condair CRC-NA 2-10V Wall Humidity Sensor
The CRC-NA 2-10V Wall Humidity Sensor is a device that measures the humidity of the environment it is installed in. It comes with a kit that includes the following components:
Kit No. | Component No. | Description |
---|---|---|
2597927 | 1509858 | 2-10V Wall Humidity Sensor |
Product Installation Instructions
Before installing the CRC-NA 2-10V Wall Humidity Sensor, please refer to the installation overview in section 2 of the user manual.Follow the steps below for installation:
- Open the screw of the housing and remove the mounting plate.
- Fix the mounting plate (plastic screw facing downwards) with two screws at the location of installation.
- Lead connecting label from the bottom into the housing and connect wires to the terminal according to the wiring diagram.
- Snap housing onto the mounting plate and fix it with a screw (do not tighten screw too much).
Note: We recommend using 18-gauge wire, and a maximum 2 sec UI and its value is displayed.
Product Operation
The CRC-NA 2-10V Wall Humidity Sensor operates under the following conditions:
- Climatic Conditions: Temperature, Humidity
Product Technical Specifications
Power| Voltage| Sensor Probe| Signal Output| Display (LCD)| Environment
Standards
---|---|---|---|---|---
Operating voltage| DC 2…10 VDC| Humidity Values| Output Signal Resolution| 3
digits| Accuracy: 0.5
Hysteresis: 2 digits
Repeatability: 0.019.5 mA
Stability: 20 mA, 500
Note: The calibration value and tool symbol is displayed when you press the UP key. Use UP/DOWN to calibrate and press UP key again to step through the next active input. Disabled inputs will not be shown.
This document covers the operation and installation instructions for the following Condair wall humidity sensor:
Kit No./ Component No./ Description
- 2597927 /1509858 /2-10V Wall Humidity Sensor
Mounting and Installation
Location:
Install the Condair CRC-NA in a protected and easy accessible place at least 1.5 m above the floor to the wall (mounting on flush-mounting or wall-mounting box). Observe the following placement notes:
- Do not place Condair CRC-NA in niches, behind, curtains, etc.
- Do not place the Condair CRC-NA near heat sources, within the area with direct air draft or direct sunlight.
Installation
Refer to installation overview in section 2.
- Open the screw of the housing and remove the mounting plate.
- At the place of location fix mounting plate (plastic screw facing downwards) with two screws.
- Lead connecting label from the bottom into the housing and connect wires to the terminal according to the wiring diagram.
- Snap housing onto the mounting plate and fix it with screw (do not tighten screw too much).
Note: We recommend using 18-gauge wire, and a maximum <100 ft distance from the unit.
Installation overview
Dimension
- 0V / GND
- 24 V AC/DC ±10%
- Do not connect
- Do not connect
- Do not connect
- 2…10VDC
- Do not connect
- Temp. Reset
Wall Sensor LCD Display
Buttons | Operation | Function |
---|---|---|
press briefly | Switching On and Off | |
press briefly | Shows temperature value | |
press long | Switching between °C and °F | |
––– | ––– |
| press briefly| Shows rH value
press long| Offset settings
- Wall Humidistat LCD Display and function of control buttons
Sensor Calibration
Sensor inputs can be calibrated if needed
- Press > 2 sec. UI and its value is displayed: 75%
- Press : Calibration value and tool symbol is displayed, UP/DOWN to calibrate: UI 1
- Press : Save calibration, tool symbol disappears.
- Press UP key again to step through the next active input: 0.0%
Note: disable inputs will not be shown ..UI 1
Product Specification
Power Voltage| Operating voltage Power consumption Terminal connection| 24 V AC 50/60 Hz ± 10 %, 24 VDC ± 10 %
Max. 2 VA
For wires 0.34…2.5 mm2 (AWG 24…12)
---|---|---
Sensor Probe| Measuring element Range
Accuracy Hysteresis Repeatability Stability
| Capacitive measuring element 0…100 % RH
± 2.5 % at 25 °C
± 1%
± 0.1%
˂ 0.5% / year
Signal Output| Analog Outputs Output Signal Resolution Maximum Load| A01
DC 2…10 VDC
10 Bit, 9.7 mV, 0.019.5 mA
20 mA, 500Ω
Display (LCD)| Humidity Values Resolution Setpoint Values| 3 digits
0.5
2 digits
Environment| Operation:
Climatic Conditions Temperature Humidity
| IEC 721-3-3
Class 3 K5
-40…70°C (-40…158°F)
<95 % rH not condensing
Standards| CE compliant to EMC Norm 2014/30/ EU, Low
Voltage Directive 2014/35/EU
Automatic electrical control and regulating devices
for domestic use and similar applications Degree of protection according to 60529
Protection class
| EN 61 000-6-1/ EN 61 000-6-3
EN 60 730-1 IP30
III (IEC 60536)
General| Housing material Mounting Plate
Weight Condair CRC (including packing)
| PC and ABS Galvanized steel 160 g (5.6 oz)
Wiring Diagrams
Wiring diagram CRC-NA for RS, EL, GS, US and SE
Wiring diagram CRC-NA for DL and ME
Wiring diagram CRC-NA with CHD-NA and APS for RS, EL, GS, US and SE
Wiring diagram CRC-NA with CHD-NA for DL and ME
For Wiring Schematic
- Get the Condair Sensor Connect App
© Condair Group AG, Switzerland
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>