HITACHI PMML0511 Heat Pump System Instruction Manual
- June 11, 2024
- Hitachi
Table of Contents
- HITACHI PMML0511 Heat Pump System Instruction Manual
- Product Information: SET FREE Mini Heat Pump System Heat Recovery System
- Product Usage Instructions
- GENERAL INFORMATION
- SAFETY
- BEFORE OPERATION
- 8 PIPING WORK
- REFRIGERANT CHARGE
- ELECTRICAL WIRING
- MAIN SAFETY DEVICES
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HITACHI PMML0511 Heat Pump System Instruction Manual
Product Information: SET FREE Mini Heat Pump System Heat Recovery System
The SET FREE Mini Heat Pump System Heat Recovery System is a product by
Hitachi that is designed to provide an efficient and eco-friendly way to
control the temperature of your home or office.
The system comes in two models: RAS-(4-6)FS(V)NME and RAS-(8-12)FSXNME. The
specifications of the product are subject to change without notice to provide
the latest innovations to customers.
It is important to note that the product should not be mixed with general house waste at the end of its life and should be retired according to the appropriate local or national regulations in an environmentally friendly way. The dismantling of the product must be done by a professional installer according to applicable regulations due to the refrigerant, oil, and other components contained in the air conditioner.
Product Usage Instructions
- Before using the SET FREE Mini Heat Pump System Heat Recovery System, ensure that it has been installed by a professional installer according to applicable regulations.
- Turn on the system by pressing the power button on the remote control.
- To set the desired temperature, press the up or down arrow buttons on the remote control.
- You can also adjust the fan speed and air flow direction using the remote control.
- When not in use, turn off the system by pressing the power button on the remote control.
- At the end of the product’s life, contact the corresponding authorities for information on retiring the product in an environmentally friendly way.
INSTRUCTION MANUAL
SET FREE MINI HEAT PUMP SYSTEM HEAT RECOVERY SYSTEM
MODELS RAS-(4-6)FS(V)NME RAS-(8-12)FSXNME
EN INSTRUCTION MANUAL ES MANUAL DE INSTRUCCIONES DE BEDIENUNGSANLEITUNG FR
MANUEL D’UTILISATION IT MANUALE DI ISTRUZIONI PT MANUAL DE INSTRUÇÕES DA
BRUGSANVISNING NL INSTALLATIEHANDLEIDING SV INSTALLATIONSHANDBOK EL
GENERAL INFORMATION
GENERAL NOTES
No part of this publication may be reproduced, copied, filed or transmitted in
any shape or form without the permission of Johnson Controls-Hitachi Air
Conditioning Spain, S.A.U.
As a result, some of the images or data used to illustrate this document may
not refer to specific models. No claims will be accepted based on the data,
illustrations and descriptions included in this manual.
Within the policy of continuous improvement of its products, Johnson Controls-
Hitachi Air Conditioning Spain, S.A.U. reserves the right to make changes at
any time without prior notification and without being compelled to introducing
them into products previously sold. This document may therefore have been
subject to amendments during the life of the product.
Hitachi makes every effort to offer correct, up-to-date documentation. Despite
this, printing errors cannot be controlled by Hitachi and are not its
responsibility.
No type of modification must be made to the equipment without prior, written
authorisation from the manufacturer.
Hitachi pursues a policy of continuing improvement in design and performance
of products. The right is therefore reserved to vary specifications without
notice.
These Outdoor units models are partial unit air conditioners, complying with
partial unit requirements of this International Standard IEC 60335 2
40:2013+AMD1:2016, and must only be connected to other units that have been
confirmed as complying to corresponding partial unit requirements of this
International Standard.
1.1.1 Norms and Regulations
Following Regulation EU No. 517/2014 on Certain Fluorinated Greenhouse gases,
it is mandatory to fill in the label attached to the unit with the total
amount of refrigerant charged on the installation.
Do not vent R410A into the atmosphere: R410A are fluorinated greenhouse gases
covered by the Kyoto protocol global warming potential (GWP) R410A = 2088.
Tn of CO2 equivalent of fluorinated greenhouse gases contained is calculated
by indicated GWP multiply by Total Charge (in kg) indicated in the product
label and divided by 1000.
Appropriate refrigerant
The refrigerant used in each unit is identified on the specification label and
manuals of the unit. Hitachi shall not be held liable for any failure,
trouble, malfunction or accident caused by units illegally charged with
refrigerants other than the specified one.
Consequences of charging non-specified refrigerant
It may cause mechanical failure, malfunction and other accidents. It may cause
operational failure of protection and safety devices of air conditioners. It
may also cause lubrication failure of the sliding part of the compressor due
to deterioration of refrigerant oil.
In particular, hydrocarbon refrigerants (such as propane, R441A, R443A, GF-08,
etc) are not allowed, since these are combustible and may cause major
accidents such as fire and explosion in case of improper handling.
Once a non-specified refrigerant has been charged, no further servicing
(including draining of refrigerant) shall be performed, even in case of
malfunction. Improper handling of refrigerant may be a cause of fire and
explosion, and servicing in such cases may be considered an illegal act.
End clients and costumers shall be informed that servicing is not approved,
and the installer who charged the nonspecified refrigerant shall be asked to
fix the unit.
Hitachi will accept no responsibility for units that have been charged with
non-specified refrigerant once.
SAFETY
APPLIED SYMBOLS
During normal air conditioning system design work or unit installation,
greater attention must be paid in certain situations requiring particular care
in order to avoid injuries and damage to the unit, the installation, the
building or to those in the surrounding area. These situations will be clearly
indicated in this manual.
Signal words (NOTE, DANGER and CAUTION) are used to identify levels of hazard
seriousness. Definitions for identifying hazard levels are provided below with
their respective signal words. Pay close attention to these symbols and to the
messages following them, as your safety and that of others depends on it.
19 PMML0511 rev.3 – 12/2020
! DANGER
· The text following this symbol contains information and instructions
relating directly to your safety.
· Not taking these instructions into account could lead to serious, very
serious or even fatal injuries to you and others standing near the unit.
! CAUTION
· The text following this symbol contains information and instructions
relating directly to your safety.
· Not taking these instructions into account could lead to minor injuries to
persons standing near the unit.
· Not taking these instructions into account could lead to unit damage.
SAFETY
? NOTE
· The text following this symbol contains information or instructions that may
be of use or that require a more thorough explanation.
· Instructions regarding inspections to be made on unit parts or systems may also be included.
2.2 IMPORTANT NOTICE
The supplementary information about the purchased products is supplied in a
CD-ROM, which can be found bundled with the outdoor unit. In case that the CD-
ROM is missing or it is not readable, please contact your Hitachi dealer or
distributor.
PLEASE READ THE MANUAL AND THE FILES ON THE CD-ROM CAREFULLY BEFORE STARTING
WORK ON THE INSTALLATION OF THE AIR CONDITIONING SYSTEM. Failure to observe
the instructions for installation, use and operation described in this
documentation may result in operating failure including potentially serious
faults, or even the destruction of the air conditioning system.
This manual should be considered as a permanent part of the
air conditioner. This manual gives a common description and information for
this air conditioner which you operate as well as for other models.
Refer to the models codification to confirm the main characteristics of your
system.
Verify, in accordance with the manuals which appear in the outdoor and indoor
units, that all the information required for the correct installation of the
system is included and correspond to your air conditioner model. If this is
not the case, contact your distributor.
If you have any questions, contact your service contractor of Hitachi.
2.3 ADDITIONAL INFORMATION ABOUT SAFETY
! DANGER
· Hitachi is not able to foresee all the circumstances which may result in a potential danger.
· Do not pour water into the indoor or outdoor unit. These products are equipped with electrical parts. If water contacts with electrical components then it will cause a serious electrical shock.
