condair DDC-NA Dehumidification 0-10V Digital Duct Humidistat Package
Product Information
The DDC-NA Dehumidification, 0-10V Digital Duct Humidistat Package is a package that includes a 2-10V Duct Sensor and a Wall Dehum Humidistat without a sensor. It is designed to measure and control the humidity levels in air ducts. The package is installed downstream of the steam distribution at a distance 1.5 times the absorption distance, which is typically 10-12 ft or 3-3.7m.
This document covers the operation and installation instructions for the following Condair digital humidistat package:
Mounting and Installation
1509857 – Duct Sensor Installation
Location
Refer to installation overviews in section 2.
The duct sensor should be installed directly on the duct in an area where the
air is well mixed with uniform flow.
- Used as supply air humidity sensor: If the sensor is used as a supply air humidity sensor it should be mounted downstream of the steam distribution at a distance 1.5 times the absorption distance (typically 10-12 ft or 3-3.7m).
- Used as return air humidity sensor: If the sensor is used as a return air humidity sensor it should be mounted close to the air inlet but downstream from a return fan if one is present.
Installation
- At the place of location drill a hole with a diameter of 16 mm (5/8″) as well as 4 holes for the self-tapping screws into the duct.
- Loosen the screw on the housing cover and open cover.
- Lead connecting cable through the cable gland and connect wires to the terminate according to the wiring diagram.
- Stick gasket on the sensor side centrally on the housing (self-adhesive).
- Insert the probe into the hole in the duct, then fix the housing to the duct using the 4 self-tapping screws provided.
- Close the cover and fix it with the screw (do not tighten the screw too much).
Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
2602802 – Dehum Humidistat w/o Sensor Installation
Location
Install the digital wall humidity controller in a protected and easily
accessible place at last 1.5 m above the floor to the wall (mounting on flush-
mounting or surface-mounting box).
Installation
Refer to installation overviews in section 2.
- Open the screw of the housing and remove mounting plate with the connecting unit.
- Connect wires of the connection cable to the terminals according to the wiring diagram.
- At the place of location fix mounting plate (plastic screw facing downwards) with two screws to the flush-mounting or wall-mounting box (see dimensional drawing).
- Carefully snap housing onto the mounting plate and fix it with the screw (do not tighten screw too much).
Note: We recommend using 18-gauge wire, and maximum <100 ft distance from the unit.
Installation overviews
CDC-NA 2602796/1509857
DDC-NA 2602796/2602802
Dimension
CDC-NA 2602796/1509857
DDC-NA 2602796/2602802
Wall Humidistat LCD Display
Configuration
Using keypad, set specified humidity. For general health and comfort, a
humidity setting of 50% is recommended.
Error Messages
- AL5 & AL7: Measured value of the external sensor fell below the lower limit of 5% RH. Check the cabling of the DDC and CDC. After eliminating the fault, acknowledge the alarm with the .
- Err2, 3 & 4: Hardware or memory problem. Replace device.
Sensor Calibration
Sensor inputs can be calibrated if needed
Setting Parameters to Configure the Controller
The control operation is defined by parameters set using the standard operation terminal. There are two levels:
- User/display parameters (password 0009)
- Control parameters (password 00241)
How to change the parameters:
User Parameters (Password 0009)
Table 1: User Parameters
Parameter | Description | Range | Default |
---|---|---|---|
UP 00 | Enable change of operation modes | ON, OFF | ON (Enabled) |
UP 01 | Enable change of setpoints | ON, OFF | ON (Enabled) |
UP 02 | State after power failure: |
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure
| 0, 1, 2| 2
UP 03| Celsius or Fahrenheit: ON = Fahrenheit, OFF = Celsius| ON, OFF| OFF
(Celsius)
UP 04| Select type of content for large digits (00= OFF): 01 = Input
02 = Setpoint
03 = Humidity Sensor
04 = External Temperature Sensor
| 00…04| 01
Control Parameters (Password 0241)
Note: Only experts should change these settings! See user parameter for
login procedure!
Table 2: Output Configuration
Parameter | Description | Range | Default |
---|---|---|---|
CP 00 | Minimum setpoint limit in humidification mode | 0..100% | 10% |
CP 01 | Maximum setpoint limit in humidification mode | 0..100% | 90% |
CP 02 | Start delay for fans |
(Time the fan runs before control output starts)
| 0…255 s| 10 s
CP 03| Stop delay for fan
(Time the fan keeps running after control output stops)
| 0…255 s| 90 s
Table 3: Temperature Setback Configuration – *For humidity control only
Parameter | Description | Range | Default |
---|---|---|---|
CP 04 | Enable temperature setback |
OFF = Temperature set back is disabled ON =Temperature setback is enabled
| ON, OFF| OFF
CP 05| Setpoint limit at full setback| 0..100 %| 20 %
CP 06| Lower temperature limit:
Outside temperature with maximum setback
The setback will be equal to the minimum setpoint limit
| -40…60°C
-40…160°F
| -30 °C (-22°F)
CP 07| Upper temperature limit:
Outside temperature at begin of setback
| -40…60°C 40…160°F| 0 °C (32°F)
CP 08| Number of seconds taken into account to calculate the average input
signal Low value = fast response
High value = slow response
| 0…100| 30
Product Specification
Power Voltage| Operating voltage Power consumption Terminal connection| 24 V AC 50/60 Hz ± 10 %, 24 VDC ± 10 %
Max. 3 VA
For wires 0.34…2.5 mm2 (AWG 24…12)
---|---|---
Signal input| Humidity sensor input| UI1
Signal Output| Analog Outputs Output Signal Resolution Maximum Load| A01
DC 0…10 VDC 39 mV, 0.078 mA
10 Ma (at 0…10 VDC)
20 Ma (at 0…20mA)
Environment| Operation:
Climatic Conditions Temperature Humidity
| IEC 721-3-3
Class 3 K5
0…50°C (32…122°F)
<95 % rH not condensing
General| Housing material Mounting Plate
Weight Condair CRC (including packing)
| ABS
Galvanized steel 260 g (9.2 oz)
Wiring Diagrams
Wiring diagram DDC-NA with CDC-NA for DA
Documents / Resources
|