 4 bar >210 kg/hr nozzle capacity: 3.7 – 4.0 l/min at 4 bar

200 … 240 VAC / 50..60 Hz, max. 6 A 115 … 240 VAC / 50..60 Hz, max. 6 A

continuous with frequency converter

­­­

55 … 65 VA (dependent on the number of switched valves and
whether the display is in sleep mode or not)

approx. 12 VA per

­­­

10 kg/hr spray capacity

24 V DC

Yes

No

0-5 VDC, 1-5VDC, 0-10 VDC, 2-10 VDC, 0-16 VDC, 3.2-16 VDC, 0-20 VDC, 4-20 VDC, 0-20mA, 4-20 mA

7-steps: ±3 %rh and 15-steps: ±2 %rh 7-steps: ±4 %rh and 15-steps: ±3 %rh

Number of steps
3 7 15 31

Possible humidifier capacity range [kg/hr] 5 – 10

10 – 560
25 – 1000
55 – 1000

min. cross section
[m2] 0.2 0.4 1.1 1.8

max. capacity at min. cross section 5)
[kg/hr] 10
45 99
204

approx. 51 dB(A)

approx. 41 dB(A)

Yes

Product specification 75

Condair DL

Type A (with booster pump)

Type B (without booster pump)

Communication

Remote operating and fault indication

Yes

Modbus RTU and Modbus TCP

Yes

BACnet IP and BACnet MS/TP Master or

Yes

Slave Mode

IoT

Yes

Interfaces

Ethernet

Yes

USB

Yes

RS 485

Yes

Air

Pressure drop (2 m/s)

approx. 40 Pa

Max. air velocity

2.5 m/s (without droplet separator), 4 m/s (with droplet separator)

Air filter quality before humidification unit

ISO ePM1 60% (F7/EU7) or better

Max. admissible air temperature

60°C (before humidification unit)

Water

Connector water supply

ø12 mm plug-in coupling or 1/2″ male thread adapter (supplied)

Connector water drain

ø10 mm plug-in coupling or 1/2″ male thread adapter (supplied)

Admissible water supply pressure

working pressure 3 … 7 bar

working pressure 3 … 7 bar

Admissible water temperature

5 … 20 °C

Water quality requirements

fully demineralised water from reverse osmosis system with 0.5…15 µS/cm (without any additives), max. 100 cfu/ml

Operating monitoring RO water

min. pressure, max. pressure, pressure after sterile filter, conductivity

Ambient conditions operation

Admissible ambient temperature

5 … 40 °C

Admissible ambient humidity

10 … 80 %rh, non-condensing

Ambient conditions storage

Admissible ambient temperature

5 … 40 °C

Admissible ambient humidity

10 … 75 %rh, non-condensing

Protection class

Control unit

IP21

Central unit

IP21

Certificates

Certificates

CE, DGUV, EAC, BTL

  1. Larger installation length on demand 2) Larger dimensions on demand 3) Larger capacities on demand (consider possible number of steps for capacity range!)
    Note: For systems “Type A” (with booster pump), the minimum output of 5 kg/hr can only be regulated at a flow pressure <4.0 bar. With a flow pressure of 4.0 bar, we recommend a minimum output of 10 kg/hr for “Type A” systems. 4) The nominal control accuracy may not always be available, because various factors (temperature control, water recycling, flap valve systems, etc.) may affect the accuracy. 5) These values can be smaller influenced by other limit values such as humidity, volume flow or air speed! The values are to be understood as theoretical appoximate values, which are determined by the number of nozzles and their size. The maximum capacity values are achieved only with a booster pump.

76 Product specification

9.2

Options
Options Leak monitoring Sterile filter Air cleaning External pipe flush External water filter 5 µm Gateway board (LonWorks or BACnet IP/BACnet MS/TP) Mounting rack for central unit and control unit Service disinfection: Connector for the hydraulic system for the introduction of disinfectant. Water temperature monitoring: Monitoring of the inlet water temperature for triggering of a flushing if the limit values for the inlet water temperature are exceeded. External valve block with additional drain valve: The valve block is integrated in an external housing separately from the central unit. Clamping sheet bottom rubber sealing post evaporator. Additional fixation of the rubber sealing with spring metal sheets. IoT Mobile Module: Enables wireless connection to Condair IoT Cloud.

  1. available only for Type B with sterile filter

Condair DL

Type A (with booster pump)

Type B (without booster pump)

x

x

x

x

x

x 1)

x

x

x

x

x

x

x

x

x

­

x

x

x

­

x

x

x

x

Product specification 77

9.3 CE declaration of conformity

Konformitätserklärung

EC
Declaration of conformity

Déclaration de conformité

Wir, Condair Group AG CH-8808 Pfäffikon SZ erklären in alleiniger Verantwortung, dass das Produkt

We, Condair Group AG CH-8808 Pfäffikon SZ declare under our sole responsibility, that the product

Nous, Condair Group AG CH-8808 Pfäffikon SZ déclarons sous notre seule responsabilité, que le produit

im Seriennummernbereich

Condair DL II A Condair DL II B
in the serial number range
1152773 to 4999999

pour les numéro de serie

auf das sich diese Erklärung bezieht, mit den folgenden Normen oder normativen Dokumenten übereinstimmt

to which this declaration relates is in

auquel se réfère cette déclaration est

conformity with the following standards or conforme aux normes ou autres

other normative standards

documents normatifs

EN 60335-1 EN 60335-2-88 EN 61000-6-2 EN 61000-6-3

und den Bestimmungen der folgenden and is corresponding to the following

Richtlinien entspricht

provisions of directives

2006 / 42 / EC 2014 / 30 / EU VDI 3803 VDI 6022-1 VDI 6022-2

et est conforme aux dispositions des directives suivantes

Pfäffikon, January 04, 2022 Condair Group AG

Eric Roth Chief Technology Officer
Condair Group AG Gwattstrasse 17 8808 Pfäffikon, Switzerland Tel. +41 55 416 61 11, Fax +41 55 588 00 07 info@condair.com, www.condairgroup.com

Adrian Spörri Corporate Systems Manager

2603625 DE/EN/FR 2201

78 Product specification

Notes

Notes

© 01.2016 Condair GmbH. Technical modifications reserved.
Condair GmbH Parkring3, 85748 Garching-Hochbrück Tel. (0) 89 207 008 -0, Fax (0) 89 207 008 -140, www.condair.de

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

condair User Manuals

Related Manuals