· Do not handle or adjust the safety devices inside the indoor and outdoor units. The handling or adjustment of these devices may result in serious accident.
· Do not open the service cover or access the indoor or outdoor units without disconnecting the main power supply.
· In case of fire Turn OFF the main switch, put out the fire at once and contact your service contractor.
· This air conditioner is equipped with a high pressure vessel under PED (Pressure Equipment Directive). The pressure vessel has been designed and tested before shipment according to PED. Also, in order to prevent the system from an abnormal pressure, a high pressure switch, which needs no field adjustment, is utilized in the refrigeration system. Therefore, this air conditioner is protected from abnormal pressures. However, if abnormally high pressure is applied to the refrigeration cycle including the high pressure vessel(s), it will result in serious injury or death due to explosion of the pressure vessel. Do not apply a pressure higher than the following pressure to the system, by modifying or changing the high pressure switch.
· Do not handle, modify or change the high pressure switch in the air conditioning unit. If abnormally high pressure is applied to the elements in the air conditioning unit refrigerant cycle, including the high pressure vessels, these could explode resulting in serious injury or loss of life.
Location High pressure switch
Structure Contact point
Pressure detected
Accumulator Compressor The label for the vessel under PED are attached on the high pressure vessel. The pressure vessel capacity and vessel category are indicated on the vessel.
Connected to the electrical wire
The high pressure switch is indicated on the electrical wiring diagram in the
outdoor unit as HPS connected to printed circuit board (PCB) in the outdoor
unit.
20 PMML0511 rev.3 – 12/2020
Start-up and Operation: Check to ensure that all the stop valves are fully
opened and no obstacle exists at the inlet/outlet sides before start-up and
during the operation.
Maintenance: Periodically check the high pressure side pressure. If the
pressure is higher than the maximum allowable pressure, stop the system and
clean the heat exchanger or remove the cause.
Refrigerant R410A
Maximun allowable pressure (MPa)
4.15
High pressure switch cut-out value (MPa)
4.00 ~ 4.10
! CAUTION
· Check for refrigerant leakage in detail. It may hinder respiration as the
gas displaces the air in the room. Also harmful gases would occur if a fire
were being used in the room.
· Fit the indoor unit, the outdoor unit, the remote control and the cable at a
minimum of 3 meters away from sources where electromagnetic waves radiate
directly towards the electrical box and the components of the unit, such as
medical equipment. Electronic noise may result in the incorrect operation of
the unit.
· Do not use sprays, such as insecticides, varnishes or enamels or any other
inflammable gas within a meter of the system.
· If the circuit breaker or supply fuse of the unit comes on frequently, stop
the system and contact the service suppler.
· Do not place any foreign material (branches, sticks, etc.) in the air inlet
or outlet of the unit. These units are fitted with high speed fans and contact
with any object is dangerous.
· This appliance must be used only by adult and capable people, having
received the technical information or instructions to handle this appliance
properly and safely.
· The air conditioning system should only be installed, carry out maintenance
or inspection by qualified personnel, with the necessary resources, tools and
equipment, who are familiar with the safety procedures required to
successfully carry out the installation.
· Children should be supervised to ensure that they do not play with the
appliance.
· This air conditioner has been designed for standard air conditioning for
human beings. For use in other applications, please contact your Hitachi
dealer or service contractor.
h
EN
BEFORE OPERATION
? NOTE
· The air in the room should be renewed and the room ventilated every 3 or 4
hours.
· The system fitter and specialist shall provide anti-leak safety in accordance with local regulations.
3 BEFORE OPERATION
! CAUTION
· Supply electrical power to the system for approximately 12 hours before
start-up or a long shutdown. Do not start the system immediately after power
supply, it may cause a compressor failure because the compressor is not heated
well.
· When the system is started after a shutdown longer that approximately 3
months, it is recommended to check the system by your service contractor.
· Turn OFF the main switch when the system is to be stopped for a long period
of time. If the main switch is not turned OFF, electricity will be used,
because the oil heater is always energised during compressor stopping.
· Make sure that the outdoor unit is not covered with snow or ice. If covered,
remove it by using hot water (up to 50°C). If the water temperature is higher
than 50 °C, it will cause damage to plastic parts.
4 ACCESSORIES FACTORY-SUPPLIED
Pipes
8HP
10HP
12HP
Gas pipe
x2 OD19.05ID15.88 OD19.05ID22.2 / 25.4 OD19.05ID22.2 / 25.4
Liquid pipe
–
OD9.52ID12.7
Name
Qty
Ring core (only for RAS-(4-6)FSVNME)
2
Cable tie (only RAS-(4-6)FSVNME)
2
Declaration of conformity
1
Transparent label
1
Installation and operation manual
1
CD-ROM
1
Comments
Yellow for L,N wire / Green for Earth wire For attaching the ring core –
For attaching in the refrigerant label Installation and operation unit
instructions Installation and operation unit instructions
5 TRANSPORTATION AND HANDLING
! CAUTION
· Transport the products as close to the installation location as practical
60º
a
c
before unpacking. Do not put any material on the products.
0.7 -1.0 m
· Apply four lifting wires on to the outdoor, when lifting it by crane.
Model RAS-(4-6)FS(V)NME RAS-(8-12)FSXNME
a (m) 5.8 6.6
h (m) 6.2 7.0
c (m) 2.1 2.0
When hanging the unit, ensure a balance of the unit, check safety and lift it up smoothly. Two or more personnel should be used to move the unit. Do not remove any packing materials. Hang the unit under packing condition with 2 rope.
For safety reasons ensure that the outdoor unit is lifted smoothly and does not lean.
21 PMML0511 rev.3 – 12/2020
UNITS INSTALLATION
6 UNITS INSTALLATION
Mount the outdoor unit in a shady location or where it will not be exposed to
direct sunlight, or to high temperatures. Check to ensure that the foundation
is flat, level and sufficiently strong. When installing the unit on a roof or
a veranda, drain water sometimes turns to ice on a cold morning. Therefore,
avoid draining in an area that people often use because it is slippery.
Do not install the outdoor unit in a space where a seasonal wind directly
blows to the outdoor fan.
When installing the outdoor unit in areas covered by snow, mount the covers
supplied by the fitter on the top of the unit and on the heat exchanger inlet
side.
Do not install the outdoor unit in zones where dust or contamination could
block the outside heat exchanger.
Do not install the outdoor unit in areas with a high air content of oil,
saline atmospheres or aggressive gases such as sulphur.
Mount the outdoor unit so that noises and the discharge of air from the unit
will not bother neighbours or the surrounding environment. In a restricted
area not accessible by the general public.
! CAUTION
· It should also be a well-ventilated spot, enclosed space may cause explosion
or fire.
· For cleaning, use noninflammable and nontoxic cleaning liquid. Toxic gas may
be produced when cleaning agent is heated to high temperature by, e.g., being
exposed to fire. Cleaning liquid shall be collected after cleaning.
· Install the outdoor unit with sufficient clearance around it for operation
and maintenance as shown in the next figures, avoid obstacles that may hamper
air intake.
· Pay attention not to clamp cables when attaching the service cover to avoid
electric shock or fire.
· Aluminium fins have very sharp edges. Pay attention to the fins to avoid
injury.
