Macurco CD-6B CO2 Gas Detection Application User Guide
- June 13, 2024
- MaCURCO
Table of Contents
- GAS DETECTION 101
- PARKING GARAGES
- CAR DEALERSHIPS / MAINTENANCE BAYS
- AMBULANCE / FIRETRUCK BAYS
- LOADING DOCKS
- BEVERAGE DISPENSING
- BREWERIES / WINERIES
- RESTAURANTS / COMMERCIAL KITCHENS
- BOILER / MECHANICAL ROOMS
- GENERAL WAREHOUSE / FORKLIFTS
- BATTERY CHARGING / DATA CENTERS
- GROW / EXTRACTION FACILITIES
- ICE RINKS
- CRYOSAUNA / LABS
- LANDFILLS
- DVP-120 CONTROL PANEL OUTPUT OPTIONS
- MACURCO COMMERCIAL PRODUCT OVERVIEW
- TYPES OF SYSTEMS
- DETECTION AND VENTILATION CONTROL PANEL (DVP-120)
- ADDRESSABLE GAS DETECTION AND CONTROL (DVP-120M / DVP-120B)
- COMMON ACCESSORIES
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APPLICATION GUIDE
This publication is intended to serve as a guideline for the use of the
Macurco products. It is not to be considered all-inclusive, nor is it intended
to replace the policy and procedures for any facility. If there are any doubts
about the applicability of the equipment to your situation, consult an
industrial hygienist or call Macurco Technical Service at
1-877-367-7891
GAS DETECTION 101
THREE TYPICAL GAS HAZARDS TO BE AWARE OF
FLAMMABLE
- Having the right combination of an ignition source, oxygen, and fuel in a gas or vapor form provides for the necessary means to create a fire or explosion
- The minimum concentration of combustible gas or vapor necessary to support its combustion in air is defined as the Lower Explosive Limit (LEL). Below this level, the gas mixture is too “lean” to burn
- The maximum concentration of a gas or vapor that will burn in the air is defined as the Upper Explosive Limit (UEL). Above this level, the mixture is too “rich” to burn
- The range between the LEL and UEL is known as the flammable range for that gas or vapor
- Gases such as Methane, Hydrogen, Propane
TOXIC
- Some gases are poisonous and are dangerous to life at very low levels. Some toxic gases have distinct odors (H2 S, NH3 ) and others have no odors at all (CO)
- Very low levels inhaled, ingested, or absorbed through the skin pose adverse effects from exposure
- Gases such as Carbon Monoxide, Nitrogen Dioxide, Ammonia, Hydrogen Sulfide
ASPHYXIANT OR OXYGEN DEPLETING
- Where Oxygen levels are too rich, environments have the potential to become an explosive environment
- Where Oxygen levels are too low, people within the environment can succumb to asphyxiation
- Gases such as Oxygen, Carbon Dioxide, Nitrogen, Helium, Argon
PARKING GARAGES
Enclosed parking garages have long been using detection for vehicle exhaust.
The primary gases present are Carbon Monoxide and Nitrogen Dioxide resulting
from incomplete combustion within vehicles.
A prominent benefit of installing a gas detection system in a garage is the
cost savings on electrical and energy consumption. On average within one year
of installing a system, the money spent on a gas detection system is recouped.
According to IMC 2018 – the only alternative to running fans at full speed
every hour of every day is to install a CO/NO2 system.
COMMON GASES:
Carbon Monoxide, Nitrogen Dioxide, Combustibles
MACURCO PRODUCTS: CX-6 (CO & NO2), CM-6 (CO), TX-6-ND (NO2), GD-6
(Combustibles)
CAR DEALERSHIPS / MAINTENANCE BAYS
Car dealerships and maintenance bays are considered occupied spaces.
Ventilation equipment is heavily relied upon to mitigate vehicle exhaust that
results in potential fumes from Carbon Monoxide and Nitrogen Dioxide.
A prominent benefit of installing a gas detection system in a garage is the
cost savings on electrical and energy consumption. On average within one year
of installing a system, the money spent on a gas detection system is recouped.
According to IMC 2018 – the only alternative to running fans at full speed
every hour of every day is to install a CO/NO2 system.
COMMON GASES: Carbon Monoxide, Nitrogen Dioxide, Combustibles
MACURCO PRODUCTS: CX-6 (CO & NO2), CM-6 (CO), TX-6-ND (NO2),GD-6
(Combustibles)
AMBULANCE / FIRETRUCK BAYS
Ambulance and firetruck bays are typically connected to another occupied
building where people reside. It is extremely critical to monitor toxic gases
and exhaust appropriately to ensure the safety of the residents and crews.
