condair CDC-NA 2-10V Duct Humidity Sensor Instruction Manual
- October 30, 2023
- condair
Table of Contents
condair CDC-NA 2-10V Duct Humidity Sensor
Product Information
CDC-NA – 2-10V Duct Humidity Sensor
The CDC-NA – 2-10V Duct Humidity Sensor is a Condair duct humidity sensor that can be configured for either humidity control or as a high limit safety device. The kit includes Component No. 2597926 and Description No. 1509857, which is the 2-10V Duct Humidity Sensor.
Product Usage Instructions
- Refer to installation overview in section 2 of the user manual.
- At the place of location, drill a hole with a diameter of 16 mm(5/8) as well as 4 holes for the self-tapping screws into the duct.
- Loosen the screw on the housing cover and open cover.
- Lead connecting cable through the cable gland and connect wires to the terminal according to the wiring diagram.
- Stick gasket on the sensor side centrally on the housing (self-adhesive).
- Insert the probe into the hole in the duct, then fix the housing to the duct using the 4 self-tapping screws provided.
- Close the cover and fix it with the screw (do not tighten the screw too much).
Note: We recommend using 18-gauge wire, and maximum.
This document covers the operation and installation instructions for the following Condair duct humidity sensor:
Kit No/ Component No/ Description
- 2597926 /1509857 /2-10V Duct Humidity Sensor
The humidistat can be configured for either humidity control or as a high limit safety device.
Mounting and Installation
Location
The Condair CDC-NA is installed directly on the duct.
- Mounting in the extract air duct (recommended):
- Mount the CDC-NA in the extract air duct close to the air outlet of the room but downstream from an extract air fan if one is present.
- Mounting in the supply air duct:
- Mount the CDC-NA in the supply air duct at least 3 meters downstream from the nearest fan and coil and with a minimum distance of 5x the humidification distance to the steam distribution.
Installation
Refer to installation overview in section 2.
- At the place of location drill a hole with a diameter of 16 mm (5/8”) as well as 4 holes for the self-tapping screws into the duct.
- Loosen the screw on the housing cover and open cover.
- Lead connecting cable through the cable gland and connect wires to the terminate according to the wiring diagram.
- Stick gasket on the sensor side centrally on the housing (self-adhesive).
- Insert the probe into the hole in the duct, then fix the housing to the duct using the 4 self-tapping screws provided.
- Close the cover and fix it with the screw (do not tighten the screw too much).
Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
Dimensions
Attention
Warning
Wiring
Product Specification
Power Supply
| Operating Voltage Power Consumption Terminal Connections| 24 V AC 50/60 Hz ± 10 % Max. 2 VA
For wires 0.34…2.5 mm2 (AWG 24…12)
---|---|---
Sensor Probe (Humidity Sensor)
| Measuring element Range
Accuracy Hysteresis Repeatability
Stability
| Capacitive measuring element 0…100 % RH
± 3.0 % at 25 °C
± 1%
± 0.1%
< 0.5% / Year
Signal Outputs
| Analog Outputs Analog Signal Resolution Maximum Load| ****
0-10V / 2-10V
10 Bit
20 mA, 500Ω
Environment
| Operation Temperature Humidity| IEC 721-3-3
-40…70°C (-40…158°F)
˂95 %rH not condensing
General| Housing Materials Filter material| PC and ABS
PTFE coated 1µm pores
Wiring Diagrams
Wiring diagram CDC-NA for RS, EL, GS, US and SE
Wiring diagram CDC-NA for DL and ME
Wiring diagram CDC-NA with CHD-NA and APS for RS, EL, GS, US and SE
Wiring diagram CDC-NA with CHD-NA for DL and ME
For Wiring Schematic:
- Get the Condair Sensor Connect App