ALDERON Industries PPRS-0001 Power Post Control Panel User Guide

June 9, 2024
ALDERON Industries

ALDERON Industries PPRS-0001 Power Post Control Panel User Guide
ALDERON Industries PPRS-0001 Power Post Control
Panel

Safety Guidelines

Warning IconsWARNING
Before proceeding with the installation or operation of this product, read all instructions thoroughly, as well as complying with all federal, state and local codes, regulations, and practices. This product must be installed by qualified personnel familiar with all applicable local electrical and mechanical codes. Refer to the National Electrical Code (NFPA 70). Failure to properly install and test this product can result in personal injury or equipment malfunction.

Installation Instructions

Step 1: Install Post

Determine location for the post in the ground near a tank and drill access holes for the float switch cables using the customer supplied conduit/fittings or Alderon’s riser connection kit. Route the cables through access holes and wire as described in step 5. Run the direct burial power wires underneath the bottom of the post as shown in the diagram.
Installation Instructions

Note: Seal all conduits to prevent moisture and gases from entering the post per local codes.

Step 2: Remove / Install Bottom Cover

Remove the bottom enclosure cover screw, slide directly downward (2A) and pull directly away (2B). To install, line up the bottom enclosure cover with the grooves (2B), then slide directly upward (2A) until it meets the top of the enclosure so the screw hole is lined up and replace the screw at the bottom of the enclosure.
Installation Instructions

**Step 3: Remove / Install Post Cap

**

Remove Post Cap:

  1. Remove Screws and Lift Cap Upwards

Install Post Cap:

  1. Position text FRONT (with arrows) Forward
  2. Align Fastener Holes
  3. Fasten Screws to Secure Cap to Post

Step 4: Installing Wire into WAGO

Before making wire connections and terminations, carefully read this step for proper functions of both types of WAGO connectors.

WARNING: Improper use of the connectors will cause damage, DO NOT use mechanical tools to open or close, hand usage only.

Wire Termination – Splice Connector WAGO (Fig. 1):

  1. Lift tab(s) upward.
  2. Insert wire(s) into slot.
  3. Press tab(s) downward.
  4. Make sure wire(s) are secured.

Wire Connection – Quick Snap Terminal WAGO (Fig. 2):

  1. Press tab(s) outward. DO NOT open past 40° angle.
  2. Insert wire(s) into slot.
  3. Press tab(s) inward.
  4. Make sure wire(s) are secured.
    Wire Connection

Step 5: Wiring and Piggyback Plug Connections
The wiring diagram shows 10 terminals on the quick snap terminal blocks that consists of five pairs of connections. Make sure to read and review the connector examples in step 4 for proper installation prior to wiring.
Note: The quick snap terminal blocks, are herein referred to as “termina ” for instruction purposes. The installation example shown is for 120VAC,  for 240VAC installation the neutral (N) wire would be replaced by line connection (L2) and white wire would include a red band to indicate the wire is hot.

  1. The first cable grip, starting at the right, has a cable grip divider allowing for two power sources to be brought into the enclosure. The right side of the cable grip is used for the pump power (attached in series). The line wire is connected to terminal 9 and neutral wire is terminated by the two-position Wago connector. The left side of the cable grip is used for the alarm/control power, which is connected to terminals 7 and 8. Terminal 7 is the neutral (N) connection and terminal 8 is the line connection (L1). The pump and alarm/control power ground wires are terminated using the three-position Wago connector. After bringing in the cables, firmly tighten the cable grip by twisting clockwise until securely fastened.
  2. The female receptacle comes pre-installed in the middle cable grip. The line wire is connected to terminal 10, neutral wire is terminated by the two-position Wago connector, and ground wire is terminated by the three-position Wago connector.
  3. The third cable grip has cable grip dividers allowing for three sensor connections. The pump control float switch is connected to terminals 1 and 2. The filter switch is connected to terminals 3  \and 4. The high level alarm float switch is connected to terminals 5 and 6. After bringing in the cables, firmly tighten the cable grip by twisting clockwise until securely fastened.
  4. NEVER leave ground wire(s) exposed, use provided Wago connector for wire termination

Wiring and Piggyback Plug Connections

OPTIONAL PIGGYBACK PLUG CONNECTIONS

  1. Plug the male end of the piggyback plug on the in-line pump switch power cable into the pre-installed female power receptacle inside the post (5A).
  2. Plug the male end of the pump power cable into the female end of the piggyback plug on the in-line pump switch power cable (5B) from #1.

PLUG CONNECTIONS

Step 6: Testing and Backfill

Make sure all steps of the installation and wiring process is completed and there is power to the product.

  1. TEST ALARM LEDs and BUZZER
    Press the test/silence pushbutton, lifetime pump run event counter statistic should display, then alarm LEDs should illuminate while cycling between red, green, blue, and off. The OLED screen should display a TESTING (COLOR) event for respective LEDs after event statistic is displayed. Last, the buzzer should annunciate and OLED screen should display a TESTING BUZZER event.

