condair CRC-NA 2-10V Wall Humidity Sensor Instruction Manual

October 30, 2023
condair

condair CRC-NA 2-10V Wall Humidity Sensor

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-product

The CRC-NA 2-10V Wall Humidity Sensor is a device that measures the humidity of the environment it is installed in. It comes with a kit that includes the following components:

Kit No. Component No. Description
2597927 1509858 2-10V Wall Humidity Sensor

Product Installation Instructions

Before installing the CRC-NA 2-10V Wall Humidity Sensor, please refer to the installation overview in section 2 of the user manual.Follow the steps below for installation:

  1. Open the screw of the housing and remove the mounting plate.
  2. Fix the mounting plate (plastic screw facing downwards) with two screws at the location of installation.
  3. Lead connecting label from the bottom into the housing and connect wires to the terminal according to the wiring diagram.
  4. Snap housing onto the mounting plate and fix it with a screw (do not tighten screw too much).

Note: We recommend using 18-gauge wire, and a maximum 2 sec UI and its value is displayed.

Product Operation

The CRC-NA 2-10V Wall Humidity Sensor operates under the following conditions:

  • Climatic Conditions: Temperature, Humidity

Product Technical Specifications

Power| Voltage| Sensor Probe| Signal Output| Display (LCD)| Environment Standards
---|---|---|---|---|---
Operating voltage| DC 2…10 VDC| Humidity Values| Output Signal Resolution| 3 digits| Accuracy: 0.5
Hysteresis: 2 digits
Repeatability: 0.019.5 mA
Stability: 20 mA, 500

Note: The calibration value and tool symbol is displayed when you press the UP key. Use UP/DOWN to calibrate and press UP key again to step through the next active input. Disabled inputs will not be shown.

This document covers the operation and installation instructions for the following Condair wall humidity sensor:

Kit No./ Component No./ Description

  • 2597927 /1509858 /2-10V Wall Humidity Sensor

Mounting and Installation

Location:

Install the Condair CRC-NA in a protected and easy accessible place at least 1.5 m above the floor to the wall (mounting on flush-mounting or wall-mounting box). Observe the following placement notes:

  • Do not place Condair CRC-NA in niches, behind, curtains, etc.
  • Do not place the Condair CRC-NA near heat sources, within the area with direct air draft or direct sunlight.

Installation

Refer to installation overview in section 2.

  1. Open the screw of the housing and remove the mounting plate.
  2. At the place of location fix mounting plate (plastic screw facing downwards) with two screws.
  3. Lead connecting label from the bottom into the housing and connect wires to the terminal according to the wiring diagram.
  4. Snap housing onto the mounting plate and fix it with screw (do not tighten screw too much).

Note: We recommend using 18-gauge wire, and a maximum <100 ft distance from the unit.

Installation overview

Dimension

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-1

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-2

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-4

  1. 0V / GND
  2. 24 V AC/DC ±10%
  3. Do not connect
  4. Do not connect
  5. Do not connect
  6. 2…10VDC
  7. Do not connect
  8. Temp. Reset

Wall Sensor LCD Display

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-6

Buttons Operation Function
press briefly Switching On and Off
press briefly Shows temperature value
press long Switching between °C and °F
––– –––

| press briefly| Shows rH value
press long| Offset settings

  • Wall Humidistat LCD Display and function of control buttons

Sensor Calibration

Sensor inputs can be calibrated if needed

  • Press > 2 sec. UI and its value is displayed: 75%
    • Press : Calibration value and tool symbol is displayed, UP/DOWN to calibrate: UI 1
    • Press : Save calibration, tool symbol disappears.
  • Press UP key again to step through the next active input: 0.0%

Note: disable inputs will not be shown ..UI 1

Product Specification

Power Voltage| Operating voltage Power consumption Terminal connection| 24 V AC 50/60 Hz ± 10 %, 24 VDC ± 10 %

Max. 2 VA

For wires 0.34…2.5 mm2 (AWG 24…12)

---|---|---
Sensor Probe| Measuring element Range

Accuracy Hysteresis Repeatability Stability

| Capacitive measuring element 0…100 % RH

± 2.5 % at 25 °C

± 1%

± 0.1%

˂ 0.5% / year

Signal Output| Analog Outputs Output Signal Resolution Maximum Load| A01

DC 2…10 VDC

10 Bit, 9.7 mV, 0.019.5 mA

20 mA, 500Ω

Display (LCD)| Humidity Values Resolution Setpoint Values| 3 digits

0.5

2 digits

Environment| Operation:

Climatic Conditions Temperature Humidity

| IEC 721-3-3

Class 3 K5

-40…70°C (-40…158°F)

<95 % rH not condensing

Standards| CE compliant to EMC Norm 2014/30/ EU, Low

Voltage Directive 2014/35/EU

Automatic electrical control and regulating devices

for domestic use and similar applications Degree of protection according to 60529

Protection class

| EN 61 000-6-1/ EN 61 000-6-3

EN 60 730-1 IP30

III (IEC 60536)

General| Housing material Mounting Plate

Weight Condair CRC (including packing)

| PC and ABS Galvanized steel 160 g (5.6 oz)

Wiring Diagrams

Wiring diagram CRC-NA for RS, EL, GS, US and SE

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-11

Wiring diagram CRC-NA for DL and ME

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-12

Wiring diagram CRC-NA with CHD-NA and APS for RS, EL, GS, US and SE

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-13

Wiring diagram CRC-NA with CHD-NA for DL and ME

condair-CRC-NA-2-10V-Wall-Humidity-Sensor-fig-14