MACURCO TXP-WABX Wireless Alarm Bar Instruction Manual
- June 14, 2024
- MaCURCO
Table of Contents
TracXP™ TXP-WABX
Wireless Alarm Bar
Instruction Manual
IMPORTANT: Read and understand contents of this manual prior to operation. Keep these user instructions for reference.
TXP-WABX Instruction Manual (Rev. 1.0)
Warnings
Warning – High voltage may be present, risk of electric shock. DO NOT open when energized, disconnect power before opening.
Warning – Hot surfaces. External surfaces and internal components may be hot after operation, take care when handling the equipment.
Please see individual product instruction manual. See Table 1 for Instruction Manual Document Number.
Rating & Marking Information
All individual unit ratings must be suitable for the installation.
Please see individual product instruction manual. See Table 1 for Instruction
Manual Document Number.
Special Conditions of Use
Please see individual product instruction manual. See Table 1 for Instruction Manual Document Number.
Component Part # Reference | Component Description | Document Number |
---|---|---|
TXP-WAR | TXP-WAR Wireless Alarm Relay |
34-2900-0208-0
D2xB1X10| 10 Joule Xenon Strobe Beacon|
D211-00-201-IS
D2xS1| Alarm Horn Sounder|
D189-00-001-IS
D2xJ1| Junction Box| D211-00-501-IS
Table 1: Product Instruction Manual Reference
Location and Mounting
The location of the Alarm Bar should be made with due regard to the area over
which the warning signal must be visible/audible. It should only be fixed to
poles that can bear the weight of the unit.
The Alarm Bar should be secured to a pole using supplied TXP-WABX Pole
Mounting Kit (Pole size up to 4” NPS).
To mount the unit to poles up to size NPS 4”, the pole mount kit should be
used (Fig. 1b, 1c). The unit should be mounted using all supplied clamps as
shown.
See document D214-00-010-IS for pole mount assembly.
Access to the Enclosure
Warning – High voltage may be present, risk of electric shock. DO NOT open when energised, disconnect power before opening.
Warning – Hot surfaces. External surfaces and internal components may be hot after operation, take care when handling the equipment.
In order to connect the electrical supply cables to the junction box it is necessary to remove the cover to gain access to the chamber. To access the chamber, loosen the four M4 posi pan head screws and remove the cover. (See figure 2).
TXP-WABX Instruction Manual (Rev. 1.0)
To replace cover, check that the ‘O’ ring seal is in place.
Carefully push the cover in place. Insert and tighten down M4 screws and fibre
washers.
Power Supply Selection
The Alarm Bar accepts power from a supply providing 115 VAC 50/60Hz. This is converted to 24 VDC via the onboard transformer, which provides DC power to the alarm horn, beacons, and wireless relay.
Please see individual product instruction manual for component Voltage Range, Current and Max Current values.
Selection of Cable, Cable Glands, Blanking Elements & Adapters
Please see individual product instruction manual.
The Alarm Bar is supplied with the following cable entries:
- 2 x 1/2″ NPT
Earthing
The Alarm Bar is provided with an M4 earth post on the plate. External earthing connections should be made to the M4 earthing post (fig. 3) using a ring crimp terminal to secure the earth conductor to the earth stud.
Cable Connections
Electrical connections are to be made into the terminals located in the junction box enclosure. See section 5 of this manual for access to the enclosure. Wires with cross sectional area of 0.5mm² to 2.5mm² may be connected to the terminals. Wires should be stripped to 8mm.
Wires may also be fitted using ferrules. Connections should be tightened with torque 0.56 Nm / 5 Lb-in. When connecting wires to the terminals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks. This is particularly important when using cables with large cross-sectional areas such as 2.5mm².
Wiring
Interchangeable & Spare Parts
The Beacon lens cover is interchangeable, contact Macurco for a replacement lens cover available in various colors.
To change the lens cover, unscrew the 4-off M5 posi pan head screws, spring and flat washers using a screw driver. Remove the wire guard and replace the old lens cover with the new lens cover.
Maintenance, Overhaul and Repair
Please see individual product instruction manual. See Table 1 for Instruction Manual Document Number.
Macurco Gas Detection Product limited warranty
Macurco warrants the TXP-WABX will be free from defective materials and
workmanship for a period of two (2) years from the date of manufacture,
provided it is maintained and used in accordance with Macurco instructions
and/or recommendations. If any component becomes defective during the warranty
period, it will be replaced or repaired free of charge, if the unit is
returned in accordance with the instructions below. This warranty does not
apply to units that have been altered or had repair attempted, or that have
been subjected to abuse, accidental or otherwise. The above warranty is in
lieu of all other express warranties, obligations or liabilities. THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED
TO A PERIOD OF TWO (2) YEARS FROM THE PURCHASE DATE. Macurco shall not be
liable for any incidental or consequential damages for breach of this or any
other warranty, express or implied, arising out of or related to the use of
said gas detector. The manufacturer or its agent’s liability shall be limited
to replacement or repair as set forth above. Buyer’s sole and exclusive
remedies are the return of the goods and repayment of the price, or repair and
replacement of non-conforming goods or parts.
Macurco Gas Detection
1504 West 51st Street
Sioux Falls, SD 57105
United States of America
Technical Support Contact Information
Phone : 1-844-325-3050
Fax : 1-605-951-9616
Email : support@tracxp.com
Website : www.tracxp.com/support/
General Contact Information
Phone : 1-877-367-7891
Fax : 1-605-951-9616
Email : info@tracxp.com
Website : www.tracxp.com
References
- TracXP Industrial Gas Solutions - Macurco Gas Detection
- TracXP Industrial Gas Solutions - Macurco Gas Detection
Read User Manual Online (PDF format)