  2. TEST ALARM FLOAT SWITCH
    Activate the alarm float switch, the red LEDs should illuminate, flashing and the buzzer should annunciate. The OLED screen should display a HIGH LEVEL ALARM event.

  3. TEST ALARM SILENCE
    Press the test/silence pushbutton on the front of the enclosure while the alarm float switch is activated. The red LEDs should keep flashing and the buzzer should silence.

  4. TEST FILTER SWITCH
    Activate the filter switch, the amber LEDs should illuminate, flashing and the buzzer should annunciate. The OLED screen should display a FILTER ALARM event.

  5. TEST PUMP AND CONTROL/IN-LINE PUMP FLOAT SWITCH
    Make sure the tank has water to perform the testing. Activate the control/in- line pump float switch, the blue LEDs should illuminate and the OLED screen should display a PUMP RUN event and the pump amps are displayed.

  6. RECOMMENDED SYSTEM SETTINGS
    Alderon™ recommends changing the factory settings for: high amp level, extended pump run time, and gallons per minute.

  7. TEST WEEKLY
    To ensure the product is functioning properly, test once a week.
    BACKFILL: After installation and testing, backfill with dirt/soil.

MAIN MENU – System Normal From SYSTEM NORMAL screen, press the MENU button to access main menu and HAND/OFF AUTO will appear. Pressing MENU button from a blank screen will also access the main menu.

Menu System - Main Menu

1.0 | MAIN MENU – HOA Pump Mode
From HAND/OFF AUTO screen, press right arrow key for menu to view system override options. Press down arrow key to the RESETBLE HISTORY screen.

2.0 | MAIN MENU – Resettable History
From the RESETBLE HISTORY screen, press right arrow key for menu. Press down arrow key to the SETTINGS screen.

3.0 | MAIN MENU – Settings
From the SETTINGS screen, press right arrow key for menu to enter password and program system settings. Press down arrow key to the LIFETIME HISTORY screen.

4.0 | MAIN MENU – Lifetime History
From the LIFETIME HISTORY screen, press right arrow key for menu. Press down arrow key to the MODEL / FIRMWARE screen.

5.0 | MAIN MENU – Model/Firmware
From the MODEL/FIRMWARE screen, press down arrow key to bring you back to the HAND/OFF AUTO screen. Note: The down arrow key will cycle through the menu options until a specific option is selected using the right arrow key

2.0 | Main Menu – Resettable History

From the RESETBLE HISTORY screen, press right arrow key to access the menu for event statistics and then press down arrow key for the available events within this menu.

Resettable History

2.1 Pump Run Stats
2.2 Extended Pump Run Stats
2.3 High Amp Stats
2.4 Pump Float Stats
2.5 Relay Stats
2.6 Dose On Stats
2.7 Peak On Stats

2.8 High Level Alarm Stats
2.9 Filter Alarm Stats
2.10 Pump Fail Stats
2.11 Relay Fail Stats
2.12 System Fail Stats
2.13** Power Loss Stats

Press right arrow key for the individual stats of each event type listed above and data stored in the system. Each resettable history event stat has a clear history function. The non-volatile memory allows all settings and statistics to be retained during power outages.
Note: The down arrow key will cycle through all the resettable history menu options until a specific option is selected using the right arrow key as displayed on the screen. Press the left arrow key to exit from any screen. Press the test/silence pushbutton to exit the menu system.
Indicates Timed Dosing only
Indicates Demand Dosing only

3.0 | Main Menu – Settings Part I

Right arrow key from SETTINGS screen for menu, down arrow key to scroll.

3.1 Password (factory set to 1919)

  1. Password 0000 will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to accept password; press left arrow to exit
  5. Incorrect entry will exit user to the settings menu

Note: To change password, use up/down arrows until password screen reappears, then enter numeric values between 0000-9999, press MENU to save.

3.2 Normal LED Setting (factory set to LED On)

  1. Normally LED Off?, press MENU to turn LED off
  2. Normally LED On?, press MENU to turn LED on

3.3 Pump Run LED Setting (factory set to LED On)

  1. Pump Run LED Off?, press MENU to turn LED off
  2. Pump Run LED On?, press MENU to turn LED on

3.4 Silence Time Setting (factory set to 24 hours)

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

3.5 Extended Pump Run Time Setting (factory set to 30 minutes)

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

3.6 High Amp Level Setting (factory set to 15 Amps)

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

3.7 Gallons Per Minute Setting (factory set to Zero)

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit
3.0 | Main Menu – Settings Part II

Right arrow key from SETTINGS screen for menu, down arrow key to scroll.

