ACV UPMXXL 25-120 Pump Control Instructions
- June 13, 2024
- ACV
Table of Contents
ACV UPMXXL 25-120 Pump Control
Instructions
When replacing any part on this appliance, use only spare parts that you can
be assured conform to the safety and performance specification that we
require. Do not use reconditioned or copy parts that have not been clearly
authorised by ACV.
For the very latest copy of literature for specification and maintenance
practices visit our website www/acv/com/gb where you can download the relevant
information in PDF format.
General
INTRODUCTION
This kit is suitable for the following boilers: Evo S range of boilers
utilising the Grundfos UPMXXL 25-120 pump.
This manual explains how to wire the pump leads to the installer wiring
connections and determine the pump settings within the boiler control.
The Pump is powered by a 230 V auxillary supply within the boiler, and
controlled by a PWM signal.
Item Description
Table 1 – Evo S from ACV
Evo S | Boiler Size |
---|---|
Evo S | 40 |
Evo S | 60 |
Evo S | 70 |
Evo S | 80 |
Evo S | 100 |
Evo S | 120 |
CONTENTS
This kit includes the following items
Item Description
1. Grundfos UPMXXL 25-120 pump
2. Fibre Washer Kit
3. Instructions
PREPARATION
Install the Pump Control kit as follows:
WARNING: Be careful when you install electrical connections.
Electric shock can cause serious injury or death and can cause damage to
equipment.
- Make sure that the electrical power supply to the boiler is set to OFF. For safe electrical isolation refer to Gas Safe technical bulletin 118. All work must be carried out by a competent person.
- For access to the control box (refer to manual ACV Evo S INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS Frame 4.6.1).
Table 2 – Evo S no separation
Boiler model | Flow rate Q (m³/hr) ∆t 20° C | Head (m) | Pump used |
---|---|---|---|
Evo S 40 | 1.72 | 4.58 | Grundfos UPMXXL 25-120 |
Evo S 60 | 2.59 | 6.01 | |
Evo S 70 | 3.02 | 5.81 | |
Evo S 80 | 3.45 | 4.89 | |
Evo S 100 | 4.28 | 7.29 | |
Evo S 120 | 5.14 | 7.75 |
INSTALLATION
Install the pump electrical connections as follows (refer to Figure 1).
- Mains power connections 13 earth, 14 live and 15 neutral.
- PWM connections 37 ground (Blue) and 38 PWM (Brown) signal, the remaining Black wire should be taped back or removed.
PUMP CONFIGURATION
The following parameters configure the PWM output to control a boiler pump.
Table 3 – Evo S PWM output
Line No. | Parameter | Settings |
---|---|---|
6085 | Function output P1 | Boiler pump Q1 |
6086 | Signal logic output P1 | Inverted |
PUMP PERFORMANCE
For pump performance refer to Figure 2 below.
PUMP PARAMETER SETTINGS
The following parameters configure how the pump speed is to be controlled.
Table 4 – Evo S pump speed control
Line No. | Parameter | Settings |
---|---|---|
2320 | Pump modulation | Burner output |
2321 | Starting speed | 100% |
The following parameters determine the PWM values to achieve the flow rates for each boiler model.
Table 5 – Cascade Boiler with LLH
Boiler Model| Line No.| Parameter| Setting| Flow
Reading (8366) l/m
---|---|---|---|---
40| 2322| Pump speed min| 69| 9.5
| 2323| Pump speed max| 95| 28.7
| 2505| Threshold flowDetect| 8.3|
| | | |
60| 2322| Pump speed min| 69| 19.2
| 2323| Pump speed max| 95| 39.3
| 2505| Threshold flowDetect| 16.7|
| | | |
70| 2322| Pump speed min| 69| 19.2
| 2323| Pump speed max| 95| 50.0
| 2505| Threshold flowDetect| 16.7|
| | | |
80| 2322| Pump speed min| 59| 38.3
| 2323| Pump speed max| 95| 69.3
| 2505| Threshold flowDetect| 35.0|
| | | |
100| 2322| Pump speed min| 69| 38.3
| 2323| Pump speed max| 95| 71.7
| 2505| Threshold flowDetect| 35.0|
| | | |
120| 2322| Pump speed min| 80| 50.0
| 2323| Pump speed max| 95| 86.0
| 2505| Threshold flow Detect| 45.8|
Notes
Table 6 – Cascade Boiler with PHEX
Boiler Model| Line No.| Parameter| Setting| Flow
Reading (8366) l/m
---|---|---|---|---
40| 2322| Pump speed min| 69| 9.5
| 2323| Pump speed max| 95| 28.7
| 2505| Threshold flowDetect| 8.3|
| | | |
60| 2322| Pump speed min| 69| 19.2
| 2323| Pump speed max| 95| 39.3
| 2505| Threshold flowDetect| 16.7|
| | | |
70| 2322| Pump speed min| 80| 19.2
| 2323| Pump speed max| 95| 50.0
| 2505| Threshold flowDetect| 16.7|
| | | |
80| 2322| Pump speed min| 69| 38.3
| 2323| Pump speed max| 95| 69.3
| 2505| Threshold flowDetect| 35.0|
| | | |
100| 2322| Pump speed min| 80| 38.3
| 2323| Pump speed max| 95| 71.7
| 2505| Threshold flowDetect| 35.0|
| | | |
120| 2322| Pump speed min| 85| 50.0
| 2323| Pump speed max| 95| 86.0
| 2505| Threshold flow Detect| 45.8|
Table 7 – Standalone Boiler
Boiler Model| Line No.| Parameter| Setting| Flow
Reading (8366) l/m
---|---|---|---|---
40| 2322| Pump speed min| | 9.5
| 2323| Pump speed max| | 28.7
| 2505| Threshold flow Detect| 8.3|
| | | |
60| 2322| Pump speed min| | 19.2
| 2323| Pump speed max| | 39.3
| 2505| Threshold flowDetect| 16.7|
| | | |
70| 2322| Pump speed min| | 19.2
| 2323| Pump speed max| | 50.0
| 2505| Threshold flowDetect| 16.7|
| | | |
80| 2322| Pump speed min| | 38.3
| 2323| Pump speed max| | 69.3
| 2505| Threshold flowDetect| 35.0|
| | | |
100| 2322| Pump speed min| | 38.3
| 2323| Pump speed max| | 71.7
| 2505| Threshold flowDetect| 35.0|
| | | |
120| 2322| Pump speed min| | 50.0
| 2323| Pump speed max| | 86.0
| 2505| Threshold flowDetect| 45.8|
The process to determine the settings for a modulating boiler pump is
dependent upon the hydraulic properties of the installation. For setting of
the minimum pump speed the worst-case flow rate of the system should be set,
this must be above the minimum flow rate allowed by the boiler model. This
will ensure that the minimum speed setting cannot result in a flow rate lower
than the minimum flow rate for the boiler model.
The table above shows the initial settings, these can then be adjusted to
ensure that the system flow meets the boiler model requirement. The actual
value of the flow through the boiler can be read from the boiler HMI under
‘Diagnostics heat generation’ 8366, also by pressing the ‘I’ information
button. The value is shown in l/m. So final adjustments can be made to ensure
compliance
Customer Service
ACV U.K. Limited
St. David’s Business Park,
Dalgety Bay
Fife, Scotland
KY11 9PF
Tel: 0044 (0)1383 820100
www.acv.com/gb
ACV pursues a policy of continuing improvement in the design and performance
of its products. The right is therefore reserved to vary specification without
notice.