7 NAME OF PARTS
7.1 RAS-(4-6)FSVNME / RAS-(4-6)FSNME
Nº
Part Name
1 Compressor
2 Crankcase heater
3 Stop valve for liquid line
4 Stop valve for gas line
5 Low pressure sensor
6 High pressure sensor
7 High pressure switch for protection
Nº
Part Name
8 Check valve
9 Solenoid valve
10 Check joint
11 Strainer
12 Reversing valve
13 Accumulator
14 Micro-computer control expansion valve
Nº
Part Name
15 Electrical control box (different for 1ph/3ph)
16 Air inlet
17 Air outlet
18 Fan propeller
19 Fan motor
20 Heat exchanger
21 Oil separator
7.2 RAS-(8-12)FSXNME
Nº
Part Name
1 Compressor
2 Crankcase heater (3 pcs)
3 Stop valve for liquid line
4 Stop valve for gas line (Low)
5 Stop valve for gas line (High / Low)
6 Low pressure sensor
7 High pressure sensor
8 High-pressure switch for protection
Nº
Part Name
Nº
Part Name
9 Check valve
17 Electrical control box
10 Solenoid valve (SVG,SVA)
18 Air inlet
11 Reversing valve (RVR1 RVR2) 12 Check joint (low)
19 Air outlet 20 Fan propeller
13 Check joint (high)
21 Fan motor
14 Check joint (for oil)
22 Heat exchanger
15 Accumulator
23 Oil separator
16 Micro-computer control expansion valve (MVB, MV1) – Strainer (not shown)
22 PMML0511 rev.3 – 12/2020
EN
NAME OF PARTS
7.3 CLEARANCE CONDITIONS
? NOTE
· (Unit: mm) · H: Height of the outdoor unit. When L > H, use a base for
outdoor unit
to make L H. Close the base not to allow the outlet air bypassed. · Be sure to
use the fan direction guide.
· 100 mm is the minimum space acceptable on the service cover side when the installation allows an outdoor unit next to other or next to a wall.
L 0 < L 1/2H 1/2H < L H
A 600 or greater 1400 or greater
B 300 or greater 350 or greater
Obstacles on inlet side
200
300
Single installation
Without obstacles on upper
side
Multiple installation (two units or
more)
50
100
B A
200 mm minimum of the back space is acceptable when the right and left sides are open. Keep both right and left sides without obstacles.
100
300
100
B (*) A
Keep both right and left sides without obstacles. When subject to direct sunlight on the back wall, ensure the length B (*) be 500 or greater.
300
300
L L
1000
1000
Single installation
Obstacles on upper
side 100
Multiple installation (two units or
more)
23 PMML0511 rev.3 – 12/2020
H
B 300
B A
Keep both right and left sides without obstacles. 300
100
1000
1000
H
H
L
B
B
A
Serial installation allowed up to two units. Keep both right and left sides without obstacles.
L
H
NAME OF PARTS
Single installation
Without obstacles on upper
side Multiple
installation (two units or
more)
Without obstacles on upper
side
Single installation
Obstacles on upper
side
L
L 1000
Obstacles on outlet side A
L H
100
50
100
A B
Keep both right and left sides without obstacles.
150
L H
A
A
B
Serial installation allowed up to two units. Keep both right and left sides without obstacles.
Obstacles beside the unit
100
50
500
500
L
L 1000
100
50
500
500
24 PMML0511 rev.3 – 12/2020
300 300
EN
NAME OF PARTS
Obstacles on inlet side
Stack installation (allowed up to 2 Units)
Single Installation
Multiple Installation
100
300
C
C
Without obstacles on upper
side
350
350
Serial sideways installation allowed up to two units. Keep both right and left sides without obstacles. Close the part C not to allow the outlet air bypassed. Install to avoid the drain water from upper unit falling on the lower unit.
Single Installation
Multiple Installation
100
300
Obstacles on
C
outlet side
C
1000
1000
Close the part C not to allow the outlet air bypassed. Install to avoid the drain water from upper unit falling on the lower unit. Serial side way installation allowed but leave open both right and left sides.
Serial multiple Installation in Multiple Rows
Allow approx. 100 mm of space from the side unit. Leave open both right and
left sides. The length A is as shown in the following table:
A
A
600 4000
A
A
600 3000
L 0<L1/2H 1/2H<LH
A 200 300
L L
L L
25 PMML0511 rev.3 – 12/2020
NAME OF PARTS
7.4 SPECIFIC CONDITIONS DEPENDING ON THE TYPE OF INSTALLATION
7.4.1 Placing the unit on a concrete foundation 7.4.2 Fixing the unit to a wall
1 Foundation must be flat and is recommended 100-300 mm higher than ground
level.
2 Install a drainage around foundation for smooth drain.
3 When installing the outdoor unit fix it with anchor bolts of M10. Cut the
portion A of the anchors to remove the service cover easily. Vibration-proof
mats must also be laid out entirely on the foundation.
Unit: mm
Outdoor unit
A
Anchor bolt M10 (Ø12.5 Hole)
Vibration-proof rubber
Drainage
Mortar hole (Ø100 x depth 150)
Drainage (wide 100 x depth 150)
-
- Space for
downward piping space
- Space for
-
Space for
-
downward piping
space
To fix the outdoor unit onto the wall as the figure indicates make sure the foundation is enough strong to avoid deformations and noises. If a prevention of vibration transfer to the building is needed, use rubber mat. (Field supplied)
A
B
Rubber Material (Field Supplied)
C
Right side
(mm)
RAS-(4-6)FS(V)NME RAS-(8-12)FSXNME
Left side
A
B
C
1109 116 30
1173 110 34.5
7.4.3 Suspending the unit
Right side
A
B
C
1109 116 75
1173 110 75
Ensure that wall can resist the outdoor unit weight indicated in specification label plate. It is recommended to select each foot support to bear the full weight of the unit (in order to consider stress fatigue applied when unit is working too). Suspend the unit as the drawing indicates.
Wall bracket (Field supplied)
Anchor Bolts (Field supplied)
! CAUTION
· Installation shall ensure that outdoor unit will not incline, vibrate, make
noise or fall down by a blast of wind or in an earthquake. Calculate quake-
resistance strength to ensure that installation is strong enough against
falling. Fix the unit with wires (field supplied) when installing in a
location without walls or windbreak and likely exposed to a blast of wind.
· To use a vibration-proof mat, fix four places to the front and back.
7.4.4 When the unit is exposed to strong wind
To install on the rooftop or a location without surrounding buildings, where
strong wind is expected against the product.
? NOTE
When the mark * dimension is secured, piping work from bottom side is easy
without interference of foundation.
4 For RAS-(4-6)FS(V)NME an additional metal plate (fieldsupplied) is needed
for steady installation in case the base width is bigger than the frame width.
– Material: Hot-Rolled Mild Steel – Plate (SPHC) Plate Thickness: 4.5 T
Metal plate width
· Choose a location where the outlet or inlet side of the product will not be
exposed to strong wind.
· When the outlet is exposed to strong wind: Direct strong wind may cause lack
of air flow and adversely affect to the operation.
! CAUTION
Excessive strong wind against the outdoor unit outlet may cause inverse
rotation and damage the fan and motor.
Frame width <
Base width of
outdoor unit
26 PMML0511 rev.3 – 12/202
8 PIPING WORK
8.1 OUTDOOR UNIT PIPING CONNECTION DIRECTION
1 The pipes can be connected from 4 directions as shown in the figure below.
Front side piping work Rear side piping work
a. For the front and side piping
RAS-(4-6)FS(V)NME
Side piping hole
RAS-(8-12)FSXNME
Side piping hole
Right side piping work
Bottom side piping work (Knock out hole)
2 Remove the necessary screws depending on the piping direction work selected as shown in the figure below.
Service cover
RAS-(4-6)FS(V)NME
Stop valves Piping work
Front piping hole
b. For the downward piping RAS-(4-6)FS(V)NME
Liquid piping Gas piping
Knock-out hole
RAS-(8-12)FSXNME
Liquid piping Gas piping Gas piping
Bottom base
c. For the rear side piping RAS-(4-6)FS(V)NME
RAS-(8-12)FSXNME
Service cover
RAS-(8-12)FSXNME
Stop valves Piping work
Rear Cover
! CAUTION
For RAS-(8-12)FSXNME heat recovery system it is necessary to configure the
installation adapting a 45º elbow extra for rear side connection.
