Simplex 4099-9006 Addressable Manual Station Instruction Manual

October 31, 2023
Simplex

Simplex 4099-9006 Addressable Manual Station

Product Information

  • Product Name: Simplex Addressable Manual Station
  • Model Numbers:
    • 4099-9004 – Single action
    • 4099-9021 – Single action NO GRIP
    • 4099-9805 – NO GRIP Retrofit kit
    • 4099-9005 – Breakglass
    • 4099-9006 – Push
  • Features:
    • UL, ULC, CSFM Listed; FM Approved
    • Multi-Application Peripherals
    • IDNet or MAPNET II Communicating Devices
    • Individually addressable manual fire alarm stations
    • Power and data supplied via IDNet or MAPNET II
    • Complies with ADA requirements
    • Visible LED indicator that flashes during operation
    • Compact construction to minimize dust infiltration
    • Mounting options: Surface, semi-flush, or flush mount with standard or matching Simplex boxes
    • Screw terminals for wiring connections
    • Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets)

Product Usage Instructions

To activate the alarm switch of the Simplex Addressable Manual Station, follow the instructions below based on the specific model:

Single Action Manual Station (4099-9004):

  1. Firmly pull the lever downward to activate the alarm switch.
  2. The action will break an internal plastic break-rod (optional) below the pull lever.
  3. The pull lever will latch into the alarm position and remain extended for visible indication.

Single Action NO GRIP Station (4099-9021):

  1. For easier operation, pull the lever downward without requiring tight grasping, pinching, or twisting of the wrist.
  2. Retrofit existing stations using the 4099-9805 Retrofit kit.

Double Action Stations (Breakglass or Push Type):

Breakglass Station:

  • Strike the front mounted hammer to break the glass and expose the recessed pull lever.
  • The pull lever then operates as a single action station.

Push Type Station:

  • Push back the spring-loaded interference plate (marked PUSH) to access the pull lever of the single action station.

To reset the manual station and deactivate the alarm switch:

  1. Use a key to reset the manual station lever.
  2. If a breakrod is used, it must be replaced after resetting.

To test the manual station:

  1. Physically activate the pull lever.
  2. Optionally, unlock the station housing to activate the alarm switch for electrical testing.

Note: Please refer to the user manual for detailed instructions specific to your model and for addressable manual station product selection.

Features

Individually addressable manual fire alarm stations with:

  • Power and data supplied via IDNet or MAPNET II addressable communications using a single wire pair
  • Operation that complies with ADA requirements
  • Visible LED indicator that flashes during communications and is on steady when the station has been activated
  • The NO GRIP Single Action Station and Retrofit Kit are available with a more easily operated pull lever for applications where anticipated users may find the standard station lever difficult to activate
  • Pull lever that protrudes when alarmed
  • Break-rod supplied (use is optional)
  • Models are available with single or double action (breakglass or push) operation
  • UL listed to Standard 38

Compatible with the following Simplex® control panels:

  • Model Series 4007ES, 4008, 4010, 4010ES, 4100ES,4100U, 4020, 4100, and 4120 fire alarm control panels equipped with either IDNet or MAPNET II communications
  • Model Series 2120 Communicating Device
    Transponders (CDTs) equipped with MAPNET II communications

Compact construction:

  • Electronics module enclosure minimizes dust infiltration
  • Allows mounting in standard electrical boxes
  • Screw terminals for wiring connections
    Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets)

Multiple mounting options:

  • Surface or semi-flush with standard boxes or matching Simplex boxes
  • Flush mount adapter kit
  • Adapters are available for retrofitting to commonly available existing boxes

Description

The Simplex addressable manual station combines the familiar Simplex manual station housing with a compact communication module that is easily installed to satisfy demanding applications. Its integral individual addressable module (IAM) constantly monitors status and communicates changes to the connected control panel via IDNet or MAPNET II communications wiring.

Refer to page 2 for specific model listings. This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7150-0026:224 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

Simplex-4099-9006-Addressable-Manual-Station-1

Simplex-4099-9006-Addressable-Manual-Station-2

Operation

Activation of the 4099-9004 single action manual station requires a firm downward pull to activate the alarm switch.
Completing the action breaks an internal plastic break-rod (visible below the pull lever, use is optional). The use of a break-rod can be a deterrent to vandalism without interfering with the minimum pull requirements needed for easy activation. The pull lever latches into the alarm position and remains extended out of the housing to provide a visible indication.

Single Action NO GRIP Station 4099-9021. For applications such as California Building Code, Title 24,which requires “Controls and operating mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist” the model 4099-9021 station provides a more easily operated pull lever compared to standard stations. Retrofit of existing stations is available using the 4099-9805 Retrofit kit.
Double Action Stations (Breakglass) require the operator to strike the front mounted hammer to break the glass and expose the recessed pull lever. The pull lever then operates as a single action station.
Double Action Stations (Push Type) require that a spring loaded interference plate (marked PUSH) be pushed back to access the pull lever of the single action station.
Station reset requires the use of a key to reset the manual station lever and deactivate the alarm switch. (If the breakrod is used, it must be replaced.)
Station testing is performed by physical activation of the pull lever. Electrical testing can be also performed by unlocking the station housing to activate the alarm switch.