A prominent benefit of installing a gas detection system in a garage is the
cost savings on electrical and energy consumption. On average within one year
of installing a system, the money spent on a gas detection system is recouped.
According to IMC 2018 – the only alternative to running fans at full speed
every hour of every day is to install a CO/NO2 system.
COMMON GASES: Carbon Monoxide, Nitrogen Dioxide, Combustibles
MACURCO PRODUCTS: CX-6 (CO & NO2), CM-6 (CO), TX-6-ND (NO2),GD-6
(Combustibles)
LOADING DOCKS
With large vehicles coming and going regularly, vehicle exhaust is a major
hazard within loading docks. If not properly ventilated, employees could be
exposed to toxic fumes regularly.
Much like a parking garage, a gas detection system can cut costs on
ventilation equipment operations and noise pollution.
According to IMC 2018 – the only alternative to running fans at full speed
every hour of every day is to install a CO/NO2 system.
COMMON GASES: Carbon Monoxide, Nitrogen Dioxide, Combustibles
MACURCO PRODUCTS: CX-6 (CO & NO2), CM-6 (CO), TX-6-ND (NO2), GD-6
(Combustibles)
BEVERAGE DISPENSING
New legislation dictates any storage of a Carbon Dioxide 100lb tank or more
for beverage dispensing must result in a Carbon Dioxide monitor present. This
is a state by state code which is indicated on what year of IFC the State has
adopted.
Restaurants & Bars / Gas Stations / Cafeterias etc. are all common
applications where the Carbon Dioxide code is prevalent.
Per IFC 2015 (5307.1) and IFC 2018 (5307), there are different alarm values
required.
• 2015 – Activate alarm at 5,000ppm of CO2 (CD-6MC)
• 2018 – Activate low alarm at 5,000ppm of CO2 (CD-6B)
• 2018 – Activate high alarm at 30,000ppm of CO2 (CD-6B)
COMMON GASES: Carbon Dioxide
MACURCO PRODUCTS: CD-6G (CO2), CD-6B (CO2)
BREWERIES / WINERIES
High levels of Carbon Dioxide are found in pits, storage tanks, bottling rooms
and the fermentation process within wineries. Carbon Dioxide is heavier than
air and will fall to the floor if leaking from a tank displacing the Oxygen.
Carbon Monoxide has the potential to be present in these applications due to
the incomplete combustion of combustible gases during their manufacturing
process and heating of the venue.
OSHA and NIOSH have regulations on exposure to these gases (CO, CO2,
Combustible) over some time.
COMMON GASES: Carbon Dioxide, Carbon Monoxide, Oxygen Deficiency, Combustibles
MACURCO PRODUCTS: CD-6MC (CO2), CD-6B (CO2), CM-6 (CO), OX-6 (O2 ), GD-6
(Combustibles)
RESTAURANTS / COMMERCIAL KITCHENS
Appliances in kitchens such as grills, stoves, and fryers are often using
natural gas and/or propane for their heating source. Carbon Monoxide is a by-
product of these gases and if methane (natural gas) or propane leak it may
cause an explosion.
Legislation for commercial kitchens may change depending on the state but
following NFPA 54 regarding the National fuel gas code is a good place to
start.
COMMON GASES: Carbon Monoxide, Combustibles
MACURCO PRODUCTS: CM-6 (CO), GD-6 (Combustibles)
BOILER / MECHANICAL ROOMS
Mechanical rooms are often forgot about as unsafe spaces. Since Methane and/or
Propane are commonly used for heating, a leak can become catastrophic. If the
gases are not fully combusted a harmful poisonous gas can result in Carbon
Monoxide. Carbon Monoxide poisoning can become fatal if concentrations become
high enough.
Chillers are also found in mechanical rooms and have the potential to leak
refrigerant gases and that can become costly and extremely hazardous.
PER OSHA – 50ppm of CO Permissible Exposure Level over 8 hours.
COMMON GASES: Carbon Monoxide, Combustibles, Refrigerants
MACURCO PRODUCTS: CM-6 (CO), GD-6 (Combustibles), RD-6 (Refrigerants)
GENERAL WAREHOUSE / FORKLIFTS
Warehouses are a busy place with personnel and forklifts. Whether gas powered
or battery powered, gases are present. Carbon Monoxide and Nitrogen Dioxide
are present due to vehicle exhaust and Hydrogen gas can be present due to the
charging of the forklift batteries.
Fixed gas detection is present in these applications for the safety of
employees and the prevention of loss of goods due to explosions from Hydrogen.
