MACURCO GD-6 Florida Boiler Code Instruction Manual

May 15, 2024
MaCURCO

MACURCO GD-6 Florida Boiler Code

MACURCO-GD-6-Florida-Boiler-Code-product

Product Information

Specifications:

  • Product Name: GD-6 Gas Detector
  • Model: CM-6 CO Detector
  • Product Type: Gas Boiler Controller
  • Compliance: Florida Boiler Code, Carbon Monoxide Code, NFPA 720
  • Additional Accessories: GBC KEY FEATURES

Product Usage Instructions

Installation Requirements:

Ensure compliance with subsection 509.211(4), F.S., and NFPA 720 regulations for carbon monoxide detector devices installation. The detector devices must bear the label of a nationally recognized testing laboratory and comply with the Underwriters Laboratories, Inc., Standard 2075.

Integration with Fire Detection System:

Integrate the devices with the public lodging establishment’s fire detection system or connect them to a control unit or combination system that will prevent the boiler from operating until manually reset.

Contact Information:

For more information or assistance, please contact Branden Dewing at 605-951-3994 or email at BDEWING@MACURCO.COM. You can also visit the website www.macurco.com or contact customer support at 1-877-367-7891.

Address: 1504 W. 51st Street Sioux Falls, SD 57105

FAQ

  • Q: How often should the gas detector be tested?
    • A: It is recommended to test the gas detector at least once a month to ensure proper functioning.
  • Q: Can the gas detector be installed outdoors?
    • A: It is not recommended to install the gas detector outdoors as it is designed for indoor use only.

Carbon Monoxide (CO)

  1. Where required by subsection 509.211(4), F.S., the installation of carbon monoxide detector devices shall comply with the requirements of NFPA 720, as adopted in rule 69A-70.005, F.A.C.
  2. Detector devices shall bear the label of a nationally recognized testing laboratory and have been tested and listed as complying with the most recent Underwriters Laboratories, Inc., Standard 2075, as adopted in rule 69A-70.005, F.A.C.
  3. The requirements herein are in addition to the requirement imposed by subsection 509.211(4), F.S., that states devices shall be integrated with the public lodging establishment’s fire detection system or connected to a control unit or combination system that will prevent the boiler from operating until it is reset manually.
  4. Business owners with boilers required to be inspected in accordance with The Boiler Safety Act, chapter 554, Florida Statutes, must post in the boiler room the “Certificate of CarbonMonoxide Detector Installation http://www.flrules.org/Gateway/reference. asp?No=Ref-08919,” Form DFS-K3-2170 (effective September 2017), which is hereby adopted and incorporated by reference, must be signed by a state-licensed alarm system contractor, a state-certified electrical contractor, or a state-licensed boiler installer indicating the required detector has been installed and has been integrated with the public lodging establishment’s fire detection system or boiler safety circuit as described and required by this rule. A copy of Form DFS-K3-2170 may be obtained by written request to the Bureau of Fire Prevention, Boiler Safety Section, 200 East Gaines Street, Tallahassee, Florida 32399-0342.

CM-6 KEY FEATURES

  • 0-200 PPM range
  • Digital display / onboard buzzer
  • 2 onboard relays to disable & engage horn/strobes
  • Easy installation to 4×4 box
  • End-of-life notification

GBC KEY FEATURES

  • 24V Input
  • Shutdown up to 8 boilers individually
  • Customize up to 8 10A SPDT relays
  • 24VDC driver for horn/strobe

Additional Accessories

MACURCO-GD-6-Florida-Boiler-Code-fig
\(2\)

CONTACT

FOR MORE INFORMATION PLEASE CONTACT

BRANDEN DEWING

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals