invt EC-TX809 PROFINET I-O Communication Expansion Module
Product Information
EC-TX809 PROFINET I/O communication expansion module
The EC-TX809 PROFINET I/O communication expansion module is a communication
module designed for use with the control box. It allows for PROFINET
communication and can be installed in expansion slots of the control box. The
module provides various indicators and interfaces for easy monitoring and
connection.
Specifications
Parameters| Working temperature| Storage temperature| Relative humidity|
Running environment| Installation method| Ingress protection (IP) rating| Heat
dissipation method| Communication rate| Network topology
---|---|---|---|---|---|---|---|---|---
Value| TBD| TBD| TBD| TBD| TBD| TBD| TBD| TBD| TBD
Product Usage Instructions
Installation and Wiring
Before installing the EC-TX809 PROFINET I/O communication expansion module,
ensure that the device is powered off. Follow the instructions below:
Installation Precautions
- There are 3 expansion module interfaces on the control box (expansion slot 1, expansion slot 2, expansion slot 3). You can use any of these slots according to the actual wiring.
- It is recommended to install the PROFINET I/O expansion module in expansion slot 3.
- Required tools: Phillips screwdriver PH1, straight screwdriver SL3
Installation Instructions
- Place the expansion module in the corresponding position of the control box expansion slot 3, align it with the slot, and then buckle it together.
- Align the expansion module positioning hole with the positioning stud.
- Fix with a M3 screw. The installation is complete.
Note : The expansion module and control box are electrically connected through slots. Please install them in place. To ensure the reliable operation of the expansion module and meet EMC requirements, please tighten the screws according to the recommended torque for reliable grounding.
Preface
Thank you for choosing INVT EC-TX809 PROFINET I/O communication expansion
modules.
EC-TX809 is a PROFINET I/O industrial Ethernet communication module that needs
to be used with the GD880 series VFD control box. It communicates with the
Ethernet master node through the PROFINET communication protocol.
This manual describes the product overview, installation, wiring, and
commissioning instructions. Before installing the VFD, read this manual
carefully to ensure the proper installation and running with excellent
performance and powerful functions into full play.
Product Features
- Supporting the PROFINET protocol and PROFINET I/O devices.
- Has two PROFINET I/O ports
- With a communication rate up to 100Mbit/s, and a short communication cycle
- Supporting line and star network topologies
Product Overview
Model description
Specifications
Table 1-1 Specifications
Parameters | Specification |
---|---|
Working temperature | -10–50ºC |
Storage temperature | -20–60ºC |
Relative humidity | 5%–95% (No condensation) |
Running environment | No corrosive gas |
Installation method | Fixed with snap-fits and screws |
Ingress protection (IP) rating | IP20 |
Heat dissipation method | Natural air cooling |
Communication rate | 100M bit/s |
Network topology | Supporting line and star network topologies |
Structure
Table 1-2 Component description
No. | Name | Description |
---|
1
|
STATUS
Bus status indicator (green)
| On: No network connection
Blinking (On: 500ms; Off: 500ms): Network connection with PROFINET controller is normal, but the communication is not established.
Off: The communication with the PROFINET controller
has been established.
2| FAULT
Fault indicator (red)
| On: PROFINET diagnosis exists. Off: No PROFINET diagnosis.
3| Installation fixing hole| To fix the expansion module and maintain a good
connection of the PE layer.
4
| X1-PROFINET
communication interface
|
Communication interface 1
5
| X2-PROFINET
communication interface
|
Communication interface 2
6| Nameplate| Including the model and sequence number of the expansion module
7| Connection port| For electrical connection with the control box.
8| Positioning hole| To align the expansion module and control box for easy
installation
Installation and wiring
Installation precautions
WARNING|
Make sure the device have been powered off before installation.
---|---
Note
| l There are 3 expansion module interfaces on the control box (expansion slot 1, expansion slot 2, expansion slot 3). You can use any of these slots according to the actual wiring.
l It is recommended to install the PROFINET I/O expansion module in the expansion slot 3.
Required tools: Phillips screwdriver PH1, straight screwdriver SL3
Table 2-1 Screw torque requirements
Screw size | Fastening torque |
---|---|
M3 | 0.55 N·m |
Dimensions
The size of the PROFINET I/O expansion module is 73.5×74×23.3 mm (WHD), as shown in Figure 2-1.
Installation instructions
It is recommended to place the PROFINET I/O expansion module at expansion slot 3 of the control box. The following is an example of the installation at slot 3.
- Step 1 Place the expansion module in the corresponding position of the control box expansion slot 3, align it with the slot, and then buckle it together.
- Step 2 Align the expansion module positioning hole with the positioning stud.
- Step 3 Fix with a M3 screw. The installation is complete.
Note:
- The expansion module and control box are electrically connected through slots. Please install them in place.
- To ensure the reliable operation of the expansion module and meet EMC requirements, please tighten the screws according to the recommended torque for reliable grounding.
Disassembly instructions
You can disassemble the module by reversing the order of steps described in section 2.3 Installation instructions.
- Step 1 Disconnect the power supply and disassemble all cables connected to the expansion module.
- Step 2 Use a Phillips screwdriver to remove the grounding screw of the module.
- Step 3 Pull the module out to a suitable position.
User’s wiring terminal Table 2-2 Function definition of RJ45 interfaces
X1–X2 terminals | Pin | Definition | Description |
---|
1615 141312 11 10 9 8 7 6 5 4 3 2 1
| 1, 9| TX+| Transmit Data+
2, 10| TX-| Transmit Data-
3, 11| RX+| Receive Data+
4, 12| n/c| Not connected
5, 13| n/c| Not connected
6, 14| RX-| Receive Data-
7, 15| n/c| Not connected
8, 16| n/c| Not connected
Wiring precautions
The PROFINET I/O communication expansion module adopts standard RJ45 interfaces, which can be used in a linear network topology and a star network topology. The electrical connection diagrams are shown in Figure 2-3 and Figure 2-4.
Note : For the star network topology, you need to prepare PROFINET switches.
Commissioning instruction
Table 3-1 Function code parameters related to the PROFINET expansion module
Function code| Name| Description| Setting range|
Default
---|---|---|---|---
P41.00
| Module online status|
Bit0–Bit8
| Online status of modules in expansion slots
(0: Offline 1: Online)
|
0–1
|
0
P41.01
| PROFINET
slave station number
| 1–125
This variable is automatically assigned
by the PLC.
|
1–125
|
1
P38.00
|
Bus adapter supporting bus type
| 0: None
1: PROFIBUS-DP module 2: PROFINET I/O module 3: CANopen module
4: EtherNET module
5: EtherCAT module
6: DeviceNet module
|
0–6
|
2
P02.00
|
Remote control channel selection
| Remote control channel selection 0: Bus adapter A
1: Bus adapter B
2: Modbus (addresses 0x4200, 0x4201) 3: Terminal start/stop module (IN1, IN2, IN3)
|
0–3
|
0
Note:
- When two identical communication expansion modules are mounted at the same time, only the expansion module at the slot with a small label number is functional, while the other expansion module is used for redundancy. For example, when two PROFINET expansion modules are inserted at slot 1 and slot 2 respectively, the PROFINET module at slot 1 is valid.
- For other parameter settings of the EC-TX809 PROFINET expansion module, see the software manuals of the GD880 series products.
Copyright INVT
Manual information may be subject to change without prior notice.
202310 (VI.O)