Elbow 45º (field-supply) Rear side
? NOTE
· To remove the service cover hold it with a hand to remove screws as the
cover may fall down.
· Slowly press down the cover ( ).
3 Check the size of the pipes to be connected and remove the
appropriate part of the cabinet (indicated with
in the
diagrams below) following the pre-cut punches.
? NOTE
Cables shall not contact directly to the pipes.
4 Check to ensure that the stop valves are closed completely before connecting
pipes.
5 Connect the pipes according with the table.
6 Mount the piping cover in order to avoid water entering into the unit. Seal
the holes where pipes and wires are inserted, by using a insulation (field-
supplied).
7 Operation of stop valve should be performed according to “8.2 Stop valves”.
27 PMML0511 rev.3 – 12/2020
PIPING WORK
8.2 STOP VALVES
LIQUID VALVE (Spindle type)
RAS-(4-6) FS(V)NME RAS-(8-12) FSXNME
GAS VALVE (Ball type)
RAS-(4-6) FS(V)NME
RAS-(8-12) FSXNME
B
A
A
A
B
B
C
C
C
D
E
E
HEX4
1.5mm 90º
90º 6mm
Tightening torque (Nm)
A
33-42
20-25
B
14-18
14-18
C
33-42
68-82
D/E
7-9
5
Nº Description
Remarks
A Cap
Core valve
B
Check Joint cap
Only the charging hose
can be connected.
27.5-32.5 12-14 95-105 5
C Flare nut
D Spindle E Stem
! CAUTION
If the flare nut is tightened too hard, the flare nut may crack after a long
time and cause refrigerant leakage. Open Counterclockwise
Close Clockwise This valve is opened or closed by rotating 90 degrees.
Rotate the stem until the pin touches the stopper. Do not apply extra force.
Do not leave the ball valve partly open.
Heat pump
(4-6)HP
8HP
1 4
Liquid pipe (ø9.52) (field-supplied)
Liquid pipe (ø15.88) (field-supplied)
1 2
Liquid pipe (ø9.52)
3
(field-supplied)
Gas pipe (ø19.05) (field-supplied)
not used
10HP
12HP
1
1
2
2
Accessory pipe
(OD9.52ID12.7)
Liquid pipe (ø9.52) (field-supplied)
3 Liquid pipe (ø12.7)
3
Accessory pipe (*)
(field-supplied)
not used
(OD19.05ID22.2)
Accessory pipe
not used
(OD19.05ID25.4)
Gas pipe (ø22.2)
(field-supplied)
Gas pipe (ø25.4)
(field-supplied)
Heat recovery
8HP
10HP
1
1
2
2
Liquid pipe (ø9.52)
Liquid pipe (ø9.52)
(field-supplied)
(field-supplied)
3
3
Gas pipe (ø19.05) (field-supplied)
Accessory pipe (*) (OD19.05ID22.2)
Accessory pipe (OD19.05ID15.88)
Gas pipe (ø22.2) (field-supplied)
Gas pipe (ø15.88) (field-supplied)
Gas pipe (ø19.05) (field-supplied)
12HP
Nº
Description
1 2
Accessory pipe (OD9.52ID12.7)
Liquid pipe (ø12.7) (field-supplied)
Stop valve for liquid line
Stop valve for gas line (Low)
Stop valve for gas line (High/Low)
Stop valve for gas line 3
Accessory pipe (*) (OD19.05ID22.2)
! CAUTION
Accessory pipe (OD19.05ID25.4)
Gas pipe (ø25.4) (field-supplied)
Gas pipe (ø22.2) (field-supplied)
Use a reducer valve when nitrogen gas blowing is performed during brazing. The gas pressure should be maintained within 0.03 to 0.05 MPa. If a excessively high pressure is applied to a pipe, it will cause an explosion.
? NOTE
· Flare all the pipes and accessories to connect with the stop valves. · (*)Cut the accesory OD19.05 ID22.2/25.4.
28 PMML0511 rev.3 – 12/2020
EN
PIPING WORK
8.3 PIPE SIZE SELECTION
Select the pipe size in line with the following instructions:
· Between the outdoor unit and the branch pipe (Multi-Kit): select the same
pipe connection size as for the outdoor unit.
· Between the branch pipe (Multi-Kit) and the indoor unit: select the same
pipe connection size as for the indoor unit.
! CAUTION
· Do not use refrigerant pipe sizes other than those indicated in the
technical information. The diameter of the refrigerant pipes depends directly
on the power of the outdoor unit.
· If larger diameter refrigerant pipes are used, the circuit lubrication oil
tends to separate from the gas carrying it. The compressor will be seriously
damaged due to a lack of lubrication.
· If smaller diameter refrigerant pipes are used, the gas or liquid
refrigerant will have serious difficulties in circulating. System performance
will be affected. The compressor will run under more severe conditions than
foreseen and will be damaged in a short space of time.
· Select the piping size with the correct thickness and correct material which
can have sufficient pressure strength.
8.3.1 Heat pump systems
A
C
2
3
3
3
IU IU IU
1
2
2
3
3
3
B
B
IU IU IU
? NOTE
Only for Hydro Free combinations maximum connection ratio is up to 200%
Main pipe diameter (from the OU to the first branch)
Outdoor unit
RAS-(4-6)FS(V)NME RAS-8FSXNME RAS-10FSXNME RAS-12FSXNME
Gas
ø15.88 ø19.05 ø22.20 ø25.40
Liquid
ø9.52 ø9.52 ø9.52 ø12.70
? NOTE
· In the case that the piping length from the Multi-Kit at the first branch to
the terminal indoor unit is over 40m, the size of the main piping should be
increased by one size.
· When the maximum length of the equivalent refrigerant pipe from the outdoor
unit to the indoor unit is over 70 m for RAS-(4-6)FS(V)NME or over 100 m for
RAS-(8-12)FSXNME, the pipe size of liquid line of the main pipe should be
increased by one size.
· In case that the selected pipe size after the first branch is larger than
the pipe size before the first branch, the size of the pipe before the first
branch shall be set to the same as the pipe after the first branch ().
Pipe diameter after first branch or between multi-kits
Total indoor unit capacity after the first branch (HP)
<6 (6-8.99) (9-11.99) (12-15.6)
Gas
ø15.88 ø19.05 ø22.20 ø25.40
Liquid
ø9.52 ø9.52 ø9.52 ø12.70
? NOTE
If the multi-kit size is larger than the first branch,adjust the multi-kit
size to the first branch.
Pipe diameter between multi-kit and indoor unit
Indoor unit capacity (HP)
0.4-1.5 2
2.5-6.0 8.0 10.0
? NOTE
Gas ø12.70 ø15.88 ø15.88 ø19.05 ø22.20
Liquid ø6.35 () ø6.35 ()
ø9.52 ø9.52 ø9.52
· (*): When the liquid piping length is longer than 15m, use Ø9.52 pipe and
reducer (field-supplied).
· The pipe diameter should be the same as the IU piping connection size. Check
the corresponding IU connection sizes.