COMMON GASES: Carbon Monoxide, Nitrogen Dioxide, Hydrogen, Combustibles
MACURCO PRODUCTS: CX-6 (CO & NO2 ), CM-6 (CO), TX-6-ND (NO2 ), GD-6
(Combustibles)
BATTERY CHARGING / DATA CENTERS
Hydrogen is a common gas present in any atmosphere where battery charging
exists. Golf cart charging/storage facilities with forklifts have become a
popular application due to the volatile nature of Hydrogen gas.
Data centers are also using Hydrogen as a footprint to replace greenhouses
gases that in the past were produced at much higher levels.
The Uniform Fire Code, International Fire Code allows Hydrogen levels at 1% by
volume or 25% of the lower explosion limit (LEL).
COMMON GASES: Hydrogen
MACURCO PRODUCTS: GD-6 (Combustibles)
GROW / EXTRACTION FACILITIES
The grow industry has evolved and become one of the hotbeds in America.
Whether growing tomatoes, lettuce or cannabis, gas detection is prevalent
throughout this application.
Carbon Dioxide is injected into these rooms at a constant PPM value of
1000-2000ppm. Other gases found within these grow houses are Carbon Monoxide
and Oxygen.
Everyday consumer products like lettuce, tomatoes, and others are being
cultivated indoors. These operations also are injecting Carbon Dioxide into
the growth areas for the optimum product.
COMMON GASES: Carbon Dioxide, Carbon Monoxide, Oxygen (enrichment or
depletion), Combustibles
MACURCO PRODUCTS: CD-6G (CO2), CD-6B (CO2), CD-6MC (CO2, CM-6 (CO), OX-6 (O2),
GD-6 (Combustibles)
ICE RINKS
Several gases can be found in ice rinks but Ammonia is the most common gas as
it is a chilling agent to keep the ice from melting. Exposure to high
concentrations of Ammonia can cause extreme health issues and needs to be
constantly monitored.
Other gases that can be found include Carbon Monoxide and Combustible gases
due to the vehicles on ice.
COMMON GASES: Ammonia, Carbon Monoxide, Combustibles
MACURCO PRODUCTS: TX-6-AM (NH3 ), CM-6 (CO), GD-6 (Combustibles)
CRYOSAUNA / LABS
Many labs use inert gases such as Nitrogen, Helium, and Argon during their
processes. These inert gases can readily deplete Oxygen level and cause
asphyxiation.
Cryosaunas are popping up everywhere as a new way to rehabilitate the body.
This cold chamber uses liquid Nitrogen to get temperatures below -100 degrees
Fahrenheit. Oxygen depletion has become a concern should a tank ever leak.
Storage of Combustible gas tanks in labs also have the potential to leak
combustible gases.
COMMON GASES: Oxygen (depletion & enrichment), Combustibles
MACURCO PRODUCTS: OX-6 (O2), GD-6 (Combustibles)
LANDFILLS
Due to growing cities, old landfills are being converted into commercial or
residential developments. Due to the dangers of methane seeping up through the
ground the need to monitor methane levels is being required.
The decomposition of garbage results in both Methane and Hydrogen Sulfide
being by-products in these environments. These landfills can have dangerous
gases rising to the surface or accumulating in the area, Methane and/or
Hydrogen Sulfide. High levels of Methane can displace Oxygen in the air
resulting in an array of health issues and at high concentrations can be
explosive. Hydrogen Sulfide is a toxic gas that has a pungent rotten egg smell
and very high levels can be deadly.
Common Gases: Methane, Hydrogen Sulfide
Macurco Products: GD-6 (Combustibles), TX-6-HS (HS)
MACURCO CONTROL PANEL OVERVIEW
DVP FAMILY DVP-120 (Analog), DVP-120M (Digital), DVP-120B/120C (Digital
w/ BACnet Output), DVP-1200 (Digital, BACnet IP, 4-20 mA Outputs)
Key Features:
- 12 analog (4-20mA) sensor connections
- DVP-120M: 87 digital sensor connections (RS-485) + 12 analog (4-20mA) sensor connections
- Three 10A SPDT fan/alarm relays
- Two 24VDC drivers for horn/strobe
- Compatible with Macurco 6-Series
- Auto recognizes Macurco detectors
- Settings are customizable, default is per OSHA
- DVP-120B: BACnet MSTP output
- DVP-120C: Title 24 compliant (CO & NO2 only)
- DVP-1200: BACnet IP, 4-20 mA outputs
DVP-120 CONTROL PANEL OUTPUT OPTIONS
| DVP-120| DVP-120M| DVP-120B| DVP-120C| DVP-1200
---|---|---|---|---|---
Analog Connections| 12| 12| 0| 0| 0
Digital Connections| 0| 87| 99| 99| 192
10 AMP Relays| 3| 3| 3| 3| 8*
24VDC Output| 2| 2| 2| 2| 4
BacNET| N/A| N/A| N/A| |
Title 24| N/A| N/A| | |
MACURCO COMMERCIAL PRODUCT OVERVIEW
Key Features:
- Easy installation to 4×4 electrical boxes via mud plate
- User-selectable settings (Default to industry standards) via two-button interface
- 5 A SPDT fan relay, 0.5A alarm relay to control fans, valves, louvers, horn, and strobes
- 4-20mA output to control VFD’s and send to BMS
- LED display to easily show gas concentrations
- Field calibration kits available
6-SERIES DETECTOR OUTPUT OPTIONS
TYPES OF SYSTEMS
STAND-ALONE DETECTORS
Dry contact relays or 4-20mA outputs to control fans, louvers, valves, horn
and strobes, etc.