3.8 Dose Setting (factory set to Timed Dosing)

  1. Demand Dose?, press MENU for Demand Dose
  2. Timed Dose?, press MENU for Timed Dose

3.9 Float Setting (factory set to Float Input)**

  1. In-line Float?, press MENU for In-line Float
  2. Float Input?, press MENU for Float Input

*3.10 Dose Off Time Setting (factory set to 10 seconds)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

*3.11 Dose On Time Setting (factory set to 5 seconds)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

*3.12 Peak Off Time Setting (factory set to 10 seconds)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

*3.13 Peak On Time Setting (factory set to 5 seconds)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

*3.14 Minimum Peak Dose Cycles Setting (factory set to 1)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3. Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

*3.15 End Dose Setting (factory set to Stop Dose)**

  1. Finish Dose?, press MENU for Finish Dose
  2. Stop Dose?, press MENU for Stop Dose

*3.16 Buzzer Delay (factory set to 20 seconds)**

  1. The current setting will appear on the screen
  2. Up or down arrow, increase/decrease selected digit
  3.  Right arrow, moves cursor to the right (blinking)
  4. Press MENU to save changes; press left arrow to exit

Settings Part II

4.0 | Main Menu – Lifetime History

From the LIFETIME HISTORY screen, press right arrow key to access the menu for event statistics and then press down arrow key for the available events within this menu.
4.1 Pump Run Stats
4.2 Extended Pump Run Stats
4.3 High Amp Stats
4.4 Pump Float Stats
4.5 Relay Stats
4.6 Dose On Stats
4.7 Peak On Stats

4.8 High Level Alarm Stats
4.9 Filter Alarm Stats
4.10 Pump Fail Stats
4.11 Relay Fail Stats
4.12 System Fail Stats**
4.13 Power Loss Stats

Lifetime History

Press right arrow key for the individual stats of each event type listed above and data stored in the system. The lifetime statistics are non-resettable and are displayed in Title Case format for visual separation from the resettable statistics, which are displayed in UPPERCASE format. The non-volatile memory allows all settings and statistics to be retained during power outages.

Note: The down arrow key will cycle through all the lifetime history menu options until a specific option is selected using the right arrow key as displayed on the screen. Press the left arrow key to exit from any screen. Press the test/silence pushbutton to exit the menu system.
Indicates Timed Dosing only
Indicates Demand Dosing only

Included with Product

  • (1) Power Post™; junction box and cable grips pre-installed on post
  • (1) Pre-installed, female, 15A, pump power receptacle (120VAC or 240VAC, voltage depends on model/part number)
  • (2) Wago connectors

Customer Support

Online
alderonind.com
Email
info@alderonind.com
QR Code
Scan code for full product details

Specifications

Pump Power Receptacle: 120VAC or 240VAC, 15A, 60Hz
Pump Power: 120VAC or 240VAC, 13A or 15A, 60Hz

Alarm Power: 120VAC, 60Hz (240VAC, 60 Hz available; consult factory)
Power Consumption: 14 Watts maximum (alarm condition)
Enclosure: Outdoor, rated Type 3R
Certifications: FCC Part 15 (US/Canada), CSA (US/Canada)

Power Post™ Control Panel – Features

  1. Power On Indicator – Green LEDs illuminate inside top cover of enclosure cover, power on indicators can be disabled in system settings
  2. Alarm Beacon – Alarm LEDs (various colors) illuminate inside the top cover of enclosure cover
  3. Pump Run Indicator – Blue LEDs illuminate inside top cover of enclosure cover, pump run indicators can be disabled in system settings
  4. System LED Indicators – Multiple color indicators will illuminate inside top cover of enclosure cover for visual indication of various system events and/or alarm conditions
  5. OLED Display Screen – Displays system functions in addition to LED indicators
  6. Menu Keypad – Toggle for system functions, program settings, and view statistics
  7. Test/Silence Pushbutton – Quick access to lifetime pump run event counter statistic, test or silence the alarm, or exit the menu system
  8. Alarm Buzzer – Annunciates to indicate an alarm event
  9. Quick Snap Terminal Blocks – Fast and easy connections for system wiring
  10. Control Relay – Controls current through pump circuit and is removable, ideal for systems with high usage environments
  11. Vented Post Cap – Allows airflow, prevents build up of gases/condensation inside post
  12. QR Code (not shown) – Scan for additional product information (alderonind.com)
  13. Cable Grips – Pre-installed for easy installation
  14. Pump Power Receptacle (not shown) – Pre-installed, female, 15A, available in either 120VAC or 240VAC (voltage depends on model/part number)
  15. Post – Provides wire routing access for system power, pump power, float switch, and sensor cables while protecting from water intrusion

Model Number Nomenclature

  1. Base Model (Power Post™ Control Panel)
  2. Alarm Options (15′ Alarm Float, 15′ Filter Switch)
  3. In-Line Pump Switch Options (15A, 15′ Wide Angle)
  4. Pump Voltage (120VAC Pump)
  5. Pump Control Float Options (15′ Wide Angle)
  6. Riser Kit/Access Options (2.5″ Riser Connection Kit)

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ALDERON Industries User Manuals

Related Manuals