A First branch and B multi-kits after the first branch
A Outdoor unit HP 4-10 12
B Total indoor unit HP <12
12-15.6
Model
E-102SN4 E-162SN4
? NOTE
In case of increasing the piping size as a consequence of the piping
restrictions, consider to use E-162SN4 instead of E-102SN4 and E-242SN3
instead of E-162SN4. C Header branch
Total indoor unit HP
2-8 4-10
Nº of header branches
4 8
Model
MH-84AN1 MH-108AN
29 PMML0511 rev.3 – 12/2020
PIPING WORK
8.3.2 Heat recovery systems
3 Low pressure gas pipe
3 High/Low pressure gas pipe
1
A
B
2
2
3
2 G CH
5
IU
B 3
B
3
3
CH
CH
G
G
5
5
IU IU
CH-M
CH
3 pipes section
2 pipes section
4 5 Liquid pipe 4 5 Gas pipe
3 Liquid pipe 3 Low pressure gas pipe 3 High/Low pressure gas pipe
3 pipes section
CH-M
G
5
5
IU IU
5
5
IU IU
B
C
3
4
CH
C 4
5
5
5
G
IU IU IU
45 Gas pipe
45 Liquid pipe
2 pipes section
4 C
5
5
IU IU
: High/ Low pressure gas pipe : Gas pipe/ Liquid pipe : Low pressure gas pipe,
liquid pipe
CH: CH-Box (Single branch pipe) CH-M:CH-Box (Multiple branch pipe)
If a header branch is used instead of multi-kit
E 2 Header branch
3
3
3
CH CH CH
F
3
CH
4 Header branch
5
5
5
IU IU IU
5
5
5
IU IU IU
! CAUTION
Header branch cannot be connected to upstream or downstream piping of CH-Box multiple.
Header branch CH CH
CH-M
CH-M
Header branch
IU IU
Upstream
IU IU IU
Downstream
IU IU
Upstream
IU IU IU
Downstream
Main pipe diameter (from the OU to the first branch)
Outdoor unit
RAS-8FSXNME RAS-10FSXNME RAS-12FSXNME
Gas, low pressure
ø19.05 ø22.20 ø25.40
Gas, high/ low pressure
ø15.88 ø19.05 ø22.20
Liquid
ø9.52 ø9.52 ø12.70
? NOTE
When the maximum length of the equivalent refrigerant pipe from the OU to the
IU is over 100 m the pipe size of liquid line of the main pipe should be
increased by one size with reducers (field-supplied).
Pipe diameter after first branch or between multi-kits and Pipe diameter
between the multi-kit and the CH-Box
Total indoor unit capacity after the first branch (HP)
Gas, low Gas, high/ pressure low pressure
Liquid (*)
< 6
ø15.88
ø12.70
ø9.52
(6-8.99)
ø19.05
ø15.88
ø9.52
(9-11.99)
ø22.20
ø19.05
ø9.52
(12-15.6)
ø25.40
ø22.20
ø12.70
? NOTE
· In the case that the piping length from the Multi-Kit at the first branch to
the terminal indoor unit is over 40m, the size of the main piping should be
increased by one size.
· (*) CH-Box (single branch type) is not connected to liquid pipe. · If the
multi-kit size is larger than the first branch,adjust the multi-kit
size to the first branch. · If the size of the diameter between the multi-kit
and the CH-Box is
larger than the main pipe diameter, adjust the diameter to the same size as
the main pipe diameter. · In case that the selected pipe size after the first
branch is larger than the pipe size before the first branch, the size of the
pipe before the first branch shall be set to the same as the pipe after the
first branch ().
Pipe diameter for 2 pipes between CH-Box and multi-kit
or between multi-kits
Total indoor unit capacity after the first branch (HP)
< 6 (6-8.99) (9-11.99) (12-15.6)
Gas, low pressure
ø15.88 ø19.05 ø22.20 ø25.40
Liquid
ø9.52 ø9.52 ø9.52 ø12.70
Pipe diameter between multi-kit and IU or between CH-
Box and IU
Indoor unit capacity (HP)
0.4-1.5 2
2.5-6.0 8.0 10.0
Gas
ø12.70 ø12.70 / ø15.88
ø15.88 ø19.05 ø22.20
Liquid
ø6.35 () ø6.35 ()
ø9.52 ø9.52 ø9.52
? NOTE
· (*): When the liquid piping length is longer than 15m, use Ø9.52 pipe and
reducer (field-supplied).
· The pipe diameter should be the same as the indoor unit piping connection
size. Check the indoor unit connection sizes.
A First branch and B multi-kits after the first branch (3 pipes section)
A Outdoor unit HP
8-10 12
B Total indoor unit HP
<6 6-11.99 12-15.6
Model
E-52XN3 E-102XN3 E-162XN3
30 PMML0511 rev.3 – 12/2020
EN
REFRIGERANT CHARGE
? NOTE
· In case of increasing the piping size as a consequence of the piping
restrictions, consider to use E-162XN3 instead of E-102XN3 and E-202XN3 or
E-242XN3 instead of E-162XN3.
C Multi-kit after the first CH-Box or cooling only section (2 pipes section)
Total indoor unit HP <12
12-15.6
Model E-102SN4 E-162SN4
? NOTE
In case of increasing the piping size as a consequence of the piping
restrictions, consider to use E-162SN4 instead of E-102SN4 and E-242SN3
instead of E-162SN4. E Header branch for 2 pipes section
F Header branch for 3 pipes section
Total indoor unit HP 2-8 4-10
G CH-Box
Nº of header branches 4 8
Model MH-84AN1 MH-108AN
Nº of CH-Box model Branch connectable
IU per branch
CH-AP160SSX
1
7
CH-AP280SSX
1
8
CH-AP04MSSX 4
6
CH-AP08MSSX 8
6
CH-AP12MSSX 12
6
CH-AP16MSSX 16
6
IU maximum connection capacity
(HP)
for 1 branch (HP)
6.0
6.0
10.0 16.0 30.0 30.0 30.0
10.0 6.0 () 6.0 () 6.0 () 6.0 ()
Total indoor unit HP 4-10
Nº of header branches 8
Model MH-108XN
? NOTE
(*) Up to two 8.0, 10.0HP type indoor units can be connected to the CH-Box
within the “Indoor unit maximum connection capacity”. Make sure to increase
the pipe connection size by using the appropriate accessory pipe.
9 REFRIGERANT CHARGE
! DANGER
Do not charge OXYGEN, ACETYLENE, or other flammable and poisonous gases into
the refrigerant because an explosion can occur. It is recommended that oxygen
free nitrogen be charged for these types of tests cycle when performing a
leakage test or an airtight test. These types of gases are extremely
dangerous.
! CAUTION
Charge the correct refrigerant quantity according to the description of label
at the inside of service cover. Overcharging or insufficient charging could
cause a compressor failure.
9.1 CAUTION OF THE PRESSURE BY CHECK JOINT
RAS-(4-6)FS(V)NME
When the pressure is measured, use the check joint of gas stop valve (A), and
use the check joint (B). Connect the pressure gauge according to the following
table because of high pressure side and low pressure side changes by operation
mode.
RAS-(8-12)FSXNME
B
To measure the pressure use the
C
check joints (A) and (B). Connect
the pressure gauge according to
the following table.
A
A B
A For gas stop valve B For piping
C For liquid stop valve
Cooling
Heating
Low pressure
High pressure
High pressure
Low pressure
Exclusive for vacuum pump and refrigerant charge
A For piping B For piping
Cooling/ Heating High pressure Low pressure
? NOTE
For all models, be careful that refrigerant and oil do not splash to the
electrical parts at removing the charge hoses.
31 PMML0511 rev.3 – 12/2020
REFRIGERANT CHARGE
9.2 ADDITIONAL REFRIGERANT CHARGE CALCULATION
Although refrigerant has been charged into this unit in advance
(W0 (kg)), additional refrigerant charge (W (kg)) is required according to
piping length.
Ensure that the total additional refrigerant charge quantity should not exceed the max. additional charge quantity shown in the table below.