- The 6 and 12 series gas detectors can be used as a stand-alone setup
- This family of detectors is offered in low voltage or line voltage and can tie directly into many different pieces of equipment using one of the two dry contact relays or the 4-20mA output
- Customizable settings are done from each detector
DETECTION AND VENTILATION CONTROL PANEL (DVP-120)
4 conductor homerun 2 for power, 2 for signal
- The DVP-120 has the capacity to handle up to 12 of the 6 series detectors via a 4-wire homerun from each detector
- The DVP-120 has three 10 amp form relays along with two 24VDC outputs
- Any combination of gases within the 6-series will work with the DVP-120
ADDRESSABLE GAS DETECTION AND CONTROL (DVP-120M / DVP-120B)
Use sheilded 3-conductor wire with one twisted pair providing a pair for signal (A&B), common (COM) and shield ground (SHD) connections.
- DVP-120M connects to 87 addressable 6 series detectors using the MRS-485 on each of the detectors in the field converting the analog signal to a digital signal
- Cost of installation decreases due to a daisy chain loop, equaling less wire and conduit costs
- The DVP-120M has three 10-amp form C relays along with two 24VDC outputs
- The DVP-120B adds an additional BACnet MSTP output being the major difference from the DVP-120M
ADDRESSABLE WITH ANALOG OUTPUT (DVP-1200)
- DVP-1200 connects up to 192 addressable 6 series detectors using the MRS-485 on each of the detectors in the field converting the analog signal to a digital signal
- Four 10-amp form C relays with the ability to add an additional 4 relay board if needed. Also includes four 24 VDC outputs
- Includes three 4-20mA outputs for VFD control
- Includes 2 Remote Relay outputs for the optional RR-24 (Remote Relay)
- Event Logging found within DVP-1200 including Trouble/Warning/Alarms
- BACnet IP output as well as a USB port for firmware upgrades
COMMON ACCESSORIES
- Horn/strobe combo with temporal 4 option
- MRS-485 modbus adapter for addressable systems
- Calibration/test kits
- Weatherproof/duct mounting housings
- Power supplies
MAINTENANCE
DEMONSTRATION AND TRAINING
Inspect the components, equipment installation and electrical connections for
optimum functionality of the product. Test the alarm setpoints of the gas
detection system with calibration and test gases and verify the sequence of
operation. Perform emonstrations and train maintenance personnel to adjust,
operate, troubleshoot, calibrate and maintain the gas detection and
ventilation control systems. Calibration and test kits should be provided with
the gas detection system. Calibration and test intervals must comply with the
manufacturer’s recommendations. If required, prepare a written report to
record test procedures, test results, and corrective actions. The report
should also cover the requirements for accessories like the acceptability of
alarm types, signs and protective equipment.
Any repair or replacement of malfunctioning units should be performed by
Macurco.
Celebrating 50 years of gas detection, the Macurco product line offers
equipment for residential, commercial and industrial applications. Since 1972
Macurco has been providing detection options for a number of different gases
including carbon monoxide (CO), nitrogen dioxide (NO2 ), hydrogen (H2 ),
propane (LP), methane (natural gas), hydrogen sulfide (H2 S), ammonia (NH3),
oxygen (O2), carbon dioxide (CO2) and refrigerants. Headquartered in Sioux
Falls, South Dakota, Aerionics manufactures Macurco Gas
Detection products. Aerionics strives to provide the highest quality
detection, safety and security solutions to customers worldwide. Whether you
are looking for gas detection for a security system, building automation or
HVAC system, for personal safety or for
monitoring specific gases in potentially hazardous environments, Macurco has a
gas detector to meet your needs.
GAS DETECTION IS ALL WE DO, AND WE DO IT BEST.
Visit www.macurco.com for additional product
information and training.
www.facebook.com/macurcogasdetection
www.linkedin.com/company/macurco-gas- detection
Manufactured by Aerionics, Inc. Sioux Falls, SD
Phone: 1- 877-367-7891 – Email:
info@macurco.com –
www.macurco.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>