Addressable Manual Station Product Selection

Addressable Manual Stations, Red Housing with White Letters and White Pull Lever

Model Description Housing Pull Lever Listings
4099-9004 Single Action, English FIRE ALARM PULL DOWN UL, ULC, FM, CSFM
4099-9004CB Single Action, Bilingual English and French FEU FIRE TIREZ
PULL ULC
4099-9004CF Single Action, French ALARME FEU ABAISSEZ
4099-9004PO Single Action, Portuguese FOGO ALARME PUXE UL, FM
4099-9004SP Single Action, Spanish ALARMA FUEGO JALE
4099-9005 Double Action, Breakglass operation, English FIRE ALARM PULL
DOWN UL, ULC, FM, CSFM
4099-9005PO Double Action, Breakglass operation, Portuguese FOGO ALARME
PUXE UL, FM
4099-9005SP Double Action, Breakglass operation, Spanish ALARMA FUEGO JALE
4099-9006 Double Action, Push operation, English FIRE ALARM PUSH PULL DOWN

UL, ULC, FM, CSFM
4099-9006PO| Double Action, Push operation, Portuguese| FOGO ALARME| EMPURRE PUXE| UL, FM
4099-9006SP| Double Action, Push operation, Spanish| ALARMA FUEGO| EMPUJE JALE
4099-9021| Single Action NO GRIP operation, English| FIRE ALARM| PULL DOWN| UL, ULC, FM, CSFM

Accessories (refer to pages 3 and 4 for details)

Model Description Model Description
2975-9022 Cast aluminum surface mount box, red 2099-9803 Replacement

breakglass
2975-9178| Surface mount steel box, red| 2099-9804| Replacement break-rod
2099-9813| Semi-flush trim plate for double gang switch box, red| 2099-9828| Institutional cover kit for field installation on 4099-9004; Note: Covers LED indicator
2099-9819| Flush mount adapter kit, black| 2099-9814| Surface trim plate for Wiremold box V5744-2, red
2099-9820| Flush mount adapter kit, beige
4099-9805| Retrofit Kit for field conversion of a single action station to a NO GRIP station; refer to Installation Instructions 579-1007 for details

Specifications

(refer to Installation Instructions 579-1135 for additional information)

Power and Communications| IDNet or MAPNET II communications, 1 address per station
---|---
Address Means| DIP switch, 8 position
Wire Connections| Screw terminal for in/out wiring, for 18 to 14 AWG wire (0.82 mm2 to 2.08 mm2)
UL Listed Temperature Range| 32° to 120° F (0° to 49° C) intended for indoor operation
Humidity Range| Up to 93% RH at 100° F (38° F)
Housing Color| Red with white raised lettering
Material| Housing and pull lever are Lexan polycarbonate or equal
Pull Lever Color| White with red raised lettering
Housing Dimensions| 5” H x 3 ¾” W x 1” D (127 mm x 95 mm x 25 mm)

Addressable Manual Station Semi-Flush Mounting

Simplex-4099-9006-Addressable-Manual-Station-3

Addressable Manual Stations Surface Mounting

Preferred Mounting. For surface mounting of these addressable manual stations, the preferred electrical boxes are shown in the illustration to the right.
Additional Mounting Reference. Refer to page 4 for Wiremold box mounting compatibility

Simplex-4099-9006-Addressable-Manual-Station-4

Surface Mount Side View with Internal Detail

Simplex-4099-9006-Addressable-Manual-Station-5

Application Reference

Refer to NFPA 72, the National Fire Alarm and Signaling Code, and all applicable local codes for complete requirements for manual stations. The following summarizes the basic requirements.

  1. Stations shall be located in the normal path of exit and distributed in the protected area such that they are unobstructed and readily accessible.
  2. Mounting shall be with the operable part not less than 42 in (1.07 m) and not more than 48 in (1.22 m) above floor level.
  3. At least one station shall be provided on each floor. Additional stations shall be provided to obtain a travel distance not more than 200 ft (61 m) to the nearest station from any point in the building.
  4. When manual station coverage appears limited in any way, additional stations should be installed.

Addressable Manual Station, Additional Mounting Information

For retrofit and new installations,additional compatible mounting boxes and the required adapter plates are shown in the illustration to the right.

Simplex-4099-9006-Addressable-Manual-Station-6

Addressable Manual Station, Flush Mounting Information

Simplex-4099-9006-Addressable-Manual-Station-7

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and Signaling Code are trademarks of the National Fire Protection Association (NFPA). Lexan is a trademark of the General Electric Co. Wiremold is a trademark of the Wiremold Company

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA

www.simplex-tire.com

© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.