Model
Refrigerant charge Maximum additional
before shipment (W0 (kg))
charge (kg)
RAS-4FS(V)NME
3.7
9.3
RAS-5FS(V)NME
4.1
8.9
RAS-6FS(V)NME
4.1
8.9
RAS-8FSXNME
4.2
26.1
RAS-10FSXNME
5.5
26.1
RAS-12FSXNME
5.5
26.1
Determine the additional refrigerant quantity according to the following
procedure, and charge the system with it. Record the additional refrigerant
quantity to facilitate maintenance and servicing activities thereafter.
9.2.1 For RAS-(4-6)FS(V)NME
Pipe diameter Total piping Refrigerant amount
(mm)
length (m) for 1m pipe (kg/m)
Ø12.70
___ m
x 0.085
Ø9.52
___ m
x 0.050
Ø6.35
___ m
x 0.020
Total additional charge for liquid piping
Additional charge (W)
=kg =kg =kg =kg
Total refrigerant charge in the system
Total refrigerant charge = W + W0 9.2.2 For RAS-(8-12)FSXNME
W1. For liquid piping (W1 kg)
Pipe diameter Total piping Refrigerant amount for Additional
(mm)
length (m)
1m pipe (kg/m)
charge
Ø15.88 Ø12.70
m m
x 0.17 x 0.11
=kg =kg
Ø9.52
___ m
x 0.056
Ø6.35
___ m
x 0.024
Total additional charge for liquid piping
? NOTE
=kg =kg =_____kg
In the case that the quantity calculated above is less than the minimum quantity indicated in the table below, adopt the quantity in the table below as the additional refrigerant quantity for piping liquid, regardless of the piping length.
Model
Minimum additional refrigerant charge of OU (kg)
RAS-(8-12)FSXNME 2.0
Maximum additional refrigerant charge must not exceed 6.0kg. Nº of IU x 0.3
kg/unit or 0.5 kg/unit = additional charge (W2 kg) 6.0 kg
W3. For indoor unit 8HP and 10HP only (W3 kg)
Additional refrigerant charge is 1kg/unit of 8HP and 10HP indoor units.
N of 8HP and 10HP IU x 1.0 kg/unit.= Additional charge (W3 kg)
W4. For indoor unit (W4 kg)
Depending on the ratio of the indoor unit connection capacity.
IU Capacity Ratio is 100% = 0.0kg IU Capacity Ratio is > 100% = 0.5kg.
W5. For each CH-Box connected (W5 kg)
If CH-Boxes (multiple branch type only) are connected, additional refrigerant charge is required. Select adequate refrigerant charge from the following table.
CH-Box Model
Additional Refrigerant Charge (kg)
CH-
CH-
CH-
CH-
AP04MSSX AP08MSSX AP12MSSX AP16MSSX
0.1
0.2
0.3
0.4
W. Calculation of additional charge (W kg)
Heat pump (W kg) = W1 + W2 + W3 + W4 Heat recovery (W kg) = W1 + W2 + W3 + W4
- W5
Total refrigerant charge in the system
Total refrigerant charge = W + W0
W2. For indoor unit (W2 kg)
Depending on the number of connected indoor units, select the
refrigerant quantity from the following table:
Indoor Unit Capacity (HP)
0.4 – 1.0
1.5 – 6.0
Refrigerant additional quantity (kg)
0.3
0.5
32 PMML0511 rev.3 – 12/2020
EN
DRAIN PIPING
10 DRAIN PIPING
When the base of the outdoor unit is temporarily utilized as a drain receiver and the drain water in it is discharged, this drain boss is utilized to connect the drain piping.
RAS-(4-6)FS(V)NME
RAS-(8-12)FSXNME
Drain hole
RAS-(4-6)FS(V)NME
1
(connexion for DBS-26) RAS-(8-12)FSXNME
2
Drain hole(*)
RAS-(4-6)FS(V)NME
4
RAS-(8-12)FSXNME
3
(*) To cover these drain holes, sealing pads are included in DBS-26 kit.
Connecting procedure for DBS-26 1 Insert the rubber cap into the drain
boss up to the extruded portions.
2 Insert the boss into the unit base and turn approximately 40 degree
counterclockwise.
3 Drain boss is 32 mm (O.D.). 4 A drain pipe should be field-supplied.
? NOTE
Drain hole (DBS-26) Drain pipe Extruted portions
Drain boss
Rubber cap
· Do not use this drain boss set in a cold area, because the drain water may
freeze. This drain boss is not sufficient to collect all the drain water. If
collecting drain water is completely required, provide a drain-pan that is
bigger than the unit base and install it under the unit with drainage.
· For RAS-(4-6)FS(V)NME, 1 kit DBS-26 needed; for RAS-(8-12) FSXNME, 2 kits
DBS-26 needed.
ELECTRICAL WIRING
11.1 GENERAL INFORMATION
! DANGER
· Do not connect or adjust any wiring or connections unless the main power
switch is OFF. Check and test to ensure that if there is more than one source
of power supply, all are turned OFF.
· Use an earth leakage breaker with medium sensitivity, and an activation
speed of 0.1 or less. If this is not fitted, there is a risk of electric shock
and/or fire.
· Install an earth leakage breaker, fuse or circuit breaker of the specific
capacity for each outdoor unit power line. Not fitting it may cause an
electric shock or fire.
· Check that the earth wire is securely connected, tagged and locked in
accordance with national and local codes.
! CAUTION
· Before any work to the electrical wiring or regular inspections, switch off
the mains power supply of the indoor and outdoor units. Wait three minutes
before starting installation or maintenance work.
· Make sure that the interior and exterior fans have come to a complete
standstill before starting work on the electrical wiring or regular
inspections.
· Protect cables, the drainage pipe, electrical components, etc. from rodents
and insects; otherwise these might damage unprotected components and this
could result in fire.
· Do not allow cables to come into contact with the refrigerant pipes, metal
edges, printed circuit boards (PCB) or the electric components inside the
unit; the cables may be damaged and this could result in fire.
· Connecting the operating line cables incorrectly may lead to faults in the
PCB.
· Firmly secure the cables inside the outdoor unit with plastic flanges.
· Check to ensure that screws for terminal block are tightly tightened. ·
Secure the cable of the remote control switch with the cord clamp
inside the electrical box.
? NOTE
· Use twist pair wire (more than 0.75 mm²) for operation wiring between
outdoor unit and indoor unit, and operation wiring between indoor unit and
indoor unit.(Do not use wire with more than 3 cores).
· H-LINK twist pair shielded cable must be grounded in the outdoor unit side.
· Use shielded wires for intermediate wiring to protect the units from noise
obstacle at length of less than 300 m and size complied with local code.
· Sometimes, the refrigeration/heating system is not able to operate correctly
in cases when the system is supplied from the same supply line as other major
consumers (heavy machinery, power inverter systems, cranes, welding machinery,
etc). Also when the supply cables of the major consumers and the system are
very close together, induction in the wiring may arise due to a rapid change
in the electricity consumption of the above consumers and their start-up.
The power supply line of the unit must have an exclusive power control switch
and a certified protective circuit breaker. All the electric components in the
installation (main power switches, circuit breakers, earth leakage breakers,
wiring, connectors and connector terminals) must have been selected and
installed correctly in line with the electrical data provided in this manual,
and must comply with the applicable local regulations, codes and standards.
11.2 CONNECTION OF THE POWER SUPPLY CIRCUITS
Supply the power sources to each outdoor unit and indoor unit respectively.
Power source wiring is fundamentally according to this method (as example).
33 PMML0511 rev.3 – 12/2020
ELECTRICAL WIRING
11.2.1 Power source wiring
Heat pump system
Power source from the outdoor unit to the indoor unit
Independent power source of outdoor unit and indoor unit
4
5
4
1
6
6
2
1
5
2
3
6
76
7
8
8
3 1
2
3
7
8
7
8
9
9
1 ELB (Earth leakage breaker) 2 CB (Circuit breaker) 3 S (Main switch) 4 Outdoor unit
5 Operation wiring (O.U~ I.U ) 6 Indoor unit 7 Remote control wire (I.U) 8 Remote control (I.U)
1 ELB (Earth leakage breaker) 6 Distribution box (field-supplied)
2 CB (Circuit breaker)
7 Indoor unit
3 S (Main switch)
8 Remote control wire (I.U)
4 Outdoor unit
9 Remote control (I.U)
5 Operation wiring (O.U~ I.U )
Heat recovery system
4
10
10
10
4
4
4
1
5
6
2
3
1 2
3
7
8
9
1 ELB (Earth leakage breaker) 2 CB (Circuit breaker) 3 S (Main switch) 4 Outdoor unit 5 Operation wiring (O.U~ I.U ) 6 Distribution box (field- supplied)
6
6
7
8
7
8
7
8
7
8
9
9
9
9
11
12
7 Indoor unit 8 Remote control wire (I.U) 9 Remote control (I.U) 10 CH-Box single 11 Indoor unit system number 0 12 Indoor unit system number 1
34 PMML0511 rev.3 – 12/2020
EN
ELECTRICAL WIRING
Detail for CH-Box multi connection
TB2
H-LINK
OU
12
G
TB1
PS
R/ S/ L1 L2
TB2 OU 12
CH-AP04MSSX
PCB1
TB3
TB4
IU
IU
AB C D
3 4 5 6 7 8 9 10
CH-AP08MSSX
PCB2
TB3
TB4
IU
IU
EF GH
3 4 5 6 7 8 9 10
CH-AP12MSSX
PCB3
TB3
TB4
IU
IU
I J KL
3 4 5 6 7 8 9 10
CH-AP16MSSX
PCB4
TB3
TB4
IU
IU
MN OP
3 4 5 6 7 8 9 10
B
1
TB2
TB2
2
WC B A 2 1
WC B A 2 1
3
IU A*
IU B*
1~ 230V/50Hz
B
TB2
TB2
WC B A 2 1
WC B A 2 1
IU L1*
IU L2*
G
PCB1
TB2 TB3
TB4
OU
IU
IU
AB C
12 3456 78
D
TB2 WC B A 2 1
CO IU
1 ELB (Earth leakage breaker) 2 CB (Circuit breaker) 3 S (Main switch)
C
Connect communication cable from OU to the terminal block (TB2) in CH-Box
D
Connect communication cable from cooling only indoor unit to the outdoor terminal block (TB2) in CH-Box
11.2.2 Cable sizes and main breaker switch
G WC OU CO IU B
CH-Box Wired controler Outdoor unit Cooling only indoor unit Communication Cable (Non-Polarity)
IU (A-L) Indoor unit (A to L indicate the Indoor Unit number).
Field minimum recommended wire sizes for power source and transmission and minimum main switches and protections sizes.
Model
RAS-(4-6)FSVNME RAS-(4-6)FSNME RAS-8FSXNME RAS-10FSXNME RAS-12FSXNME
Power supply 1N~ 230V 50Hz
3N~ 400V 50Hz
Maximum running current (A)
23.5 16 18 19 23
Power source cable size (mm2)
6 4 4 6 6
Transmitting cable size (mm2)
0.75
ELB (poles/m/mA)
2/40/30
4/40/30
CB (A)
32 20 20 25 30
? NOTE
· Follow local codes and regulations when selecting field wires, circuit
breakers and earth leakage breakers.
· Use the wires which are not lighter than the ordinary polychloroprene
sheathed flexible cord (code designation H05RN- F).
! CAUTION
Install a multi-pole main switch with a space of 3.5mm or more between each
phase.
11.2.3 Electromagnetic compatibility
Flicker, voltage fluctuation and voltage change
According to Directive 2014/30/EU, relating to electromagnetic compatibility:
· Equipment complying with EN61000-3-3:
– RAS-(4-6)FSNME and RAS-(8-12)FSXNME · Maximum allowed impedance Zmax of the
system at the
connection point of the user´s power supply, as per EN61000-3-11.
MODEL RAS-(4-6)FSVNME
Zmax () 0.29
Harmonics
In relation to EN61000-3-2 and EN 61000-3-12, the situation of harmonics for each model is as follows:
MODELS SITUATION REGARDING IEC 61000-3-2 AND
IEC 61000-3-12 Ssc “xx” Complying with IEC 61000-3-2 (professional use)
Complying with IEC 61000-3-12 (professional use)
MODELS
RAS-(4-6)FSNME RAS-(4-6)FSVNME RAS-(8/10)FSXNME RAS-(12)FSXNME
Ssc “xx” (KVA)
–
633
1860
2513
35 PMML0511 rev.3 – 12/2020
ELECTRICAL WIRING
11.3 DSW SETTING FOR OUTDOOR UNIT
11.3.1 RAS-(4-6)FSVNME
PCB1
DSW1 Setting not required (not used)
Factory setting
DSW5 transmission setting
Setting not required
Factory setting
End resistance cancellation
PCB2
DSW1 test run Setting required
Factory setting
Cooling test run
Heating test run
Forced compressor Heating intermediate Cooling intermediate
stoppage
test run
test run
? NOTE
Maximum refrigerant cycle number setting: 63.
DSW6 function selection
Setting not required Factory setting
Fixed value setting mode (used in combination with DSW2-5)
DSW7
Setting not required (not used)
Factory setting
11.3.2 RAS-(4-6)FSNME
PCB1
DSW1 test run Setting required
Factory setting
Cooling test run
Heating test run
DSW2 pipe length Setting required
Factory setting
Pipe length shorter than 5m
Pipe length longer than 30m
Control supporting Function selection External input,output
existing piping
setting mode
setting mode
Forced compressor Heating intermediate Cooling intermediate
stoppage
test run
test run
DSW2 pipe length
Setting required
Factory setting
Pipe length shorter than 5m
Pipe length longer than 30m
DSW3 supply voltage and system setting Setting not required
4HP 1-phase
5HP 1-phase
6HP 1-phase
DSW4 / RSW1 refrigerant system setting
Setting required Set all the IU and the OU belonging to the same refrigerant cycle with the same cycle number.
Factory setting
Tens digit
Units digit
Setting example Refrigerant cycle nº 25
Control supporting Function selection External input,output
existing piping
setting mode
setting mode
DSW3 supply voltage and system setting
Setting not required
4HP 3-phase
5HP 3-phase
6HP 3-phase
36 PMML0511 rev.3 – 12/2020
EN
ELECTRICAL WIRING
DSW4 / RSW1 refrigerant system setting
Setting required
Set all the IU and the OU belonging to the same refrigerant cycle with the same cycle number.
Factory setting
Tens digit
Units digit
Setting example Refrigerant cycle nº 25
? NOTE
Maximum refrigerant cycle number setting: 63.
DSW5 transmission setting
Factory setting
Setting not required
End resistance cancellation
DSW6 function selection
Setting not required Factory setting
Fixed value setting mode (used in combination with DSW2-5)
DSW2 capacity setting Setting not required
8HP
10HP
12HP
DSW3
Setting not required
? NOTE
Do not change DSW3 setting. Otherwise, it may cause abnormal operation.
Factory setting
DSW4 test run and service settings
Setting required
Factory setting
Forced compressor stoppage
External input / output setting
Cooling test run
Heating test run
Function setting
DSW7 Setting not required (not used)
PCB2
DSW1 Setting not required (not used)
Factory setting Factory setting
11.3.3 RAS-(8-12)FSXNME
PCB1
DSW1: refrigerant system setting
Setting required Set all the IU and the OU belonging to the same refrigerant
cycle with the same cycle number.
Factory setting
Tens digit
Units digit
Setting example Refrigerant cycle nº 25
DSW5 Setting not required
Factory setting
DSW6 function setting (low ambient setting) Setting required
Factory setting Cooling operation under low load operation
? NOTE
Make sure to apply snow protection hood.
DSW7 supply voltage and system setting
Setting required
Factory setting (400 V) (Heat recovery system)
Heat pump system
? NOTE
Maximum refrigerant cycle number setting: 63.
37 PMML0511 rev.3 – 12/2020
ELECTRICAL WIRING
DSW8 high static pressure mode setting Setting required
Factory setting
HSP setting
? NOTE
(*1) If the fuse (EF1) is melted, set Nº.2 pin to ON for recovery.
PCB2
DSW101 Setting required
NOTE
When adopting the air outlet duct (field-supplied), make sure to set DSW8.
DSW10 transmission setting
Setting required
INV1 Factory setting
Cancellation of current detection
Factory setting
End resistance cancellation
Fuse recovery (*1)
? NOTE
If cancellation of current detection is set, make sure to return the setting,
after service works.
11.4 ELECTRICAL WIRING FOR OUTDOOR UNIT
11.4.1 RAS-(4-6)FS(V)NME
Detail of terminal block for power source and control circuit.
RAS-(4-6)FSVNME: 1~ 230V 50Hz
Electrical box
RAS-(4-6)FSNME: 3N~ 400V 50Hz
Power source wiring
Ring core Yellow
Screw (M5) Screw (M4)
Earth terminal
Screw (M5) Screw (M4) Earth
terminal
Communication wiring Wind the wire 3 times Cable tie
Earth wire
Wind the wire 4 times
R
S
T 3 MP N
Cable tie
Power source wiring
Ring core Green
Earth wire
Control wiring
Only for RAS-(4-6)FSVNME: Cord clamp (for fixing power source wiring and control circuit wiring)
Cord clamp (for fixing power source wiring and control circuit wiring)
? NOTE
Insert the power source cables L1 and N (for 1~ 230V 50Hz ) into the yellow
ring core, coiling them with 3 turns and fix the cables using the cable tie
(accessory). As shown in next figure, do not insert the cables from different
sides into the ring core. Insert the ground cable into the green ring core,
coiling them with 4 turns and fix the cables using the cable tie.
38 PMML0511 rev.3 – 12/2020
EN
COMMISSIONING
11.4.2 For RAS-(8-12)FSXNME
Electrical box
Detail of terminal block for power source and control circuit. 3N~ 400V 50Hz
Screw (M3.5) 12
Control wiring Screw (M5)
Earth terminal
R
S
T 3 MP N
Power source wiring
Earth wire
Cord clamp (for fixing power source wiring and control circuit wiring)
12 COMMISSIONING
12.1 PRELIMINARY CHECKS
When installation is completed, perform test run according to the procedure
described in the installation and operation manual of the remote control
switch PC-ARFP1E, and hand over the system to the customer. Perform test run
regarding indoor units one by one in order. Test run is also possible from the
outdoor unit.
! CAUTION
· Make sure the refrigerant pipes and communication cables between the outdoor
and indoor units are connected to the same refrigeration cycle. Failure to do
so could lead to abnormal operations or a serious accident.
· Make sure the main power supply switch has been on for over 12 hours to heat
up the compressor oil using the heating elements.
· Make sure the electric components in the installation (earth leakage
breaker, circuit breaker, cables, connectors, cable terminals and main power
switches) have been selected correctly in line with the electrical data given
in this Manual. Also make sure that these components are compliant with
national and local codes.
? NOTE
· Check shielded cables (> 0.75 mm2) for communication installation wiring to
avoid electromagnetic noise. (Shielded cable must be less than 1000 m in total
length and its size must be compliant with local codes.)
· Check the connection of the power wiring terminals and supply voltage
according to each model specification.
Do not operate the system until all the check points have been
cleared:
· Check that the outdoor unit and the indoor units have the same cycle number
on the refrigerant cycle DSW.
· Check the end resistance cancellation DSW of the outdoor unit of the
installation.
· Confirm that the DSW setting on the printed circuit board of the indoor
units and the outdoor units are correct.
· Make sure the electrical resistance is greater than 1 M by measuring the
resistance between the ground and the terminal of the electrical components.
If not, do not use the system until the electrical leak has been detected and
repaired. Do not impress the voltage on the terminals for transmission 1 and
2. Where the total insulation resistance of the unit is below 1 M, the
compressor insulation resistance may be low due to the refrigerant held in the
compressor. This may occur if the unit is not used for long periods. –
Disconnect the compressor cables and measure the insulation resistance of the
compressor. If the resistance value is greater than 1 M, the insulation fault
has occurred in another electrical component. – If the insulation resistance
is below 1 M, disconnect the compressor cable on the inverter PCB. Then switch
on the main power supply to apply current to the crankcase heating elements.
Once current has been received for
39 PMML0511 rev.3 – 12/2020
MAIN SAFETY DEVICES
more than 3 hours, re-measure the insulation resistance. (Current may be
required for longer, depending on the air conditions, the pipe length or the
condition of the refrigerant). Check the insulation resistance and re-connect
the compressor. Where the earth leakage breaker is tripped, check the
recommended size: see in chapter “11.2.2 Cable sizes and main breaker switch”.
· Check that all components in the system are correctly connected to the power
line. If the outdoor unit is not correctly connected, the alarm code “05” will
appear.
· Check to ensure that the stop valves of the outdoor unit are fully opened,
and then start the system.
· Check to ensure that the switch on the main power source has been ON for
more than 12 hours, to warm the compressor oil by the oil heater.
Pay attention to the following items while the system is running:
· Do not touch any of the parts by hand at the discharge gas side, since the
compressor chamber and the pipes at the discharge side are heated higher than
90°C.
· DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES), it will cause a serious
accident.
· Do not touch any electrical components for more than three minutes after
turning OFF the main switch.
· Confirm that the gas line stop valve and the liquid line stop valve are
fully open.
· Confirm that the leakage of the refrigerant does not exist. The flare nuts
are sometimes loosened by vibration.
· Check whether or not the electrical wiring of the indoor units and the
outdoor units are connected as shown in the chapter “11 Electrical wiring”.
13 MAIN SAFETY DEVICES
Compressor protection: The compressor is protected by pressure switch, this
switch stops the compressor when the discharge pressure exceeds the set value.
Oil heater: this band-type heater protects against the formation of foam on
the oil during cold starts and remains enabled when the compressor is at a
standstill.
Model
Pressure Switches High
Fuse capacity 1N~ 230V 50Hz 3N~ 400V 50Hz
Oil heater capacity CCP Timer
Setting Time
Cut-Out Cut-In
Fuse capacity (2 Fan) DC 310V 3N~ 400V 50Hz
MPa MPa
A A W min.
A A
RAS-(4-6)FSVNME
RAS-(4-6)FSNME
RAS-(8-12)FSXNME
For Compressor
Automatic Reset, Non-Adjustable (each one for each compressor)
4.15
3.20
50 24
For Fan Module
32
24 Non-Adjustable
3
50 40.8(x3)
3.15
5
–
–
–
10
40 PMML0511 rev.3 – 12/2020
Johnson Controls-Hitachi Air Conditioning Spain, S.A.U. Ronda Shimizu, 1 –
Políg. Ind. Can Torrella 08233 Vacarisses (Barcelona) Spain © Copyright 2020
Johnson Controls-Hitachi Air Conditioning Spain, S.A.U. All rights reserved.
Printed